The hydraulic calculation report summarizes the design of a sprinkler system for a facility in Vietnam. It includes 30 sprinkler heads operating at a density of 18 mm/min across an area of 360 square meters. The system is supplied by a 125mm diameter main that branches into smaller diameter pipes to distribute water to the sprinkler heads at adequate pressures from a source providing 8,807 liters per minute at 15.271 bars.
The hydraulic calculation report summarizes the design of a sprinkler system for a facility in Vietnam. It includes 30 sprinkler heads operating at a density of 18 mm/min across an area of 360 square meters. The system is supplied by a 125mm diameter main that branches into smaller diameter pipes to distribute water to the sprinkler heads at adequate pressures from a source providing 8,807 liters per minute at 15.271 bars.
The hydraulic calculation report summarizes the design of a sprinkler system for a facility in Vietnam. It includes 30 sprinkler heads operating at a density of 18 mm/min across an area of 360 square meters. The system is supplied by a 125mm diameter main that branches into smaller diameter pipes to distribute water to the sprinkler heads at adequate pressures from a source providing 8,807 liters per minute at 15.271 bars.
Submitted by FHC user number: Project: ARNEPLANT VIETNAM COMPANY LIMITED
Project Ref HHT009 Area Ref: Most Unfavourable Inst. Number: 1
Tel: Fax:
Project Data and Design Parameters
Project name : Area reference : Most Unfavourable Address / location : . Project number : HHT009 Installation number(s) : 1 Drawing number(s) : --- Issue no / date : --- Designers reference : --- Project Data File : Hazard classification : Domestic Design authority : NFPA 13 : 2016 - Installation of Sprinkler S Insurance company : --- Specified density of discharge : 18.00 mm/min (l/min/m2) Assumed maximum area of operation : 360.00 m2 Number of operating sprinkler heads : 30 + 2 hydrant(s) Maximum area covered per head : 12.00 m2 Highest head / nozzle above source : 12.00 m Number of pipes in system : 52 from 25 to 125 mm Pressure loss equation used : Hazen-Williams Fluid : Water Pipe Data Table : STD_PIPE.PDT Maximum fluid velocity : 12.43 m/s in pipe 152 153 Volume of pipework and fittings : 6.16 m3 Elbows are welded for : 65 mm and above Comment : --- Checked by & Date :
Source duty = 8807.3 l/min @ 15.271 bar at node no 100
Canute FHC Ver: 1.8.4 Monday, December 6, 2021 - 16:27
Canute FHC Ver: 1.8.4 Monday, December 6, 2021 - 16:27
www.canutesoft.com Page: 3/4 FHC - Hydraulic Calculation Report Submitted by user number: Project: A COMPANY LIMITED Project Ref HHT009 Tel: Area Ref: Most Unfavourable Fax: Inst. Number: 1