Voltage Standby Rating (Esp) Prime Rating (PRP) Standby Amper
Voltage Standby Rating (Esp) Prime Rating (PRP) Standby Amper
Voltage Standby Rating (Esp) Prime Rating (PRP) Standby Amper
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and
continuous duty applications. All generator sets are factory build, and production tested.
STANDBY RATING (ESP) Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility
source. ESP is in accordance with ISO 8528. Overload is not allowed.
PRIME RATING (PRP) Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528. 10 %
overload capability is available for a period of 1 hour within 12-hour perod of operation,in accordance with ISO 3046.
General Characteristics
Model Name AD 275
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model DOOSAN P126TI
Alternator Made and Model AK 4200
Control Panel Model DSE 7320
Canopy MS 60
ENGINE SPECIFICATIONS
Engine DOOSAN
Engine Model P126TI
Number of Cylinder (L) 6 cylinders - in line
Bore (mm.) 123
Stroke (mm.) 155
Displacement (lt.) 11.051
Aspiration Turbo Charged and Intercooled (Air to Air)
Compression Ratio 17.1:1
RPM (d/dk) 1500
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2019)
Oil Capacity (Total With Filter) (lt) 23
Standby Power (kW/HP) 272/370
Prime Power (kW/HP) 241/328
Block Heater QTY 1
Block Heater Power (Watt) 3000
Fuel Type Diesel
Type of Fuel Pump Zexel P inline
Governor System Electronic
Operating Voltage (Vdc) 24 Vdc
Battery and Capacity (Qty/Ah) 2x85
Charge Alternator (A) 45
Cooling Method Water Cooled
Cooling Fan Air Flow (m3/min) 295
Coolant Capacity (engine only / with radiator) (lt) 19/51
Air Filter Dry Type
Fuel Cons. Prime With %100 Load (lt/hr) 58.1
Fuel Cons. Prime With %75 Load (lt/hr) 43.6
Fuel Cons. Prime With %50 Load (lt/hr) 30
ALTERNATOR CHARACTERISTICS
Manufacturer Aksa
Alternator Made and Model AK 4200
Frequency (Hz) 50
Power (kVA) 250
VOLTAGE (V) 400
Phase 3
A.V.R. SX440
Voltage Regulation (+/-)1%
Insulation System H
Protection IP22
Rated Power Factor 0.8
WEIGHT WOUND ROTOR (Kg) 272.6
COOLING AIR (m³/min) 34.8
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2019)
LENGTH 3960
WIDTH 1356
HEIGHT 2167
DRY WEIGHT (kg.) 2985
TANK CAPACITY (lt.) 470
1. Steel structures.
2. Emergency stop push button.
3. Control panel is mounted on the baseframe . Located
at the right side of the generator set.
4. Corrosion-resistant locks and hinges.
5. Oil could be drained via valve and a hose
6. Exhaust system in the canopy.
7. Special large access doors for easy maintanance
8. In front and back side special large access doors for
easy maintanance
9. Base frame -fuel tank.
10. Lifting points similar to ISO container , located on
each top corner of the canopy.
11. The cap on the canopy provides easy accsess to
radiator cap.
12. Sound proofing materials
13. Plastic air intake pockets.
INTRODUCTION
Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements
and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our
modular designed sound insulated canopies provide ease of access for servicing and general maintenance and
interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance,
providing you with confidence that genset ratings and ambient capability.
Control Panel
Control Module DSE
Control Module Model DSE 7320
Communication Ports MODBUS
Devices
DSE, model 7320 Auto Mains Failure control module Static battery charger Emergency stop push button and fuses for
control circuits
CONSTRUCTION and FINISH
Comonents installed in sheet steel enclosure.
Phosphate chemical, pre-coating of steel provides corrosion resistant surface
Polyester composite powder topcoat forms high gloss and extremely durable finish
Lockable hinged panel door provides for easy component access
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2019)
INSTALLATION
Control panel is mounted generating set baseframe on robust steel stand or power module. Located at side of generating
set with properly panel visibility.
GENERATING SET CONTROL UNIT
The DSE 7320 conrol module is a standard addition to our generator sets from 220 kVA upwards and it has been
designed to start and stop diesel andgas generating sets that include electronic and non electronic engines.
The DSE 7320 includes the additional capability of being able to monitor a mains (utility) supply and is therefore suitable
for controlling a standby generating set in conjunction with an automatic transfer switch.
The DSE7320 also indicates operational status and fault conditions, automatically shutting down the generating set and
indicating faults by means of its LCD display on the front panel.
STANDARD SPECIFICATIONS
Microprocessor controlled
- 132 x 64 pixel LCD display makes information easy to read
- Front panel programming and also via PC software
- Soft touch membrane keypad and five key menu navigation
- Remote communications via RS232, RS485 and ethernet.
- Event logging (50) showing date and time
- Multiple date and time engine exercise mode and maintenance scheduler
- Engine block heater control.
- Controls; stop, manuel, auto, test, start, mute lamb test/transfer to generator, transfer to mains, menu navigation.
Instruments
ENGINE
Engine speed
Oil pressure
Coolant temperature
Run time Battery volts
Engine maintenance due
GENERATOR
Voltage (L-L, L-N)
Current (L1-L2-L3)
Frequency
Earth current
kW
Pf
kVAr
kWh, kVAh, kVArh
Phase sequence
MAINS
Voltage (L-L, L-N)
Frequency
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2019)
WARNING
Charge failure
Battery under voltage
Fail to stop
Low fuel level (opt.)
kW over load
Negative phase sequence
Loss of speed signal
PRE-ALARMS
Low oil pressure
High engine temperature
Low engine temperature
Over /Under speed
Under/over generator frequency
Under/over generator voltage
ECU warning
SHUT DOWNS
Fail to start
Emergency stop
Low oil pressure
High engine temperature
Low coolant level
Over /Under speed
Under/over generator frequency
Under/over generator voltage
Oil pressure sensor open
Phase rotation
ELECTRICAL TRIP
Earth fault
kW over load
Generator over current
Negative phase sequence
Options
High oil temperature shut down
Low fuel level shut down
Low fuel level alarm
High fuel level alarm
EXPANSION MODULES
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2019)
Editional LED module (2548)
Expension relay module (2157)
Expansion input module (2130)
Standards
Elecrical Safety / EMC compatibility
BS EN 60950 Electrical business equipment
BS EN 61000-6-2 EMC immunity standard
BS EN 61000-6-4 EMC emission standard
STATIC BATTERY CHARGER
Battery charger is manufactured with switching-mode and SMD technology and it has high efficincy.
Battery charger models' output V-I characteristic is very close to square
2405 has fully output shot circuit protection and ıt can be used as a current source.
2405 charger has high efficiency, long life, low failure rate, light weight and low heat radiated in accordance with linear
alternatives.
The charger is fitted with a protection diode across the output.
Charge fail output is available.
Connect charge fail relay coil between positive output and CF output.
Input: 196-264V.
Output: 27,6V 5A or 13,8V 5A.
STANDARD SPECIFICATIONS
- Water cooled, Diesel engine
- Radiator with mechanical fan
- Protective grille for rotating and hot parts
- Electric starter and charge alternator
- Starting battery (with lead acid) including rack and cables
- Engine coolant heater
- Base frame design incorporates an integral fuel tank and anti-vibration isolators
- Flexible fuel connection hoses
- Single bearing, class H alternator
- Industrial exhaust silencer and steel bellows supplied separately(for open sets)
- Static battery charger
- Manual for application and installation
OPTIONAL EQUIPMENTS
ENGINE
Anti-Condensation Heater
Over sized alternator
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2019)
PMG excitation + AVR
Main line circuit breaker
CONTROL SYSTEM
AKSA CERTIFICATES
- TS ISO 8528
- CE
- SZUTEST
- 2000/14/EC
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2019)