Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Manufacturing Data Sheet: Low Voltage XLPE Cable Design Code: LVIS09AXSFY23.5C120SA001S Date: Rev No.

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Manufacturing Data Sheet: Low Voltage XLPE Cable

Design Code : LVIS09AXSFY23.5C120SA001S


Date : Rev No. :

S.No Particulars 3.5 X 120 MM²


1 Name of Manufacturer Polycab Wires Pvt. Ltd, Daman
2 Type of cable A2XFY
3 Voltage Grade V 1100
4 No of cores X size in sqmm 3.5 X 120
5 Conductor
H2/H4 Grade Aluminium as per Class 2 of IS:
a) Material
8130/84,latest
Max. d.c. resistance of conductor at 20° C
b) 0.253
(ohm/km) Main
Neutral 0.443
c) Shape of the conductor Stranded Compacted Sector
6 Insulation
a) Material XLPE as per IS 7098(Pt-1)/88, Latest
b) Nominal thickness (mm) Main 1.2
Neutral 1.1
c) Core Identification Red,Yellow, Blue & Black
7 Inner Sheath
a) Material Wrapping of Tapes
b) Minimum thickness (mm) 0.4
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Flat Strip
c) Nominal size of armour (mm) 4.0 x 0.8
9 Outer Sheath
a) Material Extruded PVC Type 'ST2' as per IS:5831/84
b) Thickness (mm) 1.72 (Min.)
c) Colour of outer sheath. Black
10 Electrical Parameters
Max. a.c. resistance of conductor at 90° C
a) 0.325
(ohm/km)
b) Calculated Cable reactance (ohm/km) 0.0713
c) Impedance of cable (ohm/km) 0.333
d Approx. Cable Capacitance (mfd/km) 0.67
S.No Particulars 3.5 X 120 MM²

Maximum conductor temperature under


11 90°C
normal operating conditions
Maximum conductor temperature at the
12 250°C
termination of short circuit
Short Circuit rating of conductor for the
13 11.34
duration of 1 sec (kA)

14 Continuous Current carrying capacities :-


(a) In Ground at 30°C (A) 223
(b) In Air at 40°C (A) 249
IS 8130/84,IS 7098 Part I/88, IS 5831/84, IS
15 Applicable Standard
3975/88 etc. with latest up to date amendments

16 Nominal overall diameter of the cable in mm 39.0 ± 2.0

17 Minimum bending radius 12 times Overall diameter


18 Max. Tensile strength

(i) for Cables pulled with stocking (Newtons) 9 x D², D is the cable OD in mm

ii) for Cables pulled with pulling eyes (N) 12,900

19 Embossing POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE


YEAR POLYCAB ELECTRIC 1100 VOLTS GRADE
XLPE , CABLE SIZE, CABLE TYPE WITH
20 Printing
SEQUENTIAL MARKING at every one meter
interval.
Note:-The values given above are subject to tolerances as per the relevant standards.