Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Flat Plate Heat Exchanger Performance Curves X08A Element: Supply P.D

Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X08A ELEMENT
100 1.0

Supply P.D.
90 0.8

Air
Flo
wR
% Effectiveness

atio
80 1.2 =1
.5 0.6
1.0

Pressure Drop
(Inches W.G.)
70 0.4

60 t P.D 0.2
aus
Exh
P.D
ply
Sup

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min Wgt.
X08A-4 3.94 0.16 16 32 47 63 79 7
X08A-6 5.91 0.26 26 51 77 102 128 13
X08A-10 9.84 0.45 45 90 135 181 226 17
X08A-16 15.75 0.74 74 149 223 298 372 22
X08A-18 17.72 0.84 84 168 253 337 421 30
X08A-24 23.62 1.14 114 227 341 454 568 35
X08A-30 29.53 1.43 143 286 429 572 714 39
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A A = 7.9" (Height)
D C = 0.50" (Flange Dimension)
D = 11.2"

A
B
C Specifications and Dimensions are subject to change without notice.

20
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X12A ELEMENT
100 1.0

90 0.8
Air
Flo
wR
atio
1.2 =1
% Effectiveness

.5
80 1.0 0.6

Pressure Drop
(Inches W.G.)
70 0.4

60 Exhau
st P.D 0.2
Supply P.D

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500 600
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X12A-6 5.91 0.37 37 74 110 147 184 221 7
X12A-12 11.81 0.81 81 162 243 324 405 487 13
X12A-18 17.72 1.25 125 251 376 502 627 752 17
X12A-24 23.62 1.70 170 339 509 679 848 1018 22
X12A-30 29.53 2.14 214 428 642 856 1070 1284 30
X12A-36 35.43 2.58 258 517 775 1033 1291 1550 35
X12A-42 41.34 3.03 303 605 908 1210 1513 1815 39
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A A = 11.8" (Height)
D C = 0.50" (Flange Dimension)
D = 16.7"

A
B
C Specifications and Dimensions are subject to change without notice.

21
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X14A ELEMENT
100 1.0

90 Air 0.8
Flo
w
Ra
1.2 tio
= 1.5

Pressure Drop
% Effectiveness

(Inches W.G.)
1.0
80 0.6

70 0.4

P.D
60 Exhaust 0.2
Supply P.D

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500 600
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X14A-6 5.91 0.44 44 87 131 174 218 262 7
X14A-12 11.81 0.96 96 192 288 384 481 577 15
X14A-18 17.72 1.49 149 297 446 594 743 892 20
X14A-24 23.62 2.01 201 402 603 804 1005 1207 25
X14A-30 29.53 2.54 254 507 761 1014 1268 1522 35
X14A-36 35.43 3.06 306 612 918 1224 1530 1837 40
X14A-42 41.34 3.59 359 717 1076 1434 1793 2151 45
X14A-48 47.25 4.11 411 822 1233 1644 2055 2466 51
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A = 13.8" (Height)
C = 0.50" (Flange Dimension)
A
D = 19.5"
D

A Specifications and Dimensions are subject to change without notice.


B
C
22
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X20A ELEMENT
100 1.0

90 Air
0.8
Flow
Rat
io =
1.5
1.2

80 1.0
0.6

Pressure Drop
(Inches W.G.)
% Effectiveness

70 0.4

st P.D
Exhau
60 D 0.2
Supply P.

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min (SCFM)
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500 600 700
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X20A-10 9.84 1.15 115 230 345 459 574 689 804 25
X20A-18 17.72 2.17 217 434 651 868 1085 1303 1520 41
X20A-24 23.62 2.94 294 588 881 1175 1469 1763 2057 51
X20A-30 29.53 3.70 370 741 1111 1482 1852 2223 2593 60
X20A-36 35.43 4.47 447 894 1342 1789 2236 2683 3130 70
X20A-48 47.25 6.01 601 1201 1802 2402 3003 3603 4204 101
X20A-60 59.06 7.54 754 1508 2262 3016 3770 4524 5278 121
X20A-72 70.87 9.07 907 1815 2722 3629 4537 5444 6351 141
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A A = 19.7" (Height)
D C = 1.0" (Flange Dimension)
D = 27.9"

A
Specifications and Dimensions are subject to change without notice.
B Rev. 11/95
C
23
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X20B ELEMENT
100 1.0

90 0.8

80 0.6

D
t P.

Pressure Drop
(Inches W.G.)
aus
% Effectiveness

Exh
70 .D
0.4
Air Flow Ratio = 1.5 yP
ppl
Su

1.2

60 1.0
0.2

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500 600 700
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X20B-10 9.84 1.15 115 230 345 459 574 689 804 33
X20B-18 17.72 2.17 217 434 651 868 1085 1303 1520 49
X20B-24 23.62 2.94 294 588 881 1175 1469 1763 2057 64
X20B-30 29.53 3.70 370 741 1111 1482 1852 2223 2593 79
X20B-36 35.43 4.47 447 894 1342 1789 2236 2683 3130 92
X20B-48 47.25 6.01 601 1201 1802 2402 3003 3603 4204 120
X20B-60 59.06 7.54 754 1508 2262 3016 3770 4524 5278 145
X20B-72 70.87 9.07 907 1815 2722 3629 4537 5444 6351 171
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A = 19.7" (Height)
A
C = 1.0" (Flange Dimension)
D
D = 27.9"

A Specifications and Dimensions are subject to change without notice.


B Rev. 11/95

C
24
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X24B ELEMENT
100

90 0.8
Air
Flo
wR
atio
1.2 = 1.
5

80 1.0 0.6

Pressure Drop
(Inches W.G.)
% Effectiveness

70 0.4

.D
ust P
Exha
60 Supply P.D
0.2

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
Size (B) Area 100 200 300 400 500 600 700 Wgt
Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min ft/min
X24B-12 11.81 1.70 170 339 509 679 848 1018 1188 40
X24B-18 17.72 2.62 262 525 787 1049 1312 1574 1837 61
X24B-24 23.62 3.55 355 710 1065 1420 1775 2130 2485 80
X24B-30 29.53 4.48 448 895 1343 1791 2239 2686 3134 98
X24B-36 35.43 5.40 540 1081 1621 2162 2702 3243 3783 115
X24B-48 47.25 7.26 726 1452 2177 2903 3629 4355 5081 149
X24B-60 59.06 9.11 911 1822 2734 3645 4556 5467 6378 181
X24B-72 70.87 10.97 1097 2193 3290 4386 5483 6579 7676 213
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A A = 23.6" (Height)
D C = 1.0" (Flange Dimension)
D = 33.4"

A
B Specifications and Dimensions are subject to change without notice.
Rev. 11/95
C
25
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X24D ELEMENT
100 1.0

90 0.8

80 0.6

Pressure Drop
(Inches W.G.)
% Effectiveness

.D
tP
us
xha
E

70 0.4
.D
ly P
Air Flow Ratio = 1.5 pp
Su

1.2
60 0.2
1.0

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500 600 700
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X24D-12 11.81 1.70 170 339 509 679 848 1018 1188 33
X24D-18 17.72 2.62 262 525 787 1049 1312 1574 1837 49
X24D-24 23.62 3.55 355 710 1065 1420 1775 2130 2485 64
X24D-30 29.53 4.48 448 895 1343 1791 2239 2686 3134 79
X24D-36 35.43 5.40 540 1081 1621 2162 2702 3243 3783 92
X24D-48 47.25 7.26 726 1452 2177 2903 3629 4355 5081 120
X24D-60 59.06 9.11 911 1822 2734 3645 4556 5467 6378 145
X24D-72 70.87 10.97 1097 2193 3290 4386 5483 6579 7676 171
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A A = 23.6" (Height)
D C = 1.0" (Flange Dimension)
D = 33.4"

A Specifications and Dimensions are subject to change without notice.


B Rev. 11/95

C
26
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X30B ELEMENT
100

Air
Flo
wR
90 atio
= 1.
5
1.2
1.2

1.0

80 0.9

Pressure Drop
(Inches W.G.)
% Effectiveness

70 0.6

st P.D
Exhau
60 0.3
D
Supply P.

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500 600 700
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X30B-18 17.72 3.31 331 662 993 1323 1654 1985 2316 112
X30B-24 23.62 4.48 448 896 1343 1791 2239 2687 3134 150
X30B-30 29.53 5.65 565 1129 1694 2259 2823 3388 3952 184
X30B-36 35.43 6.82 682 1363 2045 2726 3408 4089 4771 224
X30B-42 41.34 7.98 798 1597 2395 3194 3992 4790 5589 262
X30B-48 47.25 9.15 915 1831 2746 3661 4576 5492 6407 299
X30B-60 59.06 11.49 1149 2298 3447 4596 5745 6894 8043 374
X30B-72 70.87 13.83 1383 2766 4149 5531 6914 8297 9680 449
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A A = 29.5" (Height)
D C = 1.0" (Flange Dimension)
D = 41.7"

A
B Specifications and Dimensions are subject to change without notice.
Rev. 11/95
C
27
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X30D ELEMENT
100 1.0

90 0.8

80 t P.D 0.6

Pressure Drop
us

(Inches W.G.)
ha
% Effectiveness

Ex

P.D
70 Air Flow Ratio = 1.5
pp
ly 0.4
Su

1.2

60 1.0
0.2

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500 600 700
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X30D-18 17.72 3.31 331 662 993 1323 1654 1985 2316 77
X30D-24 23.62 4.48 448 896 1343 1791 2239 2687 3134 103
X30D-30 29.53 5.65 565 1129 1694 2259 2823 3388 3952 154
X30D-36 35.43 6.82 682 1363 2045 2726 3408 4089 4771 180
X30D-42 41.34 7.98 798 1597 2395 3194 3992 4790 5589 205
X30D-48 47.25 9.15 915 1831 2746 3661 4576 5492 6407 231
X30D-60 59.06 11.49 1149 2298 3447 4596 5745 6894 8043 257
X30D-72 70.87 13.83 1383 2766 4149 5531 6914 8297 9680 308
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A
A = 29.5" (Height)
D
C = 1.0" (Flange Dimension)
D = 41.7"

A
B Specifications and Dimensions are subject to change without notice.
Rev. 11/95
C
28
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X40B ELEMENT
100 1.5

Air
Flow
Rat
io =
1.5
90 1.2 1.2
1.0

80 0.9

Pressure Drop
(Inches W.G.)
% Effectiveness

70 0.6

.D
ust P
Exha
60 P.D
0.3
Supply

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500 600 700
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X40B-18 17.72 4.46 446 892 1337 1783 2229 2675 3121 173
X40B-24 23.62 6.03 603 1207 1810 2413 3016 3620 4223 231
X40B-30 29.53 7.61 761 1522 2282 3043 3804 4565 5325 289
X40B-36 35.43 9.18 918 1837 2755 3673 4591 5510 6428 347
X40B-42 41.34 10.76 1076 2151 3227 4303 5379 6454 7530 405
X40B-48 47.25 12.33 1233 2466 3700 4933 6166 7399 8633 462
X40B-60 59.06 15.48 1548 3096 4645 6193 7741 9289 10837 578
X40B-72 70.87 18.63 1863 3726 5590 7453 9316 11179 13042 693
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A = 41.3" (Height)
A C = 1.5" (Flange Dimension)
D D = 58.5"

A Specifications and Dimensions are subject to change without notice.


B Rev. 11/95

C
29
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X40D ELEMENT
100 1.0

90 0.8

80 Air Flow 0.6


Ratio =
1.5

Pressure Drop
(Inches W.G.)
% Effectiveness

1.2

70 1.0
0.4

st P.D
Exhau
60 Supply
P.D 0.2

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500 600 700
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X40D-18 17.72 4.46 446 892 1337 1783 2229 2675 3121 134
X40D-24 23.62 6.03 603 1207 1810 2413 3016 3620 4223 178
X40D-30 29.53 7.61 761 1522 2282 3043 3804 4565 5325 223
X40D-36 35.43 9.18 918 1837 2755 3673 4591 5510 6428 268
X40D-42 41.34 10.76 1076 2151 3227 4303 5379 6454 7530 312
X40D-48 47.25 12.33 1233 2466 3700 4933 6166 7399 8633 357
X40D-60 59.06 15.48 1548 3096 4645 6193 7741 9289 10837 446
X40D-72 70.87 18.63 1863 3726 5590 7453 9316 11179 13042 535
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A
D A = 41.3" (Height)
C = 1.5" (Flange Dimension)
D = 58.5"

A
B
Specifications and Dimensions are subject to change without notice.
C Rev. 11/95

30
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X50B ELEMENT
100 1.5
Air
Flo
wR
atio
1.2 = 1.5

90 1.0 1.2

80 0.9

Pressure Drop
(Inches W.G.)
% Effectiveness

70 0.6

60 st P
.D 0.3
hau P.D
Ex ply
Sup

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500 600 700
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X50B-24 23.62 7.33 703 1405 2108 2811 3514 4216 4919 324
X50B-36 35.43 11.24 1078 2156 3234 4312 5390 6468 7546 485
X50B-48 47.25 15.15 1453 2906 4359 5813 7266 8719 10172 648
X50B-60 59.06 19.07 1828 3657 5485 7313 9142 10970 12798 809
X50B-72 70.87 22.98 2204 4407 6611 8814 11018 13221 15425 971
X50B-84 82.68 26.89 2579 5157 7736 10315 12894 15472 18051 1134
X50B-96 94.49 30.80 2954 5908 8862 11816 14770 17724 20678 1295
X50B-108 106.30 33.29 3329 6658 9987 13317 16646 19975 23304 1456
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A = 49.2" (Height)
A C = 1.5" (Flange Dimension)
D D = 69.6"

A
B Specifications and Dimensions are subject to change without notice.
Rev. 11/95
C
31
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X50D ELEMENT
100 1.5

90 1.2

Air Flo
w Ratio =
80 1.5 0.9

Pressure Drop
1.2

(Inches W.G.)
% Effectiveness

1.0

70 0.6

60 t P.D
0.3
aus
Exh

P.D
Supply

50 0.0
100 200 300 400 500 600 700
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 100 200 300 400 500 600 700
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X50D-24 23.62 7.33 703 1405 2108 2811 3514 4216 4919 251
X50D-36 35.43 11.24 1078 2156 3234 4312 5390 6468 7546 376
X50D-48 47.25 15.15 1453 2906 4359 5813 7266 8719 10172 502
X50D-60 59.06 19.07 1828 3657 5485 7313 9142 10970 12798 627
X50D-72 70.87 22.98 2204 4407 6611 8814 11018 13221 15425 752
X50D-84 82.68 26.89 2579 5157 7736 10315 12894 15472 18051 878
X50D-96 94.49 30.80 2954 5908 8862 11816 14770 17724 20678 1003
X50D-108 106.30 33.29 3329 6658 9987 13317 16646 19975 23304 1128
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A = 49.2" (Height)
A C = 1.5" (Flange Dimension)
D D = 69.6"

A
B Specifications and Dimensions are subject to change without notice.
C Rev. 11/95

32
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X60D ELEMENT
100 3.0

90 2.4
Air Flo
w Rati
o = 1.5
1.2
80 1.8

Pressure Drop
(Inches W.G.)
% Effectiveness

1.0

70 1.2

60 .D
0.6
st P
hau
Ex
P. D
ply
Sup
50 0.0
200 400 600 800 1000 1200
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 200 400 600 800 1000 1200
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min ft/min Wgt.
X60D-24 23.62 8.56 1712 3424 5136 6847 8559 10271 411
X60D-36 35.43 13.23 2647 5294 7941 10588 13235 15882 616
X60D-48 47.25 17.91 3582 7164 10746 14328 17910 21492 822
X60D-60 59.06 22.59 4517 9034 13551 18068 22585 27103 1027
X60D-72 70.87 27.26 5452 10904 16357 21809 27261 32713 1232
X60D-84 82.68 31.94 6387 12775 19162 25549 31936 38324 1438
X60D-96 94.49 36.61 7322 14645 21967 29289 36612 43934 1643
X60D-108 106.30 41.29 8257 16515 24772 33030 41287 49545 1848
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A = 59.0" (Height)
C = 1.0" (Flange Dimension)
A
D = 83.4"
D

A Specifications and Dimensions are subject to change without notice.


Rev. 11/95
B
C
33
Heat- -Changer

Flat Plate Heat Exchanger Performance Curves


X80D ELEMENT
100 2.4

90 Air Flo
w Ratio = 2.0
1.5

1.2

1.0
80 1.6

Pressure Drop
(Inches W.G.)
% Effectiveness

70 1.2

.D
ust P
60 Exha 0.8
Supply P.D

50 0.4
200 400 600 800 1000
Face Velocity Ft./Min
(Refer to Conversion chart below for SCFM)

Conversion Chart - Airflow (SCFM) @ (Face Velocity x Face Area)


(AxB)
Face Element Face Velocity
(B) Area 200 400 600 800 1000
Size Length Sq. Ft. ft/min ft/min ft/min ft/min ft/min Wgt.
X80D-48 47.25 23.71 4742 9484 14226 18968 23709 1736
X80D-60 59.06 29.97 5994 11987 17981 23974 29968 2170
X80D-72 70.87 36.23 7245 14491 21736 28981 36226 2605
X80D-84 82.68 42.48 8497 16994 25491 33988 42485 3038
X80D-96 94.49 48.74 9749 19497 29246 38995 48743 3473
X80D-108 106.30 55.00 11000 22001 33001 44002 55002 3906
X80D-120 118.12 61.12 12240 24480 36730 48970 61200 4340
X80D-144 143.70 74.76 14950 29900 44860 54810 74760 5208
Performance curves are based on standard conditions. For specific entering conditions, refer to
Selection Procedures, pages 12 through 19.

A = 78.8" (Height)
C = 1.5" (Flange Dimension)
A D = 111.4"
D

Specifications and Dimensions are subject to change without notice.


Rev. 11/95
A
B
C 34
Heat- -Changer

General Specification Optional Coatings and Materials


Furnish a "Heat-X-Changer" stationary flat plate Baked Epoxy for extended cell life in highly
air-to-air heat exchanger manufactured by XeteX, Inc. corrosive conditions.
Heat transfer surface shall be pressed and formed A baked epoxy coating shall be applied to both
aluminum plates with corrugated aluminum spac- sides of the aluminum sheets prior to assembly.
ers capable of withstanding a pressure difference be-
tween airflows of 10" w.g. without deforming air Heresite Coating for maximum cell protection in
passages. The airflow passages shall provide maxi-
corrosive conditions.
mum surface area for enhanced heat transfer with
laminar airflow for low pressure drops. Exchanger A Heresite coating shall be applied to the as-
cell shall be virtually "crush-proof" and be capable sembled cell to provide complete corrosion protec-
of being installed vertically or horizontally without tion to cell material.
crushing or settling of the individual plates. Unit
shall be capable of operating in temperatures up to Xseal - an exclusive epoxy sealant for absolute
220oF. The sealing surface between plates shall have leak protection and cell rigidity.
a minimum width of 5 times the plate separation The completed exchanger cell shall be dipped in
distance. Exposed folded/crimped edges are not an epoxy sealant (Xseal) to provide an absolute seal
acceptable. Standard cell construction shall have a between airflows and increased cell rigidity.
maximum cross contamination between airflows of
0.01% of total airflow. The entire cell shall be Materials for special conditions.
capable of being visibly inspected and cleaned as Exchanger cell shall be constructed of stainless
required. Heat exchanger performance shall be steel, galvanized steel or phenolic aluminum.
certified, with documentation, by an independent
test laboratory.

Specifications and Dimensions are subject to change


without notice. Contact XeteX, Inc. for verification of
information and assistance in selection procedures.

35
XeteX, Inc.
3530 East 28th Street
Minneapolis, MN 55406
(612) 724-3101
(612) 721-6303
Printed in U.S.A. Form No. XXXXXXX-1/95

You might also like