Diesel Generator Set

MTU 18V2000 DS1250


1,000 kWe/60 Hz/Prime/380 - 4,160V
Reference MTU 18V2000 DS1250 (1,250 kWe) for Standby Rating Technical Data

System ratings
Voltage (L-L) 380V † ‡ 480V † ‡ 600V ‡ 4,160V

Phase 3 3 3 3

PF 0.8 0.8 0.8 0.8

Hz 60 60 60 60

kW 1,000 1,000 1,000 1,000

kVA 1,250 1,250 1,250 1,250

Amps 1,899 1,504 1,203 173

skVA@30% voltage dip 1,870 2,590 2,590 2,600

Generator model* 742RSL4048 741RSL4045 741RSS4284 742FSM4364

Temp rise 105 °C/40 °C 105 °C/40 °C 105 °C/40 °C 105 °C/40 °C

Connection 4 LEAD WYE 4 LEAD WYE 4 LEAD WYE 6 LEAD WYE

* Consult the factory for alternate configuration.


† UL 2200 offered
‡ CSA offered

Certifications and standards


—— Emissions —— Performance Assurance Certification (PAC)
• Fuel consumption optimized • Generator set tested to ISO 8528-5 for transient response
—— Generator set is designed and manufactured in facilities certified • Verified product design, quality, and performance integrity
to standards ISO 9001:2008 and ISO 14001:2004 • All engine systems are prototype and factory tested
—— UL 2200 - optional (refer to System ratings for availability) —— Power rating
—— CSA - optional (refer to System ratings for availability) • Accepts rated load in one step per NFPA 110
• CSA C22.2 No. 100 • Permissible average power output during 24 hours of
• CSA C22.2 No. 14 operation is approved up to 75%.
Standard features *
—— MTU is a single source supplier —— Generator
—— Global product support • Brushless, rotating field generator
—— 2 year standard warranty • 2/3 pitch windings
—— 18V2000 diesel engine • PMG (Permanent Magnet Generator) supply to regulator
• 40.2 liter displacement • 300% short circuit capability
• Common rail fuel injection —— Digital control panel(s)
• 4-cycle • UL recognized, CSA Certified, NFPA 110
—— Engine-generator resilient mounted • Complete system metering
—— Complete range of accessories • LCD display
Cooling system
• Integral set-mounted
• Engine-driven fan

Standard equipment *
Engine Digital control panel(s)
—— Air cleaners —— Digital metering
—— Oil pump —— Engine parameters
—— Oil drain extension and S/O valve —— Generator protection functions
—— Full flow oil filter —— Engine protection
—— Closed crankcase ventilation —— CANBus ECU communications
—— Jacket water pump —— Windows®-based software
—— Thermostat —— Multilingual capability
—— Blower fan and fan drive —— Remote communications to RDP-110 remote annunciator
—— Radiator - unit mounted —— Programmable input and output contacts
—— Electric starting motor - 24V —— UL recognized, CSA certified, CE approved
—— Governor – electronic isochronous —— Event recording
—— Base - formed steel —— IP 54 front panel rating with integrated gasket
—— SAE flywheel and bell housing —— NFPA 110 compatible
—— Charging alternator - 24V
—— Battery rack and cables
—— Flexible fuel connectors
—— Flexible exhaust connection

Generator
—— NEMA MG1, IEEE, and ANSI standards compliance for temperature
rise and motor starting
—— Sustained short circuit current of up to 300% of the rated current
for up to 10 seconds
—— Self-ventilated
—— Superior voltage waveform
—— Digital, solid state, volts-per-hertz regulator
—— No load to full load regulation
—— Brushless alternator with brushless pilot exciter
—— 4 pole, rotating field
—— 105 °C maximum prime temperature rise
—— 1-bearing, sealed
—— Flexible coupling
—— Full amortisseur windings
—— 125% rotor balancing
—— 3-phase voltage sensing
—— ±0.25% voltage regulation
—— 100% of rated load - one step
—— 5% maximum total harmonic distortion

* Represents standard product only. Consult the factory/MTU Distributor for additional configurations. MTU 18V2000 DS1250 (1000 kWe) - Prime / 02
Application data
Engine Fuel consumption
Manufacturer MTU At 100% of power rating: L/hr (gal/hr) 254 (67)
Model 18V2000B76 At 75% of power rating: L/hr (gal/hr) 192 (51)
Type 4-cycle At 50% of power rating: L/hr (gal/hr) 133 (35)
Arrangement 18-V
Displacement: L (in3) 40.2 (2,448) Cooling - radiator system
Bore: cm (in) 13.5 (5.3) Ambient capacity of radiator: °C (°F) 50 (122)
Stroke: cm (in) 15.6 (6.15) Maximum restriction of cooling air:
Compression ratio 17.5:1 intake and discharge side of radiator: kPa (in. H20) 0.12 (0.5)
Rated rpm 1,800 Water pump capacity: L/min (gpm) 950 (251)
Engine governor electronic isochronous (ADEC) Heat rejection to coolant: kW (BTUM) 430 (24,454)
Maximum power: kWm (bhp) 1,097 (1,471) Heat rejection to after cooler: kW (BTUM) 285 (16,208)
Speed regulation ± 0,25% Heat radiated to ambient: kW (BTUM) 107 (6,079)
Air cleaner dry Fan power: kW (hp) 33.5 (44.9)

Liquid capacity (Lubrication) Air requirements


Total oil system: L (gal) 122 (32.2) Aspirating: *m3/min (SCFM) 96.6 (3,411)
Engine jacket water capacity: L (gal) 73 (19.3) Air flow required for radiator
System coolant capacity: L (gal) 185 (48.9) cooled unit: *m3/min (SCFM) 1,512 (53,396)
Remote cooled applications; air flow required for
Electrical dissipation of radiated generator set heat for a
Electric volts DC 24 maximum of 25 °F rise: *m3/min (SCFM) 390 (13,710)
Cold cranking amps under -17.8 °C (0 °F) 2,800
* Air density = 1.184 kg/m³ (0.0739 lbm/ft³)
Fuel system
Fuel supply connection size #12 JIC 37° female Exhaust system
1” NPT adapter provided Gas temp. (stack): °C (°F) 420 (788)
Fuel return connection size #12 JIC 37° female Gas volume at stack temp: m3/min (CFM) 222 (7,840)
1” NPT adapter provided Maximum allowable back pressure at
Maximum fuel lift: m (ft) 5 (16) outlet of engine, before piping: kPa (in. H20) 5 (20)
Recommended fuel diesel #2
Total fuel flow: L/hr (gal/hr) 1,500 (396)

MTU 18V2000 DS1250 (1000 kWe) - Prime / 03


Weights and dimensions

Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.

System Dimensions (L x W x H) Weight (dry/less tank)

Open power unit (OPU) 5,036 x 2,275 x 2,454 mm (198.3 x 89.6 x 96.6 in) 9,525 kg (21,000 lb)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.

Sound data
Unit type Prime full load

Level 0:
90.2
Open power unit: dB(A)

Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.

Emissions data Rating definitions and conditions


NOx + NMHC CO PM —— Prime power ratings apply to installations where utility power
is unavailable or unreliable. At varying load, the number of
4.77 0.15 0.01 generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, ISO 3046-1, BS 5514, and AS 2789.
—— All units are in g/hp-hr and at 100% load. Emission levels of the Average load factor: ≤ 75%.
engine may vary as a function of ambient temperature, barometric —— Consult your local MTU Distributor for derating information.
pressure, humidity, fuel type and quality, installation parameters,
measuring instrumentation, etc. The data provided are laboratory
results from one engine representing this rating. The data was Subject to change. | 23948 | 2020-02
obtained under controlled environmental conditions with
calibrated instrumentation traceable to the United States National
Bureau of Standards and in compliance with US EPA regulations
found within 40 CFR Part 89. The weighted cycle value (not shown)
from each engine is guaranteed to be below the US EPA Standards
at the US EPA defined conditions.