Apd165c 6

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

APD165C-6

AKSA Power Generation has been producing industrial generator sets with an innovative compact design and
excellence in quality for over 30 years. AKSA has been providing reliable power through three main production plants and
over 15 branch offices worldwide.

General Characteristics

Model Name APD165C-6 Frequency / PF 60Hz, 1800 rpm, 0.8pf

Engine Make & Model Cummins 6BTAA5.9G2 Alternator Make Stamford

Control Panel Model DSE 6120 Base Frame / Enclosure AKSA ASM5A

Genset Rating – 60Hz, 1800rpm, 0.8pf

Standby
Engine Alternator Voltage Standby Power Prime Power
Current

UCI274E 480 / 277V 165kVA 150kVA 198A


UCI274F 380 / 222V 165kVA 150kVA 250A
6BTAA5.9G2
UCI274E 220 / 127V 165kVA 150kVA 433A

UCI274E 208 / 120V 165Kva 150kVA 458A

Stand-by Power (Maximum): Power available at variable load in the event of main power network failure. No over load is permitted.
Prime Power: Power available at variable load in lieu of a main power network. Overload of 10% is permitted for 1 hour in every 12 hours of operation.
The above ratings represent the engine performance capabilities to conditions specified in accordance with ISO 8528/5 & ISO3046.
Derating may be required for conditions outside of the test conditions.

Codes & Standards

The Generator set is designed and manufactured in a facility certified to ISO9001 standards.

The Generator set is designed and manufactured in a facility certified to ISO14001:2015 standards.

AKSA Power Generation provides single source responsibility for the generator set & accessories.

The generator set, with its components, are prototype tested and production tested

*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
APD165C-6

Engine Data Electric System

Manufacturer Cummins Engine Cranking Motor 24V

Model 6BTAA5.9G2 Engine Battery Charge System 40A, Negative Ground

Displacement & Cylinders 5.9 L / 6 Cylinders Battery Qty, Rating, CCA 2 x 60Ah

Engine Speed 1800 rpm

Engine Standby Power


145 Kw Cooling System

Engine Prime Power 132 kW Coolant Capacity (Engine Only) 10 L

Turbocharged and
Aspiration Minimum Pressure Cap 69 kPa
Charge Air Cooled
Max Coolant Friction Head 35 kPa
Compression Ratio 17.3 : 1
External to Engine

Bore / Stroke 102 mm / 120 mm Max Top Tank Temperature 104 ˚C

Governor Regulation ≤ 3% Thermostat Range 82– 95 ˚C

Piston Speed 7.2 m/s

Friction Power 16.4 kWm Exhaust System

Radiated Heat to Ambient 20 kWm Max Back Pressure 10 kPa

Engine Water Flow 2.4 L/s. Exhaust Gas Flow 401 L/s.

Exhaust Gas Temperature 570 ˚C

Min Exhaust Pipe Size 76 mm

Fuel System Air Intake System

Type Injection System BYC PB Direct Injection Intake Air Flow 142 L/s

6 kPa Dirty Element


Max Restriction @ Lift Pump 13.6 kPA Max Intake Air Restriction
4 kPa Clean Element
Max Allowable Head on Injector 67.7 kPa Min Dirt Holding Capacity 53 g/cfm
Return Line
Total Drain Flow 30 L/h Max Temp Rise from Ambient to
17 °C
Inlet of Turbo

Fuel Consumption Lubrication System

Standby Power (100%) 38 L / h Max Oil Temperature 121 ˚C

Prime Power (100%) 34 L / h Oil Capacity: High - Low 14.2 L – 12.3 L

Prime Power (75%) 25 L / h Min Required Lube Capacity 16.4 L

Prime Power (50%) 18 L / h

Prime Power (25%) 11 L / h

*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
APD165C-6

Alternator Data Controller Data

Manufacturer Stamford Manufacturer DSE

Standards BS EN 60034 Model 6120

Auto Mains Failure


Control System Self Excited Type Control

A.V.R. SX460 Controller Features & Benefits

Voltage Regulation ±1% Microprocessor controlled

Insulation System Class H License free PC Software

Protection IP23 IP65 rating offers increased resistance to water ingress

Rated Power Factor 0.8 Front Panel Editing

Stator Winding Double Layer Concentric Event log

Winding Pitch Two Thirds Back-lit icon LCD display

Winding Leads 12 LED and LCD alarm indication

Telephone Interference THF < 2 % Power save mode

Waveform Distortion No Load < 1.5 % PC and front panel configuration

Maximum Over speed 2250 rev/min Configurable timers and alarms

Battery Charger & Electrical System Data Alternative configuration

Manufacturer AKSA Three phase generator monitoring

Model SmartGen BAC06A Current monitoring and protection

Input Voltage 100V ~ 250V AC Power monitoring (kW, kVA, kVAr)

Output Voltage / Current 27,6V DC / 3A Reverse power (kW & kVAr) protection

Jacket Water Heater Data Three phase utility monitoring

Manufacturer AKSA Test feature

Model HTR1000W 100-120F Battery voltage monitoring

Input Voltage 1 ph, Based on Gen Voltage Hours counter

Power 1000W Comprehensive warning or shutdown on fault condition

*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
APD165C-6

Enclosure Features

✓ Heavy Duty Steel Structure

✓ E-Stop on Enclosure

✓ Control Panel Eliminated from Engine Vibrations

✓ Control Panel Window

✓ Plastic Covered Corrosion Resistant Locks & Hinges

✓ Internally Mounted Exhaust System with Rain Cap

✓ Coolant Fill Cap

✓ Base Frame Lifting Hooks

✓ Base Fuel Tank and Forklift Pockets

✓ Easy Access for Maintenance

✓ Sound Absorb High Density Foam

Open Skid Gen-Set Dimensions

Length 2150 mm

Width 1000 mm

Height 1474 mm

Dry Weight 1360 kg

Tank Capacity 195 L

Enclosed Gen-Set Dimensions

Length 3121 mm

Width 1068 mm

Height 1716 mm

Dry Weight 1700 kg

Tank Capacity 340 L

Sound Pressure @ 7 meters 75 dBA

*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
Enclosure Features
APD165C-6

Standard Features & Accessories Optional Accessories

✓ 24 Months / 2000 hours Limited Standby Warranty ❑ 10A Battery Charger

✓ Air Filter Restriction Gauge ❑ Advanced SMS Messaging

✓ Air Inlet & Outlet Rodent Guards ❑ Anti-condensation Heater


✓ Anti-Vibration Pads between Engine/Alternator &Base
❑ Auto Fuel Fill Control System
Frame
✓ Battery and Battery Rack ❑ Automatic Transfer Panel (ATS) – ChangeoverDesign

✓ Battery Charger ❑ Automatic Transfer Panel (ATS) – ContactorDesign

✓ Control Panel Window ❑ Battery Charge Ammeter

✓ Control Panel Window ❑ Battery Disconnect Switch

✓ Coolant Drain Valve ❑ Battery Heater

✓ Engine Jacket Water Heater ❑ Control Panel Heater

✓ Engine Manifold Cover ❑ Double Wall Base Fuel Tank

✓ Exhaust Insulation Cover ❑ Fuel Level Display & Alarm on Controller

✓ Flex Fuel Lines ❑ Fuel Water Separator Filter

✓ Fuel Drain Plug ❑ Low / High Fuel Alarms

✓ Heavy Duty Steel Base Frame ❑ Main Line CB (3 / 4 Poles)

✓ Industrial Grade Silencer Set for Open Skid Sets ❑ Manual Speed Adjust Rheostat

✓ Integral Fuel Tank ❑ Manual Voltage Adjust Rheostat

✓ Oil Drain Valve ❑ Oil Temperature Display on Controller

✓ Operations Manual ❑ PMG

✓ Protection Covers for Rotating Parts ❑ Power Plug Outlet Kit

✓ Radiator fill cap on enclosure ❑ Remote Annunciator Panel

✓ Residential Grade Silencer Inside Enclosure ❑ Remote Control & Monitoring Panel

✓ Sound Absorb Foam for Enclosure ❑ Tool Kit for Maintenance

✓ Turbocharger Cover ❑ Voltage Regulation ±0.5% w/MX321 AVR

SEDE PRINCIPAL:
Av. Nicolás Ayllón N° 2241 – Ate – Lima – Perú
Telf.: (51-1) 748-3333 / 326-0411 / Anexo 1152

*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.