Manual Servicio Chiller de Reveladora
Manual Servicio Chiller de Reveladora
Manual Servicio Chiller de Reveladora
T11021
This manual
Products covered
This manual is valid for the cooler units from Serial No: 000001
The serial number is specified on the nameplate located on the cooler unit cover.
#
This manual is for Service Technicians only.
Always read the Safety Instruction Manual part No 21741 before installing the
equipment.
Other manuals
Please also see the Standard Capacity Cooler User Manual stored on the enclosed CD.
#
Keep manuals with the machine for reference at all times.
Reservations
• This manual was written and illustrated using the best possible information
available at the time of publication.
• Any differences between this manual and the equipment reflect improvements
introduced after the publication of the manual.
• Changes, technical inaccuracies and typographic errors will be corrected in
subsequent editions.
• As a part of our policy of continuous improvement, we reserve the right to alter
design and specifications without further notice.
• This equipment generates, uses and can radiate radio frequency energy and if not
installed and used in accordance with this manual, may cause harmful interference
to radio communications.
$
Do not turn the unit upside down or place it at one of the sides.
Explanation
Approvals
• The equipment is manufactured according to legal demands. For compliance with
the requirements the equipment is tested by Underwriters Laboratories or other
accredited authority.
• Approvals will appear from the labels attached to the name plate.
Installation
• It is the responsibility of the owner and operator/s of this equipment, that the
installation is made in accordance with local regulations, and by engineers
authorized to carry out plumbing and electrical installations.
• Installation, service and repair must be performed only by service technicians who
are trained in servicing the equipment. The installation procedure and requirements
are described later in this manual.
• The manufacturer cannot be held responsible for any damage caused by incorrect
installation of this cooler.
• The unit is only for installation in a restricted access location.
Technical data
• Observe technical data from the equipment name plate located as specified on page
0-2 in this manual.
All disposal of parts from the machine must be made according to local regulations
with special regards to following parts:
#
IMPORTANT! Before disposal of the cooler unit the refrigerant system must
be emptied and refrigerant disposed of by a company authorized in handling
refrigerants and in accordance with local regulations.
Service assistance
If help is needed to correct any problem with the equipment, please contact your local
supplier.
Table of contents
Mechanical
Refrigerant
Type: R134A
All models: 180 g (6.3 oz)
#
Repair and maintenance of the closed system for refrigerant and handling of
refrigerants must be done only by a company authorized in handling
refrigerants.
Design pressure
High: 365 PSIG (24.8 bar)
Low: 88 PSIG ( 6.0 bar)
Operating temperatures
Developer: 68 - 95°F (20 - 35°C)
Room temperature
Min./Max.: 41 - 81°F (5 - 27°C)
(RH)
85%
60%
15%
(TEMP)
15°C 25°C 27°C
59°F 77°F 81°F
To ensure the reliable operation of the unit, the relative humidity (RH) and the
ambient temperature (T) in the room must fulfil the diagram shown above
"
Prevent the formation of condensation by avoiding humidity or temperature
variations.
Dimensions
Width: 310 mm (12.2”)
Height (typical): 370 mm (14.6”)
Length: 590 mm (23.2”)
Weight
Empty: 32.0 kg (70.5 lbs)
Full with water: 41.0 kg (90.4 lbs)
Electrical
Power consumption/supply
Power is supplied through the processor. The processor is equipped with a power
outlet socket for easy connection of the cooler unit to the plate processors power
supply.
Supply
Operating : 3.75 Amps, 750 Watt (1880 BTU/hour)
The unit must be provided with protective earthing conductor 230V+PE, 50/60 Hz.
Fuses
Fuse protection is located in the plate processor :
Please also see the plate processor service manual for details.
Noise level
Less than : 70 dB (A)
Automatic control
The Universal Cooler is an automatically working device designed to control the
temperature in the developer bath of a plate processor in cases where the temperature
is difficult to control due to high ambient temperatures etc.
The cooler unit consists of a water tank containing refrigeration coils. In a situation
where the developer temperature is higher than the developer temperature set point, as
set on the processor control panel, the unit provides chilled water pumped from the
cooler unit through a cooling tube situated in the bottom of the processor developer
tank. This will remove the excess heat from the developer and subsequently reduce the
developer temperature until the developer temperature set point is reached.
The unit is connected to power supply through the processor or through a connector
for an external power supply. The cooler will start automatically when power is
switched on to the processor and the developer bath exceeds the set temperature level.
The cooler will stop automatically when the developer bath temperature has been
cooled down to the set temperature.
When power is supplied through the processor, the cooler unit is automatically
disconnected when power to the processor is disconnected.
PROCESSOR
DEVELOPER SECTION
COUPLING
HEAT EXCHANGER COMPRESSOR
(evaporator)
PRESSURE SWITCH
OVERFLOW
M HEAT EXCHANGER
(condensor)
WATER
TANK FAN
M AIR INLET
DRYER FILTER
M
PUMP
COOLING UNIT
Start up
Before starting up the equipment, make installation according to the descriptions in
Part 3 of this manual.
Fill the water tank with clean cold water as illustrated in the User Manual.
Once the processor has been switched on and the cooler unit is up running the water
level may decrease due to circulation filling up hoses etc. It will then be necessary to
make adjusting fill-up to obtain correct level.
Shut down
At the end of the day switch off the cooler/processor on the processor's control panel.
Temperature setting
The cooler unit is equipped with a 3 = 6°C
thermostat which main purpose is to
prevent freezing of the water. (42.8°F)
The thermostat is default set to a
temperature of 5°C (41°F). This setting 78
12
56
should not be changed. 34
T31612
Part 3: Installation
$
Do not turn the unit upside down or place it at one of the sides. If the unit
has by accident been turned upside down, it must rest for 4 hours before
starting it.
Safety
Personnel receiving and installing the equipment should be thoroughly familiar with
all aspects of it’s operation and be proficient in it’s installation, maintenance and
service.
Follow the safety precautions described in the Safety manual also delivered with the
equipment.
Unpacking
Think about possible re-use of packaging material.
Carefully unpack the cooler unit - do not turn it upside down - and check that all parts
are in good condition.
Delivered with the cooler unit are the different parts needed for the installation.
Tools
Standard tools are sufficient.
Air inlet
For efficient operation, free space around the unit must be min. 20 cm (7’9”).
All air inlets/outlets on the unit must not be blocked by waste chemical containers etc.
$
It is of upmost importance to ensure free circulation of air around the cooler.
Otherwise the unit will be too hot which consequently will result in reduced
efficiency and risk of unnecessary operating problems.
See also illustrations regarding free circulation in the Standard Capacity Cooler User
Manual.
Installation site
• This cooler unit is for indoor installation only. Temperatures and relative humidity
as specified in Part 1 must be taken into consideration.
• One cooler should be connected to one processor only.
• Do not site the cooler adjacent to a warm air heating duct or any form of heating.
• Easy access should be provided for filling and cleaning the cooler.
• The floor must be absolutely flat.
• Carefully position the unit and ensure that the unit is level on the floor.
• The flexible hoses used with the cooler allow the unit to be installed either
underneath, or to the rear of the processor.
• The processor and the cooler unit must be installed on the same floor, and ideally
within the hose lengths provided on the processor, or if part of a retrofit kit, the
lengths of hose supplied with the cooler unit. Make sure hoses to not have sharp
bends or form water traps. This will ensure correct circulation of the chilled water.
• Please note that the temperature inside a closed stand of a processor might be
considerably higher than the room temperature. If locating the cooler inside a closed
stand it is essential to ensure a minimum clearance of 10 cm (3.9") between the floor
and the bottom edge of the processor base. If this clearance cannot be achieved then
the cooler should be placed outside of the processor.
Electrical installation
#
Installation should be made according to local regulations and by engineers
authorised to carry out electrical installations.
#
The processor is Class 1 equipment. Therefore, the processor must be
connected to earth before operation to avoid electrical shocks.
Installation procedures
$
The cooler unit is designed for connection to a plate processor only.
The cooler unit is supplied with the correct cable harness to connect to the processor.
Make the installation by following the procedure below matching the processor in
question.
General
#
Always unplug the unit from the processor or power supply before carrying
out any cleaning or maintenance procedures etc.
Repair and maintenance of the closed system for refrigerant and handling of
refrigerants must be done only by a company authorized in handling
refrigerants. Never use any other refrigerants than specified for this unit.
Refrigerant type is specified in Part 1.
$
Never turn the unit upside down or place it on one of the sides. If the unit by
accident has been turned upside down, let it rest 4 hours before starting it.
The cooler unit is fully automatic and designed to operate satisfactorily with the
minimum of maintenance.
Following the directions in this chapter will ensure that your equipment will operate
efficiently. Performing cleaning and maintenance on a schedule basis minimizes the
chance of equipment failure and loss of processing quality.
Cleaning and maintenance procedures should be performed only by persons who are
familiar with the equipment.
Daily
Check water level in tank - top up if necessary.
Monthly
• Make sure to switch off/disconnect the power supply to the cooler unit.
• Clean all external surfaces using a moist cloth.
• Remove all dust and fluff from all of the ventilation slots and the condenser fins
with a stiff (non-metal) brush. Vacuum the debris from the fins.
"
Care should be taken not to damage the fins of the condenser.
• Inspect visible parts for damage. If any damage is found that impedes normal
operation, contact your local service centre.
• Visually check hoses and hose connections for leaks and damages. Tighten any loose
connectors.
• After cleaning and inspection make sure that the cooler top cover is secured by
screws.
For references see Part 4 “Cleaning and Maintenance” and Appendix A “Electrical
Diagrams”.
#
Always unplug the cooler unit from the processor or power supply before
carrying out any repair, cleaning or maintenance procedures etc.
Tests, adjustments etc. with power connected to the unit must be made by
trained and authorized service personnel only.
Never open the closed system with refrigerant. If necessary, this must be
done only by a company authorized in handling refrigerants.
$
Always remember that the cooling unit requires air. Dirty or blocked
condenser fins or aperture grills or lack of air space around the cooler can
result in part or total failure of the unit.
Never turn the unit upside down or place it on one of its sides. If the unit by
accident has been turned upside down, let it rest for 4 hours before starting it.
If there appears to be a fault with the unit, contact your local service centre.
If the equipment should fail to function please check as suggested on the next
page and correct if possible.
CHILLED WATER PUMP • The water level is too low. • Check the water level and
FAILS TO PUMP top up if necessary.
• Processor is switched off. • Check the On/Off switch.
• No power to the Cooler. • Check the electrical supply
and switch power on if
turned off.
• No power to the pump. • Check the processor relay
Relay has energized. (See processor Manual).
• Fuse has blown. • Check the processor fuse.
(See processor Manual).
• Pump is failing. • Check pump and replace if
necessary.
"
The compressor might not be running even though the fan motor and the
pump does. A rough guide to check the compressor is to feel the temperature
of the discharge tube. This is the copper tube connecting the compressor to
the upper stub joint of the condenser. With the unit switched on the
discharge tube will gradually increase in temperature, should the discharge
tube become hot but the evaporator not cool, this could suggest a loss of
refrigerant or blockage in the refrigeration system. In the event of the
discharge tube remaining cool this would indicate a total loss of refrigerant or
a faulty compressor.
#
As the above mentioned operation will entail that the unit is operating
without top enclosure, the service engineer must observe and act very
carefully, because of access to rotating parts and primary voltage.
Please state carefully the spare part number, the specification and the number of items
wanted before you send your order.
If, though, a certain part is not specified in this section, do not hesitate to contact us for
further information.
The spare parts for the unit are specified on the next pages.
7
1 2
8
T8547
CHILLER
SPARE PARTS
Pos. No. Part No. Specification
Wiring diagram
Circuit shown with power off and chilled water temperature above set point.
C P M
3 4
2 5
1 6
Processor Processor
Power Supply Power Supply
Earth 3 2 1 Earth 3 2 1
Grn/Ylw
Black
Grn/Ylw
Red
Black
White
White
X1 X1
Earth 6 5 4 3 2 1 Earth 6 5 4 3 2 1
Chiller Chiller