Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Eaton Fire Ul Addressable Panel Ulcf3000 Datasheet v1!1!0218

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Specifier’s guide 3.

2 Control panels

ULCF3000 range - UL intelligent


SIGNALING

addressable control panels 4AC5


FIRE ALARM
EQUIPMENT

ULCF3000RM (wall mount red metal)

ULCF3000 (wall mount graphite)

The Eaton ULCF3000 is a high specification intelligent Features and benefits


addressable, wall or rack mounted, UL Listed control
panel available in various loop configurations. It combines • Large versatile touch-screen user interface
sophisticated functionality with simple operation and • 2 or 4 Class A Style 7 SLC loops
aesthetically pleasing design. • Event history buffer (9,999 events) with date/time
The control panel has the ability to support complex stamp
cause and effect programming (via site installer) and a • 4 Notification appliance circuit (NAC’s) outputs
wide range of user controllable functions that make the • Dedicated alarm, trouble, AC trouble relays
panel ideal for a diverse range of projects from industrial
• Integral short circuit isolators
applications through to large multi site commercial
developments. • Up to 200 addresses per loop
• Full network capability up to 126 panels
The ULCF3000 uses soft addressing to minimise
installation time and remove the potential for error • Supports a comprehensive range of soft addressing
associated with manual addressing. It can operate as modules and devices for greater flexibility in design
a stand alone panel or as part of a networked system, • Menu driven graphical user interface for ease of
and has powerful programming options that allow operation
configurable control over whether messages from • Reduced commissioning time through soft
specific panels are transmitted around the network or addressing and auto learn functions
remain local. • Programming and trouble shooting time minimised
by using a range of features such as auto config,
walk test, system details menus

EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©February 2015
Specifier’s guide
3.2 Control panels

Technical specification Dimensions

Code ULCF3000 / ULCF3000RM D2 D2


Description UL intelligent addressable control panel
Standards UL864 9th edition W W
Primary operating supply 120V ac / 240V ac, 60Hz, 2.0A supervised
Secondary operating supply H H
Battery voltage 24V dc
Battery charge current 1.0A (max)
Battery derating factor 0.1
Battery capacity supervised 12Ah (max)
Notification appliance circuits Class B, Style Y, Sounder Group 1, Sound-
er 1, Sounder Group 1, Sounder 2, Sounder Group 2
Output voltage 24V dc
Output current 0.75A (max) D1
ULCF3000 D1 ULCF3000RM
Line impedance 50Ω (wall mount graphite) (wall mount red metal)
When powered by 240V ac, the maximum
current of 3.0A is shared between these
circuits
Description H (mm) W (mm) D1 (mm) D2 (mm)
When powered by 120V ac, the maximum ULCF3000 397 497 75 130
current of 2.25A is shared between these ULCF3000RM 398 505 48 118
circuits
Circuits are supervised, power limited and
regulated.
Notification appliance circuits Class B, Style Y, SYNC MODULE. NAC1,
System block diagram
NAC2
Output voltage 24V dc
Output current 0.5A (max) Control Panel 2 BMS System
Interface
Line impedance 50Ω (max)
The maximum current of 0.5A is shared
between these circuits
Circuits are supervised, power limited and
regulated.
Printer Control Panel 1 PSU
Alarm, trouble contacts. Relay expansion
Unity power factor 30V dc
For connection to power limited sources only
BATT
Aux relay (AC Trouble) contacts
Unity power factor 30V dc, 1A
For connection to power limited sources only PA/VA System Site Graphics System

Signaling line circuit Style [7] Class [A] – (Addressable Loop)


Rated voltage 24V dc Catalogue numbers
Maximum current 500mA
Line impedance 50Ω (max) Description Code
Supervised, power limited 2 loop panel ULCF30002G
Network SLC 4 loop panel ULCF30004G
Voltage 5V dc 2 loop panel, integral printer ULCF30002GP
Current 100mA (max) 4 loop panel, integral printer ULCF30004GP
Line impedance 50Ω (max) 2 loop panel, network card ULCF30002GNC
Power limited 4 loop panel, network card ULCF30004GNC
Limited to same enclosure installations 2 loop panel, integral printer, network card ULCF30002GPNC
Physical 4 loop panel, integral printer, network card ULCF30004GPNC
IP Rating IP30 2 loop panel, red metal box ULCF30002GRM
4 loop panel, red metal box ULCF30004GRM
Compatibility
2 loop panel, integral printer, red metal box ULCF30002GPRM
Suitable for use with Eaton UL fire systems
4 loop panel, integral printer, red metal box ULCF30004GPRM
2 loop panel, network card, red metal box ULCF30002GNCRM
4 loop panel, network card, red metal box ULCF30004GNCRM
2 loop panel, integral printer, network card, ULCF30002GPNCRM
red metal box
4 loop panel, integral printer, network card, ULCF30004GPNCRM
red metal box
Rack mounted 2 loop panel ULR3000L2
Rack mounted 4 loop panel ULR3000L4
Rack mounted 2 loop panel c/w network card ULR3000L2NC
Rack mounted 4 loop panel c/w network card ULR3000L4NC
Loop connected repeater panel ULCF3000PRG
Touchscreen network repeater panel ULCTPR3000

EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©February 2015