SR868C8 Solar Controller For Solar Water Heater
SR868C8 Solar Controller For Solar Water Heater
SR868C8 Solar Controller For Solar Water Heater
Contents
Contents----------------------------------------------------------------------------------------------------1
1. Safety information ----------------------------------------------------------------------------------3
1.1 Installation and commissioning -----------------------------------------------------------------3
1.2 About this manual ----------------------------------------------------------------------------------3
1.3 Liability waiver ---------------------------------------------------------------------------------------3
1.4 Important remark------------------------------------------------------------------------------------4
1.5 Description of symbols----------------------------------------------------------------------------4
1.6 Description of operation button------------------------------------------------------------------4
2. Installation --------------------------------------------------------------------------------------------5
2.1 Installing the display unit of controller ---------------------------------------------------------5
2.2 Installing the control unit---------------------------------------------------------------------------5
2.3 Preparing before wire connection ---------------------------------------------------------------6
2.4 Power connection ----------------------------------------------------------------------------------6
2.5Terminal connection --------------------------------------------------------------------------------7
3. Commissioning--------------------------------------------------------------------------------------9
3.1 Set time/ week------------------------------------------------------------------------------------9
3.2 Menu structure-------------------------------------------------------------------------------------10
3.3Menu description-----------------------------------------------------------------------------------11
3.4 System description--------------------------------------------------------------------------------12
4. Controller functions----------------------------------------------------------------------- 13
4.1 Access main menu -------------------------------------------------------------------------------13
4.2 Access submenu ---------------------------------------------------------------------------------13
4.3 Main menu DT O & DT F Temperature difference function-----------------------------14
4.4 Main menu-THET timing heating-------------------------------------------------------15
4.5 TEMP Temperature main menu----------------------------------------------------------------18
4.5.1 EM Emergency collector temperature
(emergency switch-off temperature of collector)----------------------------------19
4.5.2 CMX Maximum limited collector temperature (collector cooling function)---19
4.5.3 CMN low temperature protection of collector---------------------------------------20
4.5.4 CFR frost protection of collector --------------------------------------------------21
4.5.5 SMX Maximum temperature of tank ----------------------------------------22
4.5.6 REC Tank re-cooling function----------------------------------------------------------22
4.5.7 C-F Celsius and Fahrenheit temperature transferring --------------------------23
4.6 FUN Auxiliary function--------------------------------------------------------------------------23
4.6.1 DVWG Anti-Legionella function --------------------------------------------------------24
4.6.2 CIRC Temperature controlled hot water circulation pump------------------------25
4.6.3 nMIN Solar circulation pump speed adjusting (RPM speed controlling)-------26
4.6.3.1 DTS standard temperature difference
---------------------------------------------------------------------------------------------------------------------------------------------------
-1-
Operation manual of solar water controller SR868C8/SR868C8Q
---------------------------------------------------------------------------------------------------------------------------------------------------
-2-
Operation manual of solar water controller SR868C8/SR868C8Q
1. Safety information
---------------------------------------------------------------------------------------------------------------------------------------------------
-3-
Operation manual of solar water controller SR868C8/SR868C8Q
infringements – occurring in connection with the use of this controller- on third parties
rights. The manufacturer preserves the right to put changes to product, technical date
or installation and operation instructions without prior notice. As soon as it becomes
evident that safe operation is no longer possible (e.g. visible damage). Please
immediate take the device out of operation. Note: ensure that the device cannot be
accidentally placed into operation.
---------------------------------------------------------------------------------------------------------------------------------------------------
-4-
Operation manual of solar water controller SR868C8/SR868C8Q
2.Installation
Controller can only be installed indoors, far away from dangerous place and away from
the electromagnetic field. Controller should be equipped with an additional plug, which
should have minimum 3mm distance between the pole of the plug or effective
compliance with the provisions of the installation. For example, switch or fuse, please
note that it should be separated between the wires, and use AC power.
Note: the controller can only be installed in an area having an adequate level of
protection.
---------------------------------------------------------------------------------------------------------------------------------------------------
-5-
Operation manual of solar water controller SR868C8/SR868C8Q
Please switch-off the power net before opening the controller cover, and note
the regulation of local electricity supply.
Depending on the type of installation, the cables may enter the device through the rear
hole of the case ④or the lower side hole of the case ⑤
Cable come from the rear ④: remove the plastic flaps from the rear side of the case
using an appropriate tool.
---------------------------------------------------------------------------------------------------------------------------------------------------
-6-
Operation manual of solar water controller SR868C8/SR868C8Q
Cable come from the below⑤: cut the left and right plastic flaps using an appropriate
tool (e.g. knife) and break them out of the case.
Notes: the flexible wire must be fastened on the case using the clamps provided
Terminal layout
FUSE:2A/250V
Power connection
Power connection terminal is: Input ports
Ground line terminal is GND
Display connection
Port 1: connect red wire (+12V)Port 2: connect white wire ( COM)
---------------------------------------------------------------------------------------------------------------------------------------------------
-7-
Operation manual of solar water controller SR868C8/SR868C8Q
Only original factory equipped Pt1000 temperature sensors are approved for use with
the collector, it is equipped with 1.5meter silicon cable and suitable for all weather
conditions, the temperature sensor and cable are temperature resistant up to 280℃,
not necessary to distinguish the positive and negative polarity of the sensor connection.
Only original factory equipped NTC10K,B=3950 temperature sensors are approved for
use with tank and pipe, it is equipped with 1.5meter PVC cable, and they are
temperature resistant up to 105℃, not necessary to distinguish the positive and
negative polarity of the sensor connection.
All sensor cables carry low voltage, and to avoid inductive effects, must not be laid
close to 230 volt or 400-volt cables (minimum separation of 100mm)
If external inductive effects are existed, e.g. from heavy current cables, overhead train
cables, transformer substations, radio and television devices, amateur radio stations,
microwave devices etc, then the cables to the sensors must be adequately shielded.
Sensor cables may be extended to a maximum length of ca. 100 meter, when cable’s
2
length is up to 50m, and then 0.75mm cable should be used. When cable’s length is up
2
to 100m, and then 1.5mm cable should be used.
Output ports
Output P1:For solar circuit pump, semiconductor relay (SCR relay), also suitable for
RMP control, max. switching current 1A,
Output P2:for hot water circuit pump, electromagnetic relay, and max. switching
current 3.5A,
P2 ports are always open,
Output R1:for by-pass circuit pump or valve, electromagnetic relay, max. switching
current 3.5A, R1 ports are always open,
---------------------------------------------------------------------------------------------------------------------------------------------------
-8-
Operation manual of solar water controller SR868C8/SR868C8Q
Output H1:for back-up electrical heater, electromagnetic relay, and max. switching
current 10A, H1 connection ports are always open.
3. Commissioning
Connect the sensors, pumps or switching valves to the controller before you
connect the power supply!
After switching on power to the controller, firstly it will ask for to set the time, password
and parameters of system.
MO Monday
TU Tuesday
WE Wednesday
TH Thursday
FR Friday
SA Saturday
SU Sunday
---------------------------------------------------------------------------------------------------------------------------------------------------
-9-
Operation manual of solar water controller SR868C8/SR868C8Q
Submenu:
Through submenu, customer can set the parameter as desired value, please check it
carefully.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 10 -
Operation manual of solar water controller SR868C8/SR868C8Q
Code
Code Code
(Subme Menu Description Remark
(Mainmenu) (Submenu)
nu)
DT O Switch-on temperature difference
DT F Switch-off temperature difference
THET Timing heating
TEMP Temperature
Collector
EMOF
maximum switch-off temperature
Collector
EMON
maximum switch-on temperature
Maximum temperature of collector
CMX
(Collector cooling function)
Low temperature protection of
CMN
collector
CFR Frost protection of collector
SMX Maximum temperature of tank
REC Tank re-cooling function
Celsius and Fahrenheit
C-F
temperature transferring
FUN Auxiliary function
DVWG Anti legionnaires' function
Temperature controlled hot water
CIRC
circulation pump
Speed controlling of circulation
nMIN pump
(RPM pump controlling)
Standard temperature difference
DTS (for circulation pump speed
adjust)
Increase scale (circulation pump
RIS Only available
speed adjusting parameter set)
on controller
OHQM Thermal energy measuring
SR868C8Q
FMAX Flow rate
MEDT Type of heat transfer liquid
Concentration of heat transfer
MED%
liquid
INTV Pump interval function
tSTP Pump interval time
tRUN Pump running time
BYPA By pass (high temperature)
HDN Manual controlling
PASS Password set
LOAD Recovery to factory set
---------------------------------------------------------------------------------------------------------------------------------------------------
- 11 -
Operation manual of solar water controller SR868C8/SR868C8Q
Description:
The solar circuit pump (P1) is switched on as soon as the switch-on temperature
difference (△Ton) between the collector array (T1) and the storage tank (T2) is
reached. If the temperature difference between the collector array (T1) and storage
tank (T2) drops below the switch-off temperature difference (△Toff), or the temperature
of storage tank (T3) reaches the preset maximum storage temperature, then the solar
circuit pump (P1) is switched off.
Within the preset time section of back-up heating, if the temperature T3 is below the
switch-on temperature, then the circulation pump ( H1) of back-up heating is triggered,
when T3 is heated to the switch-off temperature, circulation pump H1 of back-up
heating is ceased.
Note:
T3 is alternative sensor, when no sensor (T3) is installed in the top part of tank,
controller will use the signal of sensor T2 automatically to control the auxiliary heating
or the circulation pump.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 12 -
Operation manual of solar water controller SR868C8/SR868C8Q
4.Controller functions
---------------------------------------------------------------------------------------------------------------------------------------------------
- 13 -
Operation manual of solar water controller SR868C8/SR868C8Q
For example: the switch-on DT is 8oC, switch-off DT is 4oC, if the temperature in the
bottom part of tank is 20oC, then just when collector temperature rises up to 28 oC,
pump is triggered, and when collector temperature drops to 24 oC, pump is ceased.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 14 -
Operation manual of solar water controller SR868C8/SR868C8Q
Factory set:
The first time section: back-up heating function starts at 4:00 and ends at 5:00 am.
Within this time section, switch-on temperature is 40℃, switch-off temperature is 45℃.
The second time section: from 10:00 to 10:00 am, it means there is no back-up heating
in this time.
The third time section: back-up heating function starts at 17:00 and ends at 22:00 pm.
Within this time section, the switch-on temperature is 50℃, switch-off temperature is
55℃.
If you want to shut off one timing heating, then you can set the turning on time and
turning off time same value (for example, the second time section no this function, then
you can set turning on/off time is 10:00 ~ 10:00)
When time is outside of the preset time section, back-up heating doesn’t work
automatically even when the tank temperature reaches the switch –on temperature of
heating.
Note:
When there is no sensor installed in the top part of tank (no T3 sensor), controller
will take the signal of T2 (sensor in bottom of tank) automatically to control this
function.
The time in this controlled is 24 hours, when you set time section, the switch-off
time of heating should be larger than switch-on time. For example: if you set the
switch-on time of heating is at 17:00, but switch-off time of heating is 6:00, then
this setting doesn’t take effect, that means within this time section, heating function
doesn’t work. The correct set is like flowing: it should be divided into two time
sections, one time section is from 17:00 to 23:59, the other time section is from
00:00 to 06:00.
Setup steps:
Under standby status, access main menu tHET
►Press “SET” button, access THET program to set parameter, “tH 1o 04:00” displays
on screen, the switch-on time and temperature for first time section of heating function
---------------------------------------------------------------------------------------------------------------------------------------------------
- 15 -
Operation manual of solar water controller SR868C8/SR868C8Q
can be set
-------------------------------------------------------------------------------------------------------------------
►Press“+” button, “tH 2o 10:00” displays on screen, the switch-on time and
temperature for the second time section of heating function can be set
►Press “SET” button, “10” of hour time blinks on screen
►Press “+”“-” button to adjust hour of time
►Repress “SET” button, “00” of minute time
blinks on screen
►Press “+”“-” button to adjust minute of time
►Repress “SET” button, temperature “50℃” blinks on screen
►Press “+”“-” button to adjust switch-on temperature of heating
►Then press “ESC” to exit this set and to access the switch-off time and temperature
set
►Press “+” button, “tH 2F 10:00” displays on screen, set the switch-off time and
---------------------------------------------------------------------------------------------------------------------------------------------------
- 16 -
Operation manual of solar water controller SR868C8/SR868C8Q
---------------------------------------------------------------------------------------------------------------------------------------------------
- 17 -
Operation manual of solar water controller SR868C8/SR868C8Q
If customer use electrical heater as back-up, please according to the power of electrical
heater to equip corresponding safety devices like contactor and breaker with this
controller, we strongly recommend equipping with SR802 device with this controller,
(SR802 detailed technical data see paragraph 10 spare parts)
---------------------------------------------------------------------------------------------------------------------------------------------------
- 18 -
Operation manual of solar water controller SR868C8/SR868C8Q
---------------------------------------------------------------------------------------------------------------------------------------------------
- 19 -
Operation manual of solar water controller SR868C8/SR868C8Q
When tank temperature rises to its preset maximal temperature, solar circuit pump is
ceased compulsively even the temperature difference is satisfied. If the sunshine is
very good, as a result collector temperature will rise continuously, when collector
temperature rises up to its maximal temperature, solar pump will be triggered again
even at the case that tank temperature is already to its maximal temperature. And solar
pump works until the temperature of collector drops since this reversed circulation or
when tank temperature rises its emergency temperature (95 oC).
When displays, and blinks on the screen, it indicates that tank emergency
temperature reaches, tank temperature is ≥95℃
Setup steps:
To access main menu TEMP, then select submenu CMX “CMX 110℃” displays on
screen
---------------------------------------------------------------------------------------------------------------------------------------------------
- 20 -
Operation manual of solar water controller SR868C8/SR868C8Q
exceeds switch-on temperature difference, solar pump doesn’t work yet. When
temperature of collector is 3oC higher that the preset CMN temperature, solar circuit
pump is restarted, controller exits this program.
Setup steps:
To access main menu TEMP, then select submenu CMN, “CMN - - -” displays on
screen, default set is off.
This function is used in system, which use water as heat transfer liquid, to avoid the
freezing of solar heat transfer fluid.
Setup steps:
To access main menu TEMP, then select submenu CFR, “CFR - - -” displays on screen,
default set is off.
►Press “SET” button, default off “- - -” blinks.
►Repress “SET” button, to activate or
deactivate this function
---------------------------------------------------------------------------------------------------------------------------------------------------
- 21 -
Operation manual of solar water controller SR868C8/SR868C8Q
►Press “+”“-” button, to adjust the frost protection function, adjustable range is
(-10℃~10℃), after function activated, default set is 4℃
► Press “ESC” button to exit the menu or wait for 20 seconds to exit automatically,
parameters are saved automatically.
Note: this function is only available in special solar system which using no-anti-freezing
liquid; this kind of system is only suitable in area where the ambient temperature is near
to 0oC in only few days. If safety requirement is very high , then anti-freezing is
necessary, we suggest to use suitable anti-freezing liquid to avoid frost problem.
Setup steps:
To access main menu TEMP, then select submenu SMX, “SMX 60℃” displays on
screen.
►Press “SET” button, parameter “60℃”blinks
►Press “+”“-” button to adjust the value of
maximum temperature of tank1 adjustable
range is(2℃~95℃), default set is 60℃
►Repress “SET” button to activate and deactivate this function, if function deactivated,
“SMX - - -” displays on the screen.
► Press “ESC” button to exit the menu or wait for 20 seconds to exit automatically,
parameters are saved automatically.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 22 -
Operation manual of solar water controller SR868C8/SR868C8Q
collector, solar pump keep in working until tank temperature drops below its
maximum temperature.
Setup steps:
To access main menu TEMP, then select submenu REC, “REC OFF” displays on
screen, default set is off.
►Press “SET” button, parameter “OFF” blinks
on screen
►Repress “SET” button to activate or
deactivate this function, after function activated; factory set is “REC ON”
► Press “ESC” button to exit the menu or wait for 20 seconds to exit automatically,
parameters are saved automatically.
Setup steps:
To access main menu TEMP, then select submenu C-F, “C-F ℃” displays on screen.
Note:
Sometimes, your selected function needs an extra signal input to connect temperature
sensor or an extra output to connect pump or electromagnetic valve. in “FUN “submenu,
some functions are deactivated. Hence, for different system, activated or deactivated
status for following auxiliary functions in submenu is also different.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 23 -
Operation manual of solar water controller SR868C8/SR868C8Q
Example to explain:
If you set thermal energy measuring parameter (OHQM) is off, that means this function
is deactivated, then, FMAX, MEDT and MED% functions are disappeared in the
submenu, only when this function (OHQM) is activated, they are just appear in the
submenu. (See detailed in
§3.2 menu structure)
---------------------------------------------------------------------------------------------------------------------------------------------------
- 24 -
Operation manual of solar water controller SR868C8/SR868C8Q
Factory set: the desired hot water temperature is 40 oC, when return temperature T4
drops to 35oC, circulation pump P2 is triggered, when T4 rises up to 40 oC, circulation
pump P2 is ceased.
Condition for triggering hot water circulation pump: only when tank temperature T3
is 1oC higher than the required hot water temperature, hot water circulation pump just
can be triggered. T3 is alternative sensor, when no sensor (T3) is installed in the top
part of tank, controller will use the signal of sensor T2 automatically to control the
circulation pump P2.
Note: in order to avoid large measuring error, the sensor T4 on hot water return pipe
should be installed 1.5m far away from tank. This function isn’t available in all systems.
Setup steps:
To access main menu FUN, then select
submenu CIRC, “CIRC - - -” displays on screen,
factory set is off.
►Press “SET” button, parameter “- - -” blinks on screen.
►Repress “SET” button, parameter “40℃” blinks on screen
►Press “+”“-” button, to adjust the temperature of hot water return, adjustable range:
2℃~95℃), after function is activated, factory set is 40℃
►Press “SET” button again, “- - -” blinks on screen, function is deactivated
---------------------------------------------------------------------------------------------------------------------------------------------------
- 25 -
Operation manual of solar water controller SR868C8/SR868C8Q
► Press “ESC” button to exit the menu or wait for 20 seconds to exit automatically,
parameters are saved automatically.
4.6.3 nMIN Solar circuit pump speed adjusting(RPM speed controlling)
Note: SR868C8 doesn’t have this function
Description:
P1 output can be configured to function either as RPM controlled output or simple
switch output. When this function is activated, the output is RPM controlled output;
when parameter is set as “nMIN”100%” the output becomes a normal switch output.
RPM control output: (speed controlling is activated), the control system attempts to
maintain a constant temperature difference between collector and tank. The pump
performance is continuously adjusted and the volume flow pumped is increased or
reduced, depending on the temperature difference.
Setup steps:
To access main menu FUN, then select submenu nMIN, “nMIN 30” displays on screen.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 26 -
Operation manual of solar water controller SR868C8/SR868C8Q
achieve the controlling of pump speed. If temperature difference drops to the switch-off
TD(△T OFF), circuit pump is ceased.
Setup steps:
To access main menu FUN, then select
submenu DTS, “DTS 08oC” displays on the
screen
►Press “SET” button, parameter “08oC” blinks
on the screen
►Press “+”“-” button, to adjust standard TD, adjustable range (2℃~30℃), factory set
is 08oC
► Press “ESC” button to exit the menu or wait for 20 seconds to exit automatically,
parameters are saved automatically.
4.6.3.2 RIS Temperature increase rate (for circuit pump speed adjusting)
Note: SR868C8 doesn’t have this function
Setup steps:
To access main menu FUN, then select submenu RIS, “RIS 01 oC” displays on screen.
The thermal energy through solar system is calculated with measured parameter
temperature T1, T0 and flow rate. Thermal energy get in the current day displays in
---------------------------------------------------------------------------------------------------------------------------------------------------
- 27 -
Operation manual of solar water controller SR868C8/SR868C8Q
Note:
1) Thermal energy achieved in current day, accumulative thermal energy and operation
time of pump can be reset, doing like following
Operation steps: under standby status, doing like following
►Press “+”“-” button, select to check the thermal energy of current day, “DKWH XX”
“SET” displays on the screen.
►Press “SET” button for 3 seconds, buzzer makes 3 times “du - - - ”, the daily thermal
energy is cleared, and daily thermal energy is reset to “00”.
►Press “+”“-” button, select to check accumulative thermal energy, “KWH XX” or
“MWH XX” “SET” displays on the screen.
►Press “SET” button for 3 seconds, buzzer makes 3 times “du - - -”, the sum thermal
energy is cleared, accumulative thermal energy is reset to “00”.
►Press “+”“-” button, select to check operation time of pump, “hP XX” “SET “displays
on the screen.
►Press “SET” button for 3 seconds, buzzer makes 3 times “du - - -”, the operation time
of pump is cleared, and it is reset to “00”.
2) Only when the thermal energy balance function is activated, operation time of
circulation pump function just can be triggered.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 28 -
Operation manual of solar water controller SR868C8/SR868C8Q
Setup steps:
To access main menu FUN, then select submenu MEDT, “MEDT 01” displays on
screen.
►Press “SET” button, parameter “01” blinks
on the screen
►Press “+”“-” button, to adjust type of heat
transfer liquid, adjustable range (00~03)
► Press “ESC” button to exit the menu or wait for 20 seconds to exit automatically,
parameters are saved automatically.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 29 -
Operation manual of solar water controller SR868C8/SR868C8Q
During the period that solar pump is in operating, (the period of running time can be set
by parameter “tRUN”), controlled check the temperature signal of sensor, if the
temperature increases less than 1 oC, then solar pump is ceased automatically. After
the break time (interval can be set by parameter “tSTP”), same process repeats.
During the period that solar pump is in operating, if measured temperature increases
over 1oC, then the next interval is omitted, this omitting repeats when it caters condition
and until the switch-on temperature difference is catered or no more temperature can
be measured. After that, pump interval function recovers to pulse rate-controlled mode.
Setup steps:
To access main menu FUN, then select submenu INTV, “INTV OFF” displays on
screen.
► Press “SET” button, parameter “OFF”
displays and blinks, factory set is “OFF”
► Press “+”“-” button, to activate this function,
“INTV ON” displays on the screen.
► Press “ESC” button to exit the menu or wait for 20 seconds to exit automatically,
parameters are saved automatically.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 30 -
Operation manual of solar water controller SR868C8/SR868C8Q
For example:
If we set the temperature of bypass is 70oC, then when tank temperature (T3) rises up
to 71oC, this by-pass function is triggered, electromagnetic valve or circuit pump (R1)
and TD controlled circuit pump (P1) will be triggered simultaneously. When tank
temperature (T3) drops to 67oC, electromagnetic valve or circuit pump (R1) and TD
controlled circuit pump (P1) will be ceased simultaneously.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 31 -
Operation manual of solar water controller SR868C8/SR868C8Q
Setup steps:
To access main menu FUN, then select submenu BYPR, “BYPR - - -” displays on
screen.
►Press “SET” button, “- - -”blinks on screen,
default set is “OFF”
►Repress “SET” button, to activate by-pass
function, “BYPR 80℃” displays on the screen, “80℃” blinks
►Press “+”“-” button to adjust this parameter, adjustable range (5℃~120℃)
► Press “ESC” button to exit the menu or wait for 20 seconds to exit automatically,
parameters are saved automatically.
Application example
Picture1 Picture2
Setup steps:
To access main menu HND,
►Press “SET” button, “HND1 off” displays on the screen, P1 output manually set
►Repress “SET” button, “HND1 on”
displays on the screen, P1 output is
switched-on
►Repress “SET” again, “HND1 off”
---------------------------------------------------------------------------------------------------------------------------------------------------
- 32 -
Operation manual of solar water controller SR868C8/SR868C8Q
------------------------------------------------------------------------------------------------------------------
►Press “+” button, “HND2 off” displays on the
screen, P2 output manually set
►Press “SET” button, “HND2on” displays on
the screen, P2 output is switched-on
►Repress “SET” again, “HND2off” displays,
P2 output is switched-off
►Press “ESC” to exit P2 set program
------------------------------------------------------------------------------------------------------------------
►Press “+” button, “HND3 off” displays on the
screen, R1 output manually set
►Press “SET” button, “HND3 on” displays on
the screen, R1 output is switched-on
►Repress “SET” again, “HND3 off” displays,
R1 output is switched-off
►Press “ESC” to exit R1 set program
-------------------------------------------------------------------------------------------------------------------
---------------------------------------------------------------------------------------------------------------------------------------------------
- 33 -
Operation manual of solar water controller SR868C8/SR868C8Q
►Press “SET” button, “PWDC 0000”, the left digital blinks, ask for to enter the
password, factory set is “0000”
►Press “+”“-” button to enter the first digital
►Repress “SET” button, the second digital blinks
►Press “+”“-” button to enter the second digital
►Repress “SET” button, the third digital
blinks
►Press “+”“-” button to enter the third digital
►Repress “SET” button, the fourth digital
blinks
►Press “+”“-” button to enter the fourth digital
►Press “SET” button, “PWDN 0000” displays
on the screen, ask for entering a new
password, doing like above to enter the new
password
►Press “SET” button, “PWDG 0000” displays
on the screen, ask for reentering the new
password, doing like above to reenter the new password, “PWOK” displays on the
screen to indicate reentering password successfully.
►Press “ESC” button to exit set program or wait for 20 seconds to exit automatically.
Warning!
If the password is forgot, it is not possible to recover, but you can recover the password
to factory set, then you can reedit a password like above descript steps, doing like
following to recover to factory set.
► Open cover in the front of the display,Press and hold on,then repress the
recovery button,which on the dispaly plate.
►Buzzer makes “du - - -” 3 times, then release button. Controller recovers to
factory set, a new password can be reset now.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 34 -
Operation manual of solar water controller SR868C8/SR868C8Q
►Hold down “SET” button, buzzer makes “du - - -” 3 times, then release “SET” button.
Controller recovers to factory set, new paramters can be reset now.
►Press “ESC” button to exit set program or wait for 20 seconds to exit automatically.
►Press button for 3 seconds; controller is switched off, “OFF” displays on the
screen.
►Repress button, controller is switched-on again.
Description:
This function activates in night, solar liquid will flow from storage tank to collector to
cool the tank, and therefore to prevent high thermal loads problem of the solar system
due to completely heated storage tank. The function is activated at night between 10
pm and 6 am, when the collector temperature drops 8 ℃ below the storage tank
temperature (T2), solar circuit pump starts to work; when the temperature of collector is
2℃ below the tank temperature, and solar circuit pump is ceased.
Note: The function is deactivated when the temperature in lower section of storage
tank falls down to 35℃.
►Press “Holiday” button for a long time until the signal of holiday function displays on
the screen, and then holiday function is activated.
►Repress “Holiday” button, signal disappears, holiday function is deactivated.
Note:
This function is only activated when you are not at home for long time, when you come
back; please make sure to deactivate it.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 35 -
Operation manual of solar water controller SR868C8/SR868C8Q
Conditions for triggering manual heating function: the setting temperature should be
2℃ higher than tank temperature.
Note: manual heating can only heat tank one time, after manual heating is triggered,
when temperature of tank rises up to the preset temperature, manual heating ceases,
and manual heating function will be deactivated automatically, if customer wants to
heat again, you need redo according to above steps.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 36 -
Operation manual of solar water controller SR868C8/SR868C8Q
(DKWH) and accumulative thermal energy (KWH) or (MWH) can only be checked
after triggering of OHQM thermal energy balance function.
Press “+”“-” button can check the value of temperature sensors T1~ T4.
5. Protection function
6. Trouble shooting
If control unit does not work correctly, please check following points.
►Press “+”“-” button to check error code, signal displays on the LCD screen
---------------------------------------------------------------------------------------------------------------------------------------------------
- 37 -
Operation manual of solar water controller SR868C8/SR868C8Q
---------------------------------------------------------------------------------------------------------------------------------------------------
- 38 -
Operation manual of solar water controller SR868C8/SR868C8Q
unnecessary costs. Of course, not all possible problems can be listed here. However,
most of the normal problems encountered with the controller can be found in the list
below, only return the controller to seller when you are absolutely sure that none of the
problems listed below is responsible for the fault.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 39 -
Operation manual of solar water controller SR868C8/SR868C8Q
Warning! Remove the device from the mains supply before opening the case
A potentially defective sensor can be checked using an ohmmeter. To do this, the
sensor must be disconnected, its resistance measured, and the value compared with
the figures in the table below, small deviation (±1%) is acceptable,
PT1000 resistance value
℃ 0 10 20 30 40 50 60 70 80 90 100 110 120
Ω 1000 1039 1077 1116 1155 1194 1232 1270 1309 1347 1385 1422 1460
Ω 33620 20174 12535 8037 5301 3588 2486 1759 1270 933 697 529 407
7. Quality Guarantee
Manufacturer provides following quality responsibilities to end-users: within the period
of quality responsibilities, manufacturer will exclude the failure caused by production
and material selection. A correct installation will not lead to failure. When a user takes
incorrect handling way, incorrect installation, improper or crud handling, wrong
connection of sensor in system and incorrect operation, the quality responsibility is
invalid for them.
The warrantee expires within 24 months after the date of purchasing the controller.
---------------------------------------------------------------------------------------------------------------------------------------------------
- 40 -
Operation manual of solar water controller SR868C8/SR868C8Q
8. Technical data
Type
Specification SR868C8Q SR868C8
Appearance of
120mm×120mm×18mm 120mm×120mm×18mm
controller
Power supply AC230V±10% AC230V±10%
Power consumption < 3W < 3W
Accuracy of
temperature ±2oC ±2oC
measuring
Range of collector
temperature -10~220oC -10~220oC
measuring
Range of tank
temperature 0~110oC 0~110oC
measuring
Suitable power of
3个,≤ 600W 3个,≤ 600W
pump
Suitable power of
electrical heater 1个,≤ 1500W 1个,≤ 1500W
---------------------------------------------------------------------------------------------------------------------------------------------------
- 41 -
Operation manual of solar water controller SR868C8/SR868C8Q
9. Delivery scope
Type
Lists SR868C8Q SR868C8
Display 1 1
Controller 1 1
Operation manual 1 1
PT1000 sensor (size:Ф 6*50mm,cable
length1.5m) 2 1
NTC10K(size:Ф 6*50mm,cable length3m) 3 2
Plastic expansion screw 4 4
Screw 4 4
Strain-relief clamp 1 1
---------------------------------------------------------------------------------------------------------------------------------------------------
- 42 -