ISO 9001
The flame detectors are designed for use with our burner controls, for the super-
vision of gas and oil flames.
The QRA... and this Data Sheet are intended for use by OEMs which integrate the
flame detectors in their products.
Use
The flame detectors are used for the supervision of gas flames, yellow- or blue-burning
oil flames and for ignition spark proving.
Type reference For use with burner control type Operating mode
QRA2..., QRA10... LGB2... / LGB4... with AGQ1... Intermittent
LFL...
LFE1...
LFE10...
LMG... with AGQ2...
QRA53..., QRA55... LGK16... Continuous
LGI16...
CC1N7712en
Siemens Building Technologies
08.05.2003 HVAC Products
Warning notes
• Before performing any wiring changes in the connection area of the detector, com-
pletely isolate the equipment from the mains supply (all-polar disconnection)
• Ensure protection against electric shock hazard by providing adequate protection
for the terminals
• Check to ensure that wiring is in an orderly state
• Halogen lamps, welding equipment, special lamps or ignition sparks may produce
sufficient radiation for the detector’s UV cell to ignite. X-rays and gamma radiation
can also generate erroneous flame signals
• Fall or shock can adversely affect the safety functions. Such units may not be put
into operation, even if they do not exhibit any damage
Mounting notes
• Ensure that the relevant national safety regulations are complied with
• Mounting work must be carried out by qualified staff
Installation notes
2/8
22 23 LGK16...
23 22 LFL1...
15 13 LFE1...
7712v01/1001
Legend 1) Connection of microammeter across adapter AGQ1... / AGQ2... and flame detector
A Incidence of radiation
M Microammeter (DC), internal resistance ≤ 5000 Ω
C Electrolytic capacitor 100...470 µF, DC 10...25 V
Certificate
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity) 89 / 336 EEC
ISO 9001: 2000 ISO 14001: 1996 Valid for all Valid only for QRA2...
Cert. 00739 Cert. 38233 QRA... and QRA10...
3/8
Disposal notes
The flame detector contains electrical and electronic components and may not be dis-
posed of together with household waste.
Local and currently valid legislation must be observed.
Mechanical design
Flame detectors Plastic housing, metalized to prevent static charging caused by the air flow from the
QRA2... fan. For direct mounting on the burner. The detectors can be supplied with or without
securing flange and clamp (refer to «Type summary»).
Flame detectors Die-cast aluminium housing with a 1 in. mounting coupling (D) and a connection facility
QRA10... for cooling air. The housing of this detector has a bayonet fitting which allows it to be
secured either directly to the mounting coupling or to the glass holder AGG06. The
mounting coupling can be screwed to a viewing tube or to the ball head AGG07. The
Pg cable gland can be removed and replaced, if some other detector cable shall be
used.
Flame detectors The detector’s UV cell is located behind a swiveling shutter at the front end of the de-
QRA5... tector tube which is flanged to the housing. A quartz glass window protects the tube
and the shutter against dirt. The detector’s housing accommodates a stepper motor to
drive the shutter and the electronics to control the shutter. Using the adapter AGG16.C,
this flame detector can be mounted either directly on the burner, on a viewing tube or
on a combustion chamber viewing hole.
Plug AGM19 Plug AGM19 complete with cable for the connection of flame detectors QRA53... and
QRA55...
Adapter AGG16.C Adapter AGG16.C for QRA53..., QRA55..., made of die-cast aluminium with a 1 in.
mounting coupling. The mounting coupling (D) is attached to the housing with a bayo-
net fitting.
QRA5...
AGG16.C
AGG03
7712m08/0797
AGG06
AGG02
AGG06
D
QRA5... with AGG16.C and AGG06
AGG05
7712z05/0403
AGG07
Note AGG03 or AGG02 can also be fitted in the 1 in. mounting coupling (D) of the AGG16.C
(or QRA10...). An adapter combination with glass holder AGG06, mounting coupling
and ball joint for QRA53..., QRA55... and QRA10... is possible.
4/8
AGG16.C AGG16.C
AGG03! AGG02
AGG06 AGG06
AGG02 !
7712z06/0403
AGG03
7712z07/0403
AGG06 AGG06
Correct Wrong
AGG06 has a bayonet fitting with which it is attached either to the housing of adapter
AGG16.C or to the housing of flame detector QRA10... and the mounting coupling.
By undoing the bayonet fittings on both sides, the AGG06 glass holder(s) can be easily
detached from the combination of QRA10... or AGG16.C and QRA53..., QRA55....
This facilitates straightforward cleaning of the glass or lens without having to remove
them from the glass holder AGG06.
The intermediate rings are used for the smooth running of the bayonet fittings, espe-
cially where – after removal of the flame detector – the hole to the combustion cham-
ber serves as a viewing tube.
By fitting the intermediate ring to the appropriate bayonet connection, the combination
can be undone where required by rotating the housing of the QRA10... or AGG16.C
Quartz glass lens AGG03 with spring washer and O-ring for increasing the sensitivity.
AGG03
Heat insulation glass Heat insulation glass AGG02 with spring washer and O-ring, offering the same mount-
AGG02 ing choices as with the AGG03.
This heat insulation glass is required on applications where the temperature at the
flame detector exceeds 80 °C.
Mounting coupling (D) Using the bayonet fitting, the 1 in. mounting coupling can be attached either to the
AGG06, the AGG16.C or the flame detector QRA10....
The mounting coupling is supplied with the QRA10... or AGG16.C.
Nipple AGG05 1 in. nipple AGG05 for connecting the mounting coupling (D) to the ball head AGG07.
5/8
Flame detectors Type reference Sensitivity Flange and Terminal cover Spare UV tube
clamp
QRA2 without
QRA2(1) normal with black 4 502 1131 0
QRA2.9 ²) without
QRA2M high without green 4 502 4065 7
QRA2M(1) with
QRA10.C normal --- --- 4 502 1131 0
QRA10M.C high 4 502 4065 7
Note All QRA5... are delivered complete with clamp. Use of the detector requires a connect-
ing cable AGM19 (refer to «Accessories» for QRA5...).
6/8
Technical data
General detector data Average life of UV cell approx. 10,000 hours at max. 50 °C,
higher ambient temperatures reduce con-
siderably the cell’s life
Perm. combustion chamber pressure
- QRA10... max. 50 mbar
- QRA10... + AGG03 or AGG02 max. 500 mbar
Degree of protection
- QRA2... IP 40
- QRA10... IP 54
- QRA53..., QRA55... IP 54
Mounting position optional
Weight
- AGG01 approx. 10 g
- AGG02 approx. 10 g
- AGG03 approx. 10 g
- AGG05 approx. 170 g
- AGG06 approx. 160 g
- AGG07 approx. 1330 g
- AGG16.C approx. 650 g
- QRA2... approx. 60 g
- QRA10... approx. 740 g
- QRA10... + AGG03 approx. 750 g
- QRA53..., QRA55... approx. 900 g
Ignition cable (only QRA2...) 2 x 0.75 mm²; 5.1 mm dia.
Function
With this type of flame supervision, the UV radiation emitted by gas or oil flames is
used to generate the flame signal.
The radiation detector consists of a UV-sensitive cell with 2 electrodes, which ignite
when illuminated with radiation in the 190...270 nm range of the spectrum, thereby
triggering a current in the flame detector circuit.
The UV cell does not respond to glowing firebrick in the combustion chamber, daylight
or light from the boiler room illumination.
7/8
Dimensions in mm
QRA2... QRA10... AGG02
97 87 22,8
10
25...50 2,5
30
M4
SW20
52
18
66
22,5
48
SW22
18
120
7712m07/0597
''
7712M04
8
3
QRA5...
R1 ''
7712m02/0997
UV
Pg13,5
65
4 241 88550 QRA5... with AGG05, AGG06, AGG07, AGG16.C and AGM19 AGG03
36 22,8
24.
3
R2 R4
7
R0.3
R2
30
AGG16.C
25°
15
3
7712m09e/1001
7712M03
Company logo to 3 10 18
LN 3 8380 0102
0.2 mm elevated 24 D
48
4 241 8898 0
36
18
R4
7
25°
30
15
7712m01/0403
3
7712m10e/1001
Incidence of radiation Clamp for direct mounting on the burner or the AGG16.C