TECK90: XLPE/PVC/AIA/PVC, Control, Armored 600 V, CSA TECK90, Multi-Conductor, 14 AWG
TECK90: XLPE/PVC/AIA/PVC, Control, Armored 600 V, CSA TECK90, Multi-Conductor, 14 AWG
TECK90: XLPE/PVC/AIA/PVC, Control, Armored 600 V, CSA TECK90, Multi-Conductor, 14 AWG
November, 2014
TECK90
XLPE/PVC/AIA/PVC, Control, Armored
600 V, CSA TECK90, Multi-Conductor, 14 AWG
Features:
• Rated at 90˚C wet or dry
• Excellent crush, oil and chemical resistance
• Provides long service life
• Meets cold bend and impact tests at -40˚C
Compliances:
Industry Compliances:
• CSA Standard C22.2 No. 131 and No. 174
Flame Test Compliances:
Product Construction: Overall Jacket: • CSA FT1 and FT4
• Lead-free, ACID-FLAME-CHECK ✓✓ ® flame- • IEEE 383 (70,000 BTU/hr)
Conductors: retardant, moisture- and sunlight-resistant • UL 1581 (70,000 BTU/hr)
• 14 AWG bare copper Class B compressed Polyvinyl Chloride (PVC), black • IEEE 1202 (70,000 BTU/hr) CSA FT4
concentric round to ASTM B8 • ICEA T-30-520 (70,000 BTU/hr)
Print: Other Compliances:
Insulation: • GENERAL CABLE ® ACID-FLAME-CHECK ✓✓ ®
• Cross-linked Polyethylene (XLPE), Type RW90 • Hazardous Location Rating: HL
AG14 FT1 FT4 HL TECK90 XLPE (-40˚C)#/C • EPA 40 CFR, Part 261 for leachable lead
• Color-coded: 1 to 4 conductors—black, white, SIZE (14 AWG) 600 V DIR BUR SUN RES CSA
red and blue; over 4 conductors—per ICEA content per TCLP method
MONTH-YEAR SEQUENTIAL LENGTH MARK • OSHA Acceptable
Method 4, individual conductors colored black
with conductor number surface printed in Options: • RoHS Compliant
contrasting ink • Galvanized Steel Interlocked Armor (GSIA) Packaging:
Ground (Bonding) Conductor: Applications: • For Canadian customers, lengths are provided
• The conductor consists of one uninsulated • For exposed and concealed wiring in dry, damp on returnable wood or steel reels that require a
stranded bare copper conductor or wet locations deposit. Extra charges apply for lagging, pulling
• For use in ventilated, non-ventilated and ladder- eyes, paralleling and plexing
Inner Jacket: type cable trays in dry, damp or wet locations • For U.S. customers, material cut to length and
• Lead-free, flame-retardant, moisture- and • For direct earth burial (with protection as required shipped on non-returnable wood reels, while
sunlight-resistant Polyvinyl Chloride (PVC), black by inspection authority) lengths in excess of 10,000 lbs. are provided on
returnable steel reels that require a deposit. Extra
Armor: • For wiring in all hazardous locations when used
charges apply for cuts less than 1000 ft., lagging,
• Aluminum Interlocked Armor (AIA) with certified HL cable glands
pulling eyes, paralleling and plexing
Phone: 888-593-3355
www.generalcable.com
SPEC 8050
November, 2014
TECK90
XLPE/PVC/AIA/PVC, Control, Armored
600 V, CSA TECK90, Multi-Conductor, 12 AWG
Product Construction:
Conductor:
• 12 AWG bare copper Class B compressed
concentric round to ASTM B8
Insulation:
• Cross-linked Polyethylene (XLPE), Type RW90
• Color-coded: 1 to 4 conductors—black, white,
red and blue; over 4 conductors—per ICEA
Method 4, individual conductors colored black Options: Compliances (cont'd.):
with conductor number surface printed in
• Galvanized Steel Interlocked Armor (GSIA) Flame Test Compliances:
contrasting ink
• CSA FT1 and FT4
Ground (Bonding) Conductor: Applications: • IEEE 383 (70,000 BTU/hr)
• For exposed and concealed wiring in dry, damp • UL 1581 (70,000 BTU/hr)
• The conductor consists of one uninsulated
or wet locations • IEEE 1202 (70,000 BTU/hr) CSA FT4
stranded bare copper conductor
• For use in ventilated, non-ventilated and ladder- • ICEA T-30-520 (70,000 BTU/hr)
Inner Jacket: type cable trays in dry, damp or wet locations Other Compliances:
• Lead-free, flame-retardant, moisture- and • For direct earth burial (with protection as required • Hazardous Location Rating: HL
sunlight-resistant Polyvinyl Chloride (PVC), black by inspection authority) • EPA 40 CFR, Part 261 for leachable lead
• For wiring in all hazardous locations when used content per TCLP method
Armor: with certified HL cable glands
• Aluminum Interlocked Armor (AIA) • OSHA Acceptable
Features: • RoHS Compliant
Overall Jacket: • Rated at 90˚C wet or dry
• Lead-free, ACID-FLAME-CHECK ✓✓ ® flame- Packaging:
• Excellent crush, oil and chemical resistance • For Canadian customers, lengths are provided
retardant, moisture- and sunlight-resistant • Provides long service life
Polyvinyl Chloride (PVC), black on returnable wood or steel reels that require a
• Meets cold bend and impact tests at -40˚C deposit. Extra charges apply for lagging, pulling
Print: Compliances: eyes, paralleling and plexing
• GENERAL CABLE® ACID-FLAME-CHECK ✓✓ ® Industry Compliances: • For U.S. customers, material cut to length and
AG14 FT1 FT4 HL TECK90 XLPE (-40˚C)#/C • CSA Standard C22.2 No. 131 and No. 174 shipped on non-returnable wood reels, while
SIZE (12 AWG) 600 V DIR BUR SUN RES CSA lengths in excess of 10,000 lbs. are provided on
MONTH-YEAR SEQUENTIAL LENGTH MARK returnable steel reels that require a deposit. Extra
charges apply for cuts less than 1000 ft., lagging,
pulling eyes, paralleling and plexing
Phone: 888-593-3355
www.generalcable.com
SPEC 8075
November, 2014
TECK90
XLPE/PVC/AIA/PVC, Control, Armored
600 V, CSA TECK90, Multi-Conductor, 10 AWG
Features:
• Rated at 90˚C wet or dry
• Excellent crush, oil and chemical resistance
• Provides long service life
• Meets cold bend and impact tests at -40˚C
Compliances:
Industry Compliances:
• CSA Standard C22.2 No. 131 and No. 174
Flame Test Compliances:
Product Construction: Armor: • CSA FT1 and FT4
• Aluminum Interlocked Armor (AIA) • IEEE 383 (70,000 BTU/hr)
Conductor: • UL 1581 (70,000 BTU/hr)
• 10 AWG bare copper Class B compressed Overall Jacket: • IEEE 1202 (70,000 BTU/hr) CSA FT4
concentric round to ASTM B8 • Lead-free, ACID-FLAME-CHECK ✓✓® flame- • ICEA T-30-520 (70,000 BTU/hr)
retardant, moisture- and sunlight-resistant Other Compliances:
Insulation: Polyvinyl Chloride (PVC), black
• Cross-linked Polyethylene (XLPE), Type RW90 • Hazardous Location Rating: HL
• Color-coded: 1 to 4 conductors—black, white, Print: • EPA 40 CFR, Part 261 for leachable lead
red and blue; over 4 conductors—per ICEA • GENERAL CABLE® ACID-FLAME-CHECK ✓✓® content per TCLP method
Method 4, individual conductors colored black AG14 FT1 FT4 HL TECK90 XLPE (-40˚C)#/C • OSHA Acceptable
with conductor number surface printed in SIZE (10 AWG) 600 V DIR BUR SUN RES CSA • RoHS Compliant
contrasting ink MONTH-YEAR SEQUENTIAL LENGTH MARK Packaging:
Ground (Bonding) Conductor: Options: • For Canadian customers, lengths are provided
• The conductor consists of one uninsulated • Galvanized Steel Interlocked Armor (GSIA) on returnable wood or steel reels that require a
stranded bare copper conductor deposit. Extra charges apply for lagging, pulling
• Color-coded per ICEA Method 4; individual
Applications: eyes, paralleling and plexing
conductors colored black with conductor number • For exposed and concealed wiring in dry, damp • For U.S. customers, material cut to length and
surface printed in contrasting ink or wet locations shipped on non-returnable wood reels, while
• For use in ventilated, non-ventilated and ladder- lengths in excess of 10,000 lbs. are provided on
Inner Jacket: type cable trays in dry, damp or wet locations returnable steel reels that require a deposit. Extra
• Lead-free, flame-retardant, moisture- and • For direct earth burial (with protection as required charges apply for cuts less than 1000 ft., lagging,
sunlight-resistant Polyvinyl Chloride (PVC), black by inspection authority) pulling eyes, paralleling and plexing
• For wiring in all hazardous locations when used
with certified HL cable glands
Phone: 888-593-3355
www.generalcable.com
SPEC 8100
November, 2014
TECK90
XLPE/PVC/AIA/PVC, Power, Armored
1000 V, CSA TECK90, Single Conductor
Product Construction:
Conductor:
• 6 AWG thru 1000 kcmil bare copper compact
Class B strand
Insulation:
• Cross-linked Polyethylene (XLPE), Type RW90
• Color-coded: black
Ground (Bonding) Conductor:
• The conductor is a concentric serving of solid Applications: Compliances (cont'd.):
bare copper wires applied over the insulation • For exposed and concealed wiring in dry, damp Flame Test Compliances:
or wet locations • CSA FT1 and FT4
Inner Jacket: • For use in ventilated, non-ventilated and ladder- • IEEE 383 (70,000 BTU/hr)
• Lead-free, flame-retardant, moisture- and type cable trays in dry, damp or wet locations • UL 1581 (70,000 BTU/hr)
sunlight-resistant Polyvinyl Chloride (PVC), black • For direct earth burial (with protection as required • IEEE 1202 (70,000 BTU/hr) CSA FT4
Armor: by inspection authority) • ICEA T-30-520 (70,000 BTU/hr)
• Aluminum Interlocked Armor (AIA) • For wiring in all hazardous locations when used Other Compliances:
with certified HL cable glands • Hazardous Location Rating: HL
Overall Jacket: • EPA 40 CFR, Part 261 for leachable lead
• Lead-free, ACID-FLAME-CHECK ✓✓® flame- Features: content per TCLP method
retardant, moisture- and sunlight-resistant • Rated at 90˚C wet or dry • OSHA Acceptable
Polyvinyl Chloride (PVC), black • Excellent crush, oil and chemical resistance • RoHS Compliant
• Provides long service life
Print: • Cost effective alternative to installations in conduit Packaging:
• GENERAL CABLE ® ACID-FLAME-CHECK ✓✓® • Meets cold bend and impact tests at -40˚C • For Canadian customers, lengths are provided
AG14 FT1 FT4 HL TECK90 XLPE (-40˚C)1/C on returnable wood or steel reels that require a
SIZE (AWG OR KCMIL) 1000 V DIR BUR
Compliances: deposit. Extra charges apply for lagging, pulling
SUN RES CSA MONTH-YEAR SEQUENTIAL Industry Compliances: eyes, paralleling and plexing
LENGTH MARK • CSA Standard C22.2 No. 131 and No. 174 • For U.S. customers, material cut to length and
shipped on non-returnable wood reels, while
Options: lengths in excess of 10,000 lbs. are provided on
• Galvanized Steel Interlocked Armor (GSIA) returnable steel reels that require a deposit. Extra
charges apply for cuts less than 1000 ft., lagging,
pulling eyes, paralleling and plexing
Phone: 888-593-3355
www.generalcable.com
SPEC 8125
November, 2014
TECK90
XLPE/PVC/AIA/PVC, Control and Power, Armored
1000 V, CSA TECK90, Two Conductor
Features:
• Rated at 90˚C wet or dry
• Excellent crush, oil and chemical resistance
• Provides long service life
• Meets cold bend and impact tests at -40˚C
Compliances:
Industry Compliances:
• CSA Standard C22.2 No. 131 and No. 174
Flame Test Compliances:
Product Construction: Overall Jacket: • CSA FT1 and FT4
• Lead-free, ACID-FLAME-CHECK ✓✓® flame- • IEEE 383 (70,000 BTU/hr)
Conductor: retardant, moisture- and sunlight-resistant • UL 1581 (70,000 BTU/hr)
• 14 AWG thru 8 AWG bare copper Class B Polyvinyl Chloride (PVC), black • IEEE 1202 (70,000 BTU/hr) CSA FT4
compressed concentric round to ASTM B8 • ICEA T-30-520 (70,000 BTU/hr)
• 6 AWG thru 1000 kcmil bare copper compact Print: Other Compliances:
Class B strand • GENERAL CABLE® ACID-FLAME-CHECK ✓✓® • Hazardous Location Rating: HL
AG14 FT1 FT4 HL TECK90 XLPE (-40˚C) 2/C SIZE • EPA 40 CFR, Part 261 for leachable lead
Insulation: (AWG OR KCMIL) 1000 V DIR BUR SUN RES CSA
• Cross-linked Polyethylene (XLPE), Type RW90 content per TCLP method
MONTH-YEAR SEQUENTIAL LENGTH MARK • OSHA Acceptable
• Color-coded: 14 AWG to 2 AWG—black and
white; 1 AWG to 1000 kcmil—printed numbers Options: • RoHS Compliant
Phone: 888-593-3355
www.generalcable.com
SPEC 8150
November, 2014
TECK90
XLPE/PVC/AIA/PVC, Control and Power, Armored
1000 V, CSA TECK90, Three Conductor
Product Construction:
Conductor:
• 14 AWG thru 8 AWG bare copper Class B
compressed concentric round to ASTM B8
• 6 AWG thru 1000 kcmil bare copper compact
Class B strand
Insulation:
• Cross-linked Polyethylene (XLPE), Type RW90
• Color-coded: 14 AWG to 2 AWG—black, red and Applications: Compliances (cont'd.):
blue; 1 AWG to 1000 kcmil—printed numbers
• For exposed and concealed wiring in dry, damp Other Compliances:
Ground (Bonding) Conductor: or wet locations • Hazardous Location Rating: HL
• The conductor consists of one uninsulated • For use in ventilated, non-ventilated and ladder- • EPA 40 CFR, Part 261 for leachable lead
stranded bare copper conductor type cable trays in dry, damp or wet locations content per TCLP method
• For direct earth burial (with protection as required • OSHA Acceptable
Inner Jacket: by inspection authority) • RoHS Compliant
• Lead-free, flame-retardant, moisture- and • For wiring in all hazardous locations when used
sunlight-resistant Polyvinyl Chloride (PVC), black with certified HL cable glands
Packaging:
• For Canadian customers, lengths are provided
Armor: Features: on returnable wood or steel reels that require a
• Aluminum Interlocked Armor (AIA) • Rated at 90˚C wet or dry deposit. Extra charges apply for lagging, pulling
Overall Jacket: • Excellent crush resistance, oil and chemical eyes, paralleling and plexing
• Lead-free, ACID-FLAME-CHECK ✓✓® flame- resistance • For U.S. customers, material cut to length and
retardant, moisture- and sunlight-resistant • Provides long service life shipped on non-returnable wood reels, while
Polyvinyl Chloride (PVC), black • Meets cold bend and impact tests at -40˚C lengths in excess of 10,000 lbs. are provided on
returnable steel reels that require a deposit. Extra
Print: Compliances: charges apply for cuts less than 1000 ft., lagging,
• GENERAL CABLE® ACID-FLAME-CHECK ✓✓® AG14 Industry Compliances: pulling eyes, paralleling and plexing
FT1 FT4 HL TECK90 XLPE (-40˚C) 3/C SIZE (AWG OR • CSA Standard C22.2 No. 131 and No. 174
KCMIL) 1000 V DIR BUR SUN RES CSA MONTH- Flame Test Compliances:
YEAR SEQUENTIAL LENGTH MARK • CSA FT1 and FT4
• IEEE 383 (70,000 BTU/hr)
Options: • UL 1581 (70,000 BTU/hr)
• Galvanized Steel Interlocked Armor (GSIA) • IEEE 1202 (70,000 BTU/hr) CSA FT4
• ICEA T-30-520 (70,000 BTU/hr)
Phone: 888-593-3355
www.generalcable.com
SPEC 8175
November, 2014
TECK90
XLPE/PVC/AIA/PVC, Control and Power, Armored
1000 V, CSA TECK90, Four Conductor
Features:
• Rated at 90˚C wet or dry
• Excellent crush, oil and chemical resistance
• Provides long service life
• Meets cold bend and impact tests at -40˚C
Compliances:
Industry Compliances:
• CSA Standard C22.2 No. 131 and No. 174
Flame Test Compliances:
Product Construction: Overall Jacket: • CSA FT1 and FT4
• Lead-free, ACID-FLAME-CHECK ✓✓ ® flame- • IEEE 383 (70,000 BTU/hr)
Conductor: retardant, moisture- and sunlight-resistant • UL 1581 (70,000 BTU/hr)
• 14 AWG thru 8 AWG bare copper Class B Polyvinyl Chloride (PVC), black • IEEE 1202 (70,000 BTU/hr) CSA FT4
compressed concentric round to ASTM B8 • ICEA T-30-520 (70,000 BTU/hr)
• 6 AWG thru 1000 kcmil bare copper compact Print: Other Compliances:
Class B strand • GENERAL CABLE® ACID-FLAME-CHECK ✓✓ ® • Hazardous Location Rating: HL
AG14 FT1 FT4 HL TECK90 XLPE (-40˚C) 4/C • EPA 40 CFR, Part 261 for leachable lead
Insulation: SIZE (AWG OR KCMIL) 1000 V DIR BUR
• Cross-linked Polyethylene (XLPE), Type RW90 content per TCLP method
SUN RES CSA MONTH-YEAR SEQUENTIAL • OSHA Acceptable
• Color-coded: 14 AWG to 2 AWG—black, red, LENGTH MARK
blue and white; 1 AWG to 1000 kcmil—printed • RoHS Compliant
numbers Options: Packaging:
• Galvanized Steel Interlocked Armor (GSIA) • For Canadian customers, lengths are provided
Ground (Bonding) Conductor:
• The conductor consists of one uninsulated Applications: on returnable wood or steel reels that require a
stranded bare copper conductor • For exposed and concealed wiring in dry, damp deposit. Extra charges apply for lagging, pulling
or wet locations eyes, paralleling and plexing
Inner Jacket: • For use in ventilated, non-ventilated and ladder- • For U.S. customers, material cut to length and
• Lead-free, flame-retardant, moisture- and type cable trays in dry, damp or wet locations shipped on non-returnable wood reels, while
sunlight-resistant Polyvinyl Chloride (PVC), black • For direct earth burial (with protection as required lengths in excess of 10,000 lbs. are provided on
returnable steel reels that require a deposit. Extra
Armor: by inspection authority)
charges apply for cuts less than 1000 ft., lagging,
• Aluminum Interlocked Armor (AIA) • For wiring in all hazardous locations when used
with certified HL cable glands pulling eyes, paralleling and plexing
Phone: 888-593-3355
www.generalcable.com
SPEC 8200
November, 2014
TECK90
XLPE/PVC/AIA/PVC, Power/Control Composite
600 V, CSA TECK90, Three Power and Three 14 AWG Control Conductors
Product Construction:
Conductor:
• 12 AWG thru 8 AWG bare copper Class B
compressed concentric round to ASTM B8
• 6 AWG thru 4/0 AWG bare copper compact
Class B strand
Insulation:
• Cross-linked Polyethylene (XLPE), Type RW90
• Color-coded: 14 AWG to 2 AWG—black, red and Options: Compliances (cont'd.):
blue; 1 AWG to 4/0 AWG—printed numbers
• Galvanized Steel Interlocked Armor (GSIA) Flame Test Compliances:
Ground (Bonding) Conductor: Applications: • CSA FT1 and FT4
• The conductor consists of one uninsulated • IEEE 383 (70,000 BTU/hr)
• For exposed and concealed wiring in dry, damp • UL 1581 (70,000 BTU/hr)
stranded bare copper conductor
or wet locations • IEEE 1202 (70,000 BTU/hr) CSA FT4
Inner Jacket: • For use in ventilated, non-ventilated and ladder- • ICEA T-30-520 (70,000 BTU/hr)
• Lead-free, flame-retardant, moisture- and type cable trays in dry, damp or wet locations Other Compliances:
sunlight-resistant Polyvinyl Chloride (PVC), black • For direct earth burial (with protection as • Hazardous Location Rating: HL
required by inspection authority) • EPA 40 CFR, Part 261 for leachable lead
Armor: • For wiring in all hazardous locations when used
• Aluminum Interlocked Armor (AIA) content per TCLP method
with certified HL cable glands • OSHA Acceptable
Overall Jacket: Features: • RoHS Compliant
• Lead-free, ACID-FLAME-CHECK ✓✓ ® flame- • Rated at 90˚C wet or dry
retardant, moisture- and sunlight-resistant
Packaging:
• Excellent crush, oil and chemical resistance • For Canadian customers, lengths are provided
Polyvinyl Chloride (PVC), black • Provides long service life on returnable wood or steel reels that require a
Print: • Meets cold bend and impact tests at -40˚C deposit. Extra charges apply for lagging, pulling
• GENERAL CABLE® ACID-FLAME-CHECK ✓✓® Compliances: eyes, paralleling and plexing
AG14 FT1 FT4 HL TECK90 XLPE (-40˚C)3/C SIZE Industry Compliances: • For U.S. customers, material cut to length and
(AWG) +3/C #14 AWG 600 V DIR BUR SUN RES • CSA Standard C22.2 No. 131 and No. 174 shipped on non-returnable wood reels, while
CSA MONTH-YEAR SEQUENTIAL LENGTH MARK lengths in excess of 10,000 lbs. are provided
on returnable steel reels that require a deposit.
Extra charges apply for cuts less than 1000 ft.,
lagging, pulling eyes, paralleling and plexing
Phone: 888-593-3355
www.generalcable.com
SPEC 8225
April, 2015
TECK90
TRXLPE/PVC/AIA/PVC, Power, Unshielded, Armored
5 kV, CSA TECK90, Single Conductor
Features:
• Rated at 90˚C wet or dry
• Excellent crush, oil and chemical resistance
• Provides long service life
• Meets cold bend and impact tests at -40˚C
Compliances:
Industry Compliances:
• CSA Standard C22.2 No. 131 and No. 174
Flame Test Compliances:
Product Construction: Overall Jacket: • CSA FT1 and FT4
• Lead-free, ACID-FLAME-CHECK ✓✓ ® flame- • IEEE 383 (70,000 BTU/hr)
Conductor: retardant, moisture- and sunlight-resistant • UL 1581 (70,000 BTU/hr)
• 6 AWG thru 1000 kcmil bare copper compact Polyvinyl Chloride (PVC), orange • IEEE 1202 (70,000 BTU/hr) CSA FT4
Class B strand • ICEA T-30-520 (70,000 BTU/hr)
Print: Other Compliances:
Strand Shield: • GENERAL CABLE® ACID-FLAME-CHECK ✓✓ ®
• A thermoset semi-conducting shield is extruded • Hazardous Location Rating: HL
AG14 FT1 FT4 HL TECK90 TRXLPE (-40˚C) 1/C • EPA 40 CFR, Part 261 for leachable lead
over the conductor SIZE (AWG OR KCMIL) 5 kV DIR BUR SUN RES content per TCLP method
Insulation: CSA MONTH-YEAR SEQUENTIAL LENGTH MARK • OSHA Acceptable
• Tree-Retardant Cross-linked Polyethylene Options: • RoHS Compliant
(TRXLPE), Type RW90 • Galvanized Steel Interlocked Armor (GSIA) Packaging:
Ground (Bonding) Conductor: Applications: • For Canadian customers, lengths are provided
• The conductor is a concentric serving of solid • For exposed and concealed wiring in dry, damp on returnable wood or steel reels that require a
bare copper wires applied over the insulation or wet locations deposit. Extra charges apply for lagging, pulling
eyes, paralleling and plexing
Inner Jacket: • For use in ventilated, non-ventilated and ladder-
• For U.S. customers, material cut to length and
• Lead-free, flame-retardant, moisture- and type cable trays in dry, damp or wet locations
• For direct earth burial (with protection as required shipped on non-returnable wood reels, while
sunlight-resistant Polyvinyl Chloride (PVC), black lengths in excess of 10,000 lbs. are provided on
by inspection authority)
Armor: • For wiring in all hazardous locations when used returnable steel reels that require a deposit. Extra
• Aluminum Interlocked Armor (AIA) with certified HL cable glands charges apply for cuts less than 1000 ft., lagging,
pulling eyes, paralleling and plexing
Phone: 888-593-3355
www.generalcable.com
SPEC 8250
April, 2015
TECK90
TRXLPE/PVC/AIA/PVC, Power, Unshielded, Armored
5 kV, CSA TECK90, Three Conductor
Product Construction:
Conductor:
• 6 AWG thru 1000 kcmil bare copper compact
Class B strand
Strand Shield:
• A thermoset semi-conducting shield is extruded
over the conductor
Insulation:
• Tree-Retardant Cross-linked Polyethylene Options: Compliances (cont'd.):
(TRXLPE), Type RW90 • Galvanized Steel Interlocked Armor (GSIA) Flame Test Compliances:
• Color-coded: Black with printed numbers • CSA FT1 and FT4
Applications: • IEEE 383 (70,000 BTU/hr)
Ground (Bonding) Conductor: • For exposed and concealed wiring in dry, damp • UL 1581 (70,000 BTU/hr)
• The conductor consists of one uninsulated or wet locations • IEEE 1202 (70,000 BTU/hr) CSA FT4
stranded bare copper conductor • For use in ventilated, non-ventilated and ladder- • ICEA T-30-520 (70,000 BTU/hr)
type cable trays in dry, damp or wet locations Other Compliances:
Inner Jacket: • For direct earth burial (with protection as required
• Lead-free, flame-retardant, moisture- and • Hazardous Location Rating: HL
by inspection authority) • EPA 40 CFR, Part 261 for leachable lead
sunlight-resistant Polyvinyl Chloride (PVC), black • For wiring in all hazardous locations when used content per TCLP method
Armor: with certified HL cable glands • OSHA Acceptable
• Aluminum Interlocked Armor (AIA) Features: • RoHS Compliant
Overall Jacket: • Rated at 90˚C wet or dry Packaging:
• Lead-free, ACID-FLAME-CHECK ✓✓ ® flame- • Excellent crush, oil and chemical resistance • For Canadian customers, lengths are provided
retardant, moisture- and sunlight-resistant • Provides long service life on returnable wood or steel reels that require a
Polyvinyl Chloride (PVC), orange • Meets cold bend and impact tests at -40˚C deposit. Extra charges apply for lagging, pulling
Print: Compliances: eyes, paralleling and plexing
Industry Compliances: • For U.S. customers, material cut to length and
• GENERAL CABLE® ACID-FLAME-CHECK ✓✓® shipped on non-returnable wood reels, while
AG14 FT1 FT4 HL TECK90 TRXLPE (-40˚C) 3/C • CSA Standard C22.2 No. 131 and No. 174
lengths in excess of 10,000 lbs. are provided on
SIZE (AWG OR KCMIL) 5 kV DIR BUR SUN RES returnable steel reels that require a deposit. Extra
CSA MONTH-YEAR SEQUENTIAL LENGTH MARK charges apply for cuts less than 1000 ft., lagging,
pulling eyes, paralleling and plexing
Phone: 888-593-3355
www.generalcable.com