Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Model: A300PE3: Diesel Generator Set

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Model: A300PE3

Diesel Generator Set


FEATURES TIER III SERIES
 Armstrong provides one-source
responsibility for the generator system and
its accessories.
 All units and components are factory tested
during prototype and manufacturing stages
assuring long product life.
 Generator set accepts one-step 100% of full
load per NFPA 110.
 A one-year limited warranty covers all
systems and components. Extended
warranties are available.
 Rugged 4 cycle heavy-duty diesel engine,
with swirl intake ports for a low fuel
consumption and excellent transient
response.
Generator features:
 Unique Volts per Hertz compensated More features:
electronic AVR excitation system delivers  Controllers are available to meet your most
reliable voltage response for in rush loads. demanding applications.
 Brushless, rotating-field generator has low  In the event of low oil pressure or high coolant
reactance, 2/3 pitch, class H insulation, temperature the self-protecting system will
minimizes voltage distortion when automatically stop the engine.
powering non-linear loads.

GENERATOR SET RATINGS

Standby Prime
Volt Code Voltage Winding Connection Phase Power Factor Hz Amps Standby
Model kW / kVA kW / kVA
A300PE3 61 480 / 277 HI WYE 3 0.8 60 452 300(375) 270(338)
A300PE3 63 440 / 254 HI WYE 3 0.8 60 493 300(375) 270(338)
A300PE3 64 240 / 139 HI WYE 3 0.8 60 903 300(375) 270(338)
A300PE3 65 220 / 127 LOW WYE 3 0.8 60 985 300(375) 270(338)
A300PE3 66 208 / 120 LOW WYE 3 0.8 60 1042 300(375) 270(338)
A300PE3 67 240 / 120 LOW WYE 1 1.0 60 - - -
A300PE3 51 415 / 240 2 DELTA 3 0.8 50 - - -
A300PE3 53 380 / 220 HI WYE 3 0.8 50 - - -
A300PE3 55 220 / 127 HI WYE 3 0.8 50 - - -
A300PE3 57 220 / 110 LOW WYE 1 1.0 50 - - -

Stand-By ratings are continuous electrical service during the interruption of normal power. No overload capacity is
specified at these ratings.
Prime ratings available with variable loads are continuous, 10% overload capacity for one hour in twelve hours periods.
Both ratings per BS 5514, DIN 6271, ISO-3046
Many industrial, commercial and residential voltages are available
ALTERNATOR ESPECIFICATIONS A300PE3
Type Four pole, revolving field  Four pole, revolving field, direct coupled to
Rotor Insulation Class H engine flywheel, provides excellent
7Temperature Rise 150°C Standby alignment.
Material Epoxy resin  Insulation is of class H, ready to be used
Line-To-Line Harmonic Factor (Max) 5% on harsh environments where sea spray,
Telephone Interference Factor (Tif) 1% sand and chemical corrosion are existing
Voltage Regulator Solid State factors.
Cooling Self-ventilated and drip proof  Voltage regulator provides Volts/Hertz
Bearing 1 each, pre-lubed compensation to improve the motor starting
Coupling Direct, Flexible Disc capabilities, therefore support the engine
Load Capacity (Standby) 100% handling transient loads.
Overload Capacity (Prime) 110%  Dynamically balanced rotor, with damper
Voltage Regulation winding, help dissipate transient voltage
No Load To Full Load ±1 % interference during load variations.
One Step Load Acceptance  The windings have a 2/3 pitch in order to
Per NFPA 110 100% reduce the harmonic content of voltage.
 Robust mechanical structure permits easy
access to connections.

ENGINE ESPECIFICATIONS
Manufacturer PERKINS  Robust industrial grade PERKINS diesel
Model 2206D-E13TAG2 engine, for reliable endurance.
Bore 5.1in(130mm)
 Direct fuel injection system and swirl intake
Stroke 6.18in(157mm)
ports combine for a low fuel consumption and
Number Of Cylinders 6
excellent transient response.
Piston Displacement 768.8 in3 (12.5L)
Compression Ratio 16.3:1  Cylinder Head provides superior airflow
Cooling System Type Liquid through specially designed intake manifold
Engine Type In-Line – 4 Cycle
ports, large valves and seats resulting in
superior engine performance in torque
Aspiration Turbocharged after cooled air/air
reserve, fuel consumption and emissions. .
Engine Crankcase Vent System Closed
Cylinder Replaceable Liner  Dynamically Balanced Crankshaft, with
EPA Tier 3 induction-hardened journal surfaces
Governor Type Electronic significantly increases wear life.
Frequency Regulation  Poly Belt Fan Drive provides superior noise
No Load To Full Load 0.5 % and vibration reduction.
Air Cleaner Dry Element

Powered by : Perkins
STANDARD EQUIPMENT

ENGINE - Charging Alternator - 12v SCROLL push button


- Air Cleaner - Battery Kit & Battery Rack - Ac Voltmeter GENERAL
- Fuel Pump GENERATOR - Ac Ammeter - Integrated Fuel Tank
- Fuel Filter - Synchronous, Brush-less - Frequency Meter - Industrial Muffler
- Oil Pump - Four Pole - Vibration Shock Mounts - Rain Cap
- Full Flow Oil Filter - Single Bearing - Engine Shutdowns - Lifting Points
- Jacket Water Pump - Direct Coupled With Flex * High Water Temperature - Acrylic Enamel Paint
- Thermostat and Housing - Class H Insulation * Low Oil Pressure
- Exhaust Manifold Dry - Drip-Proof Construction - Engine Gauges
- Oil Cooler CONTROL PANEL * Battery Voltmeter
- Blower Fan & Fan Drive - Digital type * Water Temperature
- Radiator - Unit Mounted - Automatic Mains Failure module * Oil Pressure
- Electric Starting Motor 12v provides engine and electrical * Running Time Meter
- Turbocharged metering facilities via the LCD * LED and LCD alarm
- Housing & Flywheel display, accessed via the indication
INSTALLATION AND APPLICATION DATA A300PE3
Type of Operation and Application
Item Units 60 Hz
Prime Standby
Rated Speed rpm 1800 1800
Gross Engine Output bhp (kWm) 500 (373.4) 545 (406.5)
Engine
BMEP psi (kPa) 288 (1984) 315 (2171)
Mean Piston Speed Ft/s (m/s) 30.9 (9.42)
Ambient Air Temperature °F (°C) 131 (55)
Coolant Capacity engine only gal (L) -
Coolant Capacity engine + radiator gal (L) 13.6 (51.4)
Cooling
Cooling system Liquiid (50% water + 50% coolanat)
System
3 3
Pusher Fan Air Flow ft /min (m /s) 27816 - (13.1)
Heat rejection to coolant kcal/kWh -
Heat rejection to air (intercooler) kcal/kWh -
Fuel Type Diesel No.2
Fuel Consumption @ 50% Power gal/hr (L/hr) 10.8 (41) -
Fuel system
Fuel Consumption @ 75% Power gal/hr (L/hr) 15.0 (57) -
Fuel Consumption @ 100% Power gal/hr (L/hr) 19.7 (74.5) 20.9 (79)
3 3
Combustion Air Flow ft /min (m /min) 939 (26.6)
Air
Air Intake Restriction In.H2O (kPa) 10.5 (2.5) 10.5 (2.5)
Requirement
Maximun Allowable Restriction In.H2O (kPa) 26.8 (6.4) -Dirty air filter
3 3
Exhaust Gas Flow ft /min (m /min) 2703 (75.2)
Exhaust
Max temperature, after turbo °F (°C) 1256 (680)
System
Connection Outlet Size Diameter In. (mm) 5 (127)
Total Engine Oil Cap. w/ Filter(s) gal (L) 10.5 (40)
Oil Filter Type Cartridge
Oil Cooler Water Cooled
Lubrication
System Lube oil specifications API-CH4 - SAE 15W – 40
Lube oil consumption < 0.15% of full load fuel consumption
Oil and filters interval for
hours Check your engine operators book
replacement
Battery Charging Alternator Volts, Ground 24VDC, Negative

Engine Baterry Charging Alternator Rated amps 70


Electricals Recommended Battery Cold Crank CCA amps 1200 (0°F / -18°C)
Starter Motor Volts, Ground 24DC, Negative
temperature % Consult Factory
Ambient altitude > % Consult Factory
Deration
altitude > % Consult Factory
OPTIONAL EQUIPMENT A300PE3
Cooling System Start System Control Panel
 Remote Radiator  Battery Nicad  Emergency stop button
 Jacket Water Heater  Battery Warmer Plate  Microprocessor Control Panel
 Crankcase Oil Heater  Battery Charger  NFPA 110 Ready
Fuel System  Automatic Float Equalizing  Remote Annunciation Panel
 Fuel/Water Separator  Trickle  Audible Alarm
 Day Tank Switchgear General
 Above Ground Fuel Tank  Main Line Circuit Breaker  Spring vibration isolators
 Auxiliary Fuel Pump  Shunt trip  Automatic Transfer Switch
 Sub-Base Fuel Tank  Auxiliary switch  Metal Enclosure
 Double Wall  Automatic Transfer Switch  Interior lights AC or DC
 UL Listed  Paralleling  Trailer
Exhaust System  Protective Relays  Export Packaging
 Industrial Grade Muffler Generator  Special Testing
 Residential Grade Muffler  Permanent Magnet Excitation  Warranties
 Critical Grade Muffler  Space Heaters
 Super Critical Grade Muffler  Temperature Rise Detectors

DIMENSIONS AND WEIGHT

Open Sound Att.


Units
Unit Unit
Length In. (mm) 130 (3302) 178 (4521)
H
Width In. (mm) 50 (1270) 50 (1270)

Height In. (mm) 80 (2032) 88 (2235)

Weight Lbs (kg) 6253 (2833) 6864 (3120)

W L

General configuration for reference only, do not use these dimensions for installation purposes. Contact your
local dealer for certified drawings.

All Specifications and Materials are subject to change without prior notice.

ARMSTRONG POWER SYSTEMS LLC


Phone (305) 470-0058
Fax (305) 470-0068
Toll Free (800) 238-0732
nd
Address: 5100NW 72 Ave., Miami Fl 33166
Email: sales@armstrongpower.com
www.armstrongpower.com