3 Point Starter
3 Point Starter
3 Point Starter
A 3 point starter in simple words is a device that helps in the starting and running of a shunt wound dc motor or compound wound dc motor. Now the question is why these types of dc motors require the assistance of the starter in the first case. The only explanation to that is given by the presence of back emf Eb, which plays a critical role in governing the operation of the motor. The back emf, develops as the motor armature starts to rotate in presence of the magnetic field, by generating action and counters the supply voltage. This also essentially means, that the back emf at the starting is zero, and develops gradually as the motor gathers speed. The general motor emf equation E = Eb + Ia.Ra, at starting is modified to E = Ia.Ra as at starting Eb = 0.
Thus we can well understand from the above equation that the current will be dangerously high at starting (as armature resistance Ra is small) and hence its important that we make use of a device like the 3 point starter to limit the starting current to an allowable lower value. Let us now look into the construction and working of three point starter to understand how the starting current is restricted to the desired value. For that lets consider the diagram given below showing all essential parts of the three point starter.
armature field
And from there it gets the name 3 point starter Now studying the construction of 3 point starter in further details reveals that, the Point L is connected to an electromagnet called overload release (OLR) as shown in the figure. The other end of OLR is connected to the lower end of conducting lever of starter handle where a spring is also attached with it and the starter handle contains also a soft iron piece housed on it. This handle is free to move to the other side RUN against the force of the spring. This spring brings back the handle to its original OFF position under the influence of its own force. Another parallel path is derived from the stud 1, given to the another electromagnet called No Volt Coil (NVC)which is further conne cted to
terminal F. The starting resistance at starting is entirely in series with the armature. The OLR and NVC acts as the two protecting devices of the starter.
motor against the high starting current produced in the absence of back emf at starting. The 4 point starter has a lot of constructional and functional similarity to a three point starter, but this special device has an additional point and a coil in its construction, which naturally brings about some difference in its functionality, though the basic operational characteristic remains the same. Now to go into the details of operation of 4 point starter, lets have a look at its constructional diagram, and figure out its point of difference with a 3 point starter.
1. 2. 3.
L A F
to to to
of
armature field
Like in the case of the 3 point starter, and in addition to it there is 4. A 4th point N. (Connected to the No Voltage Coil) The remarkable difference in case of a 4 point starter is that the No Voltage Coil is connected independently across the supply through the fourth terminal called N in addition to the L, F and A. As a direct consequence of that, any change in the field supply current does not bring about any difference in the performance of the No Voltage Coil. Thus it must be ensured that No Voltage Coil always produce a force which is strong enough to hold the handle in its RUN position, against force of the spring, under all the operational conditions. Such acurrent is adjusted through No Voltage Coil with the help of fixed resistance R connected in series with the NVC using fourth point N as shown in the figure above. Apart from this above mentioned fact, the 4 point and 3 point starters are similar in all other ways like possessing is a variable resistance, integrated into number of sections as shown in the figure above. The contact points of these sections are called studs and are shown separately as OFF, 1, 2, 3, 4, 5, RUN, over which the handle is free to be maneuvered manually to regulate the starting current with gathering speed.
Now to understand its way of operating lets have a closer look at the diagram given above. Considering that supply is given and the handle is taken stud No. 1, then the circuit is complete and line current that starts flowing through the starter. In this situation we can see that the current will be divided into 3 parts, flowing through 3 different points.
i) 1 part flows through the starting resistance (R1+ R2+ R3..) and then to the armature. ii) A 2nd part flowing through the field winding F.
iii) And a 3rd part flowing through the No Voltage Coil in series with the protective resistance R. So the point to be noted here is that with this particular arrangement any change in the shunt field circuit does not bring about any change in the No Voltage Coil as the two circuits are independent of each other. This essentially means that the electromagnet pull subjected upon the soft iron bar of the handle by the No Voltage Coil at all points of time should be high enough to keep the handle at its
RUN position, or rather prevent the spring force from restoring the handle at its original OFF position, irrespective of how the field rheostat is adjusted. This marks the operational difference between a 4 point starter and a 3 point starter. As otherwise both are almost similar and are used for limiting the starting current to a shunt field or compound excited dc motor, and thus act as a protective device