Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

AKSA Power Generation Has Been Producing Industrial Generator Sets With An Innovative Compact Design and

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

AC1000-6

AKSA Power Generation has been producing industrial generator sets with an innovative compact design and
excellence in quality for over 30 years. AKSA has been providing reliable power through three main production plants
and over 15 branch offices worldwide.

General Characteristics

Model Name AC1000-6 Frequency / PF 60Hz, 1800 rpm, 0.8pf

Engine Make & Model Cummins QSK23G3 Alternator Make Stamford

Control Panel Model DSE 7320 Base Frame / Enclosure AK90

Genset Rating – 60Hz, 1800rpm, 0.8pf

Standby
Engine Alternator Voltage Standby Power Prime Power
Current

HCI634G (Wnd-311) 480 / 277V 1000kVA 905kVA 1202A

HCI634G (Wnd-13) 380 / 222V 1000kVA 905kVA 1519A


QSK23G3
HCI634G (Wnd-311) 220 / 127V 1000kVA 905kVA 2624A

HCI634H (Wnd-311) 208 / 120V 1000kVA 905kVA 2775A

Stand-by Power (Maximum): Power available at variable load in the event of main power network failure. No over load is permitted.
Prime Power: Power available at variable load in lieu of a main power network. Overload of 10% is permitted for 1 hour in every 12 hours of operation.
The above ratings represent the engine performance capabilities to conditions specified in accordance with ISO 8528/5 & ISO3046.
Derating may be required for conditions outside of the test conditions.

Codes & Standards

The Generator set is designed and manufactured in a facility certified to ISO9001 standards.

The Generator set is designed and manufactured in a facility certified to ISO14001:2015 standards.

AKSA Power Generation provides single source responsibility for the generator set & accessories.

The generator set, with its components, are prototype tested and production tested

*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
AC1000-6

Engine Data Electric System

Manufacturer Cummins Engine Cranking Motor 24V

Model QSK23G3 Engine Battery Charge System Negative Ground

Displacement 23.15 L Battery Qty, Rating, CCA 2 x 150Ah

Engine Speed 1800 rpm

Engine Standby Power


895 Kw Cooling System

Engine Prime Power 809 kW Coolant Capacity (Engine Only) 46.5 L

Turbocharged and
Aspiration Minimum Pressure Cap 69 kPa
Charge Air Cooled
Max Coolant Friction Head 48 kPa
Compression Ratio 16 : 1
External to Engine

Bore / Stroke 170 mm / 170 mm Max Top Tank Temperature 104 ˚C

Break Mean Effective Pressure 2600 kPa Thermostat Range 76.5– 90 ˚C

Piston Speed 10.3 m/s

Friction Power 93 kWm Exhaust System

Radiated Heat to Ambient 85 kWm Exhaust Gas Temp 514 ˚C

Steady State Stability 0.25 % Max Allowable Back Pressure 10.2 kPa

Dry Weight – fan to flywheel 2755 kg Exhaust Gas Flow 6475 cfm

Exhaust Noise 1m @Rated


TBD
Power

Fuel System Air Intake System

Type Injection System Cummins HPI-PT Intake Air Flow 2398 cfm

6.2 kPa Dirty Element


Max Fuel Flow 684 L/h Max Intake Air Restriction
3.7 kPa Clean Element

Max Return Fuel Flow 662 L/h Air Filter Type Dry Paper Element

Max Allowable Head on Injector


30 kPa
Return Line

Fuel Consumption Lubrication System

Standby Power (100%) 212 liter / hour Total System Capacity 103 L

Prime Power (100%) 189 liter / hour Sump Capacity Max / Min 95 L / 66 L

Prime Power (75%) 139 liter / hour Max Oil Temp 120 ˚C

Prime Power (50%) 97 liter / hour Oil Pressure at Rated Speed 345 – 448 kPa

Prime Power (25%) 56 liter / hour

*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
AC1000-6

Alternator Data Controller Data

Manufacturer Stamford Manufacturer DSE

Standards BS EN 60034 Model 7320

Auto Mains Failure


Control System PMG Type Control

A.V.R. MX321 Controller Features & Benefits

Voltage Regulation ± 0.5 % Microprocessor controlled

Insulation System Class H License free PC Software

Protection IP23 IP65 rating offers increased resistance to water ingress

Rated Power Factor 0.8 Modules can be integrated to building management systems

Stator Winding Double Layer Concentric Real time clock provides accurate event log

Winding Pitch Two Thirds Four line back-lit LCD text display

Winding Leads 12 Five key menu navigation

Telephone Interference THF < 2 % Front panel editing with PIN protection

Waveform Distortion No Load < 1.5 % Support up to three remote display modules

Maximum Over speed 2250 rev/min Configurable timers and alarms

Battery Charger & Electrical System Data Multiple date and timer scheduler Integral

Manufacturer AKSA PLC editor

Model SmartGen BAC06A ‘Protections disabled’ feature

Input Voltage 100V ~ 250V AC kW & kVAR protection

Output Voltage / Current 27,6V DC / 3A Reverse power (kW & kVAr) protection

Jacket Water Heater Data Power monitoring (kWh, kVAR, kVAh, kVArh)

Manufacturer AKSA Load switching (load shedding and dummy load outputs)

Model HTR4000 Unbalanced load protection

Input Voltage Based on Genset Voltage Independent Earth Fault trip

Power 4000W Fully configurable via DSE Configuration Suite PC Software

SCADA monitoring via DSE Configuration Suite PC Software

*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
AC1000-6

Enclosure Features

✓ Heavy Duty Steel Structure

✓ E-Stop on Enclosure

✓ Control Panel Eliminated from Engine Vibrations

✓ Control Panel Window

✓ Plastic Covered Corrosion Resistant Locks & Hinges

✓ Internally Mounted Exhaust System with Rain Cap

✓ Coolant Fill Cap

✓ Top Lifting Feature

✓ Base Fuel Tank

✓ Easy Access for Maintenance

✓ Sound Absorb High Density Foam

Open Skid Gen-Set Dimensions

Length 4124 mm

Width 2000 mm

Height 2261 mm

Dry Weight 6500 kg

Tank Capacity 1400 L

Enclosed Gen-Set Dimensions

Length 6500 mm

Width 2200 mm

Height 2353 mm

Dry Weight 9300 kg

Tank Capacity 1100 L

Sound Pressure @ 7 meters 77 dBA

Enclosure Features

*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
AC1000-6

Standard Features & Accessories Optional Accessories

✓ Heavy Duty Steel Base Frame ❑ Main Line CB (3 / 4 Poles)

✓ Integral Fuel Tank ❑ Anti-condensation Heater

✓ PMG w/MX321 AVR ❑ Stand Alone Bulk Fuel Tank

✓ Engine Jacket Water Heater ❑ Fuel Level Display & Alarm on Controller

✓ Battery and Battery Rack ❑ Low / High Fuel Alarms

✓ Battery Charger ❑ Fuel Water Separator Filter

✓ Battery Restraint ❑ Auto Fuel Fill Control System

✓ Anti-Vibration Pads between Engine/Alternator &Base


❑ Oil Temperature Display on Controller
Frame

✓ Residential Grade Silencer Inside Enclosure ❑ Manual Speed Adjust Rheostat

✓ Industrial Grade Silencer Set for Open Skid Sets ❑ Manual Voltage Adjust Rheostat

✓ Sound Absorb Foam for Enclosure ❑ Remote Annunciator Panel

✓ Air Inlet & Outlet Rodent Guards ❑ Remote Control & Monitoring Panel

✓ Oil Drain Valve ❑ Advanced SMS Messaging

✓ Coolant Drain Valve ❑ Control Panel Heater

✓ Flex Fuel Lines ❑ Battery Disconnect Switch

✓ Air Filter Restriction Gauge ❑ Battery Heater

✓ Engine Manifold Cover ❑ 10A Battery Charger

✓ Turbocharger Cover ❑ Battery Charge Ammeter

✓ Protection Covers for Rotating Parts ❑ Tool Kit for Maintenance

✓ Exhaust Insulation Cover ❑ Power Plug Outlet Kit

✓ Control Panel Window ❑ Automatic Transfer Panel (ATS) – Contactor Design

✓ Operations Manual ❑ Automatic Transfer Panel (ATS) – Changeover Design

✓ 24 Months / 2000 hours Limited Standby Warranty

SEDE PRINCIPAL:
Av. Nicolás Ayllón N° 2241 – Ate – Lima – Perú
Telf.: (51-1) 748-3333 / 326-0411 / Anexo 1152

*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.