Ceraphant T PTC31, PTP31, PTP35: Technical Information
Ceraphant T PTC31, PTP31, PTP35: Technical Information
Ceraphant T PTC31, PTP31, PTP35: Technical Information
Application
Pressure switch for monitoring absolute and gauge
pressures in gases, vapours, liquids and dust.
Your benefits
This compact pressure switch impresses with the latest in
technology being used:
Ceraphant T PTC31
with ceramic sensor diaphragm;
Ceraphant T PTP31
with metallic sensor diaphragm;
Ceraphant T PTP35
- for hygienic applications
54
TI384P/00/en/12.08
Ceraphant T
Ceraphant T PTC31
The process pressure acts on the ceramic sensor diaphragm and the pressure-dependent change in capacitance
of the ceramic sensor is measured. A microprocessor evaluates the signal and switches the output or outputs
the corresponding measured value.
The ceramic sensor is a dry sensor i.e. no fill fluid is needed for pressure transmission. This means that the
sensor can fully support a vacuum. Extremely high durability, on a par with the material Alloy, is achieved
through the use of the highly pure material Ceraphire as a ceramic.
Ceraphant T PTP31 and PTP35
The process pressure acting upon the metallic separating diaphragm of the sensor is transmitted to a resistance
bridge via a fluid. The change in the output voltage of the bridge is proportional to the pressure and can be
measured directly.
Measuring system
Synopsis
Ceraphant
product family
PTC31
PTP31
PTP35
P01-PTC31xxx-14-xx-xx-xx-001
P01-PTP35xxx-14-xx-xx-xx-001
P01-PTP31xxx-14-xx-xx-xx-001
Measuring cell
With piezoresistive
measuring cell and metallic
measuring diaphragm
With piezoresistive
measuring cell and metallic
measuring diaphragm for
hygienic applications
Field of
application
Measurement and
monitoring of absolute and
gauge pressures
Measurement and
monitoring of absolute and
gauge pressures in hygienic
processes
Process
connection
Thread
G female
G A and G A
G A, hole 11 mm
M 12x1,5
7/16-20 UNF
FNPT and MNPT
Thread
G female
G A and G A
G A, hole 11 mm
M 12x1,5
7/16-20 UNF
FNPT and MNPT
G A flush mounted
Hygiene
Clamp " - 2"
G 1A
Varivent F, N
DIN 11851
APV inline
SMS 1"
Measuring range
0 to 1 bar/15 psi
to
0 to 400 bar/6000 psi
0 to 1 bar/15 psi
to
0 to 40 bar/600 psi
Process
temperature
40 C to +100 C
(104 F to 212 F)
40 C to +100 C
(104 F to 212 F)
40 C to +100 C
135 C max. 1 hour
(104 F to 212 F
275 F max. 1 hour)
Endress+Hauser
Ceraphant T
DC voltage version
Positive signal at electronics switch output (PNP). Power supply, e.g. with a transmitter power supply unit.
Preferred in conjunction with programmable logic controllers (PLC) or to control relays.
A
p
P01-PTx3xxxx-14-xx-xx-xx-001
Input
Measured variable
The measured variable for the pressure switch can be selected as either gauge pressure or absolute pressure.
Measuring range
Output
Output signal
DC voltage version: Positive voltage signal (rate depends on power supply voltage) at electronics switch output
(PNP). Short-circuit proof version.
1x PNP switch output
2x PNP switch output
PNP switch output with additional active analog output 4...20 mA.
The analog output continuously represents the measuring range configured or specified by the sensor.
Endress+Hauser
Ceraphant T
Range of adjustment
Switch output:
Switch point (SP): 0.5...100 % in increments of 0.1 % (min. 1 mbar *) of the upper range limit (URL)
Switch-back point (RSP): 0...99.5 % in increments of 0.1 % (min. 1 mbar *) of the upper range limit (URL)
Min. distance between SP and RSP: 0.5% URL
* measuring ranges with negative gauge pressure up to 4 bar in increments of min. 10 mbar
Analog output (if available):
Lower range value (LRV) and upper range value (URV) can be set anywhere within the sensor range (LRL URL). Turn down of the analog output up to 4:1 of the upper range limit (URL).
Damping: can be set anywhere between 0...40 s in increments of 0.1 s
Factory setting (if no customer-specific settings have been ordered):
Switch point SP 1: 45 %; Switch-back point RSP 1: 44.5 %
Switch point SP 2: 55 %; Switch-back point RSP 2: 54.5 %
Analog output: LRV 0 %; URV 100 %
LRL = Lower Range Limit / URL = Upper Range Limit
LRV = Lower Range Value / URV = Upper Range Value
Switching capacity
DC voltage version:
Inductive load
To prevent electrical interference, only operate an inductive load (relays, contactors, solenoid valves) when
directly connected to a protective circuit (free-wheeling diode or capacitor).
Signal on alarm
Analog output
3,6 mA / last current value / 21,0 mA adjustable (if setting 21.0 mA the output is 21.5 mA)
Switch outputs: In safe state (switch normally open)
Load
Power supply
Electrical connection
M12x1
A
5 m (16.4 ft)
M16x1.5 / NPT
B
P01-PTx3xxxx-04-xx-xx-xx-001
A: M 12x1 connector;
B: M 16x1.5 or NPT valve plug
C: cable, 5 m (16.4 ft) long, 5-core
reference pressure supply
Endress+Hauser
Ceraphant T
Device connection
DC voltage version with M 12x1 connector
A2
A2
A1
L+
2
R1
L+
4
R1
L
A3
A3
L+
4
R1
4...20mA
L+
2
4
4...20mA
Diag.
L
P01-PTx3xxxx-04-xx-xx-xx-002
L+
1
3
R
L
P01-PTx3xxxx-04-xx-xx-xx-003
BN
C2
C2
L+
BK
BN
WH
BK
L+
R1
R1
BU
C3
GNYE
BN
WH
BK
L+
R1
BU
GNYE
BU
GNYE
4...20mA
L
C3
BN
WH
BK
4...20mA
BU
GNYE
L+
Diag.
L
P01-PTx3xxxx-04-xx-xx-xx-004
Endress+Hauser
Ceraphant T
Supply voltage
DC voltage version
12...30 V DC
Current consumption
Performance characteristics
The percentage information in the "Performance characteristics" section refer to the upper range limit (URL).
Reference operating
conditions
Switch output
Analog output
In the case of air pressure changes the following additional measuring errors might occur:
400 bar: max. 0.0275 %
100 bar: max. 0.1 %
40 bar: max. 0.275%
10 bar: max. 1 %
Long-term drift
Long-term reliability
Thermal change
Endress+Hauser
Ceraphant T
Any orientation
Any position-dependent zero shift can be corrected. Offset: 20 % URL
Housing can be rotated up to 310
Storage temperature
Degree of protection
M 12x1 connector
Gauge pressure sensors <10 bar: IP 60 / sensors for gauge pressure 10 bar and absolute pressure: IP 66
M 16x1.5 or NPT valve plug
Gauge pressure sensors <10 bar: IP 60 / sensors for gauge pressure 10 bar and absolute pressure: IP 65
Cable: IP 66
For applications where the device is installed outdoor or cleaned from outside we recommend the use of a
protection cap
Shock resistance
Vibration resistance
Electromagnetic
compatibility
Pressure specifications
The maximum pressure for the measuring device is dependent on the weakest element with regard to pressure,
see the following sections "Ordering information: Measuring range" and "Mechanical construction"
The MWP (maximum working pressure) is specified on the nameplate. This value refers to a reference
temperature of +20 C (-4 F) and may be applied to the device for an unlimited time.
The test pressure (Over Pressure Limit OPL) corresponds to 1.5 times the MWP and may be applied for a
limited time only in order to avoid lasting damage.
Endress+Hauser
Ceraphant T
Mechanical construction
Dimensions
M16x1.5 / NPT
M12x1
39 (1.54)
5 m (16,4 ft)
65 (2.56)
38.5 (1.52)
24 (0.94)
24 (0.94)
24 (0.94)
52 (2.05)
105 (4.13)
52 (2.05)
36 (1.42)
52 (2.05)
11 (0.43)
Design, dimensions
42.3 (1.67)
mm (inch)
P01-PTx3xxxx-06-xx-xx-xx-001
Process connection
PTP31, PTP35
PTC31
M24x1.5
P01-PTx3xxxx-06-xx-xx-xx-006
Endress+Hauser
Ceraphant T
PTC31
3
4
5
A
P01-PTx3xxxx-14-xx-xx-xx-003
Thread connections
AD
AE
AF
11 (0.43)
11 (0.43)
11 (0.43)
G1/2
17.5 (0.69)
G1/2
DD
11 (0.43)
DA
11 (0.43)
11 (0.43)
3 (0.12)
6 (0.24)
11.4
(0.45)
20* (0.79)
23.1* (0.91)
CA
BA
11 (0.43)
3 (0.12)
G1/4A
17 (0.67)
3 (0.12)
12 * (0.47)
G1/4
29.9 (1.18)
SW27
(AF27mm)
11(0.43)
11.4
(0.45)
17 (0.67)
AC
M12x1.5
7/16-20UNF
1/4NPT
25.15*
(0.99)
11.4
(0.45)
1/2NPT
mm (inch)
21.4
(0.84)
P01-PTx3xxxx-06-xx-xx-xx-002
Endress+Hauser
Ceraphant T
PTP31
PTP35
PTP
5
6
P01-PTx3xxxx-14-xx-xx-xx-002
Sensor module with adapter thread for adapters with thread connection
Sensor module with adapter thread for adapters with clamp or hygiene connection
Sensor module with clamp or hygiene connection (only versions DA, BA, BB)
"Seal" detail: sensor module, Standard O-ring, in contact with process, adapter
Dimension A: see the following dimension drawing (dimension with *). For 400 bar (6000 psi) sensor see also Page 12.
AC
AE
G1/4
45 (1.77)
12
(0.47)
23 (0.9)
3 (0.12)
G1/4A
3 (0.12)
3 (0.12)
15.5
(0.61)
34 (1.34)
34 (1.34)
AD
20 (0.79)
6 (0.24)
17.5 (0.69)
G1/2A
CA
34 (1.34)
34 (1.34)
15.5
(0.61)
42 (1.65)
20 (0.79)
15.5
(0.61)
BA
AF
3 (0.12)
M12x1.5
11.4 (0.45)
DD
17.5 (0.69)
G1/2A
23 (0.9)
25.15
(0.99)
15.5
(0.61)
47 (1.85)
DA
34 (1.34)
mm (inch)
7/16-20 UNF
26 (1.02)
23 (0.9)
11.4 (0.45)
17.3 (0.7)
11.4 (0.45)
1/4 NPT
1/2"NPT
P01-PTx3xxxx-06-xx-xx-xx-020
Process connection versions: sensor module with adapter (see also "Ordering information" section)
AC: thread ISO 228, G (female)
AD: thread ISO 228, GA
AE: thread ISO 228, GA
AF: thread ISO 228, GA, bore 11 mm (0.43 inch)
BA: Thread DIN 13, M 12x1.5
CA: thread 7/16-20 UNF (SAE)
DA: thread ANSI FNPT
DD: thread ANSI MNPT
10
Endress+Hauser
Ceraphant T
AG
11 (0.43)
mm (inch)
2.5 (0.1)
14 (0.5)
22 (0.9)
17 (0.67)
14 (14.5)
1
27 (1.06)
G
G
26 (1)
P01-PMP131xx-06-09-xx-xx-002
30(1.18)
G1"
G1"
41 (1.61)
PH
17 *
(0.67)
17 *
(0.67)
18 *
(0.71)
SW32
AF32mm
51 (2.01)
68 (2.68)
39 (1.54)
56 (2.20)
50 (1.97)
66 (2.60)
LL
HL
18 *
(0.71)
19 *
(0.75)
17
(0.67)
54,85 (2.16)
29 (1.14)
PL
SW32
AF32mm
SW32
AF32mm
11.5
(0.45)
SW41
AF41mm
41(1.61)
LB
KL
BB
32.5
(1.28)
BA
SW41
AF41mm
11.5
(0.45)
mm (inch)
25.3
(1.00)
68 (2.68)
84 (3.31)
61,5 (2.42)
82 (3.23)
100 (3.94)
P01-PTx3xxxx-06-xx-xx-xx-004
Endress+Hauser
11
Ceraphant T
27.5 (1.08)
34 (1.34
43.5 (1.71)
50.5 (1.99)
SW 28
AF28mm
56.5 (2.22)
64 (2.52
10 (0.39)
SW 28
AF28mm
17 *(0.67)
DL
17 *(0.67)
DB
28 (1.1)
DA
8.5 (0.33)
P01-PTx3xxxx-06-xx-xx-xx-005
Weight
Material
12
Endress+Hauser
Ceraphant T
Human interface
Operating elements
P01-PTx3xxxx-19-xx-xx-en-001
The background illumination of the digital display indicates the status of the device:
white = ok; red = error
On-site operation
Operating options
BASE
(basic functions)
Endress+Hauser
13
Ceraphant T
Function group
Operating options
OUT
(Configuration of
1st output)
Output function:
Hysteresis function or window function
NC contact or NO contact
(see next diagram)
Analog output 4...20 mA
Switch point:
Input value
Acceptance of applied value
Switch point anywhere between 0.5...100 % URL
(in increments of 0.1 %, min. 0,001 bar)
Switch-back point:
Input value
Acceptance of applied value
Switch-back point anywhere between 0...99.5 % URL
(in increments of 0.1 %, min. 0,001 bar)
Switch output delay: anywhere between 0...99 s (in increments of 0.1 s)
OUT 2
(Configuration of
2nd output,
only for corresponding
electronics version)
Output function:
Hysteresis function or window function
NC contact or NO contact
(see next diagram)
Analog output 4...20 mA
Switch point 2:
Input value
Acceptance of applied value
Switch point anywhere between 0.5...100 % URL
(in increments of 0.1 %, min. 0,001 bar)
Switch-back point 2:
Input value
Acceptance of applied value
Switch-back value anywhere between 0...99.5 % URL
(in increments of 0.1 %, min. 0,001 bar)
Switch output delay: anywhere between 0...99 s (in increments of 0.1 s)
4-20
(configuration of
analog output,
only for corresponding
electronic version)
Lower range value (LRV) and upper range value (URV) of analog output:
Input value
Acceptance of applied value
Anywhere within sensor range (in increments of 0.1 %); turn down up to 4 : 1
Setting of error current: choice of 3.6 mA / 21.0 mA / last current value
SERV
(service functions)
Note
14
Endress+Hauser
Ceraphant T
p
SP
SP
RSP
RSP
t
1
0
1
0
4
2
3
1
1
0
1
0
P01-PTx3xxxx-05-xx-xx-xx-001
a Hysteresis function
b Window function
Window NC contact switch status
Hysteresis NC contact switch status
Window NO contact switch status
Hysteresis NO contact switch status
SP Switch point
RSP Switch-back point
Endress+Hauser
15
Ceraphant T
Operation with PC
The device can be configured with the configuration software ReadWin 2000 or FieldCare. For the
connection between the USB port of the computer and the device a configuration kit (e. g. TXU10 or FXA291)
is necessary.
P01-PTx3xxxx-19-xx-xx-de-002
In addition to the operating options listed in the previous "On-site operation" section, the ReadWin 2000 or
FieldCare configuration software provides further information on the Ceraphant T:
Function group
Description
SERVICE
INFO
Tag number
Order code
Device serial number
Sensor serial number
Electronics serial number
Device release (change status)
Hardware version
Software version
Comprehensive information on the ReadWin 2000 configuration software may be found in the Operating
Instructions BA137R/09/en.
The configuration kit TXU10-AA is available as an accessory (see chapter Assessories). For the order of the
configuration kit FXA291 or software FieldCare please ask your E+H sales organisation.
16
Endress+Hauser
Ceraphant T
The device meets the legal requirements of the EC directives. Endress+Hauser confirms that the device has
been successfully tested by applying the CE mark.
UL listing
The device was examined by Underwriters Laboratories Inc. USA (UL) in accordance with the standards UL
61010B-1 and CSA C22.2 No. 1010.1-92 and listed under the number E225237 UL for Canada and the USA.
This measuring device corresponds to Article 3 (3) of the EC Directive 97/23/EC (Pressure Equipment
Directive) and has been designed and manufactured according to good engineering practice.
74 -
Ceraphant T PTP35
The following applies to wetted device components: They do not contain any materials derived from animals.
No auxiliaries or operating materials derived from animals are used in production or processing. Process wetted
device components are listed in the Mechanical construction and Ordering information sections.
Registered trademarks
Ceraphire
Registered trademark of Endress+Hauser GmbH+Co.KG, Maulburg, Germany
ReadWin
Registered trademark of Endress+Hauser Wetzer GmbH+Co.KG, Nesselwang, Germany
LEXAN
Registered trademark of General Electric Plastics B.V., Bergen op Zoom, Netherlands
THERMOPLAST
Registered trademark of Kraiburg TPE GmbH, Waldkraiburg, Germany
Endress+Hauser
17
Ceraphant T
Ordering Information
Ceraphant T PTC31
10
Certificate
A
20
Electrical connection
1
2
3
4
30
M 12x1 connector: IP 60; with sensors for gauge pressure 10 bar and absolute pressure: IP 66
M16x1.5 valve plug, ISO 4400: IP 60, with sensors for gauge pressure 10 bar and absolute pressure: IP 65
NPT valve plug, ISO 4400: IP 60, with sensors for gauge pressure 10 bar and absolute pressure: IP 65
5 m (16.4 ft) cable: IP 66
40
Display
1
50
60
Sensor
Gauge pressure
1C 0...0.1bar / 0...10 kPa
1F 0...0.4 bar / 0...40 kPa
1H 0...1 bar / 0...100 kPa
1M 0...4 bar / 0...400 kPa
1P 0...10 bar / 0...1000 kPa
1S 0...40 bar / 0...4000 kPa
Overload OPL
4 bar
8 bar
10 bar
25 bar
40 bar
60 bar
Overload OPL
4 bar
8 bar
10 bar
25 bar
40 bar
Absolute pressure
2F 0...0.4 bar / 0...40 kPa
2H 0...1 bar / 0...100 kPa
2M 0...4 bar / 0...400 kPa
2P 0...10 bar / 0...1000 kPa
2S 0...40 bar / 0...4000 kPa
Overload OPL
8 bar
10 bar
25 bar
40 bar
60 bar
70
80
90
Additional equipment
A
B
C
D
PTC31 -
18
Endress+Hauser
Ceraphant T
Ceraphant T PTP31
10
Certificate
A
20
Electrical connection
1
2
3
4
30
M 12x1 connector: IP 60; with sensors for gauge pressure 10 bar and absolute pressure: IP 66
M16x1.5 valve plug, ISO 4400: IP 60, with sensors for gauge pressure 10 bar and absolute pressure: IP 65
NPT valve plug, ISO 4400: IP 60, with sensors for gauge pressure 10 bar and absolute pressure: IP 65
5 m (16.4 ft) cable: IP 66
40
Display
1
50
60
Sensor
Gauge pressure
3H 0...1 bar / 0...100 kPa
3M 0...4 bar / 0...400 kPa
3P 0...10 bar / 0...1000 kPa
3S 0...40 bar / 0...4000 kPa
3U 0...100 bar / 0...10 MPa
3Z 0...400 bar / 0...40 MPa
Overload OPL
4 bar
16 bar
40 bar
160 bar
160 bar
600 bar
Overload OPL
4 bar
16 bar
40 bar
Absolute pressure
4H 0...1 bar / 0...100 kPa
4M 0...4 bar / 0...400 kPa
4P 0...10 bar / 0...1000 kPa
4S 0...40 bar / 0...4000 kPa
4U 0...100 bar / 0...10 MPa
4Z 0...400 bar / 0...40 MPa
Overload OPL
4 bar
16 bar
40 bar
160 bar
160 bar
600 bar
70
80
90
Additional equipment
A
B
C
D
PTP31 -
Endress+Hauser
19
Ceraphant T
Ceraphant T PTP35
10
Certificate
A
20
Electrical connection
1
2
3
4
30
M12x1 connector: IP 60, with sensors for gauge pressure 10 bar and absolute pressure: IP 66
M16x1.5 valve plug, ISO 4400: IP 60; with sensors for gauge pressure 10 bar and absolute pressure: IP 65
NPT valve plug, ISO 4400: IP 60; with sensors for gauge pressure 10 bar and absolute pressure: IP 65
5 m (16.4 ft) cable: IP 66
40
Display
1
50
60
Sensor
Gauge pressure
3H 0...1 bar / 0...100 kPa
3M 0...4 bar / 0...400 kPa
3P 0...10 bar / 0...1000 kPa
3S
0...40 bar / 0...4000 kPa
Overload OPL
4 bar
16 bar
40 bar
160 bar
Overload OPL
4 bar
16 bar
40 bar
Absolute pressure
4H 0...1 bar / 0...100 kPa
4M 0...4 bar / 0...400 kPa
4P 0...10 bar / 0...1000 kPa
4S 0...40 bar / 0...4000 kPa
Overload OPL
4 bar
16 bar
40 bar
160 bar
70
Clamp connections
DA
DB
DL
BA
Hygienic connections
BB
KL
LB
LL
PH
PL
HL
80
90
Additional equipment
A
B
C
D
PTP35 -
20
Endress+Hauser
Ceraphant T
The Ceraphant T pressure switch can also be ordered with customised settings. For this purpose, please use
the questionnaire below. Information on the desired switch point (SP), switch-back point (RSP), lower range
value and upper range value always refer to the pressure unit selected. The possible range of adjustment is
indicated in the questionnaire in % of the upper range limit (URL). The bold-printed specifications are the
factory settings.
( ) bar
( ) kPa/MPa
( ) psi
Output 1 (Application 1)
Function:
( ) 1 = Window normally closed ( ) 3 = Window normally open
( ) 2 = Hysteresis normally closed ( ) 4 = Hysteresis normally open
SP:
RSP:
Function:
( ) 1 = Window normally closed ( ) 3 = Window normally open
( ) 2 = Hysteresis normally closed ( ) 4 = Hysteresis normally open
SP:
RSP:
Failure mode:
( ) 1 = 3.6 mA
( ) 2 = 21.0 mA
( ) no
( ) yes
Hint: See section Devices Connection
TAG
(max. 2 x 18
characters)
P01-PTx3xxxx-16-xx-xx-en-001
Endress+Hauser
21
Ceraphant T
Accessories
Welding boss for flush mounting process
connection G1 A with metallic sealing taper
(version BA for PTP35)
Material: AISI 316L
Order number: 52005087
mm
(inch)
50 (1,97)
41 (1.6)
G1
mm (inch)
Thread adapter
24.6 (0.97)
Welding boss
with sealing surface
P01-Pxxxxxxx-00-xx-00-xx-001
29.6 (1.2)
27.5
(1.08)
30
(1.18)
Welding boss
with sealing taper
60 0.4 (2.4)
P01-PMP13xxx-00-xx-00-xx-002
Clamp adapter
22
Endress+Hauser
Ceraphant T
Hygiene adapter
P01-PMP13xxx-00-xx-00-xx-003
20 (0.8)
35 (1.4)
41 (1.6)
Plug-in jack
14.8 (0.6)
mm (inch)
P01-Pxxxxxxx-00-xx-00-xx-002
Connecting cable
Endress+Hauser
ye1
ye2
1 (bn)
2
L+
2 (wh)
4 (bk)
3 (bu)
gn
R
L
P01-PTx3xxxx-07-xx-xx-xx-001
23
Configuration kit
Documentation
This supplementary documentation can be found on our product pages on www.endress.com
Operating instructions
Technical Information
Instruments International
Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland
Tel. +41 61 715 81 00
Fax +41 61 715 25 00
www.endress.com
info@ii.endress.com
TI384P/00/en/12.08
71086744
FM+SGML 6.0
71086744