Sigma: Sigma CP Conventional Fire Alarm Control Panels

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Sigma

CP
!
EW
N
BS EN54-2

Sigma CP BS EN54-4
KM 73505

Conventional
Fire Alarm
Control Panels
Model No. K11080M2

Two, four and eight


zone, 2-wire or standard,
programmable fire
control panels
conforming to BS EN54-2
& BS EN54-4 for smaller
conventional detection
systems requiring high
performance and quality.

Features Product Overview

Fully compliant with & tested The S igma CP range consists of a series of
Adjustable sounder delay time conventional f ire alarm control panels designed in
to BS EN54-2 and BS EN54-4
Sounder configuration options accordance with European standards BS EN54-2
2-wire and standard and BS EN54-4 Fire D etection and Fire A larm
Zonal sounder delay detectors only versions in 2, 4 or 8 zones systems - Control and Indicating Equipment.

Zonal sounder delay call points only Compatible for use on


The range consists o f 2, 4 and 8 zone control
BS5839: Part 1: 2002
Coincidence input selection installations panels. A ll control panels are available in t wo
versions:
I.S Barrier selection by zone
2-wire repeaters and
Short circuit fire by zone ancillary boards Sigma K11 r ange in w hich detectors and call
points are wired on separate circuits t o
Non latching zones Fully programmable using sounders (two sounder circuits are provided).
simple menu options
Silent zones
Sigma T11 r ange in w hich detectors, c all
Simple, single board
Zone input delay points and sounders are wired to the same pair
construction
of cables. Commonly referred to a s a two-wire
General panel configuration system.
Installer friendly

Compatible with Wiring sounders to the detection circuits eliminates


wide range of the need to i nstall s ounder c ircuit cables and also
detection devices offers the ability t o provide zoned or t wo stage
sounder operation.
Two monitored
sounder outputs
All control panels have an integral, mains powered
3 Amp power supply battery charger and power s upply designed in
accordance with the requirements of BS EN54-4.
Auxiliary power output

Page 36
Technical

Specifications Size - 385mm(W) x 310mm(H) x 92mm(D)


Construction - 1.2mm mild steel
Colour - BS 00 A 05 (grey texture) - lid & box
Ral 7047 (light grey) - controls plate
DS37.05.2005 Supply voltage - 230V AC (+10%/-15%)
Mains supply fuse - 1.6 Amp 250V
Power supply DC rating - 24V 3 Amps
Maximum battery size - 7Ah 12V (2 per panel)
Fault contact rating - 30V DC 1 Amp
Local fire contact rating - 30V DC 1 Amp
Fire contact rating - 30V DC 1 Amp
Sounder output rating - 0.5A per output (max 1.6A over all outputs)
Detection zone current - 1.6 milliamps
Detection zone - 6k8 5%
end of line resistor
Sounder output - 10k 5%
end of line resistor
Cable capacity - 2.5mm² per terminal
Operating temperature - -5°C to +50°C
Operating humidity - <95% (non condensing)

90 385

Conventional
Zone Chart General System Status Fire In Zone
Fire Power Fault
1 2 3 4
1 Power On Sounder Fault/
Disablement
Zone Fault/Test/Disablement System Mode
2
Delay On General Fault
Fire In Zone
3
310

Test Mode On System Fault


4 5 6 7 8
General Alarm/Fault
Disablement Warning Silenced
5 Zone Fault/Test/Disablement Enable Control
6
Silence/Sound Alarm/Fault Reset Lamp Mode Select Enter
7 Alarm Warning Silence Test (+10) (+1)

Fire Alarm Control


Model: K11080M2

BS EN54-2 : 1998
BS EN54-4 : 1998 KM 73505

Panels

Product Description Standby Alarm


Code Current Current

K11020M2 2 zone control panel 0.065 Amps 0.1 Amps


K11040M2 4 zone control panel 0.075 Amps 0.21 Amps
K11080M2 8 zone control panel 0.093 Amps 0.55 Amps
Certificate No. FM 32987
BS EN ISO 9001: 2000
T11020M2 2 zone, 2 wire panel 0.065 Amps 0.15 Amps
T11040M2 4 zone, 2 wire panel 0.075 Amps 0.3 Amps
T11080M2 8 zone, 2 wire panel 0.093 Amps 0.63 Amps

Certificate No. 360


BS EN ISO 9001: 2000 The manufacturer reserves the right to amend specifications without prior notice Page 37