Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Autonics Panels MP5W Data Trace Automation

Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

MP5S/MP5Y/MP5W Series Pulse Meter

High Performance, Digital Panel Meter (A)


Photoelectric

Features
Sensors

(B)
3
 types of operation mode are added. Shaded parts ( ) are changed and added Fiber
(total 16 types of operation mode) functions from previous MP5. Optic
Sensors
Frequency/Revolutions/Speed, Passing speed, Cycle, Passing time,
Time interval, Time differential , Absolute ratio, Error ratio, Density, (C)
Door/Area
Error, Length measurement 1, Length measurement 2, Interval, Sensors

Accumulation, Addition/Subtraction-individual input, Addition/


(D)
Subtraction-phase difference input Proximity
Sensors
Various output models
Relay triple/quintuple output, NPN/PNP open collector quintuple output, (E)
BCD dynamic output, PV transmission output (current output), Pressure
Sensors
RS485 communication output (changed Modbus RTU) MP5S
Various functions (F)
Rotary
Selectable NPN solid state/contact input, PNP solid state/contact Encoders
input, prescale, delay monitoring, hysteresis, auto-zero time (G)
setting, lock setting, data bank function (MP5W series) Connectors/
Connector Cables/
Max. display range: -19999 to 99999 Sensor Distribution
Boxes/Sockets
Various display units
rpm, rps, Hz, kHz, sec, min, m, mm, mm/s, m/s, m/min, m/h, ℓ/s, (H)
Temperature
ℓ/min, ℓ/h, %, counts, etc. Controllers

MP5Y MP5W
(I)
Please read “Safety Considerations” in operation SSRs / Power
Controllers
manual before using.

(J)
Counters
Ordering Information
MP 5 Y - 4 N
(K)
Timers

(L)
Main output Sub output Panel
(comparative value output) (display value output) Meters
Output
S N Indicator - (M)
Tacho /
Speed / Pulse
N Indicator - Meters

1 NPN open collector quintuple output -


(N)
2 PNP open collector quintuple output - Display
Units
Y 3 Indicator BCD dynamic output
4 Indicator PV transmission output (current output) (O)
Sensor
5 Indicator RS485 communication output Controllers

6 Relay triple output (H, GO, L) -


(P)
Switching
N Indicator - Mode Power
Supplies
Relay quintuple output
A - (Q)
(HH, H, GO, L, LL) Stepper Motors
& Drivers
1 Relay triple output (H, GO, L) - & Controllers

W 2 NPN open collector quintuple output BCD dynamic output (R)


Graphic/
4 NPN open collector quintuple output PV transmission output (current output) Logic
Panels
5 PNP open collector quintuple output PV transmission output (current output)
8 NPN open collector quintuple output RS485 communication output (S)
Field
Network
9 PNP open collector quintuple output RS485 communication output Devices

Power supply 2 24VAC 50/60Hz, 24-48VDC (T)


Software
4 100-240VAC 50/60Hz

S DIN W48×H48mm
Size
Y DIN W72×H36mm
W DIN W96×H48mm
Digits
5 99999 (5-digit)
Item
MP Pulse meter

M-7
MP5S/MP5Y/MP5W Series
Specifications
Series MP5S MP5Y MP5W
Display method 7-segment LED (zero blanking method)
Character size W4×H8mm W7×H14mm
Display range -19999 to 99999
Power AC voltage 100-240VACᜠ 50/60Hz
supply AC/DC voltage 24VACᜠ 50/60Hz, 24-48VDCᜡ
Max. 7.5VA Max. 9VA Max. 15VA
Power AC voltage
(100-240VACᜠ 50/60Hz) (100-240VACᜠ 50/60Hz) (100-240VACᜠ 50/60Hz)
consum-
ption Max. 6VA (24VACᜠ 50/60Hz), Max. 7VA (24VACᜠ 50/60Hz), Max. 11VA (24VACᜠ 50/60Hz),
AC/DC voltage
max. 4.5W (24-48VDCᜡ) max. 6.2W (24-48VDCᜡ) max. 7W (24-48VDCᜡ)
Permissible voltage range 90 to 110% of rated voltage
External power supply Max. 12VDCᜡ ±10% 80mA
Sub power supply - Max. 24VDCᜡ 30mA
·Solid state input 1: max. 50kHz (pulse width: min. 10㎲)
·Solid state input 2: max. 5kHz (pulse width: min. 100㎲)
Input frequency
※For F7, F8, F9, F10 operation mode, max. 1kHz (pulse width: min. 500㎲)
·Contact input: max. 45Hz (pulse width: min. 11ms)
[Voltage input] High: 4.5-24VDCᜡ, Low: 0-1VDC, Input impedance: 3.9kΩ
Input method [No-voltage input] Short-circuit impedance: Max. 80Ω, Residual voltage: Max. 1VDC,
Open-circuit impedance: Min. 100kΩ
·Operation mode F1, F2, F7, F8, F9, F10 : 0.0005Hz to 50kHz
·Operation mode F3, F4, F5, F6 : 0.01 to max. of each time range
Measurement range
·Operation mode F11, F12, F13, F16 : 0 to 99999
·Operation mode F14, F15 : -19999 to 99999
Measurement accuracy ·Operation mode F1, F2, F7, F8, F9, F10 : F.S.±0.05%rdg±1-digit
(23℃±5℃) ·Operation mode F3, F4, F5, F6 : F.S.±0.01%rdg±1-digit
Display cycle OFF (for F2, F16 operation mode), 0.05, 0.5, 1, 2, 4, 8 sec (same as update output cycle)
Frequency/Revolutions/Speed (F1), Passing speed (F2), Cycle (F3), Passing time (F4),
Time interval (F5), Time differential (F6), Absolute ratio (F7), Error ratio (F8), Density (F9), Error (F10),
Operation mode
Length measurement 1 (F11), Interval (F12), Accumulation (F13), Addition/Subtraction-individual input (F14),
Addition/Subtraction-phase difference input (F15), Length measurement 2 (F16)
Prescale function Direct input method (0.0001×10-9 to 9.9999×109)
※1
Hysteresis 0 to 9999
Relay triple 250VACᜠ 3A resistive load
Relay quintuple - 250VACᜠ 3A resistive load
Main
NPN/PNP open
Output

Max. 30VDCᜡ 30mA


collector quintuple -
BCD dynamic Max. 30VDCᜡ 30mA
Sub PV transmission DC4-20mA/DC0-20mA max. load 500Ω
Communication RS485 communication output (Modbus RTU method)
Memory retention Non-volatile memory (number of inputs: 100,000 operations)
Insulation resistance Over 100MΩ (at 500VDC megger)
Dielectric strength 2,000VAC 60Hz for 1 min
Noise immunity ±2kV the square wave noise (pulse width: 1㎲) by the noise simulator
Mechanical 0.75mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 1 hour
Vibration
Malfunction 0.5mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 10 min
Mechanical 300m/s² (approx. 30G) in each X, Y, Z direction for 3 times
Shock
Malfunction 100m/s² (approx. 30G) in each X, Y, Z direction for 3 times
Relay Mechanical - Min. 10,000,000 operations
life cycle Electrical - Min. 100,000 operations (250VAC 3A resistive load)
Environ- Ambient temp. -10 to 50℃, storage: -20 to 60℃
ment Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
Approval
※2
Weight Approx. 191g (approx. 132g) Approx. 230g (approx. 140g) Approx. 334g (approx. 210g)
※1: Setting range will vary depending on the decimal point.
※2: The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.

M-8
Pulse Meter
Connections (A)
Photoelectric
※Terminal connections differ by power supply and output type of each series and model. Sensors

MP5S Series (B)


Fiber
Optic
Sensors

(C)
Door/Area
Sensors

Brown
Black

Black

Blue
※1 (D)
INA INB +12V 0V HOLD/RESET Proximity
Sensors

6 7 8 9 10
(E)
Pressure
Sensors

※1: Operation mode F1 to F12


: display value HOLD 11 12 (F)
Rotary
Encoders
Operation mode F13 to F16
: display value RESET (G)
Connectors/
※2: Model Source
Connector Cables/
Sensor Distribution

24-48VDC 1 2 3 4 5 Boxes/Sockets
MP5S-2N
24VAC 50/60Hz (H)
Temperature
100-240VAC Controllers
MP5S-4N - + ※2
50/60Hz
SOURCE (I)
SSRs / Power
Controllers

MP5Y Series
(J)
Power/Input Terminal (Common) Counters

※MP5Y- N (indicator) only has 'Power/Input terminals'.


(K)
Timers

(L)
Panel
※1: O
 peration mode F1 to F12 Meters
: display value HOLD
Operation mode F13 to F16 (M)
Tacho /
: display value RESET Speed / Pulse
Black Black Blue Brown Meters
※2: Model Source
1 2 3 4 5 6 7 MP5Y-2
24-48VDC (N)
24VAC 50/60Hz Display
Units
INA INB 0V +12V
100-240VAC
※1 MP5Y-4
HOLD/RESET 50/60Hz (O)
- + ※2
Sensor
SOURCE Controllers

(P)
Switching
Mode Power
Supplies
O
 utput Connector (MP5Y- 1 to 5)
(Q)
※Hirose connector: HIF3BA-10PA-2.54DS Stepper Motors
※Hirose connector socket: HIF3BA-10D-2.54R (sold separately) & Drivers
& Controllers
※Hirose connector socket is not included. Contact a hirose connector dealer regarding sockets and cables.
(R)
Graphic/
Logic
Panels
● MP5Y- 1 (NPN open collector output) ● MP5Y- 2 (PNP open collector output)
(S)
MAIN OUT (NPN OPEN COLLECTOR) MAIN OUT (PNP OPEN COLLECTOR) Field
Network
30VDC 30mA 30VDC 30mA Devices

HH GO LL HH GO LL (T)
Software

2 4 6 8 10 2 4 6 8 10

1 3 5 7 9 1 3 5 7 9
COM H L COM H L

M-9
MP5S/MP5Y/MP5W Series
● MP5Y- 3 (BCD dynamic output) ● MP5Y- 4 (PV transmission output)
BCD OUT (NPN OPEN COLLECTOR)
30VDC 30mA DC4-20mA/DC0-20mA
A C D0 D2 D4 Load 500Ω Max. (+)

2 4 6 8 10 2 4 6 8 10

1 3 5 7 9 1 3 5 7 9
COM B D D1 D3
(-)
※Autonics display unit (DS/DA Series) is recommended
for stable minus (-) sign display.

● MP5Y- 5 (RS485 communication otuput) ●Output Terminal (MP5Y- 6)


● MP5Y- 6 (Relay triple output)
RS485 B(-)

2 4 6 8 10 8 9 10 11 12 13 14 15

1 3 5 7 9 H GO L
CONTACT OUT:
RS485 A(+) 250VAC 3A RESISTIVE LOAD

MP5W Series
●Power/Input Terminal (Common)
※MP5W- N (indicator) only has 'Power/Input terminals'.

Black Black Blue Brown


※1: Operation mode F1 to F12 1 2 3 4 5 6 7 8 9
: display value HOLD
Operation mode F13 to F16 INA INB 0V 0V +12V
: display value RESET
※1
※2: Model Source HOLD/RESET - +
※2
SOURCE
24-48VDC
MP5W-2 BANK
24VAC 50/60Hz
100-240VAC
MP5W-4
50/60Hz

●Output Terminal (MP5W- A/1)


● MP5W- A (Relay quintuple output) ● MP5W- 1 (Relay triple output)
CONTACT OUT:
250VAC 3A RESISTIVE LOAD CONTACT OUT:
250VAC 3A RESISTIVE LOAD
H GO L

10 11 12 13 14 15 10 11 12 13 14 15
HH H GO L LL COM

M-10
Pulse Meter
Output Connector (MP5W- 2/4/5/8/9) (A)
Photoelectric
※Hirose connector: HIF3BA-20PA-2.54DS Sensors
※Hirose connector socket: HIF3BA-20D-2.54R (sold separately)
※Hirose connector socket is not included. Contact a hirose connector dealer regarding sockets and cables. (B)
Fiber
※1: Sub power supply Optic
Sensors
※2: POL signal turns ON when the display value is a minus (-) value.
● MP5W- 2 (NPN open collector+BCD dynamic output) (C)
Door/Area
Sensors
MAIN OUT (NPN OPEN COLLECTOR)
30VDC 30mA +24VDC (D)

30mA Max. 1 Proximity
HH GO LL B D D1 D3 DOT COM2
Sensors

2 4 6 8 10 12 14 16 18 20 (E)
Pressure
Sensors

1 3 5 7 9 11 13 15 17 19 (F)
Rotary
Encoders
※2
COM H L A C D0 D2 D4 POL
(G)
0V BCD OUT (NPN OPEN COLLECTOR) Connectors/
Connector Cables/
30VDC 30mA Sensor Distribution
Boxes/Sockets
※Autonics display unit (DS/DA Series) is recommended for stable minus (-) sign display.
(H)
Temperature
Controllers
● MP5W- 4 ● MP5W- 5
(NPN open collector+PV transmission output) (PNP open collector+PV transmission output) (I)
SSRs / Power
Controllers
MAIN OUT (PNP OPEN COLLECTOR)
MAIN OUT (NPN OPEN COLLECTOR)
30VDC 30mA
30VDC 30mA
+24VDC (J)
Counters

30mA Max. 1 (+) HH GO LL
HH GO LL
2 4 6 (K)
2 4 6 8 10 12 14 16 18 20 Timers

1 3 5 (L)

9 11 13 15 17 19
Panel
1 3 5 7 COM H L
Meters

COM H L (M)
Tacho /
0V (-) Speed / Pulse
DC4-20mA/DC0-20mA Meters

(Load 500Ω Max.)


(N)
Display
Units

● MP5W- 8 ● MP5W- 9 (O)


(NPN open collector+RS485 comm. output) (PNP open collector+RS485 comm. output) Sensor
Controllers

MAIN OUT (NPN OPEN COLLECTOR) MAIN OUT (PNP OPEN COLLECTOR)
(P)
30VDC 30mA 30VDC 30mA Switching
Mode Power
+24VDC RS485 Supplies

30mA Max. 1 B(-) HH GO LL
HH GO LL (Q)
Stepper Motors
2 4 6 & Drivers

2 4 6 8 10 12 14 16 18 20 & Controllers

(R)
Graphic/
1 3 5 Logic

1 3 5 7 9 11 13 15 17 19 Panels

COM H L (S)
Field
COM H L Network
0V A(+) Devices

RS485
(T)
Software

M-11
MP5S/MP5Y/MP5W Series
Dimensions (unit: mm)
※Nameplate design is changed from the previous MP5.
※Side dimensions of MP5Y/W differ by output type.
●MP5S Series
48 10 90

45
●MP5Y Series MP5Y- 1/2/3/4/5 MP5Y- 6
72 6 89.5 14.5 15.3

30
36

10.5 10.5
※M
 P5Y- N (indicator) does not include the shaded part
(output hirose connector or output terminal).

●MP5W Series MP5W- 2/4/5/8/9 MP5W- A/1


96 89.5 14.5 10.5
6

45
48

10.5 10.5
※MP5W- N (indicator) does not include the shaded part
(output hirose connector or output terminal).
Panel cut-out dimensions
A
(unit: mm)
D Size
A B C D
Series
B MP5S Min. 55 Min. 62 45.5 +0.5
45.5 +0.5

C
0 0

MP5Y Min. 91 Min. 40 68 +0.7


0 31.5 +0.5
0

MP5W Min. 116 Min. 52 92 +0.8


0 45 +0.6
0

 Bracket
For MP5S For MP5Y/W
41
4.2
3.9

73
30
12±0.2

10
6
45.4
50
61
4.5

0.82
4
9.5

1
15

0.2±0.2

M3
42.2
12.2 45.4
16.4 47.8
48.6 61.64

M-12
Pulse Meter
Unit Description (A)
Photoelectric
●MP5S Series ●MP5Y Series ●MP5W Series Sensors
4
4 (B)
Fiber
Optic
Sensors
1 1 1
(C)
Door/Area
Sensors

(D)
Proximity
Sensors

2 3 2 3
1: Display component (E)
2 3
Displays current value in RUN mode. Pressure
Sensors
Alternately displays setting parameters and corresponding value in SETTING mode.
2:  key
In RUN mode, press the key once to check max./min. value. (F)
Rotary
In RUN mode, hold the key for over 2 sec to enter parameter groups. Encoders
3:  , , key
Select parameter groups, and select or setting values in the corresponding parameters. (G)
Connectors/
4: O utput status indicator Connector Cables/
Sensor Distribution
Boxes/Sockets
Sold Separately (H)
Communication converter Temperature
Controllers

SCM-WF48 SCM-US48I SCM-38I


(Wi-Fi to RS485·USB wireless (USB to RS485 converter) (RS232C to RS485 converter) (I)
SSRs / Power
communication converter) Controllers

(J)
Counters

(K)
Timers

(L)
Panel
Meters

Display Units (DS/DA-T Series) (M)


DS/DA-T Series Tacho /
Speed / Pulse
(RS485 communication input type display unit) Meters

(N)
Display
Units

DS16- T DS22/DA22- T DS40/DA40- T DS60/DA60- T (O)


※Connect RS485 communication input type display unit (DS/DA-T Series) and RS485 communication output model of MP5Y/MP5W Series, Sensor
Controllers
the display unit displays present value of the device without PC/PLC.
(P)

Input Specifications Switching


Mode Power
Supplies
Input Specifications
1. Input signal (Q)
Stepper Motors
Standard duty ratio of input signal is 1:1. & Drivers

(1) Solid state input 1 ON & Controllers

Input frequency: Max. 50kHz (ON/OFF pulse width: min. 10㎲ of each) OFF (R)
(2) S
 olid state input 2 Pulse width Graphic/

Input frequency: Max. 5kHz (ON/OFF pulse width: min. 100㎲ of each) ON OFF Logic
Panels
※For F7, F8, F9, F10 operation mode, max. 1kHz (ON/OFF pulse width: min. 500㎲ of each)
(3) Contact input T (S)
Field
① Input frequency: Max. 45Hz (when each ON/OFF pulse width is over 11ms) ※T: s ingle cycle of input signal
Network
Devices
② Contact specifications: 12VDC, stable switching of load current as small as 5mA
2. Input type [IN-A, IN-B]
(T)
MP5 allows selection between NPN input (solid state/contact) or PNP input (solid state/contact). Software
(1) NPN input type (2) PNP input type
①Contact ②NPN voltage ③NPN open collector ①Contact ②PNP voltage ③PNP open collector
output type sensor output type sensor MP5 output type sensor output type sensor MP5
+12V +12V
Sensor circuit

Sensor circuit

Sensor circuit

Sensor circuit

Sensor circuit
Sensor circuit

3.9kΩ
IN
IN
0V 0V
(COM) 3.9kΩ
(COM)

M-13
MP5S/MP5Y/MP5W Series
Output Specifications
1. Relay output
① Output: Comparative or alarm output (refer to " Output Modes")
② Output type: Relay
③ Contact capacity: 250VAC 3A resistive load
④ Life cycle: [Mechanical] min. 10,000,000 operations (switching frequency 180 operations/min)
[Electrical] min. 100,000 operations (3A 250VAC, 30VDC resistive load) (switching frequency 20 operations/min)
2. Transistor output
① Output: Comparative output or alarm output (refer to " Output Modes")
② Output type: NPN/PNP open collector
③ Rated load voltage: 30VDC
④ Max. load current: 30mA
3. BCD dynamic output (negative logic) E.g.) To display value = 125.89 by BCD dynamic output
① Output: present value 104-digit 100-digit
② Output signal: BCD data (A, B, C, D, DOT)
← A: lowest bit, DOT: highest bit PV display value 1 2 5. 8 9
Digit data (D0, D1, D2, D3, D4)
A
← D0: lowest digit, D4: highest digit
③ Output type: NPN open collector B
④ Rated load voltage: 30VDC BCD
⑤ Max. load current: 30mA Data C
⑥ Dynamic COM cycle (T) = 40ms
D

DOT
D0

D1 0.1ms

D2
Digit
D3

D4
5ms 8ms
40ms

4. PV transmission output
① Application: transmit measured value
② Function: transmit measured value within setting range of high-limit output [FS-H] to low-limit output [FS-L] after conversion into
DC4-20mA or DC0-20mA current.
③O  utput range of high/low-limit
·High-limit [FS-H] range: From min. value to max. value within measurement range
·Low-limit [FS-L] range: From min. value to max. value within measurement range ([FS-H]≥[FS-L]+1)
(1) DC4-20mA transmission output (2) DC0-20mA transmission output
① Transmit measured value within setting range of high-limit ① Transmit measured value within setting range of high-limit
output [FS-H] to low-limit output [FS-L] after conversion output [FS-H] to low-limit output [FS-L] after conversion into
into DC4-20mA current. DC0-20mA current.
② Resistive load: Max. 500Ω ② Resistive load: Max. 500Ω
③ Resolution: 8000 divisions ③ Resolution: 10,000 divisions
Diplay value Display value
FS-H FS-H
FS-L FS-L
Set [FS-L] and [FS-H] and Set [FS-L] and [FS-H] and
the output is DC4-20mA. 20mA the output is DC0-20mA. 20mA

If the setting width between [FS-L] and If the setting width between [FS-L] and
[FS-H] is lower than 8000 divisions, the 4mA [FS-H] is lower than 10,000 divisions, 0mA
resolution is also reduced. the resolution is also reduced.

5. RS485 communication output


Comm. protocol Modbus RTU 2400, 4800, 9600 (default), 19200,
Communication Speed
Connection type RS485 38400 bps
Application standard Compliance with EIA RS485 Communication response time 5 to 99ms (default: 20ms)
Max. connection 31 units (address: 01 to 99) Start Bit 1-bit fixed
Synchronous method Asynchronous Data Bit 8-bit fixed
Comm. method Two-wire half duplex Parity Bit None (default), Even, Odd
Comm. distance Max. 800m Stop Bit 1, 2-bit (default)
※For more information about RS485 communication output specifications, refer to ' RS485 Communication Output'.

M-14
Pulse Meter
Parameter Groups (A)
Photoelectric
Sensors

(B)
Parameter 0 group
(max./min. monitoring value)
RUN HOLD/RESET

Fiber
Optic

mode
Sensors

※Operation mode F1 to F12 (C)


Door/Area
: display value HOLD Sensors

Operation mode F13 to F16


2 sec 3 sec : display value RESET (D)
Proximity
Sensors

Parameter 1/2/3 group


(E)
Pressure
Sensors
※Press the , , keys to select or set the desired value.
※Press the key once after changing the setting value, to save the setting value and move to the next parameter. (F)
※Hold the key for 1.5 sec at any parameters to return to the select parameter group mode. Rotary
Encoders
※Hold the key for 3 sec to save the setting value and return to RUN mode after changing the setting value.
※If there is no key input for 60 sec while setting the parameters, the new settings are ignored, and the unit will return to RUN mode with (G)
Connectors/
previous settings. Connector Cables/
Sensor Distribution
※The dotted line parameters may not appear depending on output specifications or other parameter settings. Please refer to ' Operation Boxes/Sockets
Mode by Parameter Group'. (H)
※1: Each parameter and corresponding setting value will flash alternately every 0.5 sec. Temperature
Controllers

● Parameter 0 group
(I)
SSRs / Power
Controllers
RUN mode
(J)
Counters

Flashes
※1
alternately HH comparative value (K)
PStHH 99999 ※Does not appear Timers

in F output mode
※The parameters are identical to [PStHH], (L)
[PSt H], [PSt L], [PStLL] of parameter 2 Panel
Meters
group and the setting values will be linked.
●Setting range by operation mode
PSt H 99999 H comparative value (M)
Tacho /
Operation mode Setting range Speed / Pulse
F1, F2, F7, F9, F11, Meters
0 to 99999
F12, F13, F16
(N)
F3, F4, F5, F6 0 to setting time range Display
Units
PSt L 00000 L comparative value F8, F10, F14, F15 `9999 to 99999
(the setting range varies depending on the (O)
Sensor
decimal point setting.) Controllers
※Only appears in comparative value setting
LL comparative value models. (P)

PStLL 00000 ※Does not appear


Switching
Mode Power
Supplies
in F output mode,
(Q)
Stepper Motors
& Drivers
& Controllers

hPEK 99999 Max. monitoring value (R)


Graphic/
Logic
※Resetting monitoring value Panels
:H
 old the key for over 2 sec
(S)
(reset current value) Field
Network
lPEK `9999 Min. monitoring value
Devices

(T)
Software

M-15
MP5S/MP5Y/MP5W Series
● Parameter 1 group

2 sec
RUN mode PARa1 PARa2 PARa3

3 sec
Flashes

alternately 1 Operation mode
MODE F
ㄹ 1 ●Setting range: F1 to F16

●Setting range
IN-A NPnhF Sensor type of input A Parameter Input sensor type
NPnhF NPN solid state input 1
NPnmF NPN solid state input 2
NPnlF NPN contact input
PNphF PNP solid state input 1
PNpmF PNP solid state input 2
IN-B NPnhF Sensor type of input B PNplF PNP contact input

●Setting range
Parameter Output mode Parameter Output mode
OUT-T STARD Output mode STARD S (Standard) OUT-B B (Block)
OUT-H H (High) OUT-I I (One-shot)
OUT-L L (Low) OUT-F F (Deflection)

Output hysteresis ※Does not


HYS 0001 ●Setting range: 0000 to 9999 appear in
(the setting range varies depending on the decimal point setting.) indicator
models.

GUARD fDEFY LL, L comparative output limit function

STArT 9(9
Start compensation timer function &
compensation time
●Setting range: )0 to 9(9 (sec)

AUToA 999(9 Auto-zero time for input A

●Setting range:
)1 to 999(9 (sec)

Auto-zero time for input B


AUToB 999(9

Memory retention
MEMO OFF ●Setting range: ㅒㅜON, OFF

M-16
Pulse Meter
● Parameter 2 group (A)
Photoelectric
2 sec Sensors
RUN mode PARa1 PARa2 PARa3
(B)
Fiber
3 sec Optic
Sensors

Flashes
(C)

alternately 1 Data bank Door/Area
pBANK 1 ●Setting range: 1, 2 Sensors
※Only appears in MP5W.
(D)
Proximity
Sensors

DOT 00000 Decimal point location of display value


(E)
●Setting range: 00000, 000)0, 00)00, 0)000, )0000 Pressure
Sensors

Time unit and range


●Setting range (F)
Rotary
tUNT tSEC 99(99 tSEC (sec) tMIN (min) Encoders

99(99 999.99s 99(99 999.99m (G)


999(9 9999.9s 999(9 9999.9m Connectors/
tMIN 99(99 9(5(9 99m 59.9s 9(5(9 99h 59.9m
Connector Cables/
Sensor Distribution
Boxes/Sockets
(5(59 9h 59m 59s 99(59 999h 59m
99999 99999s 99999 99999m (H)
Temperature
Controllers

HH comparative value
PStHH 99999 ※Does not appear ※The parameters are identical to [PStHH],
(I)
SSRs / Power
Controllers
in F output mode [PSt H], [PSt L], [PStLL] of parameter 0
group and the setting values will be linked.
●Setting range by operation mode (J)
Counters
PSt H 99999 H comparative value Operation mode Setting range
F1, F2, F7, F9, F11,
0 to 99999
F12, F13, F16 (K)
Timers
F3, F4, F5, F6 0 to set time range
F8, F10, F14, F15 `9999 to 99999
PSt L 00000 L comparative value (the setting range varies depending on (L)
Panel
the decimal point setting.) Meters

※Only appears in comparative value setting


(M)
models. Tacho /
LL comparative value Speed / Pulse
PStLL 00000 ※Does not appear
Meters

in F output mode (N)


Display
Units

Prescale mantissa (X) of input A


PScaH ^0000 ●Setting range: )0001 to (9999
(O)
Sensor
Controllers

(P)
Switching
Mode Power
Prescale exponent (y) of input A Supplies
PScaY 10 01 ●Setting range: 10 - 9 (10-9) to 10 09 (109) (Q)
Stepper Motors
& Drivers
& Controllers

Prescale mantissa (X) of input B (R)


PScbH ^0000 ●Setting range: )0001 to (9999
Graphic/
Logic
Panels

(S)
Field
Network
Prescale exponent (y) of input B Devices
PScbY 10 01 ●Setting range: 10 - 9 (10-9) to 10 09 (109)
(T)
Software

Display cycle of measured value


●Setting range: )05, )5, 1, 2, 4, 8 (sec)
DISpT )05 ※Setting range in operation mode F2, F16
: OFF, )05, )5, 1, 2, 4, 8 (sec)

Setting value of input B


COUnB 99999 ●Setting range: 1 to 99999

M-17
MP5S/MP5Y/MP5W Series
● Parameter 3 group
2 sec
RUN mode PARa1 PARa2 PARa3
3 sec

Flashes

alternately 1
High-limit value of PV ●Setting range by operation mode
FS-H 99999 transmission output Operation mode Setting range
F1, F2, F7, F9, F11, F12,
0 to 99999
F13, F16
F3, F4, F5, F6 0 to set time range
F8, F10, F14, F15 `9999 to 99999
Low-limit value of PV trans-
FS-L 00000 mission output
(the setting range varies depending on the
decimal point setting.)
※Only appears in PV transmission output
models.

Current output
MA 4-20 specifications
●Setting range: 4-20, 0-20

Communication address
ADDR 01 ●Setting range: 01 to 99

Communication speed
B
ㅜㅠ PS 9600 ●Setting range: 9600, 19200,
38400, 2400, 4800 (bps)

Communication parity bit


P
ㅜ RTY NONE ●Setting range: NONE (none),
EVEN (even), ODD (odd)

※Only appears in RS485


Communication stop bit comm. output models.
STP 2 ●Setting range: 1, 2

Communication response wait time


●Setting range by communication speed
RSwT 20 Communication speed Setting range
(unit: bps) (unit: ms)
2400 16 to 99
4800 8 to 99
9600, 19200, 38400 5 to 99

Communication write
COmW D
ㅇ ISA ●Setting range: ENA (enable), DISA (disable)

Lock
●Setting range
LOC OFF
Parameter Function
OFF Unlock
LOc0 Lock all
LOc1 Parameter 1/2/3 lock
LOc2 Parameter 2/3 lock
LOc3 Parameter 3 lock

M-18
Pulse Meter
Operation Mode by Parameter Groups ( : parameter display, X: no parameter display) (A)
Photoelectric
Sensors
Operation
mode F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16
Parameter (B)
Fiber
※1 Optic
PStHH Sensors
※2
PSt H
(C)
※2 Appears in all operation modes (F1 to F16). Door/Area
0 group

PSt L Sensors
※1
PSt LL
(D)
hPEK Proximity
Sensors

lPEK
(E)
MODE Pressure
Appears in all operation mode (F1 to F16). Sensors
IN-A
※3
IN-B (F)
※2 Rotary
※4
Encoders
OUT-T
1 group

※2
(G)
HYS Connectors/
※2 Connector Cables/
GVARD Sensor Distribution
Boxes/Sockets
AVToA
(H)
Temperature
AVToB Controllers

MEMO
(I)
pBANK ※Only appears in MP5W. Appears in all operation modes (F1 to F16). SSRs / Power
Controllers

DOT
(J)
tUNT Counters
※1
PStHH
※2
PSt H (K)
Timers
※2
PStLL Appears in all operation modes (F1 to F16).
2 group

※1
PSt L (L)
Panel
Meters
PScaH
PScaY (M)
Tacho /
Speed / Pulse
PScbH Meters

PScbY (N)
※5 Display
DISpT Units

COUnB
(O)
Sensor
FS-H Controllers
※Only appears in PV transmission output models.
FS-L
Appears in operation modes (F1 to F16). (P)
Switching
ㅡMA Mode Power
Supplies
ADDR
(Q)
3 group

Stepper Motors
BPS & Drivers
& Controllers
PRTY ※Only appears in RS485 comm. output models.
Appears in all operation modes (F1 to F16). (R)
STP Graphic/
Logic
Panels
REwT
(S)
COmW Field
Network
LOC Devices

※1: Only appears in only for quintuple output models. (T)


※2: Only appears in triple, quintuple output models. Software
※3: The settings for IN-B and IN-A are applied.
※4: ( ) F output mode [OUT-F] cannot be set.
※5: ( ) setting range: OFF, )05, )5, 1, 2, 4, 8

Monitoring delay function by output mode


Output mode S mode H mode L mode B mode I mode F mode
Parameter STARD OVT-; OVT-L OVT-B OVT-I OVT-F
Comparative output limit
Start compensation timer

M-19
MP5S/MP5Y/MP5W Series
Operation Modes [MODE]
Select operation mode from operation mode[MODE]of parameter 1 group..
MP5 has 16 operation modes.

F1 Mode: Frequency/Revolutions/Speed
Measures the frequency of input A and displays the calculated frequency, revolutions, and speed.

1) Frequency (Hz) =f×α (α= 1[sec])


2) Revolutions (rpm) =f×α (α= 60[sec])
3) Speed (m/min) =f×α (α= 60L[sec])
※L: travel distance of conveyor belt of 1 pulse cycle[m]
α: prescale value MP5
60L
For multiple objects, α =
N
Encoder
Display value and display unit
MP5
Display value Display unit α (prescale value)

Hz 1 Timing chart
Frequency
kHz 0.001
rps 1 Input A
Revolutions
rpm (default) 60 t1 t2 t3 t4 t5 t6
Hold
mm/sec 1,000L input
cm/sec 100L 1 α 1 α 1 α 1 α 1 α
Display t1 t2 t3 t5 t6
Speed m/sec 1L
m/min 60L
km/hour 3.6L

F2 Mode: Passing Speed MP5


Displays the passing speed between input A ON and input B ON.
Passing speed (V) = f × α (α = L[m])
※f : reciprocal of time [sec] between input A (sensor) ON and
input B (sensor) ON.
L: distance between input A (sensor) and input B (sensor) [m]
α: prescale value Sensor B
Sensor A
Display value and display unit Timing chart
Display value Display unit α (prescale value)
Input A
mm/sec 1,000L Input B
cm/sec 100L Hold ta
Passing speed m/sec (default) 1L input
t1 t2 t3 t4 t5 t6 t7
m/min 60L
1 1 1 1 1 1
α t2 α α
t3 α t7 α
Display α
km/hour 3.6L t1 t4 t6
※ta: Return time (over 20ms)
F3 Mode: Cycle
Displays the measured time from Input A ON to the next ON.
Cycle (T) = t ※t: measurement time[sec]

Display value and display unit ([tUNT] of parameter 2) Photoelectric


sensor
Display value Display unit
MP5
Sec Min Timing chart
999.99s (default) 999.99m
Input A
9999.9s 9999.9m
Cycle t1 t2 t3 t4 t5 t6
99m59.9s 99h59.9m Hold
input
9h59m59s 999h59m
Display t1 t2 t3 t5 t6
99999s 99999m

M-20
Pulse Meter
F4 Mode: Passing Time (A)
Measures the time from Input A ON to the next ON, and displays the passing time of the arbitrary distance. Photoelectric
Sensors
Passing time[sec]= t × α
(B)
L[m]
(α= ) Fiber
Distance advanced in 1 pulse cycle [m] Optic
Sensors

※t : measured time[sec], L : arbitrary distance[m] (C)


α: prescale value Door/Area
m]
gth[
Sensors

Display value and display unit ([tUNT] of parameter 2) en


L:L
(D)
Display value Display unit
MP5 Proximity
Sensors

SEC MIN
(E)
999.99s Timing chart Pressure
999.99m Sensors
(default)
Input A
Passing time 9999.9s 9999.9m (F)
t1 t2 t3 t4 t5 t6 Rotary
99m59.9s 99h59.9m Hold Encoders

input (G)
9h59m59s 999h59m Connectors/
Display t1 α t2 α t3 α t5 α t6 α Connector Cables/
99999s 99999m Sensor Distribution
Boxes/Sockets

(H)
Temperature
Controllers

(I)
F5 Mode: Time Interval SSRs / Power
Controllers
Displays measured time of Input A ON
Time interval (T) = t
MP5 (J)
※t: measured time of input A ON [sec] Counters
Motor
Display value and display unit ([tUNT] of parameter 2)
Stamp (K)
Display value Display unit Timers

SEC MIN
Timing chart (L)
Panel
999.99s
999.99m Input A
Meters
(default)
(M)
Time interval 9999.9s 9999.9m t1 ta t2 ta t3 Tacho /
Hold Speed / Pulse
99m59.9s 99h59.9m input
Meters

9h59m59s 999h59m Display t1 t2 t3 (N)


Display
99999s 99999m Units
※ta: Return time (over 20ms)
(O)
Sensor
Controllers

F6 Mode: Time Differential (P)


Switching
Displays measured time from Input A ON to Input B ON. MP5 Mode Power
Supplies
Time differential (T) = t (ta to tb)
※t (ta to tb): measured time from input A ON to input B ON [sec] (Q)
Stepper Motors
& Drivers
& Controllers

Display value and display unit ([tUNT] of parameter 2)


Sensor B (R)
Graphic/
Logic
Display value Display unit Panels
Timing chart Sensor A
SEC MIN (S)
Field
999.99s Input A Network
999.99m Devices
(default) Input B
Time 9999.9s 9999.9m ta (T)
difference Hold Software

99m59.9s 99h59.9m input


t1 t2 t3 t4 t5 t6 t7
9h59m59s 999h59m
Display t1 t2 t3 t4 t6 t7
99999s 99999m
※ta: Return time (over 20ms)

M-21
MP5S/MP5Y/MP5W Series
F7 Mode: Absolute Ratio
Measures and displays relative speed, amount, speed, etc.
of input B against input A in percentage (%).
Flow meter A Flow meter B
Absolute ratio = (Input B / Input A) × 100%
Frequency of input B[Hz] × Bα
Absolute ratio = × 100[%]
Frequency of input A[Hz] × Aα MP5
Liquid
※Aα: Prescale value of input A, Bα: Prescale value of input B
Timing chart
Display value and display unit
Input A
Display value Display unit
fA
Absolute ratio % Input B
fB
※Hold: When the hold signal turns ON, the display value is Frequency of input B[Hz] × Bα
maintained until the display cycle turns to hold OFF. Display = × 100[%]
Frequency of input A[Hz] × Aα

F8 Mode: Error Ratio


Measures and displays the relative rate of input B against the reference value of input A
in percentage (%). Conveyor A
Input B-Input A Conveyor B
Error ratio = × 100[%]
Input A
(Frequency of input B [Hz] × Bα)-
Error ratio = (Frequency of input A[Hz] × Aα) × 100[%]
Frequency of input A[Hz] × Aα
MP5

※Aα: prescale value of input A, Bα: prescale value of input B


Timing chart
Display value and display unit Input A
Display value Display unit
fA
Error ratio %
Input B
※Hold: When the hold signal turns ON, the display value is
fB
maintained until the display cycle turns to hold OFF.

F9 Mode: Density
Measures and displays the density ratio (%) of input B against the total sum of input A
and input B.
Input B
Density = × 100[%] Flow meter A Flow meter B
Input A + Input B
Frequency of Input B[Hz] × Bα
Density = × 100[%]
(Frequency of input A[Hz] × Aα) + (Frequency of input B[Hz] × Bα)
Liquid
※Aα: Prescale value of input A, Bα: Prescale value of input B MP5

Display value and display unit Timing chart


Display value Display unit
Input A
Density %
fA

※Hold: When the hold signal turns ON, the display value is Input B
maintained until the display cycle turns to hold OFF. fB

F10 Mode: Error Conveyor A


Measures and displays the error of input B against reference value of input A. Conveyor B
Error = Input B - Input A
Error = (Frequency of input B[Hz] × Bα) - (Frequency of input A[Hz] × Aα)
※Aα: prescale value of input A, Bα: prescale value of input B
Display value and display unit
MP5
Display value Display unit
Timing chart
Error END User setting Input A
※Hold: When the hold signal turns ON, the display value is fA
maintained until the display cycle turns to hold OFF.
Input B
fB

M-22
Pulse Meter
F11 Mode: Length Measurement 1 (A)
Measure and display the number of input A pulses during input B ON. Photoelectric
Sensors
Length measurement = P × α Input A
Input B (B)
※P: Number of input A pulses, α: Prescale value Fiber
Optic
Photoelectric sensor Sensors

Timing chart MP5 (C)


Display value and display unit Door/Area
Sensors
Input A
Display value Display unit 1 2 3 4 5 6 1 2 1 2 3 4
(D)
Quantity (default) Input B Proximity
Sensors
mm ta tb
Length Hold
measurement cm input (E)
Pressure
Sensors
m Display 6 α 2 α 4 α
※ta, tb: return time (over 20ms) (F)
Rotary
Encoders

F12 Mode: Interval (G)


MP5 Connectors/
Measures and displays the number of input A pulses from Input B Connector Cables/
Sensor Distribution
ON to the next ON. Boxes/Sockets

Interval = P × α (H)
※P: Number of input A pulses, α: Prescale value Temperature
Controllers

Display value and display unit Photoelectric sensor (I)


Timing chart SSRs / Power
Display value Display unit Controllers

Quantity (default) Input A


1 2 3 4 5 1 2 3 4 1 2 3 (J)
mm Input B Counters
Interval
cm ta
Hold
m input (K)
Timers

Display 5×α 4×α


(L)
※ta: return time (over 20ms) Panel
Meters

(M)
Tacho /
Speed / Pulse
F13 Mode: Accumulation Meters
Measures and displays the counted value of input A pulses.
(N)
Accumulation = P × α Display

※P: Number of input A pulses, α: Prescale value MP5 Units

Display value and display unit (O)


Sensor
Controllers
Display value Display unit
Timing chart
Accumulation Quantity[EA] (P)
Switching
Input A Mode Power
Operation 1 2 3 4 5 6 1 2 3 4 Supplies

①Counts the number of input A pulses. Input B


(Q)
②Input B is an enable input signal. During ON, the quantity and RESET Stepper Motors
& Drivers
display value of input A will be held, and during OFF input A will & Controllers

be re-counted. Display 0 1 2 3 4 5 6 0 1 2 3 4
(R)
③When RESET input is ON, the integrated counted value will be reset Graphic/
to "0". ※α=1 display value Logic
Panels

(S)
Field
Network
Devices

(T)
Software

M-23
MP5S/MP5Y/MP5W Series
F14 Mode: Addition/Subtraction-Individual Input
Displays the counted value from added input A pulses and subtracted MP5
input B pulses. When there are two inputs simultaneously, it will not count.
Addition/Subtraction = Input A × α - Input B × β
※α: Prescale value of input A, β: Prescale value of input B Photoelectric Input B
sensor Input A (subtraction)
(addition)
Timing chart
Display value and display unit
H
Display value Display unit Input A L
Addition/ H
Input B
Subtraction Quantity L
(individual input) RESET H
L
Operation and timing chart
Display 0 1 2 32 0 1 2 3 2 1
Pulse of input A is added, and pulse of input B is subtracted.
※α, β=1 display value

F15 Mode: Addition/Subtraction- Phase difference input


When input A is low, counting is added to the low of input B. Input A
When input A is low, counting is subtracted from the high of input B.
Addition/Subtraction (phase difference)
Input B
= Detects position and speed using A and B phases of MP5
encoder outputs as input. Timing chart
H
Display value and display unit Input A L
Display value Display unit H
Input B
L
Up/Down counting
(phase difference Quantity RESET H
L
input)
Display 0 1 2 3 2 1 0 1 2 0

F16 Mode: Length Measurement 2


Timing chart (e.g.) setting value of Input B=4
Measures and displays the number of pulses from input A until the value
of input B reaches the set value. H
Input A L
Length measurement 2 = P × α (until the setting value of Input B)
H 1 2 1 2 3 4 1 2 3
※P: Number of input A pulses, α: Prescale value Input B L

Display value and display unit H


RESET L
Display value Display unit 1 2 3 4 0 1 2 3 4 5 6 7 0 1 2 3 4 5
Display
Length measurement 2 Quantity[EA] ※1
0 7
Display
※If input A and input B are ON during initial power supply, it will not ※1: W
 hen the display cycle [DISpT] setting is OFF, it will maintain
count and only count the number of rising edge. the quantity of input A until the value of input B reaches the
※Display value is renewed depending on the display cycle [DISpT] setting value B [COUnB].
setting.

M-24
Pulse Meter
Output Modes [OUT-T] (A)
Photoelectric
MP5 Series supports 6 output modes. (There is no output mode in indicator models). Sensors
Requirement for setting comparative value: (B output mode) LL<L<H<HH, (F output mode) L<H,
(other output modes) individual output operation regardless of size or order of set comparative values. ※1: hysteresis (B)
Fiber
S (standard) Output Mode [STARD] H (high) Output Mode [OVT-H] Optic
Sensors
HH HH
Comparative H Comparative H (C)
L Door/Area
value L value Sensors
LL LL
※1 ※1
HH HH (D)
※1 ※1 Proximity
H H Sensors

L ※1
Output GO Output
※1 LL ※1
L (E)
Pressure
LL
※1 GO Sensors

HH output : Display value ≥ Comparative setting value HH HH output : Display value ≥ Comparative setting value HH (F)
Rotary
H output : Display value ≥ Comparative setting value H H output : Display value ≥ Comparative setting value H Encoders
L output : Display value ≤ Comparative setting value L L output : Display value ≥ Comparative setting value L
(G)
LL output : Display value ≤ Comparative setting value LL LL output : Display value ≥ Comparative setting value LL Connectors/
※GO output ON when there are no HH, H, L, LL outputs ※GO output ON when there are no HH, H, L, LL outputs Connector Cables/
Sensor Distribution
Boxes/Sockets

(H)
L (low) Output Mode [OUT-L] B (block) Output Mode [OUT-B] Temperature
Controllers
HH
Comparative H HH
Comparative H (I)
value L SSRs / Power
LL value L Controllers
LL
HH ※1 ※1
※1
HH ※1 (J)
H H Counters

L ※1
Output Output GO
※1 L ※1
LL
(K)
GO LL ※1 Timers

HH output : Display value ≤ Comparative setting value HH HH output : Display value ≥ Comparative setting value HH
H output : Display value ≤ Comparative setting value H H output : Comparative setting value HH > Display value ≥ (L)
Panel
L output : Display value ≤ Comparative setting value L Comparative setting value H Meters

LL output : Display value ≤ Comparative setting value LL L output : Comparative setting value LL < Display value ≤
(M)
※GO output ON when there are no HH, H, L, LL outputs Comparative setting value L Tacho /
LL output : Display value ≤ Comparative setting value LL Speed / Pulse
Meters
※GO output ON when there are no HH, H, L, LL outputs
(N)
I (one-shot) Output Mode [OUT-I] F (deflection) Output Mode [OVT-F] Display
Units
Transmits outputs when the saved setting value exceeds H
HH deviation or L deviation.
(O)
Comparative H Saving setting value: press the + keys to save as setting value. Sensor
value L Checking setting value: press the key to check the setting value. Controllers
LL 0.3s Setting deviation: Sets H deviation [PSt H], and L deviation[PSt
(P)
HH L] of parameter group 0,2 with the setting value as reference. (The Switching
0.3s
set deviation value is saved during Power OFF until it is re-set.) Mode Power
H Supplies
Ouput GO Deviation setting range: 0.0001 to 99999 (the setting range varies
0.3s depending on the decimal point [DOT] setting.) (Q)
Stepper Motors
L E.g.)Decimal point[DOT]: 0000.0, Setting range: 0.1 to 9999.9 & Drivers
0.3s & Controllers
LL Saving setting value ( + key)
(high-limit) (R)
H deviation Graphic/
Logic
Setting value Panels
HH output : Display value ≥ Comparative setting value HH (low-limit)
H output : Comparative setting value HH > Display value ≥ L deviation (S)
Field
Comparative setting value H ON Network
Power OFF Devices
L output : Comparative setting value H > Display value ≥
Saving ON
Comparative setting value L setting value OFF
LL output : Comparative setting value L > Display value ≥ L deviation ON ※2 (T)
Software
Comparative setting value LL output OFF
※3
※No GO output H deviation ON
output OFF
※One-shot output time is fixed at 0.3 sec.
※No hysteresis ※2: W hen selecting initial comparative output limit function, it does
not transmit outputs.
※3: The graph is assuming that there is a saved setting value prior
to the setting value save point. The actual output position may
be different.
※There are no HH, GO, LL outputs.
※The deviation can be set to "0" but the actual operation will be the
same as "1".

M-25
MP5S/MP5Y/MP5W Series
Function Comparative setting
Hysteresis [HYS] value H, HH
Near the comparative setting value, the output may turn ON/OFF
frequently and unstably. Comparative setting
To prevent this, hysteresis value is set based on the comparative value L, LL A
A
setting value.
Output H, HH
※A: hysteresis value
※The hysteresis value can be set to "0" but the actual operation value is "1". Output L, LL

Delay monitoring [GUArD]


After supplying power, the starting current of motors and other inputs are changeable. This function allows stable control by limiting all outputs
for a certain period of time, until the target measurement unit stabilizes. It may also control L, LL outputs until a specific output is reached.
C
 omparative output limit function [fDEFY]
: Only for S (Standard), B (Block), F (Deflection) output mode.
: Limits L, LL output before H, HH output.
※Initial L, LL ouptuts does not operate, so GO output operates.

1) During S (Standard) output mode 2) During B (Block) output mode


HH HH
Comparative H Comparative H
value L value L
LL LL

HH HH
H H
Output GO Output GO
L L
LL LL
Comparative output limit function Comparative output limit function
removal removal
※After supplying power, there is no initial L, LL comparative outputs ( ).
※Each setting value of HH, H, LL, L is not related to their relative sizes. Hence, HH value may be lower or equal to LL value.

3) During F (Deflection) output mode


Comparative output limit ※After supplying power, there is no comparative output ( ) of L
function removal deviation.
Comparative

H deviation ※In F output mode, the comparative output limiting function is


value

Setting value removed at the set value (standard setting)


L deviation ※H and L deviation are not related to their relative sizes.
(H deviation setting value > L deviation setting value,
H H deviation setting value < L deviation setting value)
Output
L
Monitoring delay time
Start compensation timer function [STArT]
Set monitoring delay time so that there is no output during the delay time. L, LL
comparative
setting value
No output
Output
Auto-zero time setting [AUToA, AUToB]
When there is no input signal during auto-zero setting time, the display value is automatically set to 0 (zero). Please set the auto-zero setting
time so that it is longer than the interval of the slowest input signal. If the setting time is too long and there is no input signal, the rate at which
the display value falls to 0 (zero) decrease, and output response rate may slow down.

Data bank [pBANK] (only for MP5W)


Comparative setting value and prescale value are saved as two types (data bank 1, 2) and can be selected for use by opening or shorting of
terminals.
Terminal 3, 5 open: use value of data bank 1
Terminal 3, 5 short: use value of data bank 2

Prescale [PSc .H, PSc .Y]


Displays values in required units or specific multiples by counting the number of input pulses, then multiplying the number of pulses or the
length of pulses by variables (X×10y).

Number of revolutions (rpm) = f×α


= f×60×(1 / N)
= f×60×(1 / 4) ※f: The number of input pulses per second[Hz],
MP5 = f×60×0.25 α: Prescale value
= f×15 N: The number of pulses per revolution

Setting prescale value (α=15)


Set mantissa (X) as 1.5000, and exponent (Y) as 1 for prescale value (α)=15.
The same display value can be obtained with α value set as X=0.1500, and Y=2.

M-26
Pulse Meter
RS485 Communication Output (A)
Photoelectric
 pplicable for models with RS485 communication output through sub output (MP5Y- 5, MP5W- 8/9).
A Sensors
Please refer to ' Ordering Information'.
1. Communication specifications (B)
Fiber
Optic
Comm. protocol Modbus RTU 2400, 4800, 9600 (default), 19200, Sensors
Communication Speed
Connection type RS485 38400 bps
Application standard Compliance with EIA RS485 Communication response time 5 to 99ms (default: 20ms) (C)
Door/Area
Max. connection 31 units (address: 01 to 99) Start Bit 1-bit fixed Sensors

Synchronous method Asynchronous Data Bit 8-bit fixed


Comm. method Two-wire half duplex Parity Bit None (default), Even, Odd (D)
Proximity
Comm. distance Max. 800m Stop Bit 1, 2-bit (default) Sensors

2. System configuration (E)


Pressure
RS232C/ Sensors
Terminating resistance
USB/Wi-Fi RS485 (100 to 120Ω)
B(-) RS485 (F)
Rotary
DEVICE Encoders

A(+) #31 (G)


Comm. Connectors/
Connector Cables/
converter A(+) B(-) A(+) B(-) A(+) B(-) Sensor Distribution
Boxes/Sockets
B(-)
RS485 RS485 RS485
(H)
DEVICE DEVICE DEVICE Temperature
Computer ON OFF #1 #2 #30 Controllers

(I)
A(+) SSRs / Power
Controllers
※It is recommended to use Autonics communication converter; SCM-WF48 (Wi-Fi to RS485·USB wireless communication converter, sold
separately), SCM-US48I (USB to RS485 converter, sold separately), SCM-38I (RS232C to RS485 converter, sold separately).
(J)
Please use twisted pair wire for RS485 communication. Counters
3. Communication control sequence
1. Communication equence follows Modbus RTU protocol.
2. Communication with the host system can be established after 1sec (1,000ms) of supplying power. (K)
Timers
3. The initial transmission authority is held by the host device (PC). When the host device transmits a request, the MP5W/Y Series sends a
response.
Read command

Read command

(L)
No. of data

No. of data
Address

Address

Address

Address

Panel
CRC16

CRC16

Meters

Host
system (M)
Tacho /
Speed / Pulse
※A: a
 fter 1 sec of supplying
Response command

Meters
No. of data
Address

power
CRC16

MP5W/Y B: 38400bps:
 approx. 1.75ms (N)

Series 19200bps: approx. 2ms ※The longer of the communication Display


Units
A B C 9600bps: approx. 4ms response wait time [RSwT] of
4800bps: approx. 8ms parameter group 3 and response time (O)
2400bps: approx.16ms of B is applied. Sensor
C: over 20ms Controllers
4. Cautions for communication
1. Twisted pair cable (AWG24) is recommended for RS485 communication. When not using twisted pair cables, please make sure that A (+) (P)
Switching
and B (-) cable lengths are equal. Mode Power
2. After connecting the communication cable, terminating resisters (100 to 120Ω) must be attached at both ends. Supplies

5. Communication command and block definition (Q)


Stepper Motors
5-1. read coil status (func. 01 H), read input status (func. 02 H) & Drivers
& Controllers
1) Query (Master)
(R)
Slave Function Starting Address No. of Points (no. of data) Error Check (CRC 16) Graphic/
Logic
Address (command) High Low High Low Low High Panels

1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte (S)


Field
Network
CRC16 Devices
2) Response (slave)
Slave Function Byte Count Error Check (CRC 16) (T)
Data (low) Data Data (high) Software
Address (command) (no. of data byte) Low High
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte

CRC16
5-2. Read Holding registers (func. 03 H), read input registers (func. 04 H)
1) Query (Master)
Function Starting Address No. of Points (no. of data) Error Check (CRC 16)
Slave Address
(command) High Low High Low Low High
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte

CRC16

M-27
MP5S/MP5Y/MP5W Series
2) Response (Slave)
Function Byte Count Data Data Data Error Check (CRC 16)
Slave Address
(command) (no. of data byte) High Low High Low High Low Low High
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte

CRC16

5-3. Force single coil (func. 05 H)


1) Query (Master)
Function Coil Address Force Data Error Check (CRC 16)
Slave Address
(command) High Low High Low Low High
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte
CRC16

2) Response (Slave)
Function Coil Address Force Data Error Check (CRC 16)
Slave Address
(command) High Low High Low Low High
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte

CRC16

5-4. Preset single register (func. 06 H)


1) Query (Master)

Function Register Address Preset Data Error Check (CRC 16)


Slave Address
(command)
High Low High Low Low High
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte
CRC16
2) Response (Slave)
Function Register Address Preset Data Error Check (CRC 16)
Slave Address
(command) High Low High Low Low High
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte

CRC16

5-5. Preset multiple registers (func. 10 H)


1) Query (Master)
Error Check
Slave Function Starting Address No. of Register Byte Data Data
(CRC 16)
Address (command) Count
High Low High Low High Low High Low Low High
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte

CRC16

2) Response (Slave)
Function Starting Address No. of Register Error Check (CRC 16)
Slave Address
(command) High Low High Low Low High
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte

CRC16

5-6. Exception response-error code (exception processing)


Function Error Check (CRC 16)
Slave Address Exception code
+80H Low High
1Byte 1Byte 1Byte 1Byte 1Byte

CRC16

 hen a communication error occurs, the highest bit from the received command (function) is set (1), a response command is sent, and the
W
corresponding exception code is transmitted.
(1) ILLEGAL FUNCTION (exception code: 01 H)
: Unsupported command
(2) ILLEGAL DATA ADDRESS (exception code: 02 H)
: The requested start address does not not match the transmission address of the device.
(3) ILLEGAL DATA VALUE (exception code: 03 H)
: The number of requested data does not match the transmission number of the device.
(4) S LAVE DEVICE FAILURE (exception code: 04 H)
: The requested command cannot be processed properly. (CRC)

M-28
Pulse Meter
6. Address mapping table (A)
6-1. Read coil status (func. 01) / Force single coil (func. 05) Photoelectric
Sensors
No.(Address) Func R/W Parameter Description Setting range Note
000001(0000) 01 R/W HH HH comparative output 0: OFF / 1: ON (B)
Fiber
000002(0001) 01 R/W H H comparative output Comparative 0: OFF / 1: ON Optic
Sensors
000003(0002) 01 R/W GO GO comparative output output 0: OFF / 1: ON
000004(0003) 01 R/W L L comparative output LED 0: OFF / 1: ON
(C)
000005(0004) 01 R/W LL LL comparative output 0: OFF / 1: ON Door/Area
Sensors
000006(0005) 01 R/W 0: OFF / 1: ON
000007(0006) 01 R/W 0: OFF / 1: ON
(D)
000008 to 000050 01 R/W 0: OFF / 1: ON Proximity
Sensors
6-2. Read input status (func. 02)
No.(Address) Func R/W Parameter Description Setting range Note
(E)
100001(0000) 02 R RESET(HOLD) External input RESET input status Pressure
variables Sensors
100002(0001) 02 R BANK BANK input status
100003(0002) 02 R 0: OFF / 1: ON
100004(0003) 02 R 0: OFF / 1: ON (F)
Rotary
100005(0004) 02 R 0: OFF / 1: ON Encoders
100006(0005) 02 R 0: OFF / 1: ON
(G)
100007(0008) 02 R 0: OFF / 1: ON Connectors/
Connector Cables/
100008(0007) 02 R 0: OFF / 1: ON Sensor Distribution
100009(0008) 02 R 0: OFF / 1: ON Boxes/Sockets
100010(0009) 02 R 0: OFF / 1: ON (H)
100011(000A) 02 R 0: OFF / 1: ON Temperature
Controllers
100012 to 100050 02 R 0: OFF / 1: ON

6-3. Read input registers (func. 04) (I)


SSRs / Power
No.(Address) Func R/W Parameter Description Factory default Note Controllers

300001 to 300100 04 R Reserved


300101(0064) 04 R Product number H 0 Dedicated (J)
Counters
300102(0065) 04 R Product number L 0 model number
300103(0066) 04 R Hardware Version 1
300104(0067) 04 R Software Version 1 (K)
300105(0068) 04 R Model 1 "MP" Timers

300106(0069) 04 R Model 2 "5 "


300107(006A) 04 R Model 3 "- " (L)
300108(006B) 04 R Model 4 " " MP5Y- 5, Panel
Meters
300109(006C) 04 R Model 5 " " MP5W- 8
(※MP5W- 9
300110(006D) 04 R Model 6 " " (M)
displayed as Tacho /
300111(006E) 04 R Model 7 " " MP5W- 8) Speed / Pulse
Meters
300112(006F) 04 R Model 8 " "
300113(0070) 04 R Model 9 " " (N)
300114(0071) 04 R Model 10 " " Display
Units
300115(0072) 04 R Reserved
300116(0073) 04 R Reserved (O)
300117(0074) 04 R Reserved Sensor
Controllers
300118(0075) 04 R Coil Status Start Address 0000
300119(0076) 04 R Coil Status Quantity 0 (P)
Switching
300120(0077) 04 R Input Status Start Address 0000 Mode Power
300121(0078) 04 R Input Status Quantity 0 Supplies

300122(0079) 04 R Holding Register Start Address 0000 (Q)


300123(007A) 04 R Holding Register Quantity 0 Stepper Motors
& Drivers
300124(007B) 04 R Input Register Start Address 0000 & Controllers

300125(007C) 04 R Input Register Quantity 0 (R)


300126 to 300200 04 R Reserved Graphic/
Logic
No.(Address) Func R/W Parameter Description Setting range Note Panels
HH HH LED Display 0: OFF 1: ON 0 Bit
H Front H LED Display 0: OFF 1: ON 1 Bit (S)
Field
301001(03E8) 04 R GO display GO LED Display 0: OFF 1: ON 2 Bit Network
L LED L LED Display 0: OFF 1: ON 3 Bit Devices
LL LL LED Display 0: OFF 1: ON 4 Bit
301002(03E9)
04 R PV Measurement value -19999 to 99999 (T)
301003(03EA) Software
0: 00000 3: 0)000
301004(03EB) 04 R DOT 1: 000)0 4: )0000
2: 00)00
0: 999.99s 5: 999.99m
1: 9999.9s 6: 9999.9m
301005(03EC) 04 R UNIT 2: 99m59.9s 7: 99h59.9m
3: 9h59m59s 8: 999h59m
4: 99999s 9: 99999m
0: F1 to
301006(03ED) 04 R MODE Operation mode 1: F2 14: F15
2: F3 15: F16
301007(03EE) 04 R

M-29
MP5S/MP5Y/MP5W Series
6-4. R
 ead holding registers (func. 03) / Preset single register (func. 06) /
Preset multiple registers (func. 16)
6-4-1. Comparative value settings and peak value check group
Factory
No.(Address) Func R/W Parameter Description Setting range
default
400001(0000) HH comparative
03/16 R/W PStHH Preset HH 0 to 99999 99999
400002(0001) value
400003(0002)
03/16 R/W PSt H Preset H H comparative value 0 to 99999 99999
400004(0003)
400005(0004) ※1
03/16 R/W PSt L Preset L L comparative value 0 to 99999 00000
400006(0005)
400007(0006) ※1
03/16 R/W PStLL Preset LL LL comparative value 0 to 99999 00000
400008(0007)
400009(0008) High peak value ※2
03/16 R/W hPEK High Peak 99999 -
400010(0009) of measured value
400011(000A) Low peak value ※2
03/16 R/W lPEK Low Peak -19999 -
400012(000B) of measured value
400013 to 400050 03/06/16 R/W Reserved
※1: In operation modes F8, F10, F14, F15,the setting range is -19999 to 99999
※2: Max./Min. measurement value
6-4-2. Parameter 1 group
Factory
No.(Address) Func R/W Parameter Description Setting range
default
0: F1 to
400051(0032) 03/06/16 R/W MODE Mode Input operation mode 1: F2 14: F15 0
2: F3 15: F16
400052(0033) 03/06/16 R/W IN-A Input A 0: NPnhF
1: NPnmF
2: NPnlF
Sensor type 0
400053(0034) 03/06/16 R/W IN-B Input B 3: PNphF
4: PNpmF
5: PNplF
0: STARD
1: OUT-H
2: OUT-L
400054(0035) 03/06/16 R/W OUT-T Output type Output mode 0
3: OUT-B
4: OUT-I
5: OUT-F
400055(0036) 03/06/16 R/W HYS Hysteresis Hysteresis value 1 to 9999 1
0: fDEFY
400056(0037) 03/06/16 R/W GUArD Output limit Output limit function 0
1: STArT
Start compensation
400057(0038) 03/06/16 R/W STArT Start limit value 0.0 to 99.9 0.0
timer value
400058(0039) 03/16 R/W
AUToA Auto-zero A
400059(003A) 03/16 R/W
Auto-zero time 0.1 to 9999.9 9999.9
400060(003B) 03/16 R/W
AUToB Auto-zero B
400061(003C) 03/16 R/W
0: OFF
400062(003D) 03/06/16 R/W MEMO Memory Memory retention 0
1: ON
400063 to 400100 03/06/16 R/W Reserved
6-4-3. Parameter 2 group
Factory
No.(Address) Func R/W Parameter Description Setting range
default
0: 1
400101(0064) 03/06/16 R/W pBANK Data bank Data bank 0
1: 2
0: 00000
1: 000)0
400102(0065) 03/06/16 R/W DOT Dot Decimal point 2: 00)00 0
3: 0)000
4: )0000
0: tSEC
400103(0066) 03/06/16 R/W tUNT Time unit Time unit 0
1: tMIN
0: 99(99 999.99s
1: 999(9 9999.9s
2: 9(5(9 99m59.9s
3: (5(59 9h59m59s
4: 99999 99999s
400104(0067) 03/06/16 R/W tSEC Time sec Time range 0
5: 99(99 999.99m
6: 999(9 9999.9m
7: 9(5(9 99h59.9m
8: 99(59 999h59m
9: 99999 99999m

M-30
Pulse Meter
6-4-3. Parameter 2 group
(A)
Factory Photoelectric
No.(Address) Func. R/W Parameter Description Setting range Sensors
default
400105(0068) 03/16 R/W HH (B)
PStHH Preset HH comparative 0 to 99999 99999 Fiber
400106(0069) 03/16 R/W value
Optic
Sensors

400107(006A) 03/16 R/W H comparative


PSt H Preset H 0 to 99999 99999 (C)
400108(006B) 03/16 R/W value Door/Area
Sensors
400109(006C) 03/16 R/W L comparative ※1
PSt L Preset L 0 to 99999 0
400110(006D) 03/16 R/W value
(D)
400111(006E) 03/16 R/W LL comparative ※ Proximity
PStLL Preset LL 0 to 99999 1 0 Sensors
400112(006F) 03/16 R/W value
400113(0070) 03/16 R/W Prescale A Prescale A
PScaH 0.0001 to 9.9999 6.0000 (E)
400114(0071) 03/16 R/W Mantissa mantissa Pressure
Sensors
Prescale A Prescale A 00 to 09: + (0 to 9)
400115(0072) 03/06/16 R/W PScaY 01
Exponent exponent 10 to 19: - (0 to 9)
(F)
400116(0073) 03/16 R/W Prescale B Prescale B Rotary
PScbH 0.0001 to 9.9999 6.0000 Encoders
400117(0074) 03/16 R/W Mantissa mantissa
Prescale B Prescale B 00 to 09: + (0 to 9) (G)
400118(0075) 03/06/16 R/W PScbY 01 Connectors/
Exponent exponent 10 to 19: - (0 to 9) Connector Cables/
Sensor Distribution
0: OFF 4: 2 Boxes/Sockets
1: )05 5: 4
400119(0076) 03/06/16 R/W DISpT Display time Display cycle 1 (H)
2: )5 6: 8 Temperature
3: 1 Controllers

400120(0077) 03/16 R/W Operation


INB
COUnB mode 1 to 99999 99999 (I)
400121(0078) 03/16 R/W Setting value SSRs / Power
F16 INB Controllers
400122 to 400150 03/06/16 R/W Reserved
※1: In operation modes F8, F10, F14, F15, the setting range is -19999 to 99999 (J)
Counters
6-4-4. Parameter 3 group
Factory
No.(Address) Func. R/W Parameter Description Setting range (K)
default Timers
400151(0096) High-limit value of PV
03/16 R/W FS-H Full scale High Setting range varies by 99999
400152(0097) transmission output
model and operation (L)
400153(0098) Low-limit value of PV mode 1
※ Panel
03/16 R/W FS-L Full scale Low 0 Meters
400154(0099) transmission output
Transmission output 0: 4-20(mA) (M)
400155(009A) 03/06/16 R/W MA mA 0 Tacho /
spec. 1: 0-20(mA) Speed / Pulse
Meters
400156(009B) 03/06/16 R/W ADDR Unit address Communication address 1 to 99 1
0: 2400 (N)
1: 4800 Display
Units
400157(009C) 03/06/16 R/W BPS Bit per Sec Communication Speed 2: 9600 2
3: 19200
4: 38400 (O)
Sensor
0: NONE Controllers
Communication parity
400158(009D) 03/06/16 R/W PRTY Parity bit 1: EVEN 0
bit (P)
2: ODD Switching
0: 1 Mode Power
400159(009E) 03/06/16 R/W STP Stop bit Communication stop bit 1 Supplies
1: 2
Response Communication (Q)
400160(009F) 03/06/16 R/W RSwT 5 to 99(ms) 20 Stepper Motors
waiting time response waiting time & Drivers
& Controllers
Communi Communication write 0: DISA
400161(00A0) 03/06/16 R/W COmW 0
cation write enable/disable 1: ENA (R)
Graphic/
0: OFF Logic
1: LOc0 Panels

400162(00A1) 03/06/16 R/W LOC Lock Lock 2: LOc1 0 (S)


3: LOc2 Field
Network
4: LOc3 Devices
400163 to 400200 03/06/16 R/W Reserved
(T)
※1: High-limit/low-limit setting value of PV transmission output. (varies by model and operation mode) Software

Series Operation mode Setting range


F1, F2, F7, F9, F11, F12, F13, F16 0 to 99999
MP5Y
F3, F4, F5, F6 0.01 to set time range
MP5W
F8, F10, F14, F15 -19999 to 99999

M-31
MP5S/MP5Y/MP5W Series
Comprehensive Device Management Program (DAQMaster)
●●DAQMaster is comprehensive device management program for convenient management of parameters and multiple
device data monitoring.
●●Visit our website (www.autonics.com) to download user manual and comprehensive device management program.

< Computer specification for using software > < DAQMaster screen >
Item Minimum requirements
System IBM PC compatible computer with Intel Pentium Ⅲ or above
Operations Microsoft Windows 98/NT/XP/Vista/7/8/10
Memory 256MB+
Hard disk 1GB+ of available hard disk space
VGA Resolution: 1024×768 or higher
Others RS-232 serial port (9-pin), USB port

Cautions during Use


● Please separate the unit wiring from high voltage lines or power lines to prevent inductive noise.
● Install a power switch or circuit breaker to control the power supply.
● In case of 24VAC, 24-48VDC model, power supply should be insulated and limited voltage/current or Class 2 SELV power supply device.
● The power switch or circuit breaker should be installed where it is easily accessible by the user.
● Do not use the unit in the following environments.
① Environments with high vibration or shock.
② Environments with exposure to direct sunlight.
③ Near machinery which produce strong magnetic force or electric noise.
● Storing the unit
When storing the unit for an extended period, please avoid direct exposure to sunlight. Ambient temperature should be between -20℃ to
60℃ and ambient humidity should be between 35% to 85%RH. Store in factory packaging for best results.
● Input line
Please use a shield wire in environments where noise may occur or instances where long measurement input lines are required.
● Please maintain distance between the power supply line and measurement input line.
● This product may be used in the following environments
① Indoors
② Max. altitude: 2,000m
③ Pollution degree 2
④ Installation category II

M-32

You might also like