O'Brien Atkins Associates, PA Confidential LAB AHU6-1 Page 1

FSU Chemistry Building

Static Pressure Loss Calculation Safety Factor = 1.25

AHU FAN DESIGNATION


Duct air temperature 55 dF air density 0.076684 #DIV/0!
1981
SMACNA Friction Cataloged Calculated Calculated
Velocity Loss
Duct Size Velocity Table or Loss per Static Static Equivalent length for
Section CFM Pressure Coefficient Length ft Comment
fpm ASHRAE 100 ft. Pressure Pressure design friction loss
Pv C
Fitting in. w.g. loss, in. w.g. Loss, in. w.g. per 100 ft.
W H or Diam. (feet)

AHU OUTLET 64 48 72,250 3387 0.715 6-7F 0.05 0.10 0.036 35.75
TRANSITION 82 50 72,250 2538 0.401 6-7B 0.25 0.10 0.100 100.36
90D ELBOW 82 50 72,250 2538 0.401 6-6H 0.27 0.10 0.108 108.39
STRAIGHT DUCT 82 50 72,250 2538 0.401 0.10 18 0.018 18.00
90D ELBOW 82 50 72,250 2538 0.401 6-6H 0.27 0.10 0.108 108.39
90D ELBOW 82 50 72,250 2538 0.401 6-6H 0.27 0.10 0.108 108.39
TRANSITION 66 64 72,250 2463 0.378 6-7B 0.25 0.09 0.095 105.06
SOUTH ATTENUATOR 0.64 0.640 0.00
STRAIGHT DUCT 66 64 72,250 2463 0.378 0.09 10 0.009 10.00

TAKE OFF 60X20 FROM 66X64 66 64 16,465 561 0.020 6-10N 0.91 0.09 0.018 19.86
TRANSITION 66 50 55,785 2434 0.369 6-7A 0.05 0.10 0.018 18.47
STRAIGHT DUCT 66 50 55,785 2434 0.369 0.10 10 0.010 10.00

TAKE OFF 60X20 FROM 66X50 66 50 16,430 717 0.032 6-10N 0.10 0.000 0.00
TRANSITION 66 34 39,355 2525 0.398 6-7A 0.05 0.14 0.020 14.20
STRAIGHT DUCT 66 34 39,355 2525 0.398 0.14 10 0.014 10.00

TAKE OFF 60X20 FROM 66X34 66 34 16,265 1044 0.068 6-10N 0.91 0.062 #DIV/0!
TRANSITION 66 20 23,090 2519 0.396 6-7A 0.05 0.020 #DIV/0!
STRAIGHT DUCT 66 20 23,090 2519 0.396 0.22 10 0.022 10.00

TAKE OFF 60X20 FROM 66X20 66 20 12,865 1403 0.123 6-10N 0.91 0.112 #DIV/0!
TRANSITION 44 18 9,715 1766 0.195 6-7A 0.05 0.010 #DIV/0!
STRAIGHT DUCT 44 18 9,715 1766 0.195 0.27 10 0.027 10.00
90D ELBOW 44 18 9,715 1766 0.195 6-6H 0.31 0.060 #DIV/0!
STRAIGHT DUCT 44 18 9,715 1766 0.195 0.27 4 0.011 4.00
45d ELBOW 44 18 9,715 1766 0.195 6-6D 0.31 0.060 #DIV/0!
45d ELBOW 44 18 9,715 1766 0.195 6-6D 0.31 0.060 #DIV/0!
STRAIGHT DUCT 44 18 9,715 1766 0.195 11 0.000 #DIV/0!
90D ELBOW 44 18 9,715 1766 0.195 6-6D 0.31 0.060 #DIV/0!
90D ELBOW 44 18 9,715 1766 0.195 6-6D 0.31 0.060 #DIV/0!

TAKE OFF 18RND FROM 44X18 44 18 9,715 1766 0.195 6-10T 1.1 0.214 #DIV/0!
TRANSITION 32 18 7,435 1859 0.215 6-7A 0.05 0.011 #DIV/0!
STRAIGHT DUCT 32 18 7,435 1859 0.215 0.17 58 0.099 58.00

TAKE OFF 16RND FROM 32X18 32 18 6,345 1586 0.157 6-10T 1.1 0.173 #DIV/0!
STRAIGHT DUCT 16 1,425 1021 0.065 0.09 4 0.004 4.00
TAKE OFF 10RND FR 16RND 16 1,425 1021 0.065 6-10T 0.74 0.048 #DIV/0!
STRAIGHT DUCT 16 1,090 781 0.038 0.05 0.000 0.00
TERMINAL BOX 0.5 0.500 0.00
TRANSITION FR TERM BOX TO
10X18 10 18 1,090 872 0.047 6-7A 0.05 0.002 #DIV/0!
STRAIGHT DUCT 10 18 1,090 872 0.047 0.09 4 0.004 4.00
FINAL FLEX TAKEOFF TO
DIFFUSER 16 545 391 0.010 0.2 0.200 #DIV/0!
DIFFUSER 0.1 0.100 0.00
Subtotal 3.221
Safety Factor 1.25
Total EXTERNAL static pressure 4.03

2002053 Duct static pressure loss calcs.xls