Ap 150-1
Ap 150-1
Ap 150-1
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and
continuous duty applications. All generator sets are factory build, and production tested.
STANDBY RATING (ESP) Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility
source. ESP is in accordance with ISO 8528-1. Overload is not allowed.
PRIME RATING (PRP) Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 %
overload capability is available for a period of 1 hour within 12-hour perod of operation.
General Characteristics
Model Name AP 150
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model PERKINS 1106A-70TG1
Alternator Made and Model ECP 34-2M/4 C
Control Panel Model DSE 6120
Canopy AK 49
ENGINE SPECIFICATIONS
Engine PERKINS
Engine Model 1106A-70TG1
Number of Cylinder (L) 6 cylinders - in line
Bore (mm.) 105
Stroke (mm.) 135
Displacement (lt.) 7.01
Aspiration Turbo Charged
Compression Ratio 18.2:1
RPM (d/dk) 1500
Oil Capacity (Total With Filter) (lt) 18
Standby Power (kW/HP) 135.8/182,03
Prime Power 122.7/164,47
Block Heater QTY 1
Block Heater Power (Watt) 1500
Fuel Type Diesel
Injection Type and System Direct
Type of Fuel Pump Delphi DPG Rotary Type
Governor System Mechanic
Operating Voltage (Vdc) 12 Vdc
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2024)
Battery and Capacity (Qty/Ah) 1x85
Charge Alternator (A) 65
Cooling Method Water Cooled
Coolant Capacity (engine only / with radiator) (lt) /21
Air Filter Dry Type
Fuel Cons. Prime With %100 Load (lt/hr) 30.3
Fuel Cons. Prime With %75 Load (lt/hr) 22.7
Fuel Cons. Prime With %50 Load (lt/hr) 15.9
ALTERNATOR CHARACTERISTICS
Manufacturer Mecc Alte
Alternator Made and Model ECP 34-2M/4 C
Frequency (Hz) 50
Power (kVA) 135
VOLTAGE (V) 400
Phase 3
A.V.R. DSR
Voltage Regulation (+/-)1%
Insulation System H
Protection IP23
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 388
COOLING AIR (m³/min) 29.2
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2024)
7. Lifting Points
INTRODUCTION
Sound–attenuated and Weather-protective Enclosures Sound-attenuated and weather protective enclosures for generating
sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and
development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access
for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed
to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.
Control Panel
Control Module DSE
Control Module Model DSE 6120
Communication Ports CANBUS
1. Menu navigation buttons
2. Close mains button
3. Main Status and instrumentation display
4. Alarm LED's
5. Close generator button
6. Status LED's
7. Operation selecting buttons
Devices
-DSE, model 6120 Auto Mains Failure control module.
-Battery charger input 198-264 volt, output 27,6 V 5 A (24 V) or 13,8 Volt 5A (12V)
-Emergency stop push button and fuses for control circuits.
CONSTRUCTION and FINISH
-Components installed in a sheet steel enclosure. Phosphate chemical, pre-coating of steel provides corrosion resistant
surface. Polyester composite powder topcoat forms high gloss and an extremely durable finish. Lockable and hinged
panel door provides easy access to components.
INSTALLATION
Control panel is mounted on baseframe with a steel stand. Located at the right side of the generator set (When you look
at the Gen.Set. from Alternator)
GENERATING SET CONTROL UNIT
The DSE 6120 module has been designed to monitor generator frequency, volt, current, engine oil pressure, coolant
temperature running hours and battery volts.
Module monitors the mains supply and switches over to the generator when the mains power fails.
The DSE6120 also indicates operational status and fault conditions, Automatically shutting down the Gen. Set and giving
true first-up fault condition of Gen. Set failure.The LCD display indicates the fault.
STANDARD SPECIFICATIONS
-Microprocessor controlled.
-LCD display makes information easy to read.
-Automatically transfers between mains (utility) and generator power.
-Manual programming on the front panel.
-User-friendly set-up and button layout.
-Remote start.
-Event logging (50) showing date and time.
-Controls: Stop/Reset, Manual, Auto, Test, Start, buttons. An additional push button next to the LCD display is used to
scroll through the modules' metering displays.
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2024)
Instruments
ENGINE
-Engine speed.
-Oil pressure.
-Coolant temperature.
-Run time.
-Battery volts.
-Configurable timing.
GENERATOR
-Voltage (L-L, L-N).
-Current (L1-L2-L3).
-Frequency.
-Gen. Set ready.
-Gen. Set enabled.
MAINS
-Mains ready.
-Mains enabled.
WARNING
-Charge failure.
-Battery Low/High voltage.
-Fail to stop.
-Low /High generator voltage.
-Under /Over generator frequency.
-Over /Under speed.
-Low oil pressure.
-High coolant temperature.
SHUTDOWNS
-Fail to start.
-Emergency stop.
-Low oil pressure.
-High coolant temperature.
-Over /Under speed.
-Under/over generator frequency.
-Under/over generator voltage.
-Oil pressure sensor open.
-Coolant temperature sensor open.
ELECTRICAL TRIP
-Generator over current.
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2024)
Options
-Flexible sensor can be controlled with temperature, pressure, percentage (warning/shutdown/electrical trip)
-Local setting parameters and monitoring from PC to control module with USB connection (max 6 mt).
Standards
-Elecrical Safety / EMC compatibility
-BS EN 60950 Electrical business equipment.
-BS EN 61000-6-2 EMC immunity standard.
-BS EN 61000-6-4 EMC emission standard
STATIC BATTERY CHARGER
- Battery charger is manufactured with switching-mode and SMD technology and ıt has high efficiency.
- Battery charger models' output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volts and
27,6 V for 24 V . Input 198 - 264 volt AC.
- The charger is fitted with a protection diode across the output.
- Connect charge fail relay coil between the positive output and CF output.
- They are equipped with RFI filter to reduce electrical noise radiated from the device.
- Galvanically isolated input and output typically 4kV for high reliability.
STANDARD SPECIFICATIONS
- Water cooled, Diesel engine
- Radiator with mechanical fan
- Protective grille for rotating and hot parts
- Electric starter and charge alternator
- Starting battery (with lead acid) including rack and cables
- Engine coolant heater
- Base frame design incorporates an integral fuel tank and anti-vibration isolators
- Flexible fuel connection hoses
- Single bearing, class H alternator
- Industrial exhaust silencer and steel bellows supplied separately(for open sets)
- Static battery charger
- Manual for application and installation
OPTIONAL EQUIPMENTS
ENGINE
Anti-Condensation Heater
Over sized alternator
Main line circuit breaker
CONTROL SYSTEM
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2024)
Remote annunciator panel
Remote relay output
Alarm output relays
Remote communication with modem
Earth fault, single set
Charge Ammeter
TRANSFER SWITCH
AKSA CERTIFICATES
- TS ISO 8528
- TS ISO 9001-2008
- CE
- SZUTEST
- 2000/14/EC
Manufacturer reserves the right to make change in the model, technical specifications, color, equipment, accessories and images without prior notice. (15.03.2024)