SECTION 00.FastBeginning-Quick Start Guide
SECTION 00.FastBeginning-Quick Start Guide
SECTION 00.FastBeginning-Quick Start Guide
_____________________________________
PHONE ++39 0481 77 44 11 FAX ++39 0481 77 44 55 E-MAIL: info@geoclima.com
FAST BEGINNING
Quick Start Guide
Foreword
Thanks for choosing our chiller, follow instruction book is given in order to
be on disposal of the strictly interested person to the unit service and
management. This document has been made up by
To contact us:
www.geoclima.com
info@geoclima.com
FIRST RULE
LIFTING POINT
HOT SURFACE
The Fast Beginning manual is a useful guide to start up Geoclima chiller unit. Fundamental is
follow Geoclima indication, read unit manual and its commissioning procedure.
Geoclima takes for granted that commissioning person in charge will make all commissioning
procedure checks. Furthermore all operations will be made in safety conditions for people and
things.
For doubts, suggestion or special indication, please contact aftersale@geoclima.com with follow
indication:
o model number
o wiring diagram number
1 - UNIT INSTALLATION
From the “model number” take necessary information for the installation. To
understand the model number meaning look the section “Index and
nomenclature” in the manual folder.
2 – HYDRAULIC CONNECTION
Check the water flow if the pump are not supplied from Geoclima. Check the correspondence
between pressure drop and water flow as requested from technical data.
2 - ELECTRICAL CONNECTION
User interface
With reference to indicative image of display (EO2, CO3 and UG3) proposed in figure 1.
• SET to enter in set mode and change the setup parameters values
• UP to scroll up or increase values
• DOWN to scroll down or decrease values
• ESC alarm reset or menu quit key
• ON/OFF to start/stop the controller
• MENU to access on the menu
The last display, UG3, produce above mentioned commands with follow layout:
• In the low part of the screen will be displayed the following 4 Keys
- F1 (optional)
- F2 (optional)
- F3 (optional)
- TIME and DATE
To go into details read complete electronic manual supplied on enclosed CD. For every explanation contact us.
In the normal operating mode the 20X4 LCD displays the system status, the IN and OUT
temperatures, the set point, run time of the chiller, the alarm history (e.g. list of the last 9
alarms). In addition, for each compressor:
• suction and discharge pressure
• compressor status
• fan status
• liquid line solenoid status
• run time of compressor
The control temperature (Tc) is continuously displayed on the 3 digit LED display.
(1): If SPLIT unit are used then LWT, RWT and SP values are substitute with “----“.
If system On:
GEOCLIMA
wd dd/mm/yy hh:mm wd: weekday (Su…Sa);
dd/mm/yy: actual date
hh:mm: actual time
LWT 24.5 RWT 31.5 °F (1)
SP 40°F COOLING XXX% SP= Set point (1) used for
temperature control;
cooling percentage.
XXX= Cooling value (2))
(1): If SPLIT unit are used then LWT, RWT and SP values are substitute with “----“.
(2): If heat recovery with cooling priority is enabled and then the cooling value is alternated with “REC “ string every 2
seconds)
If UP key is pressed and Units Lead Lag is enabled we show other information about the status of
the master-slave units:
UNIT LEAD LAG
STATUS
MASTER UNIT: ON Showed only in master unit
or STANDBY or ALARM (Errore. L'origine riferimento non
or FATAL è stata trovata.>0)
SLAVE UNIT: ON
or STANDBY or ALARM
H TO NEXT SWT: xxx Showed only in master unit
(Errore. L'origine riferimento non
è stata trovata.>0)
If UP key is pressed and stepless control is used we show other information about stepless
staging:
DEMAND: 0 0 Demand capacity (required by
0 Master):
Cp1 Cp2 Cp3
0 0 0 0 Cp4 Cp5 Cp6 Cp7 Cp8
0
ACTUAL: 0 0 Actual capacity (required by
0 Slave):
Cp1 Cp2 Cp3
0 0 0 0 Cp4 Cp5 Cp6 Cp7 Cp8
0
If UP key is pressed and free cooling control is enabled without dry-cooler management we show
other information about free cooling control:
FREE COOLING: XXX XXX = ON / OFF
YY-PRIORITY YY = CP / FC
TCRT=ZZZ ZZZ = RWT / TC
TFC: TAE: TFC = Free Cooling Temperature,
°F TAE = External Air Temperature
VALVE: % FAN: % VALVE = Free cooling valve
opening,
FAN = Fan speed in Free Cooling
If UP key is pressed and dry-cooler management is enabled we show other information about dry-
cooler and free cooling control :
FREE COOLING: XXX XXX = ON / OFF
----------- TCRT=ZZZ ZZZ = RWT / TC
ODT: IDT: °F ODT: Outlet Dry-cooler
Temperature,
IDT: Inlet Dry-cooler
Temperature
VALVE: % FAN: % VALVE: Free cooling valve
opening;
FAN:
Fan speed in Free Cooling
Fan speed in chiller mode when
control by Dry-cooler (Errore.
L'origine riferimento non è
stata trovata.=1)
If UP key is pressed and pumps management is enabled we show other information about pumps
management:
PUMPS AVAILABLE: N N = 0 / 1 / 2
(0 when pumps management is
enabled but digital outputs
FAN#3 are already used for
other function)
PUMP1:XXX PUMP2:XXX XXX = ON / OFF / NO
RT1 RT2 H (Run Time of the pumps)
CHANGEOVER TIME: H (showed only if Errore.
L'origine riferimento non è
stata trovata.=3)
If UP key is pressed and Evaporator Water Pressure reading is enabled and one or two barrels
are used then we show others information about the water pressures on the Evaporator#1:
EVAP. WATER PRESS.#1
IWP:XX.X OWP:XX.XKPa IWP: Intlet Water Pressure,
OWP: Outlet Water Pressure
IWP-OWP: XX.XKPa Difference between Inlet Water
Pressure and Outlet Water
Pressure
LPD:XXX HPD:XXX KPa LPD= value of Errore.
L'origine riferimento non è
stata trovata. for Low Press.
Drop alarm;
HPD= value of Errore.
L'origine riferimento non è
stata trovata. for High Press.
Drop alarm.
If UP key is pressed and Evaporator Water Pressure reading is enabled and two barrels are used
then we show others information about the water pressures on the Evaporator#2:
EVAP. WATER PRESS.#2
IWP:XX.X OWP:XX.XKPa IWP= Intlet Water Pressure,
OWP= Outlet Water Pressure
IWP-OWP: XX.XKPa Difference between Inlet Water
Pressure and Outlet Water
Pressure
LPD:XXX HPD:XXX KPa LPD= value of Errore.
L'origine riferimento non è
stata trovata. for Low Press.
Drop alarm;
HPD= value of Errore.
L'origine riferimento non è
stata trovata. for High Press.
Drop alarm.
If UP key is pressed and Evaporative Condenser is enabled then we show others information
about the Adiabatic Pump and Heaters:
EVAP. CONDENSER
SET:XX.XPSI APU:YYY SET= Setpoint for Adiabatic
(YYY=ON/OFF/NO) Pump activ.
APU= Stauts of Adiabatic Pump
(“NO” is showed when the setup
config. is not right)
SET:XX.X°F HEA:YYY SET= Setpoint for Heaters
(YYY=ON/OFF/NO) activ.
HEA= Stauts of Heaters (“NO”
is showed when the setup
config. is not right)
If UP key is pressed the system shows the alarm history pages (Alarm #1 is the more recent
alarm):
dd/mm/yy hh:mm A 1 dd/mm/yy: date when
the
alarm
occurred
hh:mm: time when the
alarm
occurred;
DESCRIPTION OF ALARM/EVENT
dd/mm/yy hh:mm A 2
DESCRIPTION OF ALARM/EVENT
dd/mm/yy hh:mm A 3
DESCRIPTION OF ALARM/EVENT
dd/mm/yy hh:mm A 4
DESCRIPTION OF ALARM/EVENT
dd/mm/yy hh:mm A 5
DESCRIPTION OF ALARM/EVENT
dd/mm/yy hh:mm A 6
DESCRIPTION OF ALARM/EVENT
dd/mm/yy hh:mm A 7
DESCRIPTION OF ALARM/EVENT
dd/mm/yy hh:mm A 8
DESCRIPTION OF ALARM/EVENT
dd/mm/yy hh:mm A 9
DESCRIPTION OF ALARM/EVENT
dd/mm/yy hh:mm A10
DESCRIPTION OF ALARM/EVENT
To clear the alarm history press together DOWN and ESC key when the controller is in ‘off’ status.
When the key UP is pressed LCD shows information about each circuit (note 0 stays for relay off,
1 means relay on):
1) If the analog inputs S1/2, D1/2 are configured as free contact then the values of SP,DP are substitute with the string “---“.
2) If Errore. L'origine riferimento non è stata trovata.=3,4 then the values of DP and SP are showed in pressure and temperature with 2 seconds of alternation.
3) If compressor screen is showed and <SET> key is pressed then the alternation of the rows is locked for 2 minutes. To restart the alternation of the rows before the 2 minutes re-
press <SET> key.
4) Evaporator Liquid Level (ELL) value is showed when EEV board is connected to SB2 via serial line and flooded evaporator is enabled
5) Discharge Superhat (DSH) value is showed when EEV board is connected to SB2 via serial line and flooded evaporator is not used
6) EEV opening value is alternated with the string “INCR” every 2 seconds when Errore. L'origine riferimento non è stata trovata. algorithm is activated
When the key UP is pressed LCD shows information about each Turbocor compressor:
CMP# xxxxxx IGV:yyy% Compressor status:
ON /
CM-ON (counting minimum time
on)/
CM-OFF (counting minimum time
off)/ OFF / ALARM / LOCKED /
ADPT-C / LP-LIM /
DT-LIM / PW-LCK /
HDT-INV / LSP-CAV /
HDP-TCR / CUR-SCR
IGV= IGV opening.
Spd:xxxxx Min:xxxxx Spd= Actual Speed
Min= Minimum Speed(Surge)
DEM:xx.x ACT:xx.x KW DEM= Demanded power
ACT= Actual power
CAV:xx.xA SCR=xx.x°F CAV= Cavity Temp.
alternate with SCR= SCR Temp.
CUR:xx.xA IVT=xx.x°F CUR= Actual Current
IVT= Inverter Temp.
1) If compressor screen is showed and <SET> key is pressed then the alternation of the rows is locked for 2 minutes. To restart the alternation of the rows before the 2 minutes re-
press <SET> key.
When an alarm is active, the following page is displayed. When there is more than 1 alarm, the
information is changed every 5 seconds.
ALARM
Compressor N
Description
If the alarm gets off and it needs manual reset, the LCD display shows this page:
ALARM
Compressor N
Description
Press <ESC> to reset
- if any screen of main data display is showed and <ESC> key is pressed, then the first page is showed;
- if the first page is showed and one or more alarms are active and <ESC> key is pressed, then an alarm screen is showed;
- if an alarm screen is showed without manual reset request and <ESC> key is pressed, then the first page is showed;
- if an alarm screen is showed with manual reset request and <ESC> key is pressed, then all the alarms which have got off are reset and
the first page is showed.
If a setup parameter is changed (by user or TelePE) then this event is notified on the alarm history
and the description of alarm/event shows:
where:
- Y = type of setup parameter (“U” if User setup parameter, “M” if Manufacturer setup parameter, “I” if I/O setup parameter)
- XXX = number of setup parameter
- value = new value of parameter
- m.u. = eventual measuring unit of parameter
Follow table (is a table) of what is displayed in case of alarm or in alarm history display.