Sigma: Extinguishant Control Panel
Sigma: Extinguishant Control Panel
Sigma: Extinguishant Control Panel
XT
!
EW
N
BS EN12094-1
Extinguishant KM 96761
Control Panel
Sigma XT is a new
generation extinguishant
releasing panel which is
fully compliant with Model No. K11031M2
European standard BS
EN12094-1.
(Fixed firefighting systems
– components for gas
extinguishing systems).
The simple, programmable
configuration options and Features Product Overview
easy to install construction
make Sigma XT panels the
ideal choice for small to
Complies with EN12094-1 Designed and manufactured to the highest
medium sized systems standards in a quality controlled environment
using all extinguishant Three detection zones and with European EN12094-1 approvals, the
agents. as standard Sigma XT extinguishant releasing panel offers
outstanding value and performance for all
Any single zone or any small to medium fixed firefighting
combinations of zones can installations.
Programmable be configured to release
Functions Configurable first stage
With three detection zones as standard,
extinguishant release can be configured to
sounder delays activate from any combination of detection
zone inputs to allow (among other
Access Level 2 Configurable detection delays combinations) any two from three type
Test Zones 1 to 3 activations such as would be required for
Disable Zones 1 to 3 Zero time delay upon detection in ceiling void, room and floor void
Disable 1st Stage Alarms manual release option applications.
Disable Pre-activated 1st Stage Relay
Disable Pre-activated 2nd Stage Relay Compatible with I.S. barriers The extensive configuration options of the
Disable Extract Fan Output Sigma XT allow the functionality of the
Disable Manual Release Input Non-latching zone input system to be extensively modified while still
Disable Extinguishant Sub System option to receive signals complying with the requirements of the
Activate Extract Fan Output from other systems such controlling standard for the equipment
Activate Alarm Delays as aspirating equipment (EN12094-1).
Access Level 3 Configurable extinguishant The panel contains a large LED display to
Sounder Delay
delays up to 60 seconds enable easy configuration and control which
Coincidence Detection
in 5 second steps also displays the time remaining until
Disable Panel Features
extinguishant release for added user safety.
Zone Alarm Delays (Detectors)
Configurable extinguishant
Zone Alarm Delay (Call Points)
duration up to 5 minutes The countdown timer is duplicated on up to
Configure Zone for I.S Barrier Use
in 5 second steps seven remote status units to provide local
Zone Short Circuit Alarm
indication of the extinguishant system status.
Zone Non Latching
Countdown timer shows
Zone Inputs Delay
time remaining until release With all of the electronics mounted on a
Extinguishant Release Time Delay
single, easily removable, steel plate Sigma XT
Extinguishant Release Duration Timer
Supports up to seven, panels are both robust and easy to install.
Extinguishant Reset Delay Timer
four wire status indicators
Sigma XT is supplied in an enclosure that
Built in Extract Fan control matches the design and colour of the Sigma
CP range.
Page 50
Extinguishant Released
Remote Auto/Manual
Releasing Solenoid
Extinguishant Low
Pressure Switch
Pressure Switch
Remote Manual
Release Switch
Specifications
Peripheral
Releasing
Detectors
Detectors
470R
470R
470R
470R
470R
DIODE
Shutdown Power
Remote
Control
6K8
6K8
6K8
Inputs
S
DS40.03.2006 O
6K8
6K8
6K8
6K8
To Status Auxiliary Signalling Relays
Units S S S L
S S
S S S
Sigma XT PCB
Panels Technical
Product Description Size Mains supply - 230V AC +10%/-15% (100 Watts maximum)
Code (mm) Mains supply fuse - 1.6 Amp (F1.6A L250V)
Power supply rating - 3 Amps total including battery charge 28V +/- 2V
K11031M2 Surface mounting panel 385 x 310 x 90 Maximum ripple current - 200 millivolts
K11031F2 Flush mounting panel * 415 x 315 x 86 Battery type (Yuasa NP) - Two 12 Volt 7Ah sealed lead acid in series
Battery charge voltage - 27.6VDC nominal (temperature compensated)
Battery charge current - 0.7A maximum
Compatible Status & Hold Off Units Battery fuse - 20mm, 3.15A glass
K911000M8 6 lamp unit (surface) Maximum current draw from batteries - 3 Amps
Quiescent current of panel in mains fail - 0.095A
K911000F8 6 lamp unit (flush)
R0V output - Fused at 500mA with electronic fuse
K911100M8 6 lamp unit c/w mode select (surface) Sounder outputs - 24V Fused at 500mA with electronic fuse
K911100F8 6 lamp unit c/w mode select (flush) Fault relay contact rating - 30VDC 1A Amp maximum
Fire relay contact rating - 30VDC 1A Amp maximum
K911110M8 6 lamp unit c/w mode select (surface)
Local fire relay contact rating - 30VDC 1A Amp maximum
and manual release
First stage contact rating - 30VDC 1A Amp maximum
K911110F8 6 lamp unit c/w mode select (flush) Second stage contact rating - 30VDC 1A Amp maximum
and manual release Extract contact rating - 30VDC 1A Amp maximum
K911113M8 10 lamp unit c/w mode select (surface) Zone quiescent current - 2mA maximum
and manual release Terminal capacity - 0.5mm² to 2.5mm² solid or stranded wire
Extinguishant
K911113F8 10 lamp unit c/w mode select (flush) Number of detectors per zone - Dependent on type (maximum 32)
and manual release Number of sounders per circuit - Dependent on type (max. 0.5A per sounder circuit)
Detection circuit end of line - 6K8 5% ½ Watt resistor
K91000M10 Extinguishant hold off switch (surface)
Monitored input end of line - 6K8 5% ½ Watt resistor
Sounder circuit end of line - 10K 5% ¼ Watt resistor
W911000W8 IP65 - 6 lamp unit (surface)
Extinguishant output end of line - 1N4004 Diode
W911100W8 IP65 - 6 lamp unit c/w mode select (surface) No. of detection circuits - 3
W911110W8 IP65 - 6 lamp unit c/w mode select (surface) No. of sounder circuits - 2 x 1st Stage, 1 x 2nd Stage
and manual release Extinguishant release output - Fused at 1 Amp
Extinguishant release delay - Adjustable 0 to 60 seconds (in 5 second steps)
W911113W8 IP65 - 10 lamp unit c/w mode select (surface)
Extinguishant release duration - Adjustable 60 to 300 seconds (in 5 second steps)
and manual release
SIL, AL, FLT, RST inputs - Switched -ve, max resistance 100 Ohms
Zone normal threshold - 8K ohms to 1K ohm
* Flush version not Kitemark Appoved Detector alarm threshold - 999 ohms to 400 ohms
Call point alarm threshold - 399 ohms to 100 ohms
Short circuit threshold - 99 ohms to 0 ohms
Head removal condition - 15.5 to 17.5 volts
Cabling - FP200 or equivalent
Monitored inputs normal threshold - 8K ohms to 1K ohm
Monitored inputs alarm threshold - 999 ohms to 100 ohms
Monitored inputs Short circuit threshold - 99 ohms to 0 ohms
Status unit/Ancillary board connection - Two wire RS485 connection
Status unit power output - Fused at 500mA with electronic fuse