BS-EN12094-1
KM 96761
SYNCRO XT+
Extinguishant Control Panel
Features
Approved to EN12094-1, EN54-2 and EN54-4
Countdown indicator shows time until release in
detection zones
16 seconds
to 4 extinguishant areas
Up
Mode select and manual release controls per area
Dual extinguishant outputs for each area (configurable as
Monitored remote manual release input
Main/Reserve)
Monitored remote hold input
First and second stage sounder outputs for each area
Monitored remote mode select (door interlock)
First and second stage volt free changeover contacts for input
each area
Monitored remote released pressure switch input
Released volt free contact per area
Monitored Abort input
Fault volt free contact per area
Serial connections for Sigma Si status units and
Programmable extinguishant delay ancillary boards. (K588)
Programmable output duration
Description
Syncro XT+ multi area addressable control panel enables extinguishing status indication and control units, or ancillary relay boards connected via a
systems to use all the features and benefits of the more sophisticated simple four-core cable.
detection techniques provided by addressable fire detectors. It also
includes other benefits of analogue addressable systems such as control With the addition of a Syncro network card, Syncro XT+ control panels can
of loop connected sounders, beacons and input/output modules. be networked to provide scalable extinguishing systems for
all sizes of installation.
With up to 16 zones of addressable detection over one or two loops it
ensures every detector can contribute to the extinguishant release.
The Syncro XT+ has up to four extinguishing areas and two releasing
outputs per area which can be controlled via simple coincidence detection
or via more complex cause and effects configured by the Loop Explorer
configuration programme.
Each extinguishant area has a comprehensive set of inputs and outputs and
is configurable via the Loop Explorer configuration programme.
All extinguishant areas may have up to seven serially connected Sigma Si
Panels
‘#’ - replace with ‘A’ for Apollo protocol or ‘H’ for Hochiki protocol.
IP Rating IP30
Colour - control panel & labels RAL 7047 light grey - satin
Weight 10kg
Power supply rating (1 & 2 area units) 3 Amps total including battery charge 28V +/- 2V
Power supply rating (3 & 4 area units) 4 Amps including battery charge 28V +/- 2V
Sigma XT+ module Aux 24V output Fused at 500mA with electronic fuse - 1 per extinguishant area
1st and 2nd stage Sounder outputs 21 to 28V DC Fused at 1A with electronic fuse
Local fire relay contact rating 5 to 30VDC 1A Amp maximum for each
Number of sounders per circuit Dependent on type and current consumption - typically 20+
No. of zones 16
SIL, AL, FLT, RST inputs Switched -ve, min resistance 0 ohms, max resistance 100 Ohms
Status unit/Ancillary board connection Two wire RS485 connection (EIA-485 specification)
Status unit power output 21 to 28V DC. Fused at 500mA with electronic fuse
Datasheet DS58/10/17
For further information visit www.kentec.co.uk
Kentec Electronics Ltd. reserves the right to alter the specification of its products from time to time without notice.
Although every effort has been made to ensure the accuracy of the information contained in this document it is not
warranted or represented by Kentec Electronics Ltd. to be a complete and up-to-date description.
PP2606/2021/Issue 2
Page 1 of 3
Discovery
Optical Smoke Detector
Technical data
All data is supplied subject to change without notice.
Specifications are typical at 24V, 25°C and 50% RH unless
otherwise stated.
Detection principle Photo-electric detection of light
scattered in a forward direction by
smoke particles
Chamber configuration Horizontal optical bench housing an
infrared emitter and sensor arranged
radially to detect forward scattered
light
Sensor Silicon PIN photo-diode
Emitter GaAlAs infra-red light emitting diode
Sampling frequency Once per second
Supply Wiring Two wire supply, polarity insensitive
Terminal functions L1 & L2 Supply in & out connections
+R Remote indicator positive
Product overview connection (internal 2.2 kΩ
resistance to positive)
Product Optical Smoke Detector
–R Remote indicator negative
Part No. 58000-600 connection (internal 2.2 kΩ
resistance to negative)
Digital Communication Discovery (XP95 and Digital communication Discovery, (XP95and CoreProtocol
CoreProtocol® compatible) compatible)
Modulation voltage 5–9 V peak to peak
Compliance Operating voltage 17 V - 28 V dc
Quiescent current 300 µA
Power-up surge current 1mA
Maximum power-up time 10 seconds
Alarm indicator Two clear 360º viewable light emitting
diode (LED) illuminating red in alarm.
Optional remote LED
Alarm current, LED 3.5 mA
illuminated
Product information Remote output Connects to positive line through
characteristics 4.5 kΩ (5 mA maximum)
The Discovery Optical Smoke Detector works on the light Clean-air analogue value 23 +4/-0
scatter principle and is ideal for applications where slow Alarm level analogue value 55
burning or smouldering fires are likely. Operating temperature -40°C to +70°C
• Responds well to slow burning, smouldering fires Storage temperature -40ºC to +80ºC
Humidity 0% to 95% RH (no condensation or
• Well suited for accommodation decks, passages and icing)
escape routes
Vibration, impact and shock EN54 - 7
• Unaffected by wind or atmospheric pressure Standards and approvals EN 54-7, CPR, LPCB, VdS, BOSEC,
SBSC, FG, CCMG, Kazaksthan
• Rejection of transient signals
Dimensions 100 mm diameter x 42 mm height
• Remote test feature (50 mm height with XPERT 7 base)
Weight 105 g
• Five EN54 approved response modes
(160 g with XPERT 7 mounting base)
Note: For system compatibility and feature support of this device, Materials Housing White flame-retardant polycarbonate
please refer to your chosen panel manufacturer. Terminals Nickel plated stainless steel
Operation Features
The Discovery Optical Smoke Detector has a white moulded Response modes
polycarbonate case with wind-resistant smoke inlets.
The indicator LEDs are colourless when the detector is in Discovery Optical Smoke Detectors can be operated in
quiescent state and red in alarm. Within the case is a printed any one of five EN54 approved response modes, which
circuit board which on one side has the light proof labyrinth can be selected through the fire control panel. Each mode
chamber with integral gauze surrounding the optical corresponds to a unique response behaviour, which is related
measuring system and on the other the address capture, to sensitivity to fire. Mode 1 gives a higher sensitivity to fire
signal processing and communications electronics. than Mode 5.
An infrared light emitting diode within its collimator is Discovery Optical Smoke Detector
arranged at an obtuse angle to the photo-diode. The photo- Response Times
diode has an integral daylight blocking filter.
Alarm Minimum
The IR LED emits a burst of collimated light every second. In Mode threshold dB/m time to alarm
clear air the photo-diode receives no light directly from the (%/m) (Seconds)
IR LED because of the angular arrangement and the chamber 1 1.4 0.08 5
baffles. When smoke enters the chamber it scatters light 2 1.4 0.08 30
from the emitter IR LED onto the photo-diode in an amount
related to the smoke characteristics and density. The photo- 3 2.1 0.12 5
diode signal is processed to provide an analogue value for 4 2.1 0.12 30
transmission when the detector is interrogated. 5 2.4 0.14 5
Discovery Optical Smoke Detector
schematic diagram Flashing LEDs
Discovery Optical Smoke Detectors have two integral LED
indicators, which can be illuminated at any time by the
Address buttons fire control panel to indicate detectors in alarm. A flashing
Optical chamber LED mode can also be programmed to activate each time a
detector is polled.
Photo-diode
PCB cover Remote test feature
The remote test feature is enabled from the fire control panel.
On receipt of the command signal from the fire control panel,
the detector is forced electrically into alarm. An analogue
value of 85 is returned to the fire control panel to indicate
that the detector is working correctly.
Features
Automatic synchronisation
Continuously rated
Dual M20 or 1/2"NPT clearance cable entries
Duplicate pluggable cable terminations – Class A
Ingress protection IP66 Type 3R/13
64 alarm tone frequencies and 4 remotely activated alarm stages
Available with custom tone configurations and frequencies
Diode polarized for use in supervised circuits
Ap p ro vals
UL: UL464, UL464A, UL1638, UL1638A
cUL: CSA C22.2 No 205-17
ULC: CAN/ULC-S525 & CAN/ULC-S526
UL EU: (EN54-3 & EN54-23) UL-EU-01154-CPR
CPR 305/2011: 2821-CPR-0109
EAC CU TR 043/2017: B.00291/21
EAC: RU D-GB.GA05.B.12595-20
RMRS Marine: No. 19.00193.278
CE, UKCA
S p ecif icatio n Part C o d es
A l ar m H or n : Var i ab l e: I d en ti f i er : D esc r i p ti on :
Maximum output: 110dB(A) @ 1 m ±3dB
Product type: AL100X Combined alarm horn sounder & Xenon strobe
[101dB(A) @ 10ft/3m ±3dB]
Voltage: DC012 12Vdc (11.5-14Vdc)
Nominal output: 102dB(A) @ 1m ±3dB
DC024 24Vdc (20-28Vdc)
[93dB(A) @ 10ft/3m ±3dB]
DC048 48Vdc (42-54Vdc)
No. of tones: 64 (UKOOA / PFEER compliant) AC024 24Vac 50/60Hz
AC048 48Vac 50/60Hz
No. of stages: 4
AC115 115Vac 50/60Hz
Volume control: -12dB(A) tone dependent AC230 230Vac 50/60Hz
Effective range: 38m/124ft @ 1KHz Back box/cable M Back box with mounting lugs – 2 x M20,
entries: [e] 1/2"NPT clearance
In rush: 636mA within 4.0ms @ 24Vdc
Stopping plug A ABS
Stage switching: Negative (common positive)
material: [m]
Xen on Str ob e:
Equip. tag/Duty 0 No equip. tag or Duty label
Energy: 5 Joules(5Ws) label: [s] 1 316 (A4) St/St Equip. tag/Duty label
Flash rate: 1Hz (60 fpm) 2 Metalised Polyester Equip. tag/Duty label
DC units: 1.5Hz (90 fpm) & Double strike Product version: A UL/cUL, CPR, RMRS, EAC, CE, UKCA
Peak Candela: 500,000 cd – calculated from energy (J) [v]
Effective cd: 250 cd – calculated from energy (J) Product option: 1 Standard product
[o] X Custom configuration – contact E2S
Peak Candela: 86,935 cd* – measured ref. to I.E.S. Z Custom alarm tone software – contact E2S
Effective cd: 200 cd* – measured ref. to I.E.S. Enclosure: [x] R Red (RAL 3000)
Tube life: Emissions may reduce to 70% after 8 million flashes G Grey (RAL7038)
W White
Gen er al :
Ingress protection: IP66 Type 3R/13 Lens colour: [y] A Amber
B Blue
Enclosure: High impact UL94 V0 & 5VA FR ABS/PC C Clear
Lens colour filter: Field replaceable UV stable PC G Green
M Magenta
Terminals: 0.5 – 2.5mm² (20-14 AWG) R Red
Line monitoring: Diode polarized for use in supervised circuits Y Yellow
Discovery
Optical/Heat Multisensor Detector
Technical data
All data is supplied subject to change without notice. Specifications
are typical at 24V, 25°C and 50% RH unless otherwise stated.
Detection principle Smoke: Photo-electric detection of light
scattered by smoke particles
Heat: Temperature-dependent resistance
Supply Wiring Two wire supply, polarity insensitive
Terminal functions L1 & L2 Supply in & out connections
+R Remote indicator positive
connection (internal 2.2kΩ
resistance to positive)
–R Remote indicator negative
connection (internal 2.2 kΩ
resistance to negative)
Operating voltage 17 - 28 V dc
Communication protocol Discovery (XP95 and CoreProtocol
compatible)
Modulation voltage 5 –9 V peak to peak
Product overview Quiescent current 400 µA
MANAGEMENT
SYSTEMS
MANAGEMENT
SYSTEMS
PRODUCT
CERTIFICATION
© Apollo Fire Detectors Ltd 2019
Assessed to ISO 9001:2015 Assessed to ISO 14001:2015 Cert/LPCB ref. 010
Cert/LPCB ref. 010 Cert/LPCB ref. 010 EMS
PP2609/2019/Issue1
Page 2 of 4
Operation Features
The way in which the signals from the two sensors are Response modes
combined depends on the response mode selected. The five
modes provide response behaviour which incorporates pure Discovery Optical/Heat Muitisensor detectors can be
heat detection, pure smoke detection and a combination of operated in any one of five EN54 approved response modes,
both. The multisensor detector is therefore useful over the which can be selected through the fire control panel. Each
widest range of applications. mode corresponds to a unique response behaviour, which is
related to sensitivity to fire. Mode 1 gives a higher sensitivity
The signals from the optical smoke sensing element and to fire than Mode 5.
the temperature sensor are independent and represent
the smoke level and the air temperature respectively in Discovery Optical/Heat Multisensor detector
the vicinity of the detector. The detectors micro-controller operating modes
processes the two signals according to the mode selected. Smoke Minimum
sensitivity Temp
When the detector is operating as a multisensor (i.e. modes Response time to
Mode (grey smoke) sensitivity
type alarm
1, 3 and 4) the temperature signal processing extracts only (relative)
%/m dB/m (seconds)
rate-of-rise information for combination with the optical
signal. 1 1.1 0.06 High Multisensor 20
2 2.1 0.12 Not set to Optical 30
In these modes the detector will not respond to a slow heat response
temperature increase - even if the temperature reaches
3 2.8 0.16 Low Multisensor 20
a high level. A large, sudden change in temperature can,
however, cause an alarm without the presence of smoke if 4 4.2 0.24 2.1 Multisensor 20
sustained for 20 seconds. 5 † No response See Mode 5 †
Heat A1R 15
to smoke
Additional heat sensor information
Characteristics of the response modes
The Discovery Optical/ Heat Multisensor detector incorporates
additional temperature information intended for use in signal The processing algorithms in modes 1 to 4 incorporate drift
processing. compensation. The characteristics of the five response
modes listed above are summarised as follows:
Temperature data can be read separately by the control
panel* and used to validate an alarm signalled by the Mode 1 has very high smoke sensitivity combined with high
multisensor analogue value. An example of this would be heat sensitivity. This gives a high overall sensitivity to both
a high multisensor analogue value not accompanied by an smouldering and flaming fires.
increase in heat: this would indicate that an agent other than Mode 2 has a smoke sensitivity similar to that of a normal
smoke, e.g. steam, had caused the high analogue value. optical smoke detector. This mode is therefore equivalent
Electrical description to a standard optical detector. It is suitable for applications
in which wide temperature changes occur under normal
The Discovery Optical/ Heat Multisensor detector is designed conditions.
to be connected to a two wire loop circuit carrying both data
and a 17 V to 28 V dc supply. The detector is connected to the Mode 3 has moderate smoke sensitivity combined with a
incoming and outgoing supply via terminals L1 and L2 in the moderate sensitivity to heat. This combination is considered
mounting base. A remote LED indicator requiring not more the optimum for most general applications since it offers
than 4 mA at 5 V may be connected between the +R and -R good response to both flaming and smouldering fires.
terminals. An earth connection terminal is also provided. Mode 4 has lower than normal smoke sensitivity combined
with high heat sensitivity. This makes it suitable for
applications in which a certain amount of fumes or smoke is
considered normal.
Mode 5† has no smoke sensitivity at all but gives a pure heat
detector response meeting the response time requirements
for a Class A1R detector in the European Standard EN 54-
5. In this mode the detector will respond to slowly changing
temperatures and has a ‘fixed temperature’ alarm threshold
at 58OC. The analogue value in this mode will give the
approximate air temperature over the range 15OC to 55ºC.
In Mode 5 the smoke sensor is still active though it does not
contribute to the analogue signal. As a consequence, if the
detector is used in a dirty or smoky environment the optical
sensor drift flag may be activated in the heat only mode.
PP2609/2019/Issue1
Page 3 of 4
Notes:
Discovery Optical/Heat Multisensor detector
1. *This applies only to the control panels that have been dimensions
programmed to read the additional information.
Address Card 38531-771
2. In-situ testing of a multisensor detector should be done supplied loose with base
4.50
9.00
3. If the multisensor detector is to be used in Mode 5, heat
detector spacing/coverage should be applied.
Flashing LEDs
Fixing slot details
72.00
LF20W is an audio warning panel, available in different models and suited for any emergency situation such as fire,
flooding, gas leaks, etc., where audio information is needed. Its special design, very pleasant is particularly suited for
hotels, shops, malls and cinemas.
2852
General Specifications
Product code LF20W (Wall mount model) Sound power (min) 79 dB(A) @ 1m
Material ABS + PMMA Sound power (max) 92,3 dB(A) @ 1m
Installation Wall mount Buzzer frequency 2,8Khz
Nominal Voltage: 24 Vd.c. Sound model Pulsed, 1Hz (500ms on,
Absorption 21mA (average) 500ms off)
Protection Class IP21C*
Type of connection With terminals
Dimensions with backbox 292x130x55mm (L x H x P)
Operating temperature Da -10°C a +55°C
www.synaps-technology.com
info@synaps-technology.com
Synaps Technology S.r.l. – Via pietraferrata 9/1, 34147 – Trieste (Italy) 2020-10-01, TSD-FOP00-21A
Optical / Acoustical Indicators
Assembly instructions
- Make four holes into the wall to fit the holders (1, fig 2)
- Fix the mounting box with the four screws (2, fig 2)
- Connect the power supply to the terminals (Figure 1)
- If the sounder is not needed, connect jumper SILENT (Figure 2)
- Fix the central part to the mounting box with the four screws (3, fig 2)
- Hook the cover and screw it (4, fig 2)
Figure 1 Figure 2
www.synaps-technology.com
info@synaps-technology.com
Synaps Technology S.r.l. – Via pietraferrata 9/1, 34147 – Trieste (Italy) 2020-10-01, TSD-FOP00-21A
JE-H(St)H FE180 E30-E90 JE-H(St)H ..Bd FE180 E30-E90
J - instalacijski kabel
FE180: IEC 60331, DIN VDE 0472 dio 814
E30-E90: DIN VDE 4102 dio 12
E - za elektroniku
H - bezhalogena izolacija
kabeli bez halogena
H - bezhalogeni plašt
..Bd - použen u svežnjevima
FE180 - očuvanje izolacijskih svojstava kabela u požaru 180 minuta
E30-E90 - očuvanje električne funkcionalnosti sustava u požaru između
30 i 90 minuta, ovisno o tehnici instalacije
164
09
Dimenzije - broj žila x Vanjski promjer Debljina izolacije Požarno opterećenje Težina Cu Težina kabela Pakovanje*
promjer vodiča
nazivno približno nazivno približno
N x mm mm mm kWh/m kg/km kg/km
1 x 2 x 0,8 5,5 0,3 0,095 15 40 REZ
2 x 2 x 0,8 6 0,3 0,123 25 56 REZ
4 x 2 x 0,8 8,7 0,3 0,21 45 96 REZ
8 x 2 x 0,8 13,7 0,3 0,52 85 218 REZ
12 x 2 x 0,8 14,6 0,3 0,58 126 270 REZ
16 x 2 x 0,8 16 0,3 0,69 166 337 REZ
20 x 2 x 0,8 18 0,3 0,80 206 403 REZ
32 x 2 x 0,8 21,8 0,3 1,02 326 570 REZ
40 x 2 x 0,8 25,3 0,3 1,38 407 739 REZ
52 x 2 x 0,8 27,6 0,3 1,59 529 906 REZ
*) Pakovanje: REZ = kabel je u različitim duljinama na bubnju ili špuli i moguće ga je rezati na željenu duljinu
165
EQPT SPECIFICATION / DATA SHEET (5)
1 REJECTED
PROJECT: K371
EMPLOYER INA Industrija Nafte, d.d. 3 APPROVED WITHOUT COMMENTS
PROJECT TITLE Rijeka Refinery Upgrade Project
P.O. N° 200-OR-EG-21211