SIGMA A-XT

Extinguishant Control Panel UL/FM Approved

Features

UL864 and FM Listed 
Compatible with I.S. barriers

Three initiation circuits as standard 
Non-latching zone input option to receive signals from

Any single zone or any combinations of zones can be other systems such as aspirating equipment
configured to release 
Configurable releasing delays up to 60 seconds in 5

Configurable first stage NAC delays second stops

Configurable detection delays 
Configurable releasing duration up to 5 minutes in 5

Zero time delay upon manual release option second steps.

Supports up to seven, four wire status indicators 
Countdown timer shows time remaining until

Built in Extract Fan control release

Description
Sigma A-XT releasing panel offers outstanding value and performance for all
small to medium fixed fire-fighting installations.

With three initiating circuits as standard, release can be configured to


activate from any combination of detection zone inputs to allow (among The countdown time is duplicated on up to seven remote status units to
other combinations) any two from three types of activations for detection in provide local indication of the system status.
ceiling void, room and floor void applications.
With all the electronics mounted on a single, easily removable, steel plate
The extensive configuration options of the Sigma A-XT allow the functionality Sigma A-XT panels are both robust and easy to install. Sigma A-XT is supplied
of the system to be extensively modified. The panel contains a large LED in an enclosure that matches the design and colour of the Elite RS range and
display to enable easy configuration and control which also displays the time is available in standard red or optional grey.
remaining until release for added user safety.

Panels

Product Code Description Size (mm)


K1810-12 Surface mounting panel- Red 115V 368 x 310 x 90

K1810-44 Surface mounting panel- Grey 115V 368 x 310 x90

K1810-13 Surface mounting panel- Red 230V 368 x 310 x 90

K1810-43 Surface mounting panel- Grey 230V 368 x 310 x 90

Specification

Construction 1.2mm mild sheet steel

IP rating IP30

Finish Epoxy powder coated

Colour- lid & box Red RAL 3002 (optional grey BS 00 A 05 semi-matt)

Mains supply 230V AC or 115V AC

Mains supply fuse 1.6Amp (FL.6A L250V)

Power supply rating 3 Amps total including battery charge 28V +/- 2V

For further information visit www.kentec.co.uk


Specification

Maximum ripple current 200 millivolts

Battery Type (Yuasa NP) Two 12 Volt 7Ah sealed lead acid in series

Battery charge voltage 27.6VDC nominal (temperature compensated)

Battery charge current 0.7A maximum

Battery fuse 20mm, 3.15A glass

Maximum current draw from batteries 3 amps

Quiescent current of panel in mains fail 0.095A

R0V output Fused at 500mA with electronic fuse

Sounder outputs 24V Fused at 500mA with electronic fuse

Fault relay contact rating 30VDC 1A Amp maximum

Fire relay contact rating 30VDC 1A Amp maximum

Local fire relay contact rating 30VDC 1A Amp maximum

First stage contact rating 30VDC 1A Amp maximum

Second stage contact rating 30VDC 1A Amp maximum

Extract contact rating 30VDC 1A Amp maximum

Zone quiescent current 2mA maximum

Terminal capacity 12 AWG

Number of detectors per zone Dependent on type (maximum 32)

NAC rating 0.5A per circuit

Detection circuit end of line 6K8 5% 1/2 Watt resistor

Monitored input end of line 6K8 5% 1/2 Watt resistor

Sounder circuit end of line 10K 5% 1/4 Watt resistor

Extinguishant output EOL 1N4004 Diode

No. of initiating circuits 3

No. of NAC circuits 2 x 1st stage, 1 x 2nd stage

Extinguishant release output Fused at 1 Amp

Extinguishant release delay Adjustable 0 to 60 seconds (in 5 second steps)

Extinguishant release duration Adjustable 60 to 300 seconds (in 5 second steps)

SIL, AL, FLT, RST inputs Switched -ve, max resistance 100 ohms

Zone normal threshold 8K ohms to 1k ohm

Detector alarm threshold 999 ohms to 400 ohms

Call point alarm threshold 399 ohms to 100 ohms

Short circuit threshold 99 ohms to 0 ohms

Monitored inputs normal threshold 8K ohms to 1k ohm

Monitored inputs alarm threshold 999 ohms to 100 ohms

Monitored inputs short circuit threshold 99 ohms to 0 ohms

Status unit/ Ancillary board connection Two wire RS485 connection

Status unit power output Fused at 500mA with electronic fuse


Programmable Functions

Access Level 2 Access Level 3

Test Zones 1 to 3 Sounder delay

Disable Zones 1 to 3 Coincidence detection

Disable 1st stage alarms Disable panel features

Disable pre-activated 1st stage relay Zone alarm delays (detectors)

Disable pre-activated 2nd stage replay Zone alarm delay (call stations)

Disable extract fan output Configure zone for I.S barrier use

Disable manual release input Zone short circuit alarm

Disable releasing sub system Zone non latching

Activate extract fan output Zone inputs delay

Activate alarm delays Extinguishant release time delay

Extinguishant release duration timer

Extinguishant reset delay timer

Extinguishant Released
Remote Auto/Manual

Remote Abort Switch

Releasing Solenoid

Extinguishant Low
Pressure Switch

Pressure Switch
Remote Manual
Release Switch

1st Stage 2nd Stage


Select Switch

Noti cation Noti cation

Extract Fan Power


Appliances Appliances
10K 10K 10K
Peripheral
Detectors
Releasing
Detectors

Stop Air Conditioning

470R

470R

470R

470R

470R
DIODE
Shutdown Power

Remote
Control
6K8

6K8

6K8

Inputs
S
O
6K8

6K8

6K8

6K8

6K8

To Status Auxiliary Signalling Relays


Units S S S L

S S
S S S

E R0V SIL AL FLT RST NC C NO NC C NO NO C NC C NO NC C NO NC C NO


AUX REMOTE DATA POWER NAC 1 NAC 2 ZONE 1ZONE 2ZONE 3 2ND 1ST 2ND MODE MAN. ABORT REL EXTING. LOW EXTRACT TROUBLE LOCAL FIRE
24V CONTROL STATUS UNITS SOUNDER STAGE STAGE SELECT RELEASE PRESS. PRES. RELAY FIRE RELAY
SWITCH SWITCH

Sigma A-XT PCB

Datasheet DS72 07/2018


For further information visit www.kentec.co.uk