Novec 1230

Download as pdf or txt
Download as pdf or txt
You are on page 1of 15

!

EW
N
A-XT

Extinguishant
Control Panel
Shield A-XT is a new
generation extinguishant
releasing panel which is
UL,FM listed
The simple, programmable
configuration options and
easy to install construction
make Shield A-XT panels the
ideal choice for small to
medium sized systems
using all extinguishant Features Product Overview
agents.

UL864 and FM listed Designed and manufactured to t he highest


standards in a quality controlled environment and
Programmable Three initiation circuits as standard with UL & FM approvals, the Shield A-XT
Functions releasing panel offers outstanding value
and performance for all small to medium fixed
Any single zone or any firefighting installations
combinations of zones can
Access Level 2
be configured to release
Test Zones 1 to 3 With t hree detection zones as standard,
Disable Zones 1 to 3 extinguishant release can be configured to
Configurable first stage
Disable 1st Stage Alarms activate from any combination of detection zone
NAC delays
Disable Pre-activated 1st Stage Relay inputs to a llow ( among other combinations) any
Disable Pre-activated 2nd Stage Relay
Configurable detection delays two from three type activations such as would be
Disable Extract Fan Output
required for detection in ceiling void, room and
Disable Manual Release Input
Zero time delay upon floor void applications.
Disable Extinguishant Sub System
manual release option
Activate Extract Fan Output
Activate Alarm Delays The extensive configuration options o f the Shield
Compatible with I.S. barriers A-XT allow the functionality of t he system to be
Access Level 3 extensively modified
Non-latching zone input
Sounder Delay option to receive signals The panel contains a large LED display to enable
Coincidence Detection from other systems such easy configuration and control which also displays
Disable Panel Features as aspirating equipment
Zone Alarm Delays (Detectors) the time remaining until extinguishant release for
Zone Alarm Delay (Call Points) added user safety.
Configurable extinguishant
Configure Zone for I.S Barrier Use delays up to 60 seconds The countdown timer is duplicated on up to seven
Zone Short Circuit Alarm in 5 second steps remote status units to p rovide local i ndication of
Zone Non Latching
the system status.
Zone Inputs Delay Configurable extinguishant
Extinguishant Release Time Delay duration up to 5 minutes With a ll o f the electronics m ounted on a single,
Extinguishant Release Duration Timer in 5 second steps easily removable, steel plate Shield A-XTpanels are
Extinguishant Reset Delay Timer
both robust and easy to install.
Countdown timer shows
time remaining until release Shield A-XT is supplied in an enclosure that matches
the design and colour of the elite RS range and is
Supports up to seven, available in standard red or optional grey.
four wire status indicators

Built in Extract Fan control

The manufacturer reserves the right to amend specifications without prior notice
Specifications

Technical
Construction - 1.2mm mild sheet steel
IP Rating - IP30
Finish - Epoxy powder coated
Colour - lid & box - Red RAL 3002 (optional grey BS 00 A 05 semi-matt)
Mains supply - 230V AC or 115V AC
Mains supply fuse - 1.6 Amp (F1.6A L250V)
Power supply rating - 3 Amps total including battery charge 28V +/- 2V
Maximum ripple current - 200 millivolts
Battery type (Yuasa NP) - Two 12 Volt 7Ah sealed lead acid in series
Battery charge voltage - 27.6VDC nominal (temperature compensated)
Battery charge current - 0.7A maximum
Battery fuse - 20mm, 3.15A glass
Maximum current draw from batteries - 3 Amps
Quiescent current of panel in mains fail - 0.095A
R0V output - Fused at 500mA with electronic fuse
Sounder outputs - 24V Fused at 500mA with electronic fuse
Fault relay contact rating - 30VDC 1A Amp maximum
Fire relay contact rating - 30VDC 1A Amp maximum
Local fire relay contact rating - 30VDC 1A Amp maximum
First stage contact rating - 30VDC 1A Amp maximum
Second stage contact rating - 30VDC 1A Amp maximum
Extract contact rating - 30VDC 1A Amp maximum
Zone quiescent current - 2mA maximum
Terminal capacity - 12 AWG
Number of detectors per zone - Dependent on type (maximum 32)
NAC rating - 0.5A per circuit
Detection circuit end of line - 6K8 5% ½ Watt resistor
Monitored input end of line - 6K8 5% ½ Watt resistor
Sounder circuit end of line - 10K 5% ¼ Watt resistor
Extinguishant output EOL - 1N4004 Diode
No. of initiating circuits - 3
No. of NAC circuits - 2 x 1st Stage, 1 x 2nd Stage
Extinguishant release output - Fused at 1 Amp
Extinguishant release delay - Adjustable 0 to 60 seconds (in 5 second steps)
Extinguishant release duration - Adjustable 60 to 300 seconds (in 5 second steps)
SIL, AL, FLT, RST inputs - Switched -ve, max resistance 100 Ohms
Zone normal threshold - 8K ohms to 1K ohm
Detector alarm threshold - 999 ohms to 400 ohms
Call point alarm threshold - 399 ohms to 100 ohms
Short circuit threshold - 99 ohms to 0 ohms
Monitored inputs normal threshold - 8K ohms to 1K ohm
Monitored inputs alarm threshold - 999 ohms to 100 ohms
Monitored inputs Short circuit threshold - 99 ohms to 0 ohms
Status unit/Ancillary board connection - Two wire RS485 connection
Status unit power output - Fused at 500mA with electronic fuse

Panels
Product Code Description Size (mm)

S115R-EXT Surface mounting panel - Red 115V 368 x 310 x 90


SHIELD FIRE, SAFETY
AND SECURITY LTD S230R-EXT Surface mounting panel - Red 230V 368 x 310 x 90

28th Floor Regus Suite S115G-EXT Surface mounting panel - Grey 115V 368 x 310 x 90
One Canada Square S230G-EXT Surface mounting panel - Grey 230V 368 x 310 x 90
Canary Wharf
London, E14 5DY
United Kingdom The manuf acturer reserves the right to amend specifications without prior notice
INTRODUCTION
Competence and innovation driven by consistent market Certifications such as UL and FM approvals have earned
development and customer requirements have shaped the SHIELD a world-renowned reputation with quality products
successful development of the SHIELD Brand. The extensive and powerful solutions.
product range of the market leader in the field of fire protection
A strong brand is generally known to be a secure basis for close
technology contains single, individually integrable system
and lasting customer relationships. In accordance with this,
performances. In this way, a customized overall fire protection
SHIELD uses available potential in order to keep on growing
concept can be planned and realized for every need with
in a dynamic competitive environment. And at the same time,
optimally synchronized products.
SHIELD stands for innovative and high quality fire protection
systems.
Performance is in international demand, SHIELD is among the
highly accredited fire protection companies that meet rigorous We invite you to explore and visit our website
British and American standards for all projects from small www.shieldglobal. com. You can also send us your feedback
conventional system to multi-site networks. and inquiry through our user-friendly online forms.

In line with SHIELD policy for continuous product development, SHIELD has the right to change specifications without prior notice.
Images shown in this catalogue are for illustrations purposes only.

www.shieldglobal.com 1
SYSTEM ASSEMBLIES
500 PSI [34.5 BAR]
Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid

DESCRIPTION
Shield Novec 1230 Clean Agent Fire Suppression Systems
are highly efficient when combined with a properly designed
plumbing network using the Shield version of the VDS Flow
Calculation Software.

COMPONENTS
1. Cylinders: cylinders are manufactured in accordance
with DOT 4BW500 and TC BWM34* standards. *490L
cylinder assemblies are only DOT T4BW500 compliant
2. Valve Assembly: All valves are of the pressure differential
design, and will not operate without deliberate actuation.
The actuation devices can be removed while under
pressure to facilitate functionality testing of the system.
It is also equipped with a monitoring Pressure Switch as
well as a port to facilitate pneumatic actuation of secondary
cylinder assemblies.
3. Cylinder Straps: The cylinder body straps are designed
to secure the system assembly during discharge. A single
strap is included with all systems up to 103L, while larger
systems are equipped with two straps. Systems 490L in
size are shipped with two wall mount straps, floor mount
straps are available upon request.

TECHNICAL SPECIFICATION
Part Number Cylinder Size Maximum Fill Minimum Fill Empty Weight
SD000015 38 lb (15 L) 38 lb (17 kg) 10 lb (4.5 kg) 37.6 lb (17.1 kg)
SD000029 75 lb (29 L) 76 lb (34.5 kg) 16 lb (7.5 kg) 54 lb (24.5 kg)
SD000062 160 lb (62 L) 164 lb (74 kg) 33 lb (15 kg) 106.2 lb (48.2 kg)
SD000103 270 lb (103 L) 271 lb (132.5 kg) 55 lb (25 kg) 154.8 lb (70.3 kg)
SD000153 400 lb (153 L) 406 lb (184 kg) 82 lb (37.5 kg) 250 lb (113.4 kg)
SD000227 600 lb (227 L) 601 lb (272.5 kg) 121 lb (55kg) 340 lb (154.3 kg)
SD000368 950 lb (368 L) 964 lb (437 kg) 196 lb (88 kg) 465.5 lb (211.2 kg)
SD000490 1300 lb (490 L) 1297 lb (588 kg) 260 lb (118 kg) 762.5 lb (345.9 kg)

SUPPRESSION AGENT ENVIRONMENT LIMITATIONS


The suppression agent used in Shield Novec 1230 Engineered • Operating Temperature: 32°F [0°C] to 130°F [54.4°C]
System Assembly is a Fluoroketone as indicated by the chemical
• System Operating Pressure: 500 psi at 70°F [34.5 bar
formula CF3CF2C(O) CF(CF3)2, more commonly known as 3M™
at 21.1°C]
Novec™ 1230 Fire Protection Fluid. Novec 1230 is a colorless
low odor fluid, low in toxicity, electrically non-conductive, leaves
no residue, and is an extremely effective fire suppression
agent. Novec 1230 is included in NFPA-2001, under the ASHRAE
designation of FK-5-1-12, and has been evaluated and approved
for use in occupied areas as a Total Flooding agent when used
in accordance with this standard.

2 www.shieldglobal.com
TECHNICAL SPECIFICATION
System Assembly Cylinder Size Dimension “A” Dimension “B” Dimension “C”
Part Number (Nominal) Inches Millimeter Inches Millimeter Inches Millimeter
SD000015 38 lb (15L) 16.7 426 27.7 705 10.0 254
SD000029 75 lb (29L) 28.7 730 33.9 861 10.0 254
SD000062 160 lb (62L) 37.7 958 43.6 1107 12.7 324
SD000103 270 lb (103L) 38.7 983 44.6 1133 16.0 406
SD000153 400 lb (153L) 55.3 1405 63.6 1615 16.0 406
SD000227 600 lb (227L) 54.0 1372 62.6 1590 20.0 508
SD000368 950 lb (368L) 58.5 1486 66.1 1679 24.0 610
SD000490 1300 lb (490L) 60 1582 68.9 1750 30.0 762

490L Assembly

www.shieldglobal.com 3
ENGINEERING CONSIDERATIONS PRESSURE SUPERVISORY SWITCH
Proper System size and agent fill weight shall be determined Electrical Rating 240 VAC - 3 A, 24 VDS - 3 A
using only genuine Shield Flow Calculation Software (P/N:
SD901001). Switch SPDT snap action

Contacts NO, NC, and Common


Floor loading varies as a function of the quantity of extinguishing
agent in each Cylinder Assembly and the values shown in the 486 ± 14 psi [33.5 ± 1.0 bar] Actuation
General Specifications Table. For further guidance on this topic Set Points
414 ± 14 psi [28.5 ± 1.0 bar] Release
contact Shield.
Pressure

SHOWN AT ATMOSPHERE Operational


-5 °F to +175 °F [-21 °C to +65 °C}
Normally Open White Temperatures
-40 °F to +260 °F [-40°C to + 135°C]

Common Black

Normally Closed Red


Pressure

Item Description
1 Cylinder
2 Valve
3 Pressure Supervising Switch
4 Cylinder Strap
5 Liquid Level Indicator Optional

LIQUID LEVEL INDICATORS: (Optional) System


Assemblies above 62L in volume can be outfitted with a Liquid PART NUMBER DESCRIPTION
Level indicator. These can be used to provide an accurate Liquid Level Indicator for 160 lb.
estimate of the agent weight contained within the assembly SD720150
{62 L] & 270 lb. [103 L]
without weighing the system assembly. These components are
Liquid Level Indicator for 400 lb.
optional and must be requested upon ordering. SD720375
[153 L] through 950lb. (368L)

LISTINGS AND APPROVALS: SD721200 Liquid Level Indicator for 1300 lb. [490 L]
• Complies with UL requirements when used with UL, &
ULC listed cylinder assemblies.
• Complies with FM requirements when used with FM
listed system assemblies.

4 www.shieldglobal.com
CYLINDER STRAPS DIMENSIONS
Cylinder Quantity Anchor Dimension “A” Dimension “B” Dimension “C” Dimension “D”
per
Size Cylinder Point
Inches Millimeter Inches Millimeter Inches Millimeter Inches Millimeter
38 lb (15 L) 1 Wall 9.8 248 12.3 311 11.3 286 1.4 35
75 lb (29 L) 1 Wall 9.8 248 12.3 311 11.3 286 1.4 35
160 lb (62 L) 1 Wall 12.5 318 15.0 381 14.0 356 1.4 35
270 lb (103 L) 1 Wall 15.8 400 18.3 464 17.3 438 1.4 35
400 lb (153 L) 2 Wall 15.8 400 18.3 464 17.3 438 1.4 35
600 lb (227 L) 2 Wall 19.8 502 22.3 565 21.3 540 1.4 35
950 lb (368 L) 2 Wall 23.8 603 26.3 667 25.3 643 1.4 35
1,300 lb (490 L) 2 Wall 29.0 737 32.3 819 31.3 794 1.4 35
1,300 lb (490 L) 2 Floor 4.5 114 10.5 267 9.5 241 1.4
*Wall mount straps included in 1300LB assembly. If floor mount is desired, floor mounts straps (SD401201) must be ordered separately.

CYLINDER WALL STRAP

CYLINDER FLOOR STRAP

Service Note: Cylinders Assemblies shall be designed, filled, pressurized


and maintained by trained personnel in accordance with Shield Design,
Installation, Operation and Maintenance Manuals (SD000003).

www.shieldglobal.com 5
MONITORED SYSTEM ACTUATORS

ELECTRIC LINEAR ACTUATOR


The Electric Linear Actuator (SD500125) is a removable device
with an internal monitoring switch. The internal monitoring
switch complies with NFPA requirements for actuation apparatus
monitoring.

The Electric Linear Actuator mounts to the threads on the


actuation adapter, located on the top of the cylinder valve. It
is permanently installed while the system is in service, but the
threaded attachment allows for ease of removal for inspection
and maintenance purposes.

The Electric Linear Actuator houses a pin magnetically held in


place while the systems remain in an idle state. Once powered,
the pin moves downward, depressing the actuation adapter
valve core and releasing pressure from the cylinder valve.

Cylinder valves equipped with the Electric Linear Actuator must


be actuated from a listed control panel for releasing device
service that is compatible with Shield equipment.

Prior to the installation of the Electric Linear Actuator to the


actuation circuit, confirm that the electrical ratings of the
solenoid are compatible with the electrical ratings of the
actuation circuit.

NOTE: The actuation circuit is rated at 24 VDC, 0.5 Amps.


The maximum supervisory current should not exceed 30 mA.

Wiring of the Electric Linear Actuator to the actuation circuit


shall comply with wiring methods in accordance with NFPA
requirements and the installation instructions provided with
the listed control panel for releasing device service. A diagram
for proper wiring has been provided below. For more information,
refer to the wiring methods found in NFPA 72, Chapter 17.

6 www.shieldglobal.com
MONITORED SYSTEM ACTUATORS
The Electric Linear Actuator shall be installed with listed
conduit connectors.

By utilizing flexible metal conduit connectors or liquid-tight


conduit connectors, the solenoid coil wires and dual leads for
the internal monitoring switch are mechanically protected from
damage.
WIRE DIAGRAM

ELECTRIC LINEAR ACTUATOR WIRING DIAGRAM

MANUAL OVERRIDE
The Manual Override (SD500126) features a push button that
moves the internal pin downward and manually actuates the
Electric Linear Actuator.

The Manual Override mounts to the threads located on the top


of the Electric Linear Actuator. The threaded attachment allows
for ease of removal for inspection and maintenance purposes.

LISTINGS AND APPROVALS


• Complies with UL requirements when used with UL, &
ULC listed cylinder assemblies.
• Complies with FM requirements when used with FM
listed system assemblies.

Service Note: Cylinders Assemblies shall be designed, filled, pressurized


and maintained by trained personnel in accordance with Shield Design,
Installation, Operation and Maintenance Manuals (SD000003).

www.shieldglobal.com 7
PRESSURE OPERATED SWITCH

DESCRIPTION
The Pressure Operated Switch (SD503013) is used as a
discharge confirmation. If the pressure operated switch
detects pressure above the activation set point, the switch
contacts will close, providing a signal to the control panel
indicating that the system assembly has been activated.

Electrical Rating 240 VAC- 3 A, 24 VDC - 3 A,

Switch SPDT snap action


Contacts NO, NC and Common
Activation: 20 + 5 psig [1.4 + 0.3 bar]
Set Points Manual Reset: 10 + 6 psig
[0.7 + 0.4 bar]

Operation -5 °F to + 175 °F [-29 °C to + 66 °C]


Temperatures -40 °F to + 260 °F [-54 °C to + 127 °C]

LISTINGS AND APPROVALS: SHOWN AT ATMOSPHERE


• Complies with UL requirements when used with UL, & Normally Open White
ULC listed cylinder assemblies.
• Complies with FM requirements when used with FM Common Black
listed system assemblies.

Normally Closed Red

Pressure

8 www.shieldglobal.com
PNEUMATIC COMPONENTS FOR MULTIPLE
CYLINDER SYSTEM DESIGNS
PRODUCT OVERVIEW
Shield offers pneumatic elbow, tees and flex hoses to insure
that proper connections are made between master and slave
cylinders. The SD700021 elbow attaches to the “M” port of
the master cylinder valve. The SD700033 elbow is used on
the slave cylinder pneumatic actuator, located at the end of
a cylinder in a bank. The pneumatic tee, SD700032, is used to
attach multiple pneumatic activators to one master cylinder.
Refer to the Shield Design, Installation, Operation & Maintenance
Manual (SD000003) for more information on the proper design
of master and slave cylinder banks.

PNEUMATIC ACTUATOR
A pneumatic actuator is used in a multiple cylinder configuration.
It features a pneumatically driven piston that slides downward,
depressing the actuation adapter valve core allowing the
cylinder valve to activate.
Multiple cylinders equipped with a Pneumatic Actuator can be
activated from one master cylinder using the ex hoses.
The Pneumatic Actuator mounts on the top of the cylinder
valve.

LISTINGS AND APPROVALS:


• Complies with UL requirements when used with UL, &
Part Number Description
ULC listed cylinder assemblies.
• Complies with FM requirements when used with FM SD700021 Pneumatic Elbow (Used at Valve)
listed system assemblies. SD700033 Pneumatic Elbow (Used at Actuator)
SD700032 Pneumatic Tee
SD700024 Flex Hose-Actuation (24” Length)
SD700025 Flex Hose-Actuation (36” Length)
SD700004 Flex Hose-Actuation (48” Length)
SD700041 Pneumatic Actuator

www.shieldglobal.com 9
DISCHARGE NOZZLES
500 PSI [34.5 BAR]
Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid

DESCRIPTION
The function of the Discharge Nozzle is to distribute the Clean
Agent in a uniform, pre-determined pattern and concentration.
The nozzles are designed to complete the discharge in 10
seconds, or less, when installed within the design limitations
of the Shield Design, Installation, Operation, & Maintenance
Manual (SD000003).

Discharge Nozzles are available in sizes ranging from ½” to


2½”. Each nozzle is available in two configurations: 180 and
360 degree distribution patterns, and is made of aluminum,
brass, or stainless steel with female pipe threads. Orifice sizes
are determined by hydraulic flow calculations. All nozzles are
rated for a maximum hazard height of 14 feet. If hazards
exceed 14 feet in height, a second tier of nozzles must be used.

DISCHARGE NOZZLE SELECTION SIDE-WALL 180° DISCHARGE NOZZLE SELECTION CENTRAL 360°
Typically installed adjacent to the center of the wall in the Typically installed at the center of the ceiling in an enclosure.
enclosure. Its discharge path will be across the enclosure. Its discharge path will be across the enclosure.

*ALUMINUM NOZZLES
Part Number Description Part Number Description
SD661100 ½” [13 mm] (360°) Central SD661200 ½” [13 mm] (180°) Sidewall
SD662100 1” [25 mm] (360°) Central SD662200 1” [25 mm] (180°) Sidewall
SD663100 1½” [38 mm] (360°) Central SD663200 1½” [38 mm] (180°) Sidewall
SD664100 2” [50 mm] (360°) Central SD664200 2” [50 mm] (180°) Sidewall
SD665100 2½” [63.5 mm] (360°) Central SD665200 2½” [63.5 mm] (180°) Sidewall
*Aluminum nozzles are not FM approved

BRASS NOZZLE
Part Number Description Part Number Description
SD661300 ½” [13 mm] (360°) Central SD661400 ½” [13 mm] (180°) Sidewall
SD662300 1” [25 mm] (360°) Central SD662400 1” [25 mm] (180°) Sidewall
SD663300 1½” [38 mm] (360°) Central SD663400 1½” [38 mm] (180°) Sidewall
SD664300 2” [50 mm] (360°) Central SD664400 2” [50 mm] (180°) Sidewall
SD665300 2½” [63.5 mm] (360°) Central SD665400 2½” [63.5 mm] (180°) Sidewall

STAINLESS STEEL NOZZLES


Part Number Description Part Number Description
SD661500 ½” [13 mm] (360°) Central SD661600 ½” [13 mm] (180°) Sidewall
SD662500 1” [25 mm] (360°) Central SD662600 1” [25 mm] (180°) Sidewall
SD663500 1½” [38 mm] (360°) Central SD663600 1½” [38 mm] (180°) Sidewall
SD664500 2” [50 mm] (360°) Central SD664600 2” [50 mm] (180°) Sidewall
SD665500 2½” [63.5 mm] (360°) Central SD665600 2½” [63.5 mm] (180°) Sidewall

LISTINGS AND APPROVALS:


• Complies with UL requirements when used with UL, &
ULC listed cylinder assemblies.
• Complies with FM requirements when used with FM
listed system assemblies.

10 www.shieldglobal.com
DISCHARGE COMPONENTS
Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid

DESCRIPTION
Flexible discharge hoses are used to connect the cylinders
to discharge piping network in either a single or the multiple
cylinder installation.
A Check Valve is required for a manifold system to enable
two or more agent storage cylinders to share one common
discharge piping network. The Check Valve is spring assisted
to ensure the valve closes to prevent ow reversal, and may
be installed in the vertical or horizontal position.

DISCHARGE HOSES
Part Number Size Length Material End Connection
SD701005 1” [25 mm] 24” [610 mm] Rubber 1” MNPT
SD701505 1 1½” [40 mm] 24” [610 mm] Rubber 1½” MNPT
SD702504 2½” [65 mm] 32” [813 mm] S.S. Braided 2½” MNPT
SD704005 4” [100 mm] 40” [1016 mm] S.S. Braided 4” Grooved

CHECK VALVES LISTINGS AND APPROVALS:


Part Number Body Number Fitting Style • Complies with UL requirements when used with UL, &
ULC listed cylinder assemblies.
SD701001 Brass 1” FNPT
• Complies with FM requirements when used with FM
SD701501 Brass 1½” FNPT listed system assemblies.
SD702501 Brass 2½” FNPT
SD704003 Ductile Iron 4” Grooved

www.shieldglobal.com 11
SYSTEM ACCESSORIES
Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid

DESCRIPTION
Shield offers three different hazard signs which are placed near
the doors of a hazard to inform the occupants of the installed
Shield Clean Agent Fire Suppression System. The signs are
red with white lettering and measure 7.5” W x 3.5” H x 0.25” T.

The Shield Main/Reserve Switch allows the user to quickly


switch the electrical panel (connection) between a main and
reserve system in the event of system maintenance or a
discharge. The switch allows for easy and worry free servicing
and shorter downtimes in the event of a discharge.

DISCHARGE HOSES
Part Number Description

Hazard Sign: “Caution: When Alarm


SD 710001 Sounds Vacate Room, Fire Suppression
System Being Discharged”

Hazard Sign: “Caution: Do Not Enter Room


SD 710002 When Alarm Sounds. Fire Suppression
System Being Discharged”

Hazard Sign: “Caution: Operation of


SD 710003 Manual Station Will Result in Immediate
Discharge of Fire Suppression System”

SD 502001 Main/Reserve Switch

LISTINGS AND APPROVALS:


• Complies with UL requirements when used with UL, &
ULC listed cylinder assemblies.
• Complies with FM requirements when used with FM
listed system assemblies.

12 www.shieldglobal.com
VDS FLOW CALCULATION SOFTWARE
Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid

DESCRIPTION
Shield Novec™ systems use a customized version of VDS’s 8. Once these steps have been performed it is now time
FK-5-1-12 Flow Calculation Software. This software has been to install the Codemeter runtime software. To install this
designed to accurately represent Shield Systems and you will need to:
Components during the flow calculation. Licenses and A.) Open the VDS folder on your desktop
software can be purchased directly through Shield to
enable distributors to perform ow calculations. B.) Find the Codemeter folder and open it
C.) Select the file named “CodeMeterRunt - ime_5.0.exe”
VDS SOFTWARE INSTALLATION: D.) Follow the prompts on the screen.
Installing the VDS Software is a multiple step procedure
that includes copying the program files to your desktop, 9. Now to verify that everything set up properly plug in
installing the VDS and Codemeter programs, and then the silver VdS USB dongle and open the program.
establishing your default settings. To accomplish these
10. Once the program is open Select the “Files” Option at
task you must:
the top of the screen
1. Copy the VDS.zip File onto the installation computer’s
desktop. 11. From the drop down menu choose the “Options”
selection.
2. Right Click on the VDS.zip le and choose “Extract All”
from the drop down menu. 12. A window will open up with several tabs, choose the
“Directories” tab.
3. You will now see a regular folder titled “VDS”, open it.
13. At the bottom of this window you will see a dialogue
4. Contained within this file you will now see an additional box, verify that the settings are all as shown in the
folder titled “FK-5-1-12Normal”, open this folder. illustration below:
5. You should now see will see a file entitled “Setup_FK-
5-1- 12_7.5.exe”, click on this file and follow the
instructions on the screen.
6. Now that the VDS program is installed you will need to
upload the Shield Licensing information to the program
files. To do this you will need to:
A.) Copy the lst_.chk file
• Go to the VDS folder on your desktop and open it
• Click on the FK-5-1-12 Normal folder and open it
• Highlight the lst_.chk file and copy it
7. Next, to copy component files into your program
directory you will need to:
A.) Open the VDS folder on your desktop
14. Now click on the “Default Values” tab and ensure
B.) Copy the following Shield Component files: your settings are as follows:
• FT Components 1.0.0.arm
• FT Nozzles - 1.0.2.nox
• FT Pipe - Schedule 40 - 1.0.0.rkl
C.) Paste them into the program files in the catalogue
folder by:
• Go to your C drive
• Click on Program Files (x86)
• Click on VDS
• Click on FK-5-1-12
• Open the Comp folder, and paste the three files here

15. Once this final step is complete you are now ready to
begin operating the program.

www.shieldglobal.com 13