Model DV-5 Deluge Valve, Diaphragm Style,


1-1/2 thru 8 Inch (DN40 thru DN200),
Deluge System — Electric Actuation
General
Description
The Model DV-5 Deluge Valve (de-
scribed in Technical Data Sheet
TFP1305) is a diaphragm style valve
that depends upon water pressure in
the Diaphragm Chamber to hold the
Diaphragm closed against the water
supply pressure. When the DV-5 Valve
is set for service, the Diaphragm
Chamber is pressurized through the
trim connections from the inlet side of
the system’s main control valve, for
example an O.S.&Y. gate valve or but-
terfly valve (Ref. Figures 1 and 3).
Operation of an electrical device such
as a heat sensitive thermostat, smoke
detector, or electrical manual control
station signals the deluge valve releas-
ing panel to energize the Solenoid
Valve. In turn, the energized Solenoid
Valve opens to release water from the
Diaphragm Chamber faster than it can
be replenished through the 1/8 inch
(3,2 mm) restriction provided by the
Model ASV-1 Automatic Shut-Off
Valve in the diaphragm supply connec-
tions (Item 5 - Fig. 2A and 4, also
described in Technical Data Sheet
TFP1384). This results in a rapid pres-
sure drop in the Diaphragm Chamber
and the force differential applied
through the Diaphragm that holds it in
the set position is reduced below the
valve trip point. The water supply pres- of the DV-5 during a fire (as may be the impair the performance of these de-
sure then forces the Diaphragm open case should the Solenoid Valve be- vices.
permitting water to flow into the system come de-energized after its initial op-
The owner is responsible for maintain-
piping, as well as through the Alarm eration).
ing their fire protection system and de-
Port to actuate the system alarms. vices in proper operating condition.
As water flows into the system, the The installing contractor or manufac-
WARNING
pilot chamber of the Model ASV-1 turer should be contacted with any
The Model DV-5 Deluge Valve with
Automatic Shut-Off Valve (Item 5 - Fig. questions.
Electric Actuation Trim described
2A and 4) becomes pressurized and herein must be installed and main-
the ASV-1 automatically shuts off the tained in compliance with this docu-
diaphragm chamber supply flow to the ment, as well as with the applicable
DV-5 Diaphragm Chamber. Shutting standards of the National Fire Protec-
off the diaphragm chamber supply flow tion Association, in addition to the
prevents the DV-5 Diaphragm Cham- standards of any other authorities hav-
ber from becoming re-pressurized, ing jurisdiction. Failure to do so may
thereby preventing inadvertent closing

Page 1 of 14 MARCH, 2004 TFP1320


Close

Page 2 of 14 TFP1320

5 6
5

13

15
8

11

14
7

9
3

1
4

1 - Model DV-5 Deluge Valve 7 - Water Supply Pressure Gauge 12 - Waterflow Pressure Alarm Switch
2 - Main Control Valve (N.O.) 8 - Diaphragm Chamber Pressure (Shown at Rear of Valve)
3 - Diaphragm Chamber Supply Gauge 13 - Water Motor Alarm (Optional)
Control Valve (N.O.) 9 - System Drain Valve (N.C.) 14 - Solenoid Valve
4 - Local Manual Control Station 10 - Main Drain Valve (N.C.) 15 - Deluge Valve Releasing Panel
5 - Open Nozzles or Sprinklers (Shown at Rear of Valve)
6 - Heat Detectors, Smoke Detectors, 11 - Diaphragm Chamber Automatic
etc. (Fire Detection) Shut-Off Valve

FIGURE 1 — PART 1 OF 2
SYSTEM SCHEMATIC (Front View) — ELECTRIC ACTUATION
Close

TFP1320 Page 3 of 14

5
5 6

13

15 12
11

14

9
3

10
1

1 - Model DV-5 Deluge Valve 7 - Water Supply Pressure Gauge 13 - Water Motor Alarm (Optional)
2 - Main Control Valve (N.O.) (Shown at Front of Valve) 14 - Solenoid Valve
3 - Diaphragm Chamber Supply 8 - Diaphragm Chamber Pressure 15 - Deluge Valve Releasing Panel
Control Valve (N.O.) Gauge (Shown at Front of Valve)
4 - Local Manual Control Station 9 - System Drain Valve (N.C.)
(Shown at Front of Valve) 10 - Main Drain Valve (N.C.)
5 - Open Nozzles or Sprinklers 11 - Diaphragm Chamber Automatic
6 - Heat Detectors, Smoke Detectors, Shut-Off Valve
etc. (Fire Detection) 12 - Waterflow Pressure Alarm Switch

FIGURE 1 — PART 2 OF 2
SYSTEM SCHEMATIC (Rear View) — ELECTRIC ACTUATION
Close

Page 4 of 14 TFP1320

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa 15 3/32" Vent Fitting . . . . . . . 1 92-032-1-002 35 1/2" x 2-1/2" Nipple . . . . . 4 CH
Water Pressure Gauge . . 2 92-343-1-005 16 1/4" x 18" Tubing . . . . . . . 1 CH 36 1/2" x 5" Nipple . . . . . . . . 2 CH
2 1/4" Gauge Test Valve . . 1 46-005-1-002 17 1/2" Tubing Connector . . 1 CH 37 1/2" x 7" Nipple . . . . . . . . 1 CH
3 Model MC-1 Manual 18 1/2" x 12" Tubing . . . . . . . 1 CH 38 Select Nipple per Table . . 2 CH
Control Station . . . . . . . . . 1 52-289-2-001 19 1/4" Plug. . . . . . . . . . . . . . 1 CH 39 Select Nipple per Table . . 2 CH
4 Model AD-1 Automatic 20 3/4" Plug. . . . . . . . . . . . . . 1 CH 40 3/4" x Close Nipple . . . . . 1 CH
Drain Valve . . . . . . . . . . . 1 52-793-2-004 21 1/2" Union . . . . . . . . . . . . 5 CH 41 3/4" x 1-1/2" Nipple . . . . . 8 CH
5 Automatic Shut-Off Valve, 22 3/4" Union . . . . . . . . . . . . 2 CH 42 3/4" x 2" Nipple . . . . . . . . 1 CH
Model ASV-1 . . . . . . . . . . 1 92-343-1-021 23 1/4" 90° Elbow . . . . . . . . . 1 CH 43 3/4" x 4" Nipple . . . . . . . . 1 CH
6 Waterflow Pressure Ordered 24 1/2" 90° Elbow . . . . . . . . . 8 CH 44 Select Nipple per Table . . 2 CH
Alarm Switch . . . . . . . . . . 1 Separately 25 3/4" 90° Elbow . . . . . . . . . 1 CH
7 1/2" Ball Valve . . . . . . . . . 2 46-050-1-004 26 1/2" Tee . . . . . . . . . . . . . . 3 CH E1 Solenoid Valve Per Data Ordered
8 1/2" Spring Loaded 27 1/2" x 1/4" x 1/2" Tee . . . . 3 CH Sheet TFP2180 . . . . . . . 1 Separately
Check Valve . . . . . . . . . . 1 92-322-1-002 28 3/4" Tee . . . . . . . . . . . . . . 2 CH E2 1/2" Tubing Connector . . 1 CH
9 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 29 3/4" x 1/2" x 3/4" Tee . . . . 2 CH E3 1/2" x 24" Tubing . . . . . . . 1 CH
10 3/4" Swing Check Valve . 1 46-049-1-005 30 3/4" x 3/4" x 1/2" Tee . . . . 1 CH E4 1/2" x 1-1/2" Nipple . . . . . 1 CH
11 3/4" Angle Valve . . . . . . . 2 46-048-1-005 31 1/4" x Close Nipple . . . . . 2 CH
12 Drip Funnel Connector . . 1 92-211-1-005 32 1/2" x Close Nipple . . . . . 3 CH
13 Drip Funnel Bracket . . . . 1 92-211-1-003 33 1/2" x 1-1/2" Nipple . . . . . 11 CH Select Appropriate Nipple Sizes
14 Drip Funnel . . . . . . . . . . . 1 92-343-1-007 34 1/2" x 2" Nipple . . . . . . . . 1 CH Nipple per DV-5 Deluge Valve Size
Number
1-1/2" (DN40) 2" (DN50)
6
16 40 11 38 1/2" x Close 1/2" x 2"
(ORDERED
SEPARATELY) 30 39 1/2" x 5" 1/2" x 5-1/2"
27 41 44 44 3/4" x 1-1/2" 3/4" x 2-1/2"
15
29 E1
(GREEN 24
LOCATION 20 (ORDERED
TINT) 35
FOR OPTIONAL 4 SEPARATELY)
ELECTRICALLY 28 E3
35 41 33 E4
SUPERVISED 41 E2
22 21
N.O. ALARM 42 36 21 32
CONTROL VALVE 41 25 33
(BVS-3/4") 41
22
10 26 26
33 41 24 39
41
24 41 35 24 24
29 12 1
14 26
38 28 33 32
11 43 33 27
7
13 37
35 1 8 33 3

21 5
19 2 33 21
NOTES:
36 24 32
1. Electric Actuation Trim is 9 34
comprised of Items 1-44 33 2" (DN50) 18
33
plus Items E1-E4. 31 27 GROOVE x GROOVE 33 17
MODEL DV-5 24 24
2. All Fittings and Nipples are 31
galvanized (Standard Order). 23 DELUGE VALVE 21
SHOWN
3. CH: Common Hardware.
4. See Figure 2 of TFP1305 for 33
Valve Port identification. 7
5. Route all Tubing to Drip Funnel,
Item 14.

FIGURE 2A — PART 1 OF 3
1-1/2 and 2 INCH (DN40 and DN50) MODEL DV-5 DELUGE VALVES
— EXPLODED VIEW OF VERTICAL ELECTRIC ACTUATION TRIM (52-477-X-109) —
Close

TFP1320 Page 5 of 14

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa 14 Drip Funnel Bracket . . . . 1 92-211-1-003 33 1/4" x Close Nipple . . . . . 2 CH
Water Pressure Gauge . . 2 92-343-1-005 15 Drip Funnel . . . . . . . . . . . 1 92-343-1-007 34 1/2" x Close Nipple . . . . . 2 CH
2 1/4" Gauge Test Valve . . 1 46-005-1-002 16 3/32" Vent Fitting . . . . . . . 1 92-032-1-002 35 1/2" x 1-1/2" Nipple . . . . .13 CH
3 Model MC-1 Manual 17 1/4" x 18" Tubing . . . . . . . 1 CH 36 1/2" x 2-1/2" Nipple . . . . . 2 CH
Control Station . . . . . . . . . 1 52-289-2-001 18 1/2" Tubing Connector . . 1 CH 37 1/2" x 3-1/2" Nipple . . . . . 1 CH
4 Model AD-1 Automatic 19 1/2" x 12" Tubing . . . . . . . 1 CH 38 1/2" x 4" Nipple . . . . . . . . 1 CH
Drain Valve . . . . . . . . . . . 1 52-793-2-004 20 1/4" Plug. . . . . . . . . . . . . . 1 CH 39 1/2" x 4-1/2" Nipple . . . . . 1 CH
5 Automatic Shut-Off Valve, 21 3/4" Plug. . . . . . . . . . . . . . 1 CH 40 1/2" x 5" Nipple . . . . . . . . 1 CH
Model ASV-1 . . . . . . . . . . 1 92-343-1-021 22 1/2" Union . . . . . . . . . . . . 5 CH 41 1/2" x 5-1/2" Nipple . . . . . 1 CH
6 Waterflow Pressure Ordered 23 3/4" Union . . . . . . . . . . . . 2 CH 42 1/2" x 7" Nipple . . . . . . . . 2 CH
Alarm Switch . . . . . . . . . . 1 Separately 24 1/4" 90° Elbow . . . . . . . . . 1 CH 43 3/4" x Close Nipple . . . . . 3 CH
7 1/2" Ball Valve . . . . . . . . . 2 46-050-1-004 25 1/2" 90° Elbow . . . . . . . . . 8 CH 44 3/4" x 1-1/2" Nipple . . . . . 5 CH
8 1/2" Spring Loaded 26 3/4" 90° Elbow . . . . . . . . . 1 CH 45 3/4" x 2" Nipple . . . . . . . . 1 CH
Check Valve . . . . . . . . . . 1 92-322-1-002 27 1/2" Tee . . . . . . . . . . . . . . 3 CH 46 3/4" x 4-1/2" Nipple . . . . . 1 CH
9 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 28 1/2" x 1/4" x 1/2" Tee . . . . 3 CH 47 1-1/4" x 2" Nipple . . . . . . . 1 CH
10 3/4" Swing Check Valve . 1 46-049-1-005 29 3/4" Tee . . . . . . . . . . . . . . 1 CH 48 1-1/4" x 4" Nipple . . . . . . . 1 CH
11 3/4" Angle Valve . . . . . . . 1 46-048-1-005 30 3/4" x 1/2" x 3/4" Tee . . . . 2 CH
12 1-1/4" Angle Valve . . . . . . 1 46-048-1-007 31 3/4" x 3/4" x 1/2" Tee . . . . 1 CH E1 Solenoid Valve Per Data Ordered
13 Drip Funnel Connector . . 1 92-211-1-005 32 1-1/4" x 3/4" x 1-1/4" Tee . 1 CH Sheet TFP2180 . . . . . . . 1 Separately
E2 1/2" Tubing Connector . . 1 CH
E3 1/2" x 24" Tubing . . . . . . . 1 CH
6
17 43 11 E4 1/2" x 1-1/2" Nipple . . . . . 1 CH
(ORDERED
SEPARATELY) 31
28 44 46
16 25 E1
30
(GREEN (ORDERED
LOCATION 21 TINT) 36 35 SEPARATELY)
FOR OPTIONAL 26 E3
ELECTRICALLY 36 29 E2 E4
SUPERVISED 44 22
23 27 4 41 22 35
N.O. ALARM 45
44 35
CONTROL VALVE 43
(BVS-3/4") 44 27
23 38
35 10 25 42
43 13
44 25 25
25 15 1
30 27
35 35 34
32 35 28
7 47 48 14
42
12 35 3
40
1
35 5 22
NOTES: 22 8
20 2 25 35
1. Electric Actuation Trim is 37 34
9
comprised of Items 1-48 19
39 35
plus Items E1-E4. 18
35 3" (DN80) 25 25
2. All Fittings and Nipples are 33 28 GROOVE x GROOVE
galvanized (Standard Order). 22
33 MODEL DV-5
3. CH: Common Hardware. 24 DELUGE VALVE
4. See Figure 2 of TFP1305 for SHOWN 35
Valve Port identification. 7
5. Route all Tubing to Drip Funnel,
Item 15.

FIGURE 2A — PART 2 OF 3
3 INCH (DN80) MODEL DV-5 DELUGE VALVES
— EXPLODED VIEW OF VERTICAL ELECTRIC ACTUATION TRIM (52-477-X-106) —
Close

Page 6 of 14 TFP1320

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa 18 1/2" Tubing Connector . . 1 CH 41 Select Nipple per Table . . 2 CH
Water Pressure Gauge . . 2 92-343-1-005 19 1/2" x 24" Tubing . . . . . . . 1 CH 42 Select Nipple per Table . . 2 CH
2 1/4" Gauge Test Valve . . 1 46-005-1-002 20 1/4" Plug. . . . . . . . . . . . . . 1 CH 43 Select Nipple per Table . . 2 CH
3 Model MC-1 Manual 21 3/4" Plug. . . . . . . . . . . . . . 1 CH 44 3/4" x 1-1/2" Nipple . . . . . 1 CH
Control Station . . . . . . . . . 1 52-289-2-001 22 1/2" Union . . . . . . . . . . . . 5 CH 45 3/4" x 2" Nipple . . . . . . . . 1 CH
4 Model AD-1 Automatic 23 1" Union . . . . . . . . . . . . . . 2 CH 46 Select Nipple per Table . . 2 CH
Drain Valve . . . . . . . . . . . 1 52-793-2-004 24 1/4" 90° Elbow . . . . . . . . . 1 CH 47 1" x Close Nipple . . . . . . . 5 CH
5 Automatic Shut-Off Valve, 25 1/2" 90° Elbow . . . . . . . . . 8 CH 48 1" x 3" Nipple . . . . . . . . . . 1 CH
Model ASV-1 . . . . . . . . . . 1 92-343-1-021 26 1" 90° Elbow . . . . . . . . . . 1 CH 49 Select Nipple per Table . . 2 CH
6 Waterflow Pressure Ordered 27 1/2" Tee . . . . . . . . . . . . . . 3 CH 50 2" x 3" Nipple . . . . . . . . . . 1 CH
Alarm Switch . . . . . . . . . . 1 Separately 28 1/2" x 1/4" x 1/2" Tee . . . . 3 CH 51 2" x 5" Nipple . . . . . . . . . . 1 CH
7 1/2" Ball Valve . . . . . . . . . 2 46-050-1-004 29 3/4" x 1/2" x 3/4" Tee . . . . 2 CH
8 1/2" Spring Loaded 30 1" x 1" x 1/2" Tee . . . . . . . 1 CH E1 Solenoid Valve Per Data Ordered
Check Valve . . . . . . . . . . 1 92-322-1-002 31 1" x 3/4" x 1" Tee . . . . . . . 1 CH Sheet TFP2180 . . . . . . . 1 Separately
9 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 32 2" x 1" x 2" Tee . . . . . . . . 1 CH E2 1/2" Tubing Connector . . 1 CH
10 3/4" Swing Check Valve . 1 46-049-1-005 33 1/4" x Close Nipple . . . . . 2 CH E3 1/2" x 24" Tubing . . . . . . . 1 CH
11 1" Angle Valve . . . . . . . . . 1 46-048-1-006 34 1/2" x Close Nipple . . . . . 2 CH E4 1/2" x 1-1/2" Nipple . . . . . 1 CH
12 2" Angle Valve . . . . . . . . . 1 46-048-1-009 35 1/2" x 1-1/2" Nipple . . . . .10 CH
13 Drip Funnel Connector . . 1 92-211-1-005 36 1/2" x 2-1/2" Nipple . . . . . 3 CH
Select Appropriate Nipple Sizes
14 Drip Funnel Bracket . . . . 1 92-211-1-003 37 1/2" x 3" Nipple . . . . . . . . 1 CH
Nipple per DV-5 Deluge Valve Size
15 Drip Funnel . . . . . . . . . . . 1 92-343-1-007 38 1/2" x 5" Nipple . . . . . . . . 2 CH
16 3/32" Vent Fitting . . . . . . . 1 92-032-1-002 39 1/2" x 6" Nipple . . . . . . . . 1 CH No. 4" 6" 8"
17 1/4" x 24" Tubing . . . . . . . 1 CH 40 1/2" x 7" Nipple . . . . . . . . 2 CH (DN100) (DN150) (DN200)
41 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8 -1/2"
42 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
43 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
6 47 11 46 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
17
(ORDERED 49 1" x 6" 1" x 9" 1" x 12"
30
SEPARATELY)
47 49
28 E1
25 (ORDERED
29 16
LOCATION 36 E3 SEPARATELY)
21 (GREEN
FOR OPTIONAL 26 37 E2 E4
TINT)
ELECTRICALLY 36 47 22
SUPERVISED 44 4 39 22 42
23 23 35
N.O. ALARM 45 27
CONTROL VALVE 47
31 36 27
(BVS-3/4") 43
47 25
35 10 13
25 25
25 46 15 1
48 27
29
35 34
41 35 28
14
32 40
7
50 51 35 3
12 35
1 5 22
NOTES: 40 8
1. Electric Actuation Trim is 22 34
20 2 9 35 38
comprised of Items 1-51 19
25
plus Items E1-E4. 38 35 18
25 25
2. All Fittings and Nipples are 35
galvanized (Standard Order). 4" (DN100) 22
33 28
3. CH: Common Hardware. FLANGE x FLANGE
33 MODEL DV-5
4. See Figure 2 of TFP1305 for 24 35
DELUGE VALVE
Valve Port identification. SHOWN
5. Route all Tubing to Drip Funnel, 7
Item 15.

FIGURE 2A — PART 3 OF 3
4, 6, and 8 INCH (DN100, DN150, and DN200) MODEL DV-5 DELUGE VALVES
— EXPLODED VIEW OF VERTICAL ELECTRIC ACTUATION TRIM (52-477-X-103) —
Close

TFP1320 Page 7 of 14

NOTES: Nipple Select Appropriate Nipple Sizes per DV-5 Deluge Valve Size
1. Install subassemblies in alphabetical order. Number 1-1/2" (DN40) 2" (DN50) 3" (DN80) 4" (DN100) 6" (DN150) 8" (DN200)
2. See Figure 2 of TFP1305 for Valve Port 1 1/2" x Close 1/2" x 2" 1/2" x 1-1/2" 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
identification.
2 1/2" x Close 1/2" x Close 1/2" x 1-1/2" 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
3. Route all Tubing to Drip Funnel.
3 1/2" x 5" 1/2" x 5-1/2" 1/2" x 7" 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
4. When DV-5 trips, the Automatic Shut-Off Valve
4 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
shuts off the diaphragm chamber supply.
5 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 4-1/2" 1" x 6" 1" x 9" 1" x 12"
5. Nipples 1-5 vary in length relative to the Model
DV-5 size. Select per the table. All other nipples Main Drain
3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
packed unassembled shall be installed per the Size
appropriate trim exploded view, Figure 2A Part
1, 2, or 3.
VENT FITTING
(GREEN TINT)
WATERFLOW SYSTEM
PRESSURE ALARM DRAIN VALVE
SWITCH, ORDERED (NORMALLY
SEPARATELY CLOSED)
SOLENOID VALVE,
AUTOMATIC ORDERED SEPARATELY
3/4 INCH NPT (NORMALLY CLOSED)
DRAIN VALVE
CONNECTION FOR
WATER MOTOR
B 1/2 INCH CONDUIT
ALARM CONNECTION
FOR "ELECTRIC
NIPPLE DETECTION"
4 NIPPLE 4" (DN100)
DRIP 5 FLANGE x FLANGE
FUNNEL MODEL DV-5 NIPPLE
DELUGE VALVE 2
1-1/4 INCH NPT SHOWN
CONNECTION NIPPLE
NIPPLE TO DRAIN 3
1
A
MAIN DIAPHRAGM
DRAIN VALVE D CHAMBER
(NORMALLY PRESSURE
CLOSED) GAUGE
ALARM MAIN DRAIN
TEST VALVE CONNECTION
(NORMALLY (SIZED PER MANUAL
CLOSED) TABLE) CONTROL
STATION
SYSTEM AUTOMATIC
WATER DIAPHRAGM
SUPPLY
C CHAMBER SUPPLY SHUT-OFF VALVE
CONTROL VALVE (NORMALLY
PRESSURE OPEN)
GAUGE (NORMALLY
OPEN) 1/2 INCH NPT
CONNECTION FROM
WATER SUPPLY

FIGURE 2B
1-1/2 thru 8 INCH (DN40 thru DN200) MODEL DV-5 DELUGE VALVES
— OPERATIONAL COMPONENTS OF VERTICAL ELECTRIC ACTUATION TRIM —

• Water Supply Pressure Gauge fittings. The galvanized and brass trim
Technical • Diaphragm Chamber are intended for non-corrosive or cor-
Pressure Gauge rosive conditions, whereas the black
Data • Diaphragm Chamber Connections
trim is principally intended for use with
AFFF systems.
Approvals: • Manual Control Station
UL Listed, C-UL Listed, and FM Ap- • Main Drain Valve NOTE
proved. • System Drain Valve When the system pressure is greater
than 175 psi (12,1 bar), provision is to
Valve Trim: • Alarm Test Valve
The Vertical Electric Actuation Trim be made to replace the standard order
• Automatic Drain Valve 300 psi (20,7 bar) Water Pressure
(Fig. 2A/2B) and the Horizontal Elec-
tric Actuation Trim (Fig. 4) form a part Gauges, shown in Figure 2A/2B and 4
To ease field assembly of the trim ar- with separately ordered 600 psi (41,4
of the laboratory listings and approvals rangement, the vertical trim compo-
for the DV-5 Valve and is necessary for bar) Water Pressure Gauges.
nents are provided partially assem-
its proper operation. bled as shown in Figure 2B. The Electric Actuation Trim is required
Each package of trim includes the fol- for electric operation of the DV-5 Valve
The trim arrangement is provided with by a detection system consisting of
lowing items: galvanized, black, or brass nipples and electrical devices such as heat sensi-
Close

Page 8 of 14 TFP1320

Valve Nominal Installation Dimensions in Inches and (mm)


Size A B C D E F G H J K L M
1-1/2" 7.00 8.88 13.19 10.50 15.25 1.25 5.81 1.81 3.00 7.00 3.88 8.00
(DN40) (177,8) (225,4) (335,0) (266,7) (387,4) (31,8) (147,6) (46,0) (76,2) (177,8) (98,4) (204,0)
2" 7.13 9.13 13.19 10.50 15.56 0.94 6.00 2.00 3.00 7.00 3.00 8.63
(DN50) (181,0) (231,8) (335,0) (266,7) (395,3) (23,8) (152,4) (50,8) (76,2) (177,8) (76,2) (220,0)
3" 7.81 10.44 13.19 10.50 19.13 1.63 6.69 2.69 4.25 7.00 0.88 12.75
(DN80) (198,4) (265,1) (335,0) (266,7) (485,8) (41,3) (170,0) (68,3) (108,0) (177,8) (22,2) (324,0)
4" 10.00 11.75 14.31 10.50 22.13 1.75 8.56 4.44 6.25 7.13 0.63 15.75
(DN100) (254,0) (298,5) (363,5) (266,7) (562,0) (44,5) (217,5) (112,7) (158,8) (181,0) (15,9) (400,0)
6" 11.38 14.31 15.31 10.50 23.31 3.50 9.94 5.81 6.25 7.13 1.81 18.13
(DN150) (289,0) (363,5) (388,9) (266,7) (592,1) (88,9) (252,4) (147,6) (158,8) (181,0) (46,0) (460,4)
8" 12.00 16.00 16.25 10.50 25.50 1.75 10.75 6.50 6.25 7.13 7.38 22.50
(DN200) (304,8) (406,4) (412,8) (266,7) (647,7) (44,5) (273,1) (165,1) (158,8) (181,0) (187,3) (570,0)

* MINIMUM CLEARANCE.

A* B C* D*
SOLENOID
VALVE

1/2" NPS
DIAPHRAGM E*
CHAMBER SUPPLY
CONNECTING TRIM M
(FIELD FABRICATED) L

2" NPS 1-1/4" NPS


MAIN DRAIN DRAIN
H CONTROL K
VALVE
G J

LEFT VIEW FRONT VIEW


FIGURE 3
1-1/2 thru 8 INCH (DN40 thru DN200) MODEL DV-5 DELUGE VALVE
— VERTICAL ELECTRIC ACTUATION / NOMINAL INSTALLATION DIMENSIONS —

tive thermostats, smoke detectors, risdiction regarding installation criteria the DV-5 Diaphragm Chamber from
and/or electric manual pull stations. pertaining to electric actuation cir- becoming re-pressurized, and pre-
Information on the various types of cuitry. venting an inadvertent closing of the
separately ordered Solenoid Valves DV-5 during a fire event.
The Electric Actuation Trim is provided
that may be used with this trim pack-
with a Model ASV-1 Automatic Shut-
age is given in Technical Data Sheet
Off Valve (Item 5 - Fig. 2A and 4);
TFP2180. Nominal installation dimen-
consequently, the release circuit of the
sions for the Vertical Electric Actuation
releasing panel need only provide the
Trim are shown in Figure 3.
standard ten minutes of alarm condi-
tion intended to energize the Solenoid
NOTES
Valve to open. After the ten minute
Approval by Factory Mutual is contin-
duration, at which point should the So-
gent on the use of an FM Approved
lenoid Valve become de-energized
24VDC Solenoid Valve. FM only ap-
and close (especially while operating
proves solenoid valves for use in non-
under battery back-up), the Automatic
hazardous locations.
Shut-Off Valve will have already auto-
Consult with the Authority Having Ju- matically closed, thereby preventing
Close

TFP1320 Page 9 of 14

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa 9 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 23 1/4" 90° Elbow . . . . . . . . . 1 CH
Water Pressure Gauge . . 2 92-343-1-005 10 3/4" Swing Check Valve . 1 46-049-1-005 24 1/2" 90° Elbow . . . . . . . . . 8 CH
2 1/4" Gauge Test Valve . . 1 46-005-1-002 11 3/4" Angle Valve . . . . . . . 2 46-048-1-005 25 3/4" 90° Elbow . . . . . . . . . 1 CH
3 Model MC-1 Manual 12 Drip Funnel Connector . . 1 92-211-1-005 26 1/2" Tee . . . . . . . . . . . . . . 3 CH
Control Station . . . . . . . . . 1 52-289-2-001 13 Drip Funnel Bracket . . . . 1 92-211-1-003 27 1/2" x 1/4" x 1/2" Tee . . . . 3 CH
4 Model AD-1 Automatic 14 Drip Funnel . . . . . . . . . . . 1 92-343-1-007 28 3/4" Tee . . . . . . . . . . . . . . 2 CH
Drain Valve . . . . . . . . . . . 1 52-793-2-004 15 3/32" Vent Fitting . . . . . . . 1 92-032-1-002 29 3/4" x 1/2" x 3/4" Tee . . . . 2 CH
5 Automatic Shut-Off Valve, 16 1/4" x 18" Tubing . . . . . . . 1 CH 30 3/4" x 3/4" x 1/2" Tee . . . . 1 CH
Model ASV-1 . . . . . . . . . . 1 92-343-1-021 17 1/2" Tubing Connector . . 1 CH 31 1/4" x Close Nipple . . . . . 2 CH
6 Waterflow Pressure Ordered 18 1/2" x 12" Tubing . . . . . . . 1 CH 32 1/2" x Close Nipple . . . . . 3 CH
Alarm Switch . . . . . . . . . . 1 Separately 19 1/4" Plug. . . . . . . . . . . . . . 1 CH 33 1/2" x 1-1/2" Nipple . . . . . 11 CH
7 1/2" Ball Valve . . . . . . . . . 2 46-050-1-004 20 3/4" Plug. . . . . . . . . . . . . . 1 CH 34 1/2" x 2" Nipple . . . . . . . . 1 CH
8 1/2" Spring Loaded 21 1/2" Union . . . . . . . . . . . . 5 CH 35 1/2" x 2-1/2" Nipple . . . . . 4 CH
Check Valve . . . . . . . . . . 1 92-322-1-002 22 3/4" Union . . . . . . . . . . . . 2 CH 36 1/2" x 5" Nipple . . . . . . . . 2 CH
37 1/2" x 7" Nipple . . . . . . . . 1 CH
38 Select Nipple per Table . . 2 CH
33 33 E2
33 24 39 Select Nipple per Table . . 2 CH
33 40 3/4" x Close Nipple . . . . . 1 CH
24 5 39 E3
1 7 41 3/4" x 1-1/2" Nipple . . . . . 8 CH
E4 42 3/4" x 2" Nipple . . . . . . . . 1 CH
21 9
E1
2 8 26 43 3/4" x 4" Nipple . . . . . . . . 1 CH
19 (ORDERED
2" (DN50) 24 44 Select Nipple per Table . . 2 CH
SEPARATELY)
GROOVE x GROOVE 32 1
MODEL DV-5 34 33 E1 Solenoid Valve Per Data Ordered
31 DELUGE VALVE 37 Sheet TFP2180 . . . . . . . 1 Separately
31 24 21
33 SHOWN 33 E2 1/2" Tubing Connector . . 1 CH
21 E3 1/2" x 24" Tubing . . . . . . . 1 CH
23 21 32 26 E4 1/2" x 1-1/2" Nipple . . . . . 1 CH
36 33
27 33 27

21 Select Appropriate Nipple Sizes


35 35 3 Nipple per DV-5 Deluge Valve Size
Number
36 1-1/2" (DN40) 2" (DN50)
LOCATION 7 38 1/2" x Close 1/2" x 2"
FOR OPTIONAL 24 32 39 1/2" x 5" 1/2" x 5-1/2"
ELECTRICALLY 33 44 3/4" x 1-1/2" 3/4" x 2-1/2"
SUPERVISED 38
N.O. ALARM 29 24
CONTROL 24 17
22 41
VALVE 42 18
(BVS-3/4") 10 NOTES:
41 41 4
1. Electric Actuation Trim is comprised of
20 27 26 Items 1-44 plus Items E1-E4.
29 28 35 2. All Fittings and Nipples are galvanized
41 14
30 (Standard Order).
35 15
(GREEN 3. CH: Common Hardware.
6 43 TINT) 16 12 4. See Figure 2 of TFP1305 for Valve Port
(ORDERED identification.
SEPARATELY) 41
5. Route all Tubing to Drip Funnel, Item 14.
40
11 22 6. Horizontal Arrangement uses only 7 out of
41 41 44 13 8 of Item 24, and 10 out of 11 of Item 33.
11 Discard unused material.
28 25
41

FIGURE 4 — PART 1 OF 3
1-1/2 and 2 INCH (DN40 and DN50) MODEL DV-5 DELUGE VALVES
— EXPLODED VIEW OF HORIZONTAL ELECTRIC ACTUATION TRIM (52-477-X-209) —
Close

Page 10 of 14 TFP1320

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa 7 1/2" Ball Valve . . . . . . . . . 2 46-050-1-004 14 Drip Funnel Bracket . . . . 1 92-211-1-003
Water Pressure Gauge . . 2 92-343-1-005 8 1/2" Spring Loaded 15 Drip Funnel . . . . . . . . . . . 1 92-343-1-007
2 1/4" Gauge Test Valve . . 1 46-005-1-002 Check Valve . . . . . . . . . . 1 92-322-1-002 16 3/32" Vent Fitting . . . . . . . 1 92-032-1-002
3 Model MC-1 Manual 9 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 17 1/4" x 18" Tubing . . . . . . . 1 CH
Control Station . . . . . . . . . 1 52-289-2-001 10 3/4" Swing Check Valve . 1 46-049-1-005 18 1/2" Tubing Connector . . 1 CH
4 Model AD-1 Automatic 11 3/4" Angle Valve . . . . . . . 1 46-048-1-005 19 1/2" x 12" Tubing . . . . . . . 1 CH
Drain Valve . . . . . . . . . . . 1 52-793-2-004 12 1-1/4" Angle Valve . . . . . . 1 46-048-1-007 20 1/4" Plug. . . . . . . . . . . . . . 1 CH
5 Automatic Shut-Off Valve, 13 Drip Funnel Connector . . 1 92-211-1-005 21 3/4" Plug. . . . . . . . . . . . . . 1 CH
Model ASV-1 . . . . . . . . . . 1 92-343-1-021 22 1/2" Union . . . . . . . . . . . . 5 CH
6 Waterflow Pressure Ordered 23 3/4" Union . . . . . . . . . . . . 2 CH
Alarm Switch . . . . . . . . . . 1 Separately E2 24 1/4" 90° Elbow . . . . . . . . . 1 CH
25 1/2" 90° Elbow . . . . . . . . . 8 CH
35 35 25 E3 26 3/4" 90° Elbow . . . . . . . . . 1 CH
E4 27 1/2" Tee . . . . . . . . . . . . . . 3 CH
35 E1
25 28 1/2" x 1/4" x 1/2" Tee . . . . 3 CH
(ORDERED 29 3/4" Tee . . . . . . . . . . . . . . 1 CH
22 9 SEPARATELY)
34 30 3/4" x 1/2" x 3/4" Tee . . . . 2 CH
35 8 31 3/4" x 3/4" x 1/2" Tee . . . . 1 CH
42
1 5 32 1-1/4" x 3/4" x 1-1/4" Tee . 1 CH
7 25 35 1 33 1/4" x Close Nipple . . . . . 2 CH
20 3" (DN80) 37
34 1/2" x Close Nipple . . . . . 2 CH
2 GROOVE x GROOVE 25 27 22 35 1/2" x 1-1/2" Nipple . . . . .13 CH
MODEL DV-5 35
42 36 1/2" x 2-1/2" Nipple . . . . . 2 CH
33 DELUGE VALVE 22
33 37 1/2" x 3-1/2" Nipple . . . . . 1 CH
SHOWN 35 27
35 38 1/2" x 4" Nipple . . . . . . . . 1 CH
35 28 39 1/2" x 4-1/2" Nipple . . . . . 1 CH
24 22
35 40 1/2" x 5" Nipple . . . . . . . . 1 CH
39 41 1/2" x 5-1/2" Nipple . . . . . 1 CH
28
3 42 1/2" x 7" Nipple . . . . . . . . 2 CH
22
38 43 3/4" x Close Nipple . . . . . 3 CH
40 44 3/4" x 1-1/2" Nipple . . . . . 5 CH
41 45 3/4" x 2" Nipple . . . . . . . . 1 CH
34 46 3/4" x 4-1/2" Nipple . . . . . 1 CH
LOCATION 7 25 47 1-1/4" x 2" Nipple . . . . . . . 1 CH
FOR OPTIONAL 48 1-1/4" x 4" Nipple . . . . . . . 1 CH
25
ELECTRICALLY 35
SUPERVISED 35 18
E1 Solenoid Valve Per Data Ordered
N.O. ALARM 30 19 Sheet TFP2180 . . . . . . . 1 Separately
CONTROL 25
23 44 E2 1/2" Tubing Connector . . 1 CH
VALVE 45 E3 1/2" x 24" Tubing . . . . . . . 1 CH
(BVS-3/4") 10
E4 1/2" x 1-1/2" Nipple . . . . . 1 CH
44 44 4
21 28 27
NOTES:
30 29 36
44 1. Electric Actuation Trim is comprised of
31 15
36 16 Items 1-48 plus Items E1-E4.
(GREEN 2. All Fittings and Nipples are galvanized
6 48 TINT) 17 13 (Standard Order).
(ORDERED 3. CH: Common Hardware.
SEPARATELY) 44
43 4. See Figure 2 of TFP1305 for Valve Port
23 identification.
12
47 43 46 14 5. Route all Tubing to Drip Funnel, Item 15.
32 26 11 6. Horizontal Arrangement uses only 7 out of
43 8 of Item 25, and 12 out of 13 of Item 35.
Discard unused material.

FIGURE 4 — PART 2 OF 3
3 INCH (DN80) MODEL DV-5 DELUGE VALVES
— EXPLODED VIEW OF HORIZONTAL ELECTRIC ACTUATION TRIM (52-477-X-206) —
Close

TFP1320 Page 11 of 14

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa 10 3/4" Swing Check Valve . 1 46-049-1-005 23 1" Union . . . . . . . . . . . . . . 2 CH
Water Pressure Gauge . . 2 92-343-1-005 11 1" Angle Valve . . . . . . . . . 1 46-048-1-006 24 1/4" 90° Elbow . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . 1 46-005-1-002 12 2" Angle Valve . . . . . . . . . 1 46-048-1-009 25 1/2" 90° Elbow . . . . . . . . . 8 CH
3 Model MC-1 Manual 13 Drip Funnel Connector . . 1 92-211-1-005 26 1" 90° Elbow . . . . . . . . . . 1 CH
Control Station . . . . . . . . . 1 52-289-2-001 14 Drip Funnel Bracket . . . . 1 92-211-1-003 27 1/2" Tee . . . . . . . . . . . . . . 3 CH
4 Model AD-1 Automatic 15 Drip Funnel . . . . . . . . . . . 1 92-343-1-007 28 1/2" x 1/4" x 1/2" Tee . . . . 3 CH
Drain Valve . . . . . . . . . . . 1 52-793-2-004 16 3/32" Vent Fitting . . . . . . . 1 92-032-1-002 29 3/4" x 1/2" x 3/4" Tee . . . . 2 CH
5 Automatic Shut-Off Valve, 17 1/4" x 24" Tubing . . . . . . . 1 CH 30 1" x 1" x 1/2" Tee . . . . . . . 1 CH
Model ASV-1 . . . . . . . . . . 1 92-343-1-021 18 1/2" Tubing Connector . . 1 CH 31 1" x 3/4" x 1" Tee . . . . . . . 1 CH
6 Waterflow Pressure Ordered 19 1/2" x 24" Tubing . . . . . . . 1 CH 32 2" x 1" x 2" Tee . . . . . . . . 1 CH
Alarm Switch . . . . . . . . . . 1 Separately 20 1/4" Plug. . . . . . . . . . . . . . 1 CH 33 1/4" x Close Nipple . . . . . 2 CH
7 1/2" Ball Valve . . . . . . . . . 2 46-050-1-004 21 3/4" Plug. . . . . . . . . . . . . . 1 CH 34 1/2" x Close Nipple . . . . . 2 CH
8 1/2" Spring Loaded 22 1/2" Union . . . . . . . . . . . . 5 CH 35 1/2" x 1-1/2" Nipple . . . . .10 CH
Check Valve . . . . . . . . . . 1 92-322-1-002 36 1/2" x 2-1/2" Nipple . . . . . 3 CH
9 1/2" Y-Strainer . . . . . . . . . 1 52-353-1-005 E2 37 1/2" x 3" Nipple . . . . . . . . 1 CH
38 1/2" x 5" Nipple . . . . . . . . 2 CH
35 35 E3 39 1/2" x 6" Nipple . . . . . . . . 1 CH
25 E4 40 1/2" x 7" Nipple . . . . . . . . 2 CH
35 E1 41 Select Nipple per Table . . 2 CH
25 (ORDERED 42 Select Nipple per Table . . 2 CH
22 9 SEPARATELY) 43 Select Nipple per Table . . 2 CH
34
35 8 44 3/4" x 1-1/2" Nipple . . . . . 1 CH
43 45 3/4" x 2" Nipple . . . . . . . . 1 CH
5
7 25 35 1 46 Select Nipple per Table . . 2 CH
1
38 47 1" x Close Nipple . . . . . . . 5 CH
20 4" (DN100) 27 22 48 1" x 3" Nipple . . . . . . . . . . 1 CH
25 35
2 FLANGE x FLANGE 49 Select Nipple per Table . . 2 CH
MODEL DV-5 22 40 50 2" x 3" Nipple . . . . . . . . . . 1 CH
33 DELUGE VALVE 35 27 51 2" x 5" Nipple . . . . . . . . . . 1 CH
33 SHOWN
35 35 28
42 E1 Solenoid Valve Per Data Ordered
24 22 Sheet TFP2180 . . . . . . . 1 Separately
38 3 E2 1/2" Tubing Connector . . 1 CH
28 22 E3 1/2" x 24" Tubing . . . . . . . 1 CH
39
40 E4 1/2" x 1-1/2" Nipple . . . . . 1 CH

34
Select Appropriate Nipple Sizes
LOCATION 36 Nipple per DV-5 Deluge Valve Size
FOR OPTIONAL 7 25
25 No. 4" 6" 8"
ELECTRICALLY 35 18 (DN100) (DN150) (DN200)
41
SUPERVISED 41 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8 -1/2"
29 19
N.O. ALARM
CONTROL 25 42 1/2" x 2" 1/2" x 3" 1/2" x 3-1/2"
46 23 48 43 1/2" x 6-1/2" 1/2" x 7-1/2" 1/2" x 9"
VALVE 45
(BVS-3/4") 10 46 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
44 47 4 49 1" x 6" 1" x 9" 1" x 12"
21 28 27
29 NOTES:
31 37
51 15 1. Electric Actuation Trim is comprised of
16 30
36 Items 1-51 plus Items E1-E4.
(GREEN
50 2. All Fittings and Nipples are galvanized
6 TINT) 17 13 (Standard Order).
(ORDERED
SEPARATELY) 47 3. CH: Common Hardware.
12
47 4. See Figure 2 of TFP1305 for Valve Port
23
identification.
47 49 11 14 5. Route all Tubing to Drip Funnel, Item 15.
32 26
6. Horizontal Arrangement uses only 7 out of
47 8 of Item 25, and 2 out of 3 of Item 36.
Discard unused material.

FIGURE 4 — PART 3 OF 3
4, 6, and 8 INCH (DN100, DN150, and DN200) MODEL DV-5 DELUGE VALVES
— EXPLODED VIEW OF HORIZONTAL ELECTRIC ACTUATION TRIM (52-477-X-203) —
Close

Page 12 of 14 TFP1320

3/32" Vent Fitting. Brass per ASTM that it will not cause accidental dam-
Materials Of B16. age to property or danger to persons.

Construction Tubing Connector. Brass per ASTM


B16.
Step 7. Connect the Diaphragm
Chamber Supply Control Valve to the
inlet side of the system’s main control
NOTES Tubing. Type L copper per ASTM B88.
valve in order to facilitate setting of the
The galvanized or brass, nipples and
Pipe Fittings. Galvanized malleable DV-5 Valve (Ref. Figure 3).
fittings for the Valve Trim provide cor-
iron per ANSI B16.3 or cast iron per
rosion resistance and are intended to Step 8. Unused pressure alarm switch
ANSI B16.4; black malleable iron per
extend the life of the installation of the connections must be plugged.
ANSI B16.3 or cast iron per ANSI
DV-5 Valve when exposed to internal
B16.4; or, bronze per ANSI B16.15. Step 9. Conduit and electrical connec-
and external corrosive conditions. Al-
tions are to be made in accordance
though these selections are intended Pipe Nipples. Schedule 40 galvanized
with the requirements of the authority
to resist corrosion, it is recommended steel per ASTM A53 or A135; Sched-
having jurisdiction and/or the National
that the end user or other technical ule 40 black steel per ASTM A53 or
Electric Code.
expert familiar with conditions at the A135; or, Schedule 40 red brass pipe
proposed installation be consulted per ASTM B43. Step 10. Before a system hydrostatic
with respect to these selections for a test is performed in accordance with
given corrosive condition. NFPA 13 system acceptance test re-
Systems using a seawater or brackish
Installation quirements, the DV-5 Diaphragm
Chamber is to be depressurized; the
water supply require special consid- NOTES Automatic Drain Valve (Item 4, Fig. 2A
erations in order to extend the life of Proper operation of the Model DV-5 and 4) is to be temporarily replaced
the valve and trim. This type of system Deluge Valves depends upon their trim with a 1/2 inch NPT plug, the 3/32 inch
ideally should be configured with a pri- being installed in accordance with the Vent Fitting (16 - Fig. 2A and 4) is to be
mary source of clean fresh water (e.g., instructions given in this Technical temporarily replaced with a 1/4 inch
a pressurized water tank) and that only Data Sheet. Failure to follow the ap- NPT plug, and the Diaphragm Cover
upon system operation is the secon- propriate trim diagram may prevent Bolts must be uniformly and se-
dary water supply (seawater or brack- the DV-5 Valve from functioning prop- curely tightened using a cross-draw
ish water) allowed to enter the system. erly, as well as void listings, approvals, sequence. After tightening, double-
After the system operation, the system and the manufacturer’s warranties. check to make certain that all of the
should be thoroughly flushed with
The DV-5 Valve must be installed in a Diaphragm Cover Bolts are securely
clean fresh water. Following this rec-
readily visible and accessible location. tightened.
ommendation will increase the service
life of the DV-5 Valve and Valve Trim. The DV-5 Valve, associated trim, and
Pressure Gauges. Bronze bourdon wet pilot lines must be maintained at a Valve Setting
tube with brass socket. minimum temperature of 40°F/4°C.
Gauge Test Valve. Bronze body per Heat tracing of the DV-5 Valve or its Procedure
ASTM B584. associated trim is not permitted. Heat Steps 1 through 11 are to be per-
tracing can result in the formation of formed when initially setting the Model
Manual Control Station. Corrosion hardened mineral deposits that are ca-
resistant copper alloys and glass filled DV-5 Deluge Valve; after an opera-
pable of preventing proper operation. tional test of the fire protection system;
PTFE seals. Thermoplastic enclosure.
The Model DV-5 Deluge Valve is to be or, after system operation due to a fire.
Automatic Drain Valve. Brass body installed in accordance with the follow-
per ASTM B584, Type 440 stainless ing criteria: NOTE
steel or brass per ASTM B134 Ball, When the system is using either a
and galvanized steel inlet. Step 1. All nipples, fittings, and de- seawater or brackish water supply, it is
vices must be clean and free of scale recommended that the system be thor-
Automatic Shut-Off Valve. Brass and burrs before installation. Use pipe
body, cover, and center seat per UNS oughly flushed with clean fresh water.
thread sealant sparingly on male pipe Following this recommendation will in-
C36000, Type 316 stainless steel threads only.
spring, and Nylon fabric reinforced, crease the service life of the DV-5
natural rubber diaphragm per ASTM Step 2. The DV-5 Valve must be Valve and Trim.
D2000. trimmed in accordance with Figure Step 1. Close the Main Control Valve.
2A/2B and 4.
Ball Valve. Corrosion resistant copper Step 2. Close the Diaphragm Cham-
alloys and glass filled PTFE seals. Step 3. Care must be taken to ensure ber Supply Control Valve.
that check valves, strainers, globe
Spring Loaded Check Valve. Brass valves, etc. are installed with the flow Step 3. Open the Main Drain Valve,
body and buna-n seal. arrows in the proper direction. System Drain Valve, and all auxiliary
Y-Strainer. Bronze body per ASTM drains in the system. Close the System
Step 4. Drain tubing to the drip funnel Drain Valve and auxiliary drain valves
B584 and Type 304 stainless steel must be installed with smooth bends
screen. after water ceases to discharge. Leave
that will not restrict flow. the Main Drain Valve open.
Swing Check Valve. Bronze body per Step 5. The main drain and drip funnel
ASTM B584 and buna-n seal. Step 4. Depress the plunger of the
drain may be interconnected provided Automatic Drain Valve to verify that it
Angle Valve. Bronze body per ASTM a check valve is located at least 12 is open and that the DV-5 Valve is
B584 and nitrile disc (Teflon disc for 2 inches (300 mm) below the drip funnel. completely drained.
inch size valve). Step 6. Suitable provision must be Step 5. Clean the Strainer in the Dia-
made for disposal of drain water. phragm Chamber Supply connection
Drainage water must be directed such
Close

TFP1320 Page 13 of 14

by removing the clean-out plug and opened, the pressure on the Dia- affected fire protection systems must
strainer basket. The Strainer may be phragm Chamber may increase. This first be obtained from the proper
flushed out by momentarily opening increase in pressure is normal, and if authorities and all personnel who may
the Diaphragm Chamber Supply Con- the pressure is greater than 250 psi be affected by this action must be no-
trol Valve. (17,2 bar), the pressure is to be re- tified. Reset the Model DV-5 Deluge
lieved by partially and temporarily Valve in accordance with the Valve
Step 6. Reset the actuation system.
opening the Manual Control Station; Setting Procedure section.
Manual Actuation — Push the operat- however, do not allow the pressure as
ing lever up; however, do not close the indicated on the Diaphragm Chamber Annual Operation Test Procedure
hinged cover at this time. Pressure Gauge to drop below the Proper operation of the DV-5 Valve
supply pressure shown on the Water (i.e., opening of the DV-5 Valve as dur-
Electric Actuation — Reset the electric ing a fire condition) must be verified at
Supply Pressure Gauge, since this ac-
detection system in accordance with least once a year as follows:
tion may result in tripping of the DV-5
the manufacturer’s instructions to de-
Valve.
energize the solenoid valve.
After setting a fire protection system, Step 1. If water must be prevented
Step 7. Open the Diaphragm Chamber from flowing beyond the riser, perform
notify the proper authorities and ad-
Supply Control Valve and allow time for the following steps.
vise those responsible for monitoring
full pressure to build up in the Dia-
proprietary and/or central station
phragm Chamber. • Close the Main Control Valve. Open
alarms.
Step 8. Operate (open) the Manual the Main Drain Valve.
Control Station to vent trapped air from • Open the Main Control Valve one
the Diaphragm Chamber. If necessary, Care and turn beyond the position at which
first open the hinged cover, and then water just begins to flow from the
fully pull down on the operating lever. Maintenance Main Drain Valve.
SLOWLY close the operating lever, by • Close the Main Drain Valve.
pushing it up, after aerated water The following procedures and inspec-
ceases to discharge from the Manual tions must be performed as indicated,
in addition to any specific require- Step 2. Test the deluge releasing
Control Station drain tubing. Close the panel in accordance with the manufac-
hinged cover and insert a new break ments of the NFPA, and any impair-
ment must be immediately corrected. turer’s instructions to energize the so-
rod in the small hole through the top of lenoid valve.
the enclosing box. The owner is responsible for the in-
Step 9. Inspect the drain connections spection, testing, and maintenance of NOTE
from the Manual Control Station and their fire protection system and de- Be prepared to quickly perform Steps
Solenoid Valve. Any leaks must be cor- vices in compliance with this docu- 3, 4, and 5, if water must be prevented
rected before proceeding to the next ment, as well as with the applicable from flowing beyond the riser.
step. standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in Step 3. Verify that the DV-5 Valve has
Step 10. Verify the ability for the DV-5 addition to the standards of any tripped, as indicated by the flow of
Diaphragm to hold pressure as fol- authority having jurisdiction. The in- water into the system.
lows: stalling contractor or product manufac- Step 4. Close the system’s Main Con-
With the diaphragm chamber pressur- turer should be contacted relative to trol Valve.
ized per Step 8, temporarily close the any questions.
Step 5. Close the Diaphragm Cham-
Diaphragm Chamber Supply Control It is recommended that automatic ber Supply Control Valve.
Valve, and monitor the Diaphragm sprinkler systems be inspected,
Chamber Pressure Gauge for a drop in tested, and maintained by a qualified Step 6. Reset the DV-5 Deluge Valve
pressure. Inspection Service in accordance with in accordance with the Valve Setting
local requirements and/or national Procedure.
If a drop in pressure is noted, the DV-5
Diaphragm is to be replaced and/or codes.
Quarterly Waterflow Alarm Test
any leaks must be corrected before Procedure
proceeding to the next step. NOTES
Some of the procedures outlined in Testing of the system waterflow alarms
If the Diaphragm Chamber Pressure this section will result in operation of must be performed quarterly. To test
Gauge indicates no drop in pressure, the associated alarms. Consequently, the waterflow alarm, open the Alarm
re-open the Diaphragm Chamber Sup- notification must first be given to the Test Valve, which will allow a flow of
ply Control Valve and proceed to the owner and the fire department, central water to the Pressure Alarm Switch
next step. station, or other signal station to which and/or Water Motor Alarm. Upon satis-
the alarms are connected. factory completion of the test, close
Step 11. Slowly open the Main Control the Alarm Test Valve.
Valve. Close the Main Drain Valve as When the system is using either a
soon as water discharges from the seawater or brackish water supply, in- Quarterly Solenoid Valve Test Pro-
drain connection. Observe the Auto- ternal and external inspection of the cedure For Electric Actuation
matic Drain Valve for leaks. If there are DV-5 Valve and Trim is essential. Proper operation of the Solenoid Valve
leaks, determine/correct the cause of Parts showing any signs of corrosion for electric actuation must be verified
the leakage problem. If there are no must be replaced to ensure the integ- at least quarterly as follows:
leaks, the DV-5 Valve is ready to be rity of the system.
placed in service and the Main Control Step 1. Close the Main Control Valve.
Valve must then be fully opened. Before closing a fire protection system
main control valve for maintenance Step 2. Open the Main Drain Valve.
NOTES work on the fire protection system that Step 3. Test the deluge releasing
When the Main Control Valve is it controls, permission to shut down the panel in accordance with the manufac-
Close

Page 14 of 14 TFP1320

turer’s instructions to energize the so-


lenoid valve. Limited Ordering
Step 4. Verify that the flow of water
from the Solenoid Valve drain connec- Warranty Procedure
tion increases to a full flow. Products manufactured by Tyco Fire NOTE
Step 5. Verify that the Diaphragm Products are warranted solely to the Part Numbers for factory pre-trimmed
Chamber pressure has decreased to original Buyer for ten (10) years Model DV-5 Valves are provided in the
below 25% of the water supply pres- against defects in material and work- Price Book.
sure. manship when paid for and properly
installed and maintained under normal 4 and 6 Inch (DN100 and DN150)
Step 6. Reset the electric detection use and service. This warranty will ex- DV-5 Semi-Preassembled Vertical
system in accordance with the manu- pire ten (10) years from date of ship- Electric Actuation Trim:
facturer’s instructions to de-energize ment by Tyco Fire Products. No war- Specify: (specify size and finish — gal-
the solenoid valve. Check the Solenoid ranty is given for products or vanized is standard) Semi-Preassem-
Valve drain for leaks. Any leaks must components manufactured by compa- bled Vertical Electric Actuation Trim for
be corrected before proceeding to the nies not affiliated by ownership with Model DV-5 Deluge Valves, P/N (spec-
next step. Tyco Fire Products or for products and ify).
Step 7. Slowly open the Main Control components which have been subject
Valve. Close the Main Drain Valve as to misuse, improper installation, corro- 1-1/2 & 2 Inch Galvanized . P/N 52-477-2-109
sion, or which have not been installed, 1-1/2 & 2 Inch Black . . . . . . P/N 52-477-1-109
soon as water discharges from the 1-1/2 & 2 Inch Brass . . . . . . P/N 52-477-3-109
drain connection. Observe the Auto- maintained, modified or repaired in ac-
matic Drain Valve for leaks. If there are cordance with applicable Standards of 3 Inch Galvanized . . . . . . . . P/N 52-477-2-106
leaks, determine/correct the cause of the National Fire Protection Associa- 3 Inch Black. . . . . . . . . . . . . P/N 52-477-1-106
the leakage problem. If there are no tion, and/or the standards of any other 3 Inch Brass . . . . . . . . . . . . P/N 52-477-3-106
leaks, the DV-5 Valve is ready to be Authorities Having Jurisdiction. Mate-
4, 6 & 8 Inch Galvanized . . P/N 52-477-2-103
placed in service and the Main Control rials found by Tyco Fire Products to be 4, 6 & 8 Inch Black . . . . . . . P/N 52-477-1-103
Valve must then be fully opened. defective shall be either repaired or 4, 6 & 8 Inch Brass . . . . . . . P/N 52-477-3-103
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as- DV-5 Unassembled Electric Actua-
sumes, nor authorizes any person to tion Trim for Vertical or Horizontal
assume for it, any other obligation in Installation:
connection with the sale of products or
Specify: (specify size and finish — gal-
parts of products. Tyco Fire Products
vanized is standard) Unassembled
shall not be responsible for sprinkler
Electric Actuation Trim for vertical or
system design errors or inaccurate or
horizontal installation Model DV-5 Del-
incomplete information supplied by
uge Valves, P/N (specify).
Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE 1-1/2 & 2 Inch Galvanized . P/N 52-477-2-209
1-1/2 & 2 Inch Black . . . . . . P/N 52-477-1-209
PRODUCTS BE LIABLE, IN CON- 1-1/2 & 2 Inch Brass . . . . . . P/N 52-477-3-209
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE- 3 Inch Galvanized . . . . . . . . P/N 52-477-2-206
ORY, FOR INCIDENTAL, INDIRECT, 3 Inch Black. . . . . . . . . . . . . P/N 52-477-1-206
SPECIAL OR CONSEQUENTIAL 3 Inch Brass . . . . . . . . . . . . P/N 52-477-3-206
DAMAGES, INCLUDING BUT NOT 4, 6 & 8 Inch Galvanized . . P/N 52-477-2-203
LIMITED TO LABOR CHARGES, RE- 4, 6 & 8 Inch Black . . . . . . . P/N 52-477-1-203
GARDLESS OF WHETHER TYCO 4, 6 & 8 Inch Brass . . . . . . . P/N 52-477-3-203
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH Accessories:
DAMAGES, AND IN NO EVENT Refer to the Technical Data Sheets for
SHALL TYCO FIRE PRODUCTS’ LI- the following, as applicable, for details
ABILITY EXCEED AN AMOUNT and additional accessories:
EQUAL TO THE SALES PRICE.
600 PSI Water
THE FOREGOING WARRANTY IS Pressure Gauge . . . . . . P/N 92-343-1-004
MADE IN LIEU OF ANY AND ALL Solenoid Valve for Elec-
OTHER WARRANTIES EXPRESS OR tric Actuation . . . . . . . . . See TFP2180
IMPLIED, INCLUDING WARRANTIES Model PS10-2A
Potter Electric
OF MERCHANTABILITY AND FIT- Waterflow
NESS FOR A PARTICULAR PUR- Pressure
POSE. Alarm Switch . . . . . . . . . P/N 2571
Model WMA-1 Water
Motor Alarm . . . . . . . . . P/N 52-630-1-001

Replacement Trim Parts:


Specify: (description) for use with
(Model DV-5 Deluge Valve, P/N (see
Figure 2A or 4).