MVcables Design
MVcables Design
MVcables Design
INTRODUCTION
Gulf Cable and Electrical Industries Company K.S.C. (Gulf Cable) is the only domestic manufacturer and exporter
of power cables, control cables, telecommunication cables and overhead conductors in Kuwait. We were established
in March 1975 and have been listed on the Kuwait Stock Exchange since 1984. Our manufacturing operations
commenced in 1979.
We embarked upon a massive restoration of our plant & it's facilities during the early 90's when state-of-the-art
machinery and testing equipment were acquired. Thereafter, new machines are recurrently being introduced to
enhance our production capacity and product range. The new machines and equipment have numerous built-in
functions and features assuring precision and consistency of the highest standard.
On a regular basis, we develop new products and enhance our existing ones. At Gulf Cable we pay utmost attention
to product quality, and to ensure this, we have adapted a comprehensive Quality Assurance System that complies
with international standards.
Quality has always been our top priority and meeting customer's expectations has been our prime objective. The
very basis on which we have earned the confidence of our clientele.
At Gulf Cable we follow stringent quality standards which go beyond stipulatations of international specifications,
rendering long term performance and reliability to our products during their service life.
At Gulf Cable we always aim for the best. When most of the cable manufacturers in the region settled for ISO:
9002, we stand out with ISO 9001, which recognizes our ability for Design and Development as well. We are also
acknowledged by the Kuwait Quality Mark issued by the Ministry of Commerce and Industries.
Gulf Cable & Electrical Ind. Co.
CONTENTS
INTRODUCTION
PRODUCT RANGE I-II
PRODUCT DATA TABLES
AUXILIARY CABLES
Pilot Cables – 16 and 34 Core Cables 22
TECHNICAL INFORMATION
CURRENT RATING
Installation Conditions 23-24
3.8/6.6 to 19/33 KV XLPE Insulated Cables 25
DRUMS
Drum Sizes and Dimensions 36
Gulf Cable & Electrical Ind. Co.
PRODUCT RANGE
We at Gulf Cable always aim for the best. While most of the Cable Manufacturers in Gulf and Middle East region settled for
ISO 9002, we stand out with ISO 9001 which recognizes our ability for Design & Development as well.
As a philosophy, our commitment to customers does not end with a sale. We also offer a host of related services before and
after the sale. These include,
• Application engineering service for selection of appropriate product best suiting the end use.
• An extensive range of cables, single core wires, flexible cords bare & insulated conductors manufactured to stringent Quality
Standards going beyond international specifications.
• Design and Development of products tailored to meet specific requirements of the application.
• To help the customers understand the product intricacies and its performance levels.
NOTE 1: THE TABULATIONS ON SUBSEQUENT PAGES FURNISH OVERALL DIMENSIONS, NET & GROSS WEIGHTS AND DRUM
DIMENSIONS. PLEASE NOTE THAT THESE ARE "APPROXIMATE" VALUES. THEY HAVE BEEN FURNISHED FOR GENERAL GUIDELINES
AND INTENDED TO BE USED FOR THUMB RULE ESTIMATIONS/FREIGHT CALCULATIONS.
TWO DISTINCT SYSTEMS OF VOLTAGE DESIGNATION ARE GENERALLY IN USE. EQUIVALENCE BETWEEN THESE TWO SYSTEMS
BASED ON INSULATION THICKNESS AND MAXIMUM VALUE OF HIGHEST SYSTEM VOLTAGE IS AS TABULATED BELOW:
Where,
Uo is rated power frequency voltage between conductor and earth or metallic screen, for which the cable is designed.
U is the rated power frequency voltage between conductors, for which the cable is designed.
Um is the maximum value of "highest system voltage" for which the equipment may be used.
FROM ABOVE TABULATION, EQUIVALENT IEC / BS DESIGNATION CAN BE DETERMINED FOR ANY SYSTEM AS APPROPRIATE.
Gulf Cable & Electrical Ind. Co.
PRODUCT RANGE
II
NOTE 3: THE FOLLOWING LIST TABULATES ONLY THE "STANDARD" PRODUCTS. FOR ANY PRODUCT NOT LISTED BELOW, PLEASE
DO NOT HESITATE TO CONTACT OUR SALES & MARKETTING DIVISION. WE SHALL BE TOO PLEASED TO MEET YOUR SPECIFIC
REQUIREMENTS.
PRODUCT STANDARD
• XLPE insulated, single core or multicore armoured or unarmoured cables IEC 60502 / BS 6622
Auxiliary Cables
• 16 core or 34 core pilot cables to be used along with underground MEW / ESI Standards
powerlines 11KV, 132 KV and beyond
Gulf Cable & Electrical Ind. Co.
(Cu/SC/XLPE/SC/AWA/PVC)
Nominal Maximum Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Bedding Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation (Semiconducting) Wire Sheath Diameter Weight Length Weight
at 20ºC Tape
35 0.524 2.5 0.4 1.6 1.8 23.9 860 500 D-11 530
50 0.387 2.5 0.4 1.6 1.8 25.0 1010 500 D-12 615
70 0.268 2.5 0.4 1.6 1.8 26.6 1250 500 D-12 735
95 0.193 2.5 0.4 1.6 1.8 28.5 1560 500 D-12 890
120 0.153 2.5 0.4 1.6 1.9 30.2 1840 500 D-14 1070
150 0.124 2.5 0.4 1.6 1.9 31.6 2160 500 D-14 1230
185 0.0991 2.5 0.4 1.6 2.0 33.4 2530 500 D-16 1480
240 0.0754 2.6 0.4 2.0 2.1 37.1 3240 500 D-18 1860
300 0.0601 2.8 0.4 2.0 2.2 39.7 3900 500 D-18 2190
400 0.0470 3.0 0.4 2.0 2.3 43.2 4870 500 D-18 2680
500 0.0366 3.2 0.4 2.5 2.4 47.8 6110 500 D-19 3380
630 0.0283 3.2 0.4 2.5 2.5 51.8 7520 500 D-19 4080
(Cu/SC/XLPE/SC/SWA/PVC)
Nominal Maximum Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Bedding Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation (Semiconducting) Wire Sheath Diameter Weight Length Weight
at 20ºC Tape
35 0.524 2.5 0.4 2.0 2.3 43.9 3310 500 D-18 1900
50 0.387 2.5 0.4 2.5 2.4 47.5 4230 500 D-19 2440
70 0.268 2.5 0.6 2.5 2.5 51.1 5100 500 D-19 2870
95 0.193 2.5 0.6 2.5 2.7 56.2 6260 500 D-21 3550
120 0.153 2.5 0.6 2.5 2.8 59.7 7240 500 D-22 4090
150 0.124 2.5 0.6 2.5 2.9 62.9 8310 250 D-18 2320
185 0.0991 2.5 0.6 2.5 3.0 66.6 9570 250 D-18 2630
240 0.0754 2.6 0.6 2.5 3.2 72.8 11650 250 D-21 3330
300 0.0601 2.8 0.6 3.15 3.4 79.7 14740 250 D-23 4190
400 0.0470 3.0 0.6 3.15 3.7 87.4 18020 250 D-23 5010
(Cu/SC/XLPE/SC/AWA/PVC)
Nominal Maximum Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Bedding Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation (Semiconducting) Wire Sheath Diameter Weight Length Weight
at 20ºC Tape
35 0.524 3.4 0.4 1.6 1.8 26.0 950 500 D-12 585
50 0.387 3.4 0.4 1.6 1.8 27.0 1110 500 D-12 660
70 0.268 3.4 0.4 1.6 1.8 28.0 1340 500 D-12 780
95 0.193 3.4 0.4 1.6 1.9 30.5 1670 500 D-14 985
120 0.153 3.4 0.4 1.6 1.9 32.0 1940 500 D-14 1120
150 0.124 3.4 0.4 1.6 2.0 33.6 2280 500 D-16 1350
185 0.0991 3.4 0.4 2.0 2.0 36.0 2730 500 D-18 1600
240 0.0754 3.4 0.4 2.0 2.1 39.0 3340 500 D-18 1910
300 0.0601 3.4 0.4 2.0 2.2 40.9 3990 500 D-18 2240
400 0.0470 3.4 0.4 2.0 2.3 44.0 4930 500 D-18 2710
500 0.0366 3.4 0.4 2.5 2.4 48.2 6150 500 D-19 3390
630 0.0283 3.4 0.4 2.5 2.5 52.2 7560 500 D-19 4100
(Cu/SC/XLPE/SC/CuT/PVC/AWA/PVC)
4
Nominal Maximum Thickness Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Extruded Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Bedding Wire Sheath Diameter Weight Length Weight
at 20ºC
35 0.524 3.4 0.075 1.2 1.6 1.8 27.3 1130 500 D-12 675
50 0.387 3.4 0.075 1.2 1.6 1.8 28.4 1290 500 D-12 755
70 0.268 3.4 0.075 1.2 1.6 1.9 30.2 1560 500 D-14 930
95 0.193 3.4 0.075 1.2 1.6 1.9 32.1 1880 500 D-16 1150
120 0.153 3.4 0.075 1.2 1.6 2.0 33.8 2190 500 D-16 1330
150 0.124 3.4 0.075 1.2 2.0 2.1 36.2 2620 500 D-18 1550
185 0.0991 3.4 0.075 1.2 2.0 2.1 37.8 3000 500 D-18 1740
240 0.0754 3.4 0.075 1.2 2.0 2.2 40.5 3640 500 D-18 2060
300 0.0601 3.4 0.075 1.2 2.0 2.2 42.5 4290 500 D-18 2390
400 0.0470 3.4 0.075 1.2 2.0 2.4 45.8 5270 500 D-19 2960
500 0.0366 3.4 0.075 1.3 2.5 2.5 50.2 6550 500 D-19 3600
630 0.0283 3.4 0.075 1.4 2.5 2.6 54.4 8020 500 D-21 4430
(Cu /SC/XLPE/SC/SWA/PVC)
Nominal Maximum Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Bedding Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation (Semiconducting) Wire Sheath Diameter Weight Length Weight
at 20ºC Tape
35 0.524 3.4 0.4 2.5 2.4 49.0 4060 500 D-19 2350
50 0.387 3.4 0.4 2.5 2.5 51.6 4640 500 D-19 2640
70 0.268 3.4 0.6 2.5 2.7 56.0 5630 500 D-21 3240
95 0.193 3.4 0.6 2.5 2.8 60.3 6720 500 D-22 3830
120 0.153 3.4 0.6 2.5 2.9 63.8 7720 250 D-18 2170
150 0.124 3.4 0.6 2.5 3.0 67.0 8800 250 D-18 2440
. 185 0.0991 3.4 0.6 2.5 3.1 70.7 10080 250 D-21 2940
240 0.0754 3.4 0.6 3.15 3.3 77.9 12960 250 D-21 3660
300 0.0601 3.4 0.6 3.15 3.5 82.5 15150 250 D-23 4290
400 0.0470 3.4 0.6 3.15 3.7 89.1 18270 250 D-23 5070
(Cu/SC/XLPE/SC/CuT/PVC/SWA/PVC)
6
Nominal Maximum Thickness Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Extruded Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Bedding Wire Sheath Diameter Weight Length Weight
at 20ºC
35 0.524 3.4 0.075 1.3 2.5 2.5 52.0 4700 500 D-19 2670
50 0.387 3.4 0.075 1.4 2.5 2.6 54.8 5300 500 D-21 3070
70 0.268 3.4 0.075 1.4 2.5 2.7 58.5 6240 500 D-22 3590
95 0.193 3.4 0.075 1.5 2.5 2.9 63.2 7460 500 D-23 4230
120 0.153 3.4 0.075 1.6 2.5 3.0 66.8 8530 500 D-23 4770
150 0.124 3.4 0.075 1.6 2.5 3.1 70.0 9650 500 D-23 5330
185 0.0991 3.4 0.075 1.7 2.5 3.2 73.9 11040 250 D-21 3180
240 0.0754 3.4 0.075 1.8 3.15 3.4 81.2 14060 250 D-23 4020
300 0.0601 3.4 0.075 1.9 3.15 3.6 86.1 16340 250 D-23 4590
400 0.0470 3.4 0.075 2.0 3.15 3.8 93.0 19610 250 D-23 5400
(AI/SC/XLPE/SC/SWA/PVC)
Nominal Maximum Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Bedding Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation (Semiconducting) Wire Sheath Diameter Weight Length Weight
at 20ºC Tape
35 0.868 3.4 0.4 2.5 2.4 49.0 3440 500 D-19 2040
50 0.641 3.4 0.4 2.5 2.5 51.6 3790 500 D-19 2220
70 0.443 3.4 0.6 2.5 2.7 56.5 4430 500 D-21 2640
95 0.320 3.4 0.6 2.5 2.8 60.6 5050 500 D-22 3000
120 0.253 3.4 0.6 2.5 2.9 63.8 5550 500 D-23 3280
150 0.206 3.4 0.6 2.5 3.0 67.0 6070 500 D-23 3540
185 0.164 3.4 0.6 2.5 3.1 70.9 6740 250 D-21 2110
240 0.125 3.4 0.6 3.15 3.3 78.0 8590 250 D-21 2570
300 0.100 3.4 0.6 3.15 3.5 82.5 9640 250 D-23 2910
400 0.0778 3.4 0.6 3.15 3.7 89.6 11160 250 D-23 3290
(AI/SC/XLPE/SC/CuT/PVC/SWA/PVC)
8
Nominal Maximum Thickness Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Extruded Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Bedding Wire Sheath Diameter Weight Length Weight
at 20ºC
35 0.868 3.4 0.075 1.3 2.5 2.5 52.0 4090 500 D-19 2370
50 0.641 3.4 0.075 1.4 2.5 2.6 54.8 4450 500 D-21 2650
70 0.443 3.4 0.075 1.4 2.5 2.7 58.9 5080 500 D-22 3010
95 0.320 3.4 0.075 1.5 2.5 2.9 63.4 5750 500 D-23 3380
120 0.253 3.4 0.075 1.6 2.5 3.0 66.8 6350 500 D-23 3680
150 0.206 3.4 0.075 1.6 2.5 3.1 70.0 6920 500 D-23 3960
185 0.164 3.4 0.075 1.7 2.5 3.2 74.1 7700 500 D-23 4350
240 0.125 3.4 0.075 1.8 3.15 3.4 81.4 9690 500 D-24 5450
300 0.100 3.4 0.075 1.9 3.15 3.6 86.1 10830 500 D-25-S 6170
400 0.0778 3.4 0.075 2.0 3.15 3.8 93.4 12500 250 D-23 3630
(Cu/SC/XLPE/SC/AWA/PVC)
Nominal Maximum Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Bedding Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation (Semiconducting) Wire Sheath Diameter Weight Length Weight
at 20ºC Tape
35 0.524 4.5 0.4 1.6 1.8 27.9 1050 500 D-12 635
50 0.387 4.5 0.4 1.6 1.8 29.0 1210 500 D-12 715
70 0.268 4.5 0.4 1.6 1.9 30.8 1470 500 D-14 885
95 0.193 4.5 0.4 1.6 1.9 32.7 1780 500 D-16 1100
120 0.153 4.5 0.4 2.0 2.0 35.2 2170 500 D-18 1330
150 0.124 4.5 0.4 2.0 2.1 36.8 2510 500 D-18 1500
185 0.0991 4.5 0.4 2.0 2.1 38.4 2890 500 D-18 1680
240 0.0754 4.5 0.4 2.0 2.2 41.1 3510 500 D-18 2000
300 0.0601 4.5 0.4 2.0 2.3 43.3 4170 500 D-18 2330
400 0.0470 4.5 0.4 2.5 2.4 47.4 5240 500 D-19 2950
500 0.0366 4.5 0.4 2.5 2.5 50.6 6350 500 D-19 3500
630 0.0283 4.5 0.4 2.5 2.6 54.6 7780 500 D-21 4310
(Cu/SC/XLPE/SC/CuT/PVC)
10
Nominal Maximum Thickness Thickness Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Sheath Diameter Weight Length Weight
at 20ºC
185 0.0991 4.5 0.075 2.0 33.2 2480 500 D-16 1450
240 0.0754 4.5 0.075 2.0 35.7 3070 500 D-18 1780
300 0.0601 4.5 0.075 2.1 37.9 3700 500 D-18 2090
400 0.0470 4.5 0.075 2.2 41.0 4620 500 D-18 2550
500 0.0366 4.5 0.075 2.3 44.2 5660 500 D-18 3070
630 0.0283 4.5 0.075 2.4 48.2 7040 500 D-19 3840
(Cu/SC/XLPE/SC/CuT/PVC/AWA/PVC)
11
Nominal Maximum Thickness Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Extruded Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Bedding Wire Sheath Diameter Weight Length Weight
at 20ºC
35 0.524 4.5 0.075 1.2 1.6 1.9 29.7 1270 500 D-12 745
50 0.387 4.5 0.075 1.2 1.6 1.9 30.8 1430 500 D-14 865
70 0.268 4.5 0.075 1.2 1.6 1.9 32.4 1700 500 D-16 1060
95 0.193 4.5 0.075 1.2 2.0 2.0 35.3 2130 500 D-18 1310
120 0.153 4.5 0.075 1.2 2.0 2.1 37.0 2440 500 D-18 1460
150 0.124 4.5 0.075 1.2 2.0 2.1 38.4 2780 500 D-18 1630
185 0.0991 4.5 0.075 1.2 2.0 2.2 40.2 3180 500 D-18 1830
240 0.0754 4.5 0.075 1.2 2.0 2.3 42.9 3840 500 D-18 2160
300 0.0601 4.5 0.075 1.2 2.0 2.3 44.9 4490 500 D-18 2490
400 0.0470 4.5 0.075 1.3 2.5 2.5 49.4 5660 500 D-19 3150
500 0.0366 4.5 0.075 1.3 2.5 2.6 52.6 6770 500 D-19 3710
630 0.0283 4.5 0.075 1.4 2.5 2.7 56.8 8280 500 D-21 4560
(Cu/SC/XLPE/SC/CuT/PVC)
12
Nominal Maximum Thickness Thickness Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Sheath Diameter Weight Length Weight
at 20ºC
185 0.0991 4.5 0.075 3.1 70.2 8030 500 D-23 4520
240 0.0754 4.5 0.075 3.3 76.0 9930 500 D-23 5470
300 0.0601 4.5 0.075 3.4 80.6 11890 500 D-23 6450
400 0.0470 4.5 0.075 3.7 87.4 14800 250 D-23 4200
(Cu/SC/XLPE/SC/CuT/PVC/SWA/PVC)
13
Nominal Maximum Thickness Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Extruded Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Bedding Wire Sheath Diameter Weight Length Weight
at 20ºC
35 0.524 4.5 0.075 1.4 2.5 2.7 57.4 5320 500 D-22 3130
50 0.387 4.5 0.075 1.5 2.5 2.8 60.2 5980 500 D-22 3460
70 0.268 4.5 0.075 1.5 2.5 2.9 63.8 6940 500 D-23 3870
95 0.193 4.5 0.075 1.6 2.5 3.0 68.3 8170 500 D-23 4590
120 0.153 4.5 0.075 1.7 2.5 3.1 72.0 9270 500 D-23 5140
150 0.124 4.5 0.075 1.7 2.5 3.2 75.2 10410 500 D-23 5710
185 0.0991 4.5 0.075 1.8 3.15 3.4 80.5 12630 500 D-23 6820
240 0.0754 4.5 0.075 1.9 3.15 3.6 86.5 14930 500 D-25-S 8220
300 0.0601 4.5 0.075 2.0 3.15 3.7 91.3 17230 500 D-25-S 9370
400 0.0470 4.5 0.075 2.1 3.15 4.0 98.3 20580 400 D-25-S 8980
(AI/SC/XLPE/SC/CuT/PVC/SWA/PVC)
14
Nominal Maximum Thickness Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Extruded Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Bedding Wire Sheath Diameter Weight Length Weight
at 20ºC
35 0.868 4.5 0.075 1.4 2.5 2.7 57.4 4710 500 D-19 2680
50 0.641 4.5 0.075 1.5 2.5 2.8 60.2 5130 500 D-22 3040
70 0.443 4.5 0.075 1.5 2.5 2.9 64.2 5740 500 D-23 3370
95 0.320 4.5 0.075 1.6 2.5 3.0 68.5 6460 500 D-23 3730
120 0.253 4.5 0.075 1.7 2.5 3.1 72.0 7100 500 D-23 4050
150 0.206 4.5 0.075 1.7 2.5 3.2 75.2 7680 500 D-23 4340
185 0.164 4.5 0.075 1.8 3.15 3.4 80.8 9370 500 D-23 5190
240 0.125 4.5 0.075 1.9 3.15 3.6 86.8 10580 500 D-25-S 6040
300 0.100 4.5 0.075 2.0 3.15 3.7 91.3 11720 500 D-25-S 2930
400 0.0778 4.5 0.075 2.1 3.15 4.0 98.8 13490 400 D-25-S 6150
(Cu/SC/XLPE/SC/CuT/PVC)
15
Nominal Maximum Thickness Thickness Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Sheath Diameter Weight Length Weight
at 20ºC
185 0.0991 5.5 0.075 2.0 35.2 2600 500 D-18 1540
240 0.0754 5.5 0.075 2.1 37.9 3200 500 D-18 1840
300 0.0601 5.5 0.075 2.2 40.1 3850 500 D-18 2170
400 0.0470 5.5 0.075 2.3 43.2 4770 500 D-18 2630
500 0.0366 5.5 0.075 2.4 46.4 5830 500 D-19 3240
630 0.0283 5.5 0.075 2.5 50.4 7220 500 D-19 3930
(Cu/SC/XLPE/SC/CuT/PVC)
16
Nominal Maximum Thickness Thickness Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Sheath Diameter Weight Length Weight
at 20ºC
185 0.0991 5.5 0.075 3.3 75.0 8540 500 D-23 4770
240 0.0754 5.5 0.075 3.4 80.6 10440 250 D-23 3110
300 0.0601 5.5 0.075 3.6 85.3 12450 250 D-23 3610
400 0.0470 5.5 0.075 3.8 91.9 15370 200 D-23 3570
(Cu/SC/XLPE/SC/CuT/PVC/SWA/PVC)
17
Nominal Maximum Thickness Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Extruded Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Bedding Wire Sheath Diameter Weight Length Weight
at 20ºC
35 0.524 5.5 0.075 1.5 2.5 2.8 62.1 5920 500 D-23 3460
50 0.387 5.5 0.075 1.6 2.5 2.9 64.9 6600 500 D-23 3800
70 0.268 5.5 0.075 1.6 2.5 3.1 68.7 7610 500 D-23 4310
95 0.193 5.5 0.075 1.7 2.5 3.2 73.2 8870 500 D-23 4940
120 0.153 5.5 0.075 1.7 3.15 3.3 78.0 10730 250 D-21 3100
150 0.124 5.5 0.075 1.8 3.15 3.4 81.4 12000 250 D-23 3500
185 0.0991 5.5 0.075 1.9 3.15 3.6 85.5 13460 200 D-22 3160
240 0.0754 5.5 0.075 2.0 3.15 3.7 91.3 15780 200 D-23 3660
300 0.0601 5.5 0.075 2.0 3.15 3.9 96.0 18110 200 D-24 4220
400 0.0470 5.5 0.075 2.2 3.15 4.1 103.0 21500 200 D-24 4900
(AI/SC/XLPE/SC/CuT/PVC/SWA/PVC)
18
Nominal Maximum Thickness Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Extruded Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Bedding Wire Sheath Diameter Weight Length Weight
at 20ºC
35 0.868 5.5 0.075 1.5 2.5 2.8 62.1 5300 500 D-23 3150
50 0.641 5.5 0.075 1.6 2.5 2.9 64.9 5740 500 D-23 3370
70 0.443 5.5 0.075 1.6 2.5 3.1 69.2 6400 500 D-23 3710
95 0.320 5.5 0.075 1.7 2.5 3.2 73.5 7170 500 D-23 4090
120 0.253 5.5 0.075 1.7 3.15 3.3 78.0 8550 250 D-21 2560
150 0.206 5.5 0.075 1.8 3.15 3.4 81.4 9260 250 D-23 2820
185 0.164 5.5 0.075 1.9 3.15 3.6 85.7 10130 200 D-22 2500
240 0.125 5.5 0.075 2.0 3.15 3.7 91.5 11420 200 D-23 2780
300 0.100 5.5 0.075 2.0 3.15 3.9 96.0 12590 200 D-23 3020
400 0.0778 5.5 0.075 2.2 3.15 4.1 103.5 14410 200 D-23 3380
(Cu/SC/XLPE/SC /CuT/PVC/AWA/PVC)
19
Nominal Maximum Thickness Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Extruded Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Bedding Wire Sheath Diameter Weight Length Weight
at 20ºC
50 0.387 8.0 0.075 1.2 2.0 2.2 39.4 2050 500 D-18 1270
70 0.268 8.0 0.075 1.2 2.0 2.2 41.0 2330 500 D-18 1410
95 0.193 8.0 0.075 1.2 2.0 2.3 43.1 2710 500 D-18 1600
120 0.153 8.0 0.075 1.2 2.0 2.3 44.6 3020 500 D-18 1750
150 0.124 8.0 0.075 1.3 2.5 2.4 47.4 3570 500 D-19 2110
185 0.0991 8.0 0.075 1.3 2.5 2.5 49.2 3990 500 D-19 2320
240 0.0754 8.0 0.075 1.3 2.5 2.5 51.7 4670 500 D-19 2660
300 0.0601 8.0 0.075 1.4 2.5 2.6 54.1 5410 500 D-21 3130
400 0.0470 8.0 0.075 1.4 2.5 2.7 57.2 6430 500 D-22 3690
500 0.0366 8.0 0.075 1.5 2.5 2.8 60.6 7620 500 D-22 4280
630 0.0283 8.0 0.075 1.6 2.5 2.9 64.8 8935 500 D-21 M 4890
20
Nominal Maximum Thickness Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Extruded Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Bedding Wire Sheath Diameter Weight Length Weight
at 20ºC
50 0.387 8.0 0.075 1.8 3.15 3.4 78.8 9230 500 D-23 5120
70 0.268 8.0 0.075 1.8 3.15 3.5 82.5 10310 500 D-24 5760
95 0.193 8.0 0.075 1.9 3.15 3.6 87.0 11640 500 D-25-S 6570
120 0.153 8.0 0.075 2.0 3.15 3.7 90.6 12850 250 D-23 3710
150 0.124 8.0 0.075 2.0 3.15 3.8 93.8 14150 250 D-23 4040
185 0.0991 8.0 0.075 2.1 3.15 4.0 97.9 15700 250 D-23 4430
240 0.0754 8.0 0.075 2.2 3.15 4.1 104.0 18120 250 D-25 5280
300 0.0601 8.0 0.075 2.3 3.15 4.3 109.0 20570 200 D-25 4860
21
Nominal Maximum Thickness Thickness Thickness Dia of Thickness Approx. Approx. Standard Drum Approx.
Area of Conductor of XLPE of Copper of Extruded Armour of Outer Overall Cable Packing Size Gross
Conductor Resistance Insulation Tape Bedding Wire Sheath Diameter Weight Length Weight
at 20ºC
50 0.641 8.0 0.075 1.8 3.15 3.4 78.8 8380 500 D-23 4690
70 0.443 8.0 0.075 1.8 3.15 3.5 82.9 9120 500 D-24 5160
95 0.320 8.0 0.075 1.9 3.15 3.6 87.2 10000 500 D-25-S 5750
120 0.253 8.0 0.075 2.0 3.15 3.7 90.6 10680 250 D-23 3170
150 0.206 8.0 0.075 2.0 3.15 3.8 93.8 11410 250 D-23 3350
185 0.164 8.0 0.075 2.1 3.15 4.0 98.1 12370 250 D-23 3590
240 0.125 8.0 0.075 2.2 3.15 4.1 104.0 13760 250 D-25 4190
300 0.100 8.0 0.075 2.3 3.15 4.3 109.0 15060 200 D-25 3760
PILOT CABLE
22
Total To CONDUCTOR Thickness Thickness Thickness Thickness Diameter Thickness Approx. Approx. Standard Drum Approx.
Number Withstand of of of of of of Overall Cable Packing Size Gross
of Maximum Nominal Number Maximum Screened Pair Unscreened Pair Insulation Screening PE PE Armour Outer Diameter Weight Length Weight
Cores Induced Area of Resistance (Min.) Tape Bedding Inner Wire Sheath
Voltage of Cores at 20ºC Sheath (Min.)
Number Nominal Number Nominal
Level Conductor
of Diameter of Diameter
Pairs of Pairs of
Wires Wires
INSTALLATION CONDITIONS
OTHER CONDITIONS
i) Three cables, trefoil, in air, two point bonding, separated from wall.
ii) Three cables flat with a gap of one cable diameter installed vertically in air,
separated from wall. Single point or cross bonded.
iii) Three cables with gap one cable diameter laid horizontally underground.
INSTALLATION DETAILS
a) Single Core
b) Multi Core
II) IN GROUND
a) Single Core
b) Multi Core
NOTE:-
25
26
Ambient temperature º C 25 30 35 40 45 50 52 55 60
XLPE insulated cables 1.37 1.30 1.24 1.17 1.09 1.03 1.00 0.95 0.88
XLPE insulated cables 1.16 1.13 1.08 1.03 1.00 0.95 0.90
0.50 - -
0.60 - -
0.75 - -
Depth of laying is measured from surface of ground to the centre of a Cable/Duct or to the centre of a trefoil group of Cables/ ducts as the case may be.
Gulf Cable & Electrical Ind. Co.
27
Touching
Trefoil Flat 0.15 0.30 0.45 0.60 Touching 0.15 0.30 0.45 0.60
2 0.78 0.80 0.81 0.85 0.88 0.90 0.80 0.85 0.89 0.90 0.92
3 0.66 0.69 0.71 0.76 0.80 0.83 0.69 0.75 0.80 0.84 0.86
4 0.60 0.63 0.65 0.72 0.76 0.80 0.63 0.70 0.77 0.80 0.84
5 0.55 0.58 0.61 0.68 0.73 0.77 0.57 0.66 0.73 0.78 0.81
6 0.52 0.55 0.58 0.66 0.72 0.76 0.55 0.63 0.71 0.76 0.80
Gulf Cable & Electrical Ind. Co.
28
1.5/2.5 1.12 1.09 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.70 0.66
4 1.13 1.10 1.07 1.05 1.0 0.94 0.85 0.79 0.74 0.69 0.65
6 1.14 1.10 1.07 1.05 1.0 0.93 0.85 0.79 0.74 0.68 0.64
10 1.15 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.67 0.63
16 1.16 1.12 1.08 1.05 1.0 0.93 0.84 0.77 0.72 0.66 0.62
25 1.17 1.13 1.09 1.05 1.0 0.93 0.83 0.77 0.71 0.65 0.61
35 1.17 1.13 1.09 1.06 1.0 0.92 0.83 0.76 0.71 0.65 0.61
50 1.17 1.13 1.09 1.06 1.0 0.92 0.83 0.76 0.71 0.65 0.61
70 1.18 1.14 1.09 1.06 1.0 0.92 0.83 0.75 0.70 0.64 0.60
95 1.18 1.14 1.09 1.06 1.0 0.92 0.83 0.75 0.70 0.64 0.60
120 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.75 0.69 0.63 0.60
150 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.75 0.69 0.63 0.59
185 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.74 0.69 0.63 0.59
240 1.20 1.15 1.10 1.07 1.0 0.92 0.81 0.74 0.69 0.63 0.59
300/400 1.20 1.15 1.10 1.07 1.0 0.92 0.81 0.74 0.69 0.63 0.59
50 1.21 1.16 1.11 1.07 1.0 0.91 0.81 0.73 0.68 0.63 0.59
70 1.22 1.16 1.12 1.07 1.0 0.91 0.81 0.73 0.68 0.63 0.59
95 1.22 1.16 1.12 1.07 1.0 0.91 0.81 0.73 0.68 0.63 0.59
120 1.22 1.16 1.12 1.07 1.0 0.91 0.81 0.73 0.68 0.63 0.59
150 1.22 1.16 1.12 1.07 1.0 0.91 0.81 0.73 0.68 0.63 0.59
185 1.22 1.17 1.12 1.07 1.0 0.91 0.81 0.73 0.68 0.62 0.59
240 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.73 0.68 0.62 0.59
300 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.73 0.68 0.62 0.59
400 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.73 0.67 0.62 0.58
500 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.73 0.67 0.62 0.58
630 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.73 0.67 0.61 0.58
800 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.72 0.66 0.61 0.58
1000 1.24 1.18 1.12 1.07 1.0 0.91 0.80 0.72 0.66 0.61 0.58
Gulf Cable & Electrical Ind. Co.
29
1.5/2.5 1.04 1.03 1.02 1.02 1.0 0.98 0.94 0.91 0.88 0.86 0.83
4 1.04 1.04 1.03 1.02 1.0 0.97 0.94 0.90 0.87 0.85 0.82
6 1.05 1.04 1.03 1.02 1.0 0.97 0.93 0.90 0.86 0.84 0.81
10 1.05 1.04 1.03 1.02 1.0 0.97 0.93 0.89 0.86 0.83 0.80
16 1.06 1.04 1.03 1.02 1.0 0.97 0.92 0.88 0.85 0.82 0.79
25 1.06 1.05 1.03 1.02 1.0 0.96 0.92 0.88 0.84 0.82 0.78
35 1.06 1.05 1.03 1.02 1.0 0.96 0.92 0.87 0.83 0.81 0.77
50 1.07 1.05 1.03 1.02 1.0 0.96 0.91 0.87 0.83 0.80 0.77
70 1.07 1.05 1.04 1.02 1.0 0.96 0.91 0.86 0.82 0.79 0.76
95 1.07 1.06 1.04 1.02 1.0 0.96 0.91 0.86 0.82 0.78 0.75
120 1.08 1.06 1.04 1.03 1.0 0.95 0.90 0.85 0.81 0.78 0.74
150 1.09 1.06 1.04 1.03 1.0 0.95 0.90 0.85 0.80 0.77 0.73
185 1.09 1.07 1.05 1.03 1.0 0.95 0.89 0.84 0.80 0.76 0.72
240 1.09 1.07 1.05 1.03 1.0 0.95 0.89 0.84 0.79 0.76 0.72
300/400 1.10 1.07 1.05 1.03 1.0 0.95 0.88 0.83 0.78 0.75 0.71
50 1.08 1.06 1.04 1.03 1.0 0.96 0.90 0.85 0.81 0.77 0.74
70 1.08 1.06 1.05 1.03 1.0 0.96 0.90 0.84 0.80 0.76 0.73
95 1.08 1.07 1.05 1.03 1.0 0.95 0.89 0.84 0.80 0.75 0.72
120 1.09 1.07 1.05 1.03 1.0 0.95 0.89 0.83 0.79 0.75 0.71
150 1.09 1.07 1.05 1.03 1.0 0.95 0.88 0.83 0.79 0.74 0.71
185 1.09 1.07 1.05 1.03 1.0 0.95 0.88 0.83 0.78 0.74 0.70
240 1.10 1.08 1.05 1.04 1.0 0.95 0.88 0.82 0.78 0.73 0.70
300 1.10 1.08 1.06 1.04 1.0 0.95 0.87 0.82 0.77 0.72 0.69
400 1.11 1.08 1.06 1.04 1.0 0.94 0.87 0.82 0.77 0.72 0.68
500 1.12 1.08 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.71 0.68
630 1.12 1.09 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.71 0.67
800 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.71 0.67
1000 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.70 0.66
Gulf Cable & Electrical Ind. Co.
30
50 1.11 1.08 1.06 1.04 1.0 0.94 0.87 0.82 0.77 0.73 0.69
70 1.12 1.09 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.72 0.68
95 1.12 1.09 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.72 0.68
120 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.72 0.67
150 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.71 0.67
185 1.13 1.10 1.07 1.04 1.0 0.93 0.86 0.79 0.75 0.70 0.67
240 1.14 1.11 1.07 1.04 1.0 0.93 0.86 0.79 0.74 0.70 0.66
300 1.14 1.11 1.08 1.05 1.0 0.93 0.85 0.79 0.74 0.69 0.65
400 1.14 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.68 0.65
500 1.15 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.68 0.64
630 1.15 1.12 1.08 1.05 1.0 0.93 0.84 0.78 0.72 0.68 0.64
800 1.16 1.12 1.09 1.05 1.0 0.93 0.84 0.77 0.72 0.67 0.64
1000 1.16 1.13 1.09 1.05 1.0 0.92 0.84 0.77 0.71 0.67 0.63
Gulf Cable & Electrical Ind. Co.
31
3.8/6.6 KV CABLES
A.C. RESISTANCE, REACTANCE AND CAPACITANCE VALUES
Conductor * Single Core Cables 3-Core Cables
size
A.C. Resistance at 90ºC Reactance (50 Hz) Capacitance A.C. Resistance at 90ºC Reactance Capacitance
(50 Hz)
Sq.mm Copper Aluminium Trefoil Flat* Copper Aluminium
(Ω/km) (Ω/km) (Ω/km) (Ω/km) ( µF/km) (Ω/km) (Ω/km) (Ω/km) (µ F/Km)
185 0.127 0.211 0.107 0.165 0.55 0.127 0.211 0.086 0.56
240 0.0974 0.161 0.103 0.161 0.60 0.0971 0.162 0.083 0.61
300 0.0782 0.129 0.101 0.159 0.61 0.0778 0.130 0.082 0.62
400 0.0621 0.101 0.097 0.156 0.64 0.0614 0.102 0.080 0.65
500 0.0495 0.0792 0.097 0.155 0.67 - - - -
630 0.0398 0.0623 0.094 0.152 0.75 - - - -
6.35/11 KV CABLES
A.C. RESISTANCE, REACTANCE AND CAPACITANCE VALUES
Conductor * Single Core Cables 3-Core Cables
size
A.C. Resistance at 90ºC Reactance (50 Hz) Capacitance A.C. Resistance at 90ºC Reactance Capacitance
(50 Hz)
Sq.mm Copper Aluminium Trefoil Flat* Copper Aluminium
(Ω/km) (Ω/km) (Ω/km) (Ω/km) ( µF/km) (Ω/km) (Ω/km) (Ω/km) (µ F/Km)
185 0.127 0.211 0.111 0.169 0.42 0.128 0.211 0.091 0.43
240 0.0973 0.161 0.106 0.164 0.47 0.097 0.161 0.087 0.48
300 0.0782 0.129 0.102 0.161 0.51 0.0778 0.129 0.085 0.52
400 0.0620 0.101 0.099 0.157 0.57 0.0614 0.101 0.082 0.59
500 0.0494 0.0792 0.098 0.156 0.63 - - - -
630 0.0396 0.0623 0.094 0.152 0.71 - - - -
*Twice Cable diameter spacing between centres.
Gulf Cable & Electrical Ind. Co.
32
8.7/15 KV CABLES
A.C. RESISTANCE, REACTANCE AND CAPACITANCE VALUES
Conductor * Single Core Cables 3-Core Cables
size
A.C. Resistance at 90ºC Reactance (50 Hz) Capacitance A.C. Resistance at 90ºC Reactance Capacitance
(50 Hz)
Sq.mm Copper Aluminium Trefoil Flat* Copper Aluminium
(Ω/km) (Ω/km) (Ω/km) (Ω/km) ( µF/km) (Ω/km) (Ω/km) (Ω/km) (µ F/Km)
185 0.127 0.211 0.115 0.173 0.33 0.127 0.211 0.096 0.34
240 0.0973 0.161 0.109 0.167 0.37 0.0970 0.161 0.092 0.38
300 0.0780 0.129 0.106 0.164 0.40 0.0778 0.129 0.090 0.41
400 0.0619 0.101 0.104 0.162 0.45 0.0614 0.101 0.086 0.46
500 0.0493 0.0792 0.101 0.159 0.50 - - - -
630 0.0395 0.0622 0.097 0.155 0.55 - - - -
* Twice Cable diameter spacing between centres.
12.7/22 KV CABLES
A.C. RESISTANCE, REACTANCE AND CAPACITANCE VALUES
Conductor * Single Core Cables 3-Core Cables
size
A.C. Resistance at 90ºC Reactance (50 Hz) Capacitance A.C. Resistance at 90ºC Reactance Capacitance
(50 Hz)
Sq.mm Copper Aluminium Trefoil Flat* Copper Aluminium
(Ω/km) (Ω/km) (Ω/km) (Ω/km) ( µF/km) (Ω/km) (Ω/km) (Ω/km) (µ F/Km)
185 0.127 0.211 0.107 0.164 0.30 0.127 0.211 0.101 0.29
240 0.0974 0.161 0.102 0.160 0.34 0.0970 0.161 0.096 0.32
300 0.0782 0.129 0.099 0.157 0.37 0.0778 0.129 0.093 0.35
400 0.0621 0.101 0.096 0.154 0.40 0.0614 0.101 0.090 0.39
500 0.0495 0.0791 0.093 0.151 0.44 - - - -
630 0.0398 0.0621 0.090 0.148 0.49 - - - -
*Twice Cable diameter spacing between centres.
Gulf Cable & Electrical Ind. Co.
33
19/33 KV CABLES
A.C. RESISTANCE, REACTANCE AND CAPACITANCE VALUES
Conductor * Single Core Cables 3-Core Cables
size
A.C. Resistance at 90ºC Reactance (50 Hz) Capacitance A.C. Resistance at 90ºC Reactance Capacitance
(50 Hz)
Sq.mm Copper Aluminium Trefoil Flat* Copper Aluminium
(Ω/km) (Ω/km) (Ω/km) (Ω/km) ( µF/km) (Ω/km) (Ω/km) (Ω/km) (µ F/Km)
120 0.196 0.325 0.134 0.192 0.19 0.196 0.325 0.118 0.19
150 0.159 0.265 0.132 0.190 0.20 0.159 0.264 0.114 0.20
185 0.127 0.211 0.128 0.186 0.21 0.127 0.211 0.110 0.22
240 0.0972 0.161 0.121 0.179 0.24 0.0970 0.161 0.105 0.24
300 0.0780 0.129 0.118 0.176 0.25 0.0777 0.129 0.102 0.26
400 0.0617 0.101 0.113 0.172 0.28 - - - -
34
A
Isc = 0.14
√ t
35
A
Isc = 0.094
√ t
36
DIMENSIONS
Drum Size A B C D E
D-No