TAPCON230
TAPCON230
TAPCON230
r
z
t
!
!
Easy parameter setting
A clearly arranged, 4-line LCD display not only allows the presenta-
tion of important transformer data such as desired value, measuring
voltage and tap position, but also comfortably guides the way
through setting the parameters using the function keys, some of
which are labelled with pictograms.
It goes without saying that the parameters can also be set using
the Windows-based PC software.
Clearly marked LEDs on the user interface of the device allow the
operating status signals to be displayed. These, like the display, can
be seen and read well through the window even when the housing is
closed.
Basic equipment
Clearly arranged display
At a glance, the network voltage and the desired voltage can be
seen at a single glance. That way, no other displays are required
in the control cabinet.
Quick installation
The device can be installed on a mounting board or in a control
panel. Connection is via terminals which can be freely accessed by
opening the cover. The assignment of the terminals is of course
functionally compatible with previous voltage regulators from
Maschinenfabrik Reinhausen.
Multi-meter function
Apart from the voltage, the device allows one other measuring
value, such as current, apparent power, active or reactive
power to be set as a permanent display. This saves not only the
costs of an additional display, but extra wiring costs as well.
Manual control
In addition to manual/automatic keys, two additional keys are
provided on the user interface of the device for manual
higher/lower operation of the tap changer.
Parallel control of the transformers
Parallel control is either according to the principle of the minimum
circulating reactive current or according to the Master/Follower
method. Both options are adjustable and can be activated at
commissioning, as required.
The use of a bus system allows up to 8 transformers to be con-
trolled in parallel groups without an additional device.
Naturally, the voltage regulator TAPCON 230 can be used with-
out problem where an existing plant already equipped with an MR
parallel control device needs to be expanded.
A
C
H
T
U
N
G
!
!
S
e
i
t
e
w
i
r
d
u
m
2
c
m
a
u
f
1
9
c
m
v
e
r
k
r
z
t
!
!
TAPCON 230: Setting ranges
TAPCON 230: Operation elements, display
Function keys Manual / Automatic
Raise / Lower
Menu keys
Display 4-line, 16-digit LC display
1 LED lamp (green) for signalling status
1 LED lamp (red) each for signalling U<, U>, I>
1 LED lamp (green) for signalling, parallel operation active status
1 LED lamp (green) for signalling NORMset active status
Power supply 115 V (+25% / -35%) 40 - 60 Hz, can be chosen either
from the measuring voltage or separately.
Intermountable in factory to a voltage supply of 230 VAC
Power consumption approx. 5.5 VA (at 115 V, idle state)
Protective housing Steel-plate housing with inspection window for flush or projected
panel mounting
216 x 326 x 137 mm (W x H x D)
Degree of protection provided by enclosure: IP 44 according to
IEC 60529, Weight approx. 5.4 kgs
Range
Desired voltage level 1 ... 3 85 ... 140 V
Bandwidth 0,5 9%
Delay time T1 1 ... 180 s
Delay time T2 1 ... 10 s
Switching pulse duration 1.5 s
LDC Ur = 0 25 V
Ux = 0 25 V
Z compensation selection Voltage rise 0 ... 15% of desired voltage level
Limitation 0 ... 15% of desired voltage level
Undervoltage blocking 70 ... 99% of desired voltage level
Overvoltage detection with 101 ... 130% of desired voltage level
high speed return
control (interruptible) Pulse signal 1.5 / 1.5 s
Overcurrent blocking 50 ... 210%
Voltage transformer 0.1 ... 999.9 kV / 100 V
Current transformer 100 ... 5000 A / 5 / 1 / 0.2 A
www.reinhausen.com
Maschinenfabrik Reinhausen GmbH
Falkensteinstrasse 8
93059 Regensburg, Germany
Phone +49 (0)941 40 90-0
Fax +49 (0)941 40 90-600
E-mail sales@reinhausen.com
Please note: The data in our publications may differ from the data of the devices delivered.
We reserve the right to make changes without notice.
IN186/03en 0105/1500 186/03/01/0 F0102002 dp Printed in Germany