Hopkinson'S Test: Technical Manual FOR
Hopkinson'S Test: Technical Manual FOR
Hopkinson'S Test: Technical Manual FOR
: M-18
TECHNICAL MANUAL
FOR
HOPKINSON’S TEST
Manufactured by :
HOPKINSON’ TEST
AIM : (a) To perform Hopkinson’s test on two identical DC machines.
(b) To determine the efficiency of the DC Machine as motor at 50%, 75%, and
100% of full load.
MACHINES USED
Two identical D.C. machines, 230 V, 1500 RPM, coupled mechanically through flexible coupling and
mounted on m.s. channel base.
SPECIFICATIONS:
DC SHUNT MOTOR : 1.5 HP/KW, 230V ,1500 R.P.M. Screen Protected, Horizontal Foot Mounted,
Class ‘B’ Insulation, Internally Fan Cooled, With Interpoles . ‘RAJAT’ Make with DC starter
faceplate type.
D.C. SHUNT GENERATOR : 1.5 HP/KW, 230V,1500 R.P.M. Screen Protected, Horizontal Foot
mounted, Self Excited Type, Class ‘B’ Insulation ,Internally Fan Cooled With Interpoles. ‘RAJAT’
Make
Both the machines are flexibly coupled and mounted on sturdy m.s. channel base. The terminals of
armature and shunt field windings of both the machines shall be brought over to bakelite plate fixed on
c.i. terminal box fitted on top of machine .
Fitted on bakelite sheet enclosed in almirah type ms box with lock & handle arrangement suitable for
table mounting.
FOR DC MOTOR :-
FOR DC GENERATOR :
THEORY
The efficiency of the DC machine can be accurately determined by the regenerative method,
normally known as Hopkinson’s test. This test overcomes the drawback of Swinburne’s test, which
does not take any account of the stray load losses occurring in DC machines under loaded condition.
As such the efficiency, calculated by Swinburne’s test is comparatively higher than the actual one.
Hopkinson’s test needs two identical DC machines coupled mechanically and connected electrically as
shown in Fig. ‘A’. One of the machines is operated as motor, driving the other machine as a generator.
The output power of the generator is fed to the motor. Thus the power drawn from the supply is only
to overcome the losses of both the machines. By varying the field current of generator and motor i.e. I 4
and I3 any desired load can be adjusted on these two machines. Rating the circuit diagram of Fig ‘A’
following expression can be established for the case.
Let the sum of iron losses and mechanical losses of each machine be Wc, then
Efficiency of Motor
2
PREMIER TRADING CORPORATION
Hence, the efficiency of the both machines at various loads can be worked out, recording the
various currents and voltage during the experiment and measuring the resistance of armature of both
the machines.
2. Both the DC machines are operating under loaded conditions, can such stray load losses
are taken into account.
CIRCUIT DIAGRAM
Fig ‘A’ shows the circuit diagram; in which two identical DC machines are connected in such a
way that one of them is acting as a motor and another as a generator. The following instruments
connected in the circuit serve the function indicated against each.
1. Ammeters A1(I1), A2(I2) – to measure the current drawn from the supply and the
generator current respectively.
2. Ammeters, A3(I3), A4(I4) – to measure the field current of motor and generator
respectively.
PROCEDURE :
1. Connect the two DC machines, coupled mechanically as per the circuit diagram shown
in attached sheet.
3. Adjust the rheostat, so that the field current of the motor is MAXIMUM.
4. Adjust the rheostat, so that the field current of the motor is MINIMUM.
5. Switch on the DC supply and start the DC motor using the starter properly.
3
PREMIER TRADING CORPORATION
6. Adjust the speed of the motor to rated value by varying the rheostat provided in its field
circuit.
7. Adjust rheostat in the field circuit of generator, so that the generated voltage of the
generator is equal to the supply voltage.
8. The control panel connection diagram is done as per the schematic diagram given in
figure ‘A’. We have internally connected as per the polarity the respective armature
terminals of motor and generator i.e. armature terminals A and AA of motor is
connected to respective armature terminals A and AA of generator and now check the
voltage across the switch, S. In case of right polarity the voltmeter V1 will read
practically zero voltage but if you have to show to the students regarding the wrong
polarity connections then you have to interchange the sequence of armature
connections of generator, then in that case the voltmeter will record twice the supply
voltage. Repeat steps 5, 6 and 7. Now the voltmeter V1 reads zero. Under this condition,
the machine working as a generator is just floating i.e. neither drawing any current from
nor giving into the lines. Now check the applied voltage Vs and generated voltage Vg,
and observed that both the applied voltage and generated voltage are nearly same.
9. Now to study the behaviour under various load conditions, the SPST switch is put to
ON position and various values of load current is put on the generator, keeping the
motor to its rated speed under various load conditions (which is done by decreasing the
field current of the motor). At various load setting note down the corresponding applied
voltage Vs, I1, I2, I3 & I4.
11. Reduce the load on the generator and motor by varying their field current.
13. Measure the resistance of the armature circuit of motor and generator by usual
voltammeter method.
S Vs Vg I1 I2 I3 I4 Wc m1 m2
No.
4
PREMIER TRADING CORPORATION