(3.6/6 KV 18/30 KV) Cu/XLPE/CTS/SWA/PVC (N2XSEYRY) : SNI IEC 60502-2 / IEC 60502-2
(3.6/6 KV 18/30 KV) Cu/XLPE/CTS/SWA/PVC (N2XSEYRY) : SNI IEC 60502-2 / IEC 60502-2
(3.6/6 KV 18/30 KV) Cu/XLPE/CTS/SWA/PVC (N2XSEYRY) : SNI IEC 60502-2 / IEC 60502-2
Copper conductor
Conductor screen
XLPE insulation
Insulation screen
Identification of core
(Red, Yellow, Blue by colored tape)
Copper tape screen
Filler (Polyprophylene yarn, or
extruded filler upon request)
Special application upon request :
* Available product in accordance to SPLN, JIS, BS, Binding tape (manufacturer's option )
ICEA/NEMA, AS standard or other requirement. PVC Separation sheath
* Flame retardant test acc. to IEC 60332-3 Cat. A, B or C.
* Longitudinally Water Blocking characteristic. Galvanized Round Steel Wire Armour
* Anti termite and anti rodent performance.
* Tin coated Copper conductor. Binding tape (manufacturer's option)
* Copper wire screen.
* Polyethylene/Low Smoke Free Halogen sheath. PVC sheath (Red or Black color)
CONSTRUCTION DATA
No. of Core - 3 3 3 3 3 3 3 3 3 3
Nom. Cross-section Area mm² 25 35 50 70 95 120 150 185 240 300
No. of Wire - 7 7 19 19 19 37 37 37 37 61
1)
Diameter of Conductor (approx.) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7
Nom. Thickness of Insulation mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.8
Nom. Thickness of Copper tape mm 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085
Nom. Thickness of Separation Sheath mm 1.2 1.3 1.3 1.4 1.4 1.5 1.6 1.6 1.7 1.8
Nom. Diameter of Round Steel Wire mm 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.15 3.15
Nom. Thickness of Outer Sheath mm 2.3 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.3 3.5
Overall Diameter of Cable mm 41.0 44.5 47.0 50.5 55.0 58.5 62.0 65.5 71.0 79.0
Weight of Cable (approx.) kg/km 2970 3810 4360 5265 6385 7360 8485 9775 11905 15090
ELECTRICAL DATA
AC Voltage Test for 5 min. kV 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5
Partial Discharge Test at max. 10pC kV 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23 6.23
DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601
AC Resistance at 90°C Ω/km 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0981 0.0792
Insulation Resistance at 20°C MΩ.km 2500 2000 2000 1500 1500 1500 1500 1500 1000 900
Capacitance µF/km 0.266 0.300 0.328 0.373 0.427 0.463 0.502 0.550 0.593 0.615
Inductance mH/km 0.360 0.340 0.326 0.309 0.294 0.285 0.277 0.270 0.263 0.258
Reactance Ω/km 0.113 0.107 0.102 0.0970 0.0922 0.0895 0.0871 0.0847 0.0825 0.0810
2)
Current Carrying Capacity :
- Buried direct in ground at 20°C A 129 154 181 220 263 298 332 374 431 482
- In a Buried duct at 20°C A 112 134 158 194 232 264 296 335 387 435
- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599
Short circuit current rating at 1 sec.
kA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90
(approx.)
1)
Diameter compacted shape
2)
Thermal Resistivity of soil : 1.5°K.m/W, Depth of laying : 0.8 m
Sumi Indo Kabel
Thermal Resistivity of earthenware ducts : 1.2 K.m/W D-1 Katalog Kabel Tegangan Menengah
6/10 (12) kV Cu/XLPE/CTS/SWA/PVC ( N2XSEYRY ) 3 x ( 25 - 300 ) mm²
CONSTRUCTION DATA
No. of Core - 3 3 3 3 3 3 3 3 3 3
Nom. Cross-section Area mm² 25 35 50 70 95 120 150 185 240 300
No. of Wire - 7 7 19 19 19 37 37 37 37 61
1)
Diameter of Conductor (approx.) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7
Nom. Thickness of Insulation mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
Nom. Thickness of Copper tape mm 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085
Nom. Thickness of Separation Sheath mm 1.3 1.3 1.4 1.5 1.5 1.6 1.6 1.7 1.8 1.9
Nom. Diameter of Round Steel Wire mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.15 3.15
Nom. Thickness of Outer Sheath mm 2.5 2.6 2.7 2.8 2.9 3.0 3.1 3.2 3.4 3.6
Overall Diameter of Cable mm 46.0 48.5 51.5 55.0 59.5 62.5 65.5 69.5 76.5 82.0
Weight of Cable (approx.) kg/km 3755 4280 4870 5800 6905 7915 8965 10305 13260 15615
ELECTRICAL DATA
AC Voltage Test for 5 min. kV 21 21 21 21 21 21 21 21 21 21
Partial Discharge Test at max. 10pC kV 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38
DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601
AC Resistance at 90°C Ω/km 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0980 0.0791
Insulation Resistance at 20°C MΩ.km 3000 2500 2500 2000 2000 2000 1500 1500 1500 1500
Capacitance µF/km 0.211 0.236 0.257 0.291 0.330 0.357 0.386 0.421 0.468 0.518
Inductance mH/km 0.384 0.632 0.347 0.328 0.311 0.302 0.293 0.284 0.274 0.266
Reactance Ω/km 0.121 0.114 0.109 0.103 0.0977 0.0947 0.0920 0.0892 0.0862 0.0836
2)
Current Carrying Capacity :
- Buried direct in ground at 20°C A 129 154 181 220 263 298 332 374 431 482
- In a Buried duct at 20°C A 112 134 158 194 232 264 296 335 387 435
- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599
Short circuit current rating at 1 sec.
kA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90
(approx.)
1)
Diameter compacted shape
2)
Thermal Resistivity of soil : 1.5°K.m/W, Depth of laying : 0.8 m
Thermal Resistivity of earthenware ducts : 1.2 K.m/W
CONSTRUCTION DATA
No. of Core - 3 3 3 3 3 3 3 3 3 3
Nom. Cross-section Area mm² 25 35 50 70 95 120 150 185 240 300
No. of Wire - 7 7 19 19 19 37 37 37 37 61
1)
Diameter of Conductor (approx.) mm 5.9 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7
Nom. Thickness of Insulation mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
Nom. Thickness of Copper tape mm 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085
Nom. Thickness of Separation Sheath mm 1.4 1.4 1.5 1.5 1.6 1.7 1.7 1.8 1.9 2.0
Nom. Diameter of Round Steel Wire mm 2.5 2.5 2.5 2.5 2.5 2.5 3.15 3.15 3.15 3.15
Nom. Thickness of Outer Sheath mm 2.6 2.7 2.8 2.9 3.1 3.2 3.3 3.4 3.6 3.8
Overall Diameter of Cable mm 51.0 54.0 56.5 60.0 64.5 67.5 72.0 76.0 81.5 87.5
Weight of Cable (approx.) kg/km 4335 4840 5440 6380 7575 8540 10455 11885 14150 16450
ELECTRICAL DATA
AC Voltage Test for 5 min. kV 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5
Partial Discharge Test at max. 10pC kV 15.05 15.05 15.05 15.05 15.05 15.05 15.05 15.05 15.05 15.05
DC Resistance at 20°C Ω/km 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601
AC Resistance at 90°C Ω/km 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0979 0.0789
Insulation Resistance at 20°C MΩ.km 3500 3000 3000 2500 2500 2000 2000 2000 1500 1500
Capacitance µF/km 0.173 0.192 0.208 0.234 0.264 0.284 0.307 0.333 0.369 0.407
Inductance mH/km 0.411 0.387 0.370 0.350 0.331 0.320 0.310 0.301 0.289 0.280
Reactance Ω/km 0.129 0.121 0.116 0.110 0.104 0.101 0.0975 0.0944 0.0909 0.0879
2)
Current Carrying Capacity :
- Buried direct in ground at 20°C A 129 154 181 220 263 298 332 374 431 482
- In a Buried duct at 20°C A 112 134 158 194 232 264 296 335 387 435
- In Air at 30°C A 143 172 205 253 307 352 397 453 529 599
Short circuit current rating at 1 sec.
kA 3.58 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90
(approx.)
1)
Diameter compacted shape
2)
Thermal Resistivity of soil : 1.5°K.m/W, Depth of laying : 0.8 m
Sumi Indo Kabel
Thermal Resistivity of earthenware ducts : 1.2 K.m/W D-2 Katalog Kabel Tegangan Menengah
12 / 20 ( 24 ) kV Cu/XLPE/CTS/SWA/PVC ( N2XSEYRY ) 3 x ( 35 - 300 ) mm²
CONSTRUCTION DATA
No. of Core - 3 3 3 3 3 3 3 3 3
Nom. Cross-section Area mm² 35 50 70 95 120 150 185 240 300
No. of Wire - 7 19 19 19 37 37 37 37 61
1)
Diameter of Conductor (approx.) mm 7.1 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7
Nom. Thickness of Insulation mm 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
Nom. Thickness of Copper tape mm 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085
Nom. Thickness of Separation Sheath mm 1.5 1.6 1.6 1.7 1.8 1.8 1.9 2.0 2.1
Nom. Diameter of Round Steel Wire mm 2.5 2.5 2.5 2.5 3.15 3.15 3.15 3.15 3.15
Nom. Thickness of Outer Sheath mm 2.9 3.0 3.1 3.2 3.4 3.5 3.6 3.8 3.9
Overall Diameter of Cable mm 59.0 62.0 65.0 69.5 74.0 77.5 81.5 87.0 92.0
Weight of Cable (approx.) kg/km 5495 6120 7055 8215 10030 11255 12715 14985 17345
ELECTRICAL DATA
AC Voltage Test for 5 min. kV 42 42 42 42 42 42 42 42 42
Partial Discharge Test at max. 10pC kV 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76 20.76
DC Resistance at 20°C Ω/km 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601
AC Resistance at 90°C Ω/km 0.668 0.494 0.342 0.247 0.196 0.159 0.128 0.0978 0.0788
Insulation Resistance at 20°C MΩ.km 3500 3500 3000 2500 2500 2500 2000 2000 2000
Capacitance µF/km 0.165 0.178 0.199 0.224 0.240 0.258 0.279 0.309 0.339
Inductance mH/km 0.408 0.391 0.369 0.349 0.337 0.327 0.316 0.303 0.293
Reactance Ω/km 0.128 0.123 0.116 0.109 0.106 0.103 0.0991 0.0953 0.0920
2)
Current Carrying Capacity :
- Buried direct in ground at 20°C A 154 181 220 263 298 332 374 431 482
- In a Buried duct at 20°C A 134 158 194 232 264 296 335 387 435
- In Air at 30°C A 172 205 253 307 352 397 453 529 599
Short circuit current rating at 1 sec.
kA 5.01 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90
(approx.)
1)
Diameter compacted shape
2)
Thermal Resistivity of soil : 1.5°K.m/W, Depth of laying : 0.8 m
Thermal Resistivity of earthenware ducts : 1.2 K.m/W
CONSTRUCTION DATA
No. of Core - 3 3 3 3 3 3 3 3
Nom. Cross-section Area mm² 50 70 95 120 150 185 240 300
No. of Wire - 19 19 19 37 37 37 37 61
1)
Diameter of Conductor (approx.) mm 8.1 9.7 11.6 12.9 14.3 16.0 18.3 20.7
Nom. Thickness of Insulation mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
Nom. Thickness of Copper tape mm 0.085 0.085 0.085 0.085 0.085 0.085 0.085 0.085
Nom. Thickness of Separation Sheath mm 1.8 1.8 1.9 2.0 2.0 2.1 2.2 2.3
Nom. Diameter of Round Steel Wire mm 3.15 3.15 3.15 3.15 3.15 3.15 3.15 3.15
Nom. Thickness of Outer Sheath mm 3.4 3.5 3.7 3.8 3.9 4.0 4.2 4.3
Overall Diameter of Cable mm 75.0 78.5 83.0 86.5 89.5 93.5 99.0 105.0
Weight of Cable (approx.) kg/km 8520 9570 10930 12070 13255 14845 17185 19685
ELECTRICAL DATA
AC Voltage Test for 5 min. kV 63 63 63 63 63 63 63 63
Partial Discharge Test at max. 10pC kV 31.14 31.14 31.14 31.14 31.14 31.14 31.14 31.14
DC Resistance at 20°C Ω/km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601
AC Resistance at 90°C Ω/km 0.494 0.342 0.247 0.196 0.159 0.127 0.0976 0.0785
Insulation Resistance at 20°C MΩ.km 4000 4000 3500 3500 3000 3000 2500 2500
Capacitance µF/km 0.138 0.153 0.170 0.182 0.194 0.209 0.229 0.250
Inductance mH/km 0.433 0.408 0.385 0.372 0.360 0.347 0.333 0.318
Reactance Ω/km 0.136 0.128 0.121 0.117 0.113 0.109 0.105 0.100
2)
Current Carrying Capacity :
- Buried direct in ground at 20°C A 181 220 263 298 332 374 431 482
- In a Buried duct at 20°C A 158 194 232 264 296 335 387 435
- In Air at 30°C A 205 253 307 352 397 453 529 599
Short circuit current rating at 1 sec.
kA 7.15 10.01 13.59 17.16 21.45 26.46 34.32 42.90
(approx.)
1)
Diameter compacted shape
2)
Thermal Resistivity of soil : 1.5°K.m/W, Depth of laying : 0.8 m
Sumi Indo Kabel
Thermal Resistivity of earthenware ducts : 1.2 K.m/W D - 3
Katalog Kabel Tegangan Menengah