Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

John Thompson Electropac Boiler Brochure

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

JOHN THOMPSON ELECTROPAC

LV Electrode Boiler
JOHN THOMPSON ELECTROPAC™
LV Electrode Boiler

Features & benefits • Total package incorporates a feedwater • Fully automatic


pump, controls and all necessary valves
• The Electropac is a vertical type shell boiler, • Microprocessor technology
and fittings
with top-mounted electrodes, suitable for a
• No pollution
low voltage supply and a working pressure • Quality management systems are audited
of 1 000 kPa to SABS and satisfy the requirements of Optional Extras
• Designed and manufactured in accordance ISO 9001: 2008
• Feedwater tank
with BS1894 – 1992
• All boilers are inspected and certified by
• Blowdown vessel
• Design pressure 1 100 kPa an Approved Inspection Authority before
• Robust design and construction for long life despatch • Automatic conductivity control

• Thermal efficiency 99% • Full steam pressure within ten minutes • No-volt solenoid.

Notes
1. All dimensions, masses and fuel
consumption are approximate based
upon a boiler pressure of 1 000 kPa
2. Full range of support services are
available from our regional offices
3. Whilst all information is given in good
faith, it should be confirmed before
establishing any contractual commitment.

Boiler Model Number THE 80 150 300 500 1 000 2 000


Boiler Rating: At 525 volt, 3 phase kW 72 135 270 450 900 1 800
Evaporation: From and at 100°C kg/h 115 215 431 718 1 436 2 872
At 1 000 kPa, feedwater 20°C kg/h 96 180 361 601 1 202 2 404
Boiler Rating: At 400 volt, 3 phase kW 55 103 206 343 686 1 372
Evaporation: From and at 100°C kg/h 88 164 328 547 1 094 2 188
At 1 000 kPa, feedwater 20°C kg/h 74 137 275 458 916 1 831
Height A mm 1 385 1 700 1 740 2 170 2 270 2 630
Minimum Roof Clearance B mm 2 080 2 400 2 740 3 450 3 900 4 100
Width C mm 1 150 1 300 1 445 1 640 1 840 1 960
Depth D mm 550 610 745 840 950 1 150
Blowdown E mm 170 170 180 200 200 200
Steam Outlet F mm 1 055 1290 1 390 1 595 1 700 1 980
Main Steam Valve Diameter mm 20 25 32 50 80 80
Safety Valve Exhaust Diameter mm 15 20 25 32 80 80
Bleed Off Valve Diameter mm 15 15 15 15 15 15
Blowdown Valve Diameter mm 40 40 40 40 40 40
Mass: Empty kg 230 330 520 780 1 200 1 800
Operating kg 350 460 690 1 000 1 600 2 300

JOHN THOMPSON a division of ACTOM (Pty) Ltd.


Cape Town Head Office PO Box 129, Bellville, 7535, RSA Tel:+27 (0)21 959-8400 Fax:+27 (0)21 959-8545
Johannesburg Office PO Box 8382, Edenglen, 1613, RSA Tel:+27 (0)11 392-0900 Fax:+27 (0)11 392-0938
Durban Office PO Box 32292, Mobeni, 4060, RSA Tel:+27 (0)31 408-9700 Fax:+27 (0)31 408-9722
e-mail: info@johnthompson.co.za www.johnthompson.co.za

10/2015

You might also like