13 Alarm Codes: Traction Controller
13 Alarm Codes: Traction Controller
13 Alarm Codes: Traction Controller
13 Alarm codes
This chapter explains the meaning of the various alarms that the different controllers
may produce. Refer to the chapter 11 for information on the TruckTool diagnostics
application.
NOTE: Before you start to troubleshoot the truck, make sure that all the power
supplies, fuses and connections are in order. Low voltage in the traction controller
can cause different sorts of alarms.
The fault diagnostic system of the traction controller is divided into two main groups:
• Alarms
These are faults, which open the power bridge and, when possible, also the main
contactor is opened and the magnetic brake activated. Failures in the motor, the
controller or the safety functions cause alarms.
• Warning
These are faults, which do not stop the truck or stop the truck by using regeneration
braking. The controller is working well, but it has detected some conditions that
reduce the performance or stop the truck without opening the power devices.
Incorrect operation sequences or conditions requiring performance reductions (for
example, high temperatures) cause warnings.
The text “Stored” means that the alarm or warning is stored in the traction controller
logbook.
This is a safety-related self diagnosis test within the logic between the master (drive) and slave
(pump) microcontrollers. The alarm indicates that the master and slave watchdog message is
missing or late.
This alarm can be caused by a CAN bus malfunction, which blinds the master-slave
communication. Check all the CAN bus cables and measure the bus resistance between CAN
high and low. The bus resistance value should be 60 Ω. Measure also the CAN cables’
resistance between the truck chassis and the 0 cables. There should not be any significant
connection and the resistance value should be over 1 M Ω.
If CAN bus is OK, the problem is in the controller and it must be replaced.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 247 (322)
NSP Service Manual
This warning is caused by a hardware or software defect of the non-volatile embedded memory
supporting the controller parameters. This alarm does not prevent truck operation, but the truck
will work with the default values.
In case of this warning, perform a CLEAR EEPROM operation. Switch the key off and on to
check the result. If the alarm occurs permanently, replace the traction controller. If the alarm
disappears, the previously stored parameter values will have been replaced by the default
values.
This alarm is caused by a hardware problem in the logic card circuit for high current (overload)
protection.
This fault is not related to external components, so when it appears, replace the traction
controller.
This alarm is caused by a fault in the logic board managing the phase’s voltage feedback.
This fault is not related to external components, so when it appears, replace the traction
controller.
This alarm is displayed when the controller detects an overvoltage or undervoltage condition.
The overvoltage threshold is 35 V and the undervoltage threshold is 9.5 V in the 24V controller.
If the alarm is displayed at startup or in the standby mode, it is due to an undervoltage. In such
a case, check the following:
• The key input signal voltage drops below the undervoltage threshold due to external loads,
such as DC/DC converters starting up or relays or contactors energizing or de-energizing.
• If no voltage transient is detected on the supply line and the alarm is displayed every time
the key is switched ON, the problem is in the traction controller.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 248 (322)
NSP Service Manual
This test is carried out when the pump motor is running. The alarm indicates that the pump
motor output is higher than expected.
In such a case, check the following:
• Motor connections
• If the motor windings or cables have leakage currents towards the truck frame
If no problems are found on the motor, the problem is in the traction controller.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 249 (322)
NSP Service Manual
Cause 1:
Before switching the main contactor on, the software checks the power bridge. It turns the low
side and high side power MOSFETs on one by one and expects the phase voltage to decrease
down to –Batt. If the phase voltage does not decrease, this alarm occurs.
In such a case (the main contactor does not close at all), check the following:
• Motor internal connections (ohmic continuity)
• Motor power connections
• Motor leakage current to the truck frame
If the motor connections are OK, the problem is in the traction controller.
Cause 2:
This alarm may also occur when the startup diagnosis has been completed and the main
contactor is closed. In this case, the phase voltage is expected to be lower than 50% of the
battery voltage. If it is higher than this value, this alarm occurs.
In such a case (the main contactor closes and then opens again), check the following:
• Motor connections
• Whether the motor’s phase windings or cables have leakage currents towards the truck
frame
• That the main contactor closes properly, with a good contact
If no faults are found, the problem is in the traction controller.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 250 (322)
NSP Service Manual
Before driving the main contactor coil, the controller checks that the contactor is not stuck
(closed). The controller drives the MOSFETs for some milliseconds, trying to discharge the
capacitor bank. If the contactor is stuck, this alarm occurs.
In such a case, check the main contactor tips. If needed, replace the main contactor.
This alarm occurs if the main contactor has been driven by the controller, but the contactor
does not close.
In such a case, check that the wires to the main contactor coil are not interrupted or
disconnected.
The alarm can also be caused by a fault in the main contactor itself. If needed, replace the
contactor.
This test is carried out when the pump motor is running, and it verifies that the current feedback
sensor is not constantly stuck to 0.
If this warning is displayed, check that the motor connection has continuity. If the motor
connection is opened, the current cannot flow, so the test fails and the warning is displayed.
If the motor circuit is OK, the problem can be in the current sensor. In this case, replace the
traction controller.
This alarm is displayed if the current transducer or the current feedback circuit is damaged in
the controller.
This fault is not related to external components, so when it appears, replace the traction
controller.
When the main contactor is open, the bus capacitors are charged from the key line through a
charging resistor. If the voltage on the bus capacitors is low and does not increase, this alarm
is displayed.
In such a case, there are four possibilities:
• Another device connected in parallel with the bus capacitors has failed.
• Something is draining the current between the main contactor and the controller when the
main contactor is open.
• There is a problem in the charging section (for example, a bad contact in the key line).
• A power failure or a logic failure occurred in the controller. In this case, replace the traction
controller.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 251 (322)
NSP Service Manual
This alarm indicates that the controller temperature is over 85°C. The maximum current is
reduced proportionally to the temperature increase. The controller stops when 105°C is
reached.
If this alarm occurs when the controller is cold, there are three possibilities:
• There is a fault in the thermal sensor wiring.
• There is a failure in the thermal sensor.
• There is a failure in the logic.
In all of the above cases, replace the traction controller.
This alarm occurs when the analogue temperature sensor has exceeded the threshold 150°C.
In such a case, check the following:
• The thermal sensor inside the motor and the outside wiring. The resistance of the sensor
(type KTY83) is 960 Ω at 20°C.
• If the warning occurs when the motor is cold and the thermal sensor is OK, the problem is
in the traction controller.
• If the motor is overheating, check that air ventilates freely in the motor compartment.
This warning occurs when the battery charge is calculated as being less or equal to 10% of a
full charge and the BATTERY CHECK parameter is set to a value other than 0 (located in the
SET OPTION menu).
In such a case, charge the battery. If it does not help, measure the battery voltage with a
voltmeter and compare it with the value of the BATTERY VOLTAGE parameter. If they are
different, adjust the value of the ADJUST BATTERY parameter.
When adjusting the battery voltage, voltage should be measured from the key line, after the
reverse polarity protection diode. A good measuring point is, for example, the emergency stop
button terminal. If the battery voltage is measured anywhere else, it will cause invalid operation
of the battery discharge indicator.
This alarm occurs if the driver of the main contactor coil is shorted or the coil is disconnected.
In such a case, check the following:
• If there is a short circuit between the connector XA1 C pin 6 and –Batt.
• Condition of the wiring of the main contactor related harness.
If there is no short circuit and the wiring is OK, the driver circuit in the traction controller is
damaged.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 252 (322)
NSP Service Manual
This alarm indicates that the main contactor driver is not able to drive the load. The device itself
or its driving circuit is damaged.
This fault is not related to external components, so when it appears, replace the traction
controller.
This alarm occurs when the accelerator output voltage differs more than 1 V from the acquired
minimum during PROGRAM VACC.
In such a case, check the functionality of the accelerator. Perform the accelerator calibration
wizard function.
This warning occurs when both travel demands are active at the same time.
Use a tester to check for possible reasons for this warning. If both directions are active at the
same time, check the accelerator and its wiring.
If no direction signals are active at the same time outside the controller, the problem is in the
traction controller.
This alarm occurs if the frequency supplied to the motor is higher than 40 Hz and the feedback
signal from the encoder has a jump higher than 40 Hz within 20-40 milliseconds. This condition
is related to a malfunction of the encoder. In such a case, check the encoder’s mechanical
functioning and its wirings’ connections. Also check the encoder’s mechanical installation; if the
encoder slips inside the housing, it causes this alarm.
Also electromagnetic noise on the encoder can cause this alarm. In such a case, replace the
encoder. If the alarm persists after replacing the encoder, the problem is in the traction
controller.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 253 (322)
NSP Service Manual
The software checks for the connection of the two supply ends of the accelerator’s
potentiometer. The test consists of reading the voltage drop on a sense diode connected
between NPOT and GND. If the accelerator gets disconnected on PPOT or NPOT, no current
flows in this sense diode and the voltage on the NPOT connection drops down.
This alarm occurs if the NPOT voltage is less than 0.3 V and also when the NPOT voltage is
higher than 2 V (to detect also the condition of a broken sense diode).
In such a case, check the voltage on the NPOT and the accelerator connections.
If the truck is not equipped with side stabilizers, check that the parameter INITIAL LIFT is not
set to 2.
If the truck is equipped with side stabilizers:
• Check the wiring of the height sensor.
• Disconnect the height sensor and test the redundant switches. If the states are not equal,
test if the switch works by moving a magnet in front of it.
• Check that the magnet counterpart (attached to the lifting carriage) is intact.
• Check the wiring of the encoder card (extra I/O).
If the problem persists, replace the height sensor.
This is only a notification. To limit further heat generation, the parameter cutback starts when
the motor temperature reaches 120 ˚C. The truck can be used normally.
This is only a notification. To limit further heat generation, the parameter cutback starts when
the controller temperature reaches 75 ˚C. The truck can be used normally.
This warning indicates a pressure sensor problem. Either the pressure sensor’s voltage is not
within the calibrated value range or it exceeds the calibrated values too much.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 254 (322)
NSP Service Manual
One possible cause for this alarm is too steep braking ramp (parameter). Try to lower the
braking ramps from the parameters. Also braking at a slope when the truck is loaded can
cause this error.
This alarm indicates that there is some problem in the steering and the steering has frozen.
This is a general warning indicating only that the truck is waiting for an operator.
This alarm occurs if the motor resistance is different than the value of the parameter MOTOR
RESIST.
In such a case, teach the new motor resistance value by setting the parameter MOTOR
RESIST to 0 and saving the value while holding the tiller arm in the drive position. Restart the
truck after the main contactor is opened. The new settings are active after the restart.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 255 (322)
NSP Service Manual
This warning occurs if the controller did not acquire the motor resistance value correctly.
In most cases, this alarm signals that the controller cannot inject current in the motor coils for
some reason. Check the motor connections. Also make sure that the main contactor is closed.
This alarm indicates damage to the controller’s hardware which provides feedback for the
sensorless motor control.
If the problem occurs permanently, replace the controller.
This warning is displayed when the PIN code teaching procedure is active. It disappears when
the teaching is finished.
This warning should occur only if the truck is equipped with a PIN code lock.
This warning indicates that the controller is waiting for a valid PIN code. If it occurs in a truck
that does not use PIN code lock, check that the PIN CODE LOCK parameter is set to ABSENT.
This warning should occur only if the truck is equipped with a PIN code lock.
This alarm indicates that the controller entered the throttle lever teaching mode. It disappears
as soon as the teaching of the throttle lever is finished.
This warning is displayed when the lifting cut off timer has expired (the default value is seven
seconds).
In case of this warning, release the lift button. If the lift buttons are released and the warning
persists: check the following:
• The lift inputs are correct in the tester menu.
• Operation of the tiller and the lift buttons is correct.
• There are no short circuits in the lift button wirings.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 256 (322)
NSP Service Manual
Cause 1: At startup
The software checks the voltage on the –P terminal and expects it to remain at a steady value.
This alarm occurs if the value does not remain steady.
Cause 2: During operation
If this alarm is displayed during operation, it indicates that the voltage on the –P terminal is too
low when the main contactor is closed.
The software waits for 30 seconds before displaying this alarm, because there are situations
where the pump motor can rotate while the –P output is not activated (pump deceleration).
During this time, it shows the WAIT MOT P STILL warning.
In case of this alarm, check the following:
• Pump motor internal connections
• Pump motor power cable connections
• Pump motor leakage current to the truck frame
If the pump motor connections are OK, the problem is in the traction controller.
See the description of the alarm 203 PUMP VMN NOT OK.
Before switching the main contactor on, the software checks the power bridge voltage without
driving it. The software expects the voltage to be at a steady state value. If the voltage is too
high, this alarm occurs.
In such a case, check the following:
• Motor internal connections
• Motor power cable connections
• Motor leakage current to the truck frame
If the motor connections are OK, the problem is in the traction controller.
Before switching the LC on, the software checks the power bridge voltage without driving it.
The software expects the voltage to be at a steady state value. If the voltage is too low, this
alarm occurs.
In such a case, check the following:
• Motor internal connections (ohmic continuity)
• Motor power cable connections
• Motor leakage current to the truck frame
If the motor connections are OK, the problem is in the traction controller.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 257 (322)
NSP Service Manual
This alarm is caused by a hardware or software defect in the non-volatile embedded memory
supporting the controller parameters. This alarm does not prevent the truck from operating, but
the truck will work with the default values.
In the case of this alarm, perform the CLEAR EEPROM operation. Switch the key off and on to
check the result. If the alarm persists, replace the traction controller. If the alarm disappears,
the previously stored parameter values will have been replaced by the default parameter
values.
This alarm is caused by a hardware or software defect in the volatile embedded memory.
The controller could be damaged and it should be replaced.
This alarm indicates that the traction rotor is stuck or the encoder signal is not correctly
received by the controller.
In the case of this alarm, check if the sign of FREQUENCY and ENCODER on the tester menu
are the same. Also check that it is not zero during a traction request.
If this alarm occurs, the POSITIVE EB parameter is probably not set correctly. Set the
parameter to LEVEL=0.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 258 (322)
NSP Service Manual
This alarm is displayed if the microcontroller detects a mismatch between the valve set-point
and the voltage measured on the solenoid valve output. This can be caused by the following:
• The solenoid valve coil circuit is shorted.
• The traction solenoid valve driver is shorted.
If there is low impedance between the negative of the solenoid valve coil and –Batt, the driver
circuit is damaged and the traction controller must be replaced.
This alarm indicates that the pump motor’s current feedback sensor has detected current
flowing in the circuit while the pump motor is not running.
This fault is not related to external components, so when it appears, replace the traction
controller.
This warning indicates a motor thermal sensor knockout, meaning that the motor thermal
sensor has either short or open circuited.
In such a case, check that the connector contacts and the cables are in order. Measure the
resistance of the thermal sensor (960 Ω at 20°C).
This alarm indicates that the voltage on the positive line of the EV outputs (B2) is too high or
too low.
In such a case, check if the voltage dropped down because of a faulty load connected to B2. If
not, replace the traction controller.
This is a startup diagnostic for the key line. This alarm occurs if the key line (XA1 C/1) voltage
drops below the threshold level of 9.5 V.
In such a case, check if the key input signal voltage drops below the undervoltage threshold
due to external loads, such as DC/DC converters starting up or relays or contactors energizing
or de-energizing.
If no voltage transient is detected on the supply line and the alarm occurs every time the key is
switched ON, the problem is in the traction controller.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 259 (322)
NSP Service Manual
This alarm indicates that the built-in smart driver is open and not able to provide the magnetic
brake positive.
In such a case, check the harness to see if the smart driver output XA1 B/1 is shorted to –Batt.
If the output stays at a low level even when disconnecting the wire from the connector pin, the
problem is in the traction controller.
This alarm occurs when there is a short circuit in the main contactor or magnetic brake coil.
The typical root cause for this alarm is a problem in the harness or in the coil. Check the
connections and wiring between the controller and coils.
If there are no external failures or problems, the problem is in the controller and it needs to be
replaced.
This warning indicates that the controller has received a message from the CAN bus that
another controller or device in the network has experienced a failure. As a consequence, the
traction controller itself cannot operate, but has to wait for the other controller or device to
recover from the failure.
In case of this warning, check the additional CAN bus devices for faults.
This warning occurs when the tiller is released after a fixed time in the standby mode with the
main contactor open (30 seconds).
After the next travel request, the warning disappears.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 260 (322)
NSP Service Manual
This alarm is displayed when the output of the built-in smart driver, which supplies the positive
to the electromechanical brake coil, is high when the tiller and the brake release switch are
open.
In such a case, check the wiring to see that there is no extra positive supply connected to the
electromechanical brake at the connector XA1 B/1 when the tiller and the brake release switch
are open.
If the output stays at a low value even when disconnecting the wire from the connector pin, the
problem is in the traction controller.
This is a safety related, self-diagnosis test within the logic. The watchdog circuit is composed of
two monostable multivibrators, so there is a double-check of the software execution.
This alarm can be caused by a hardware failure in one or both of the multivibrators or it can be
due to a software execution problem. In both cases, the problem is in the traction controller,
which must be replaced.
This alarm is displayed if the hydraulic valve coil load is too high for the controller valve driver
circuit.
In such a case, check the following:
• Hydraulic valve coil condition
• Wiring
If the device or its driving circuit is damaged, replace the controller.
Before switching the main contactor on, the software checks the power bridge. It turns the low
and high side power MOSFETs on one by one and expects the phase voltage to decrease
down to –Batt. If the phase voltage does not decrease, this alarm occurs.
This fault is not related to external components, so when it appears, replace the traction
controller.
This alarm is displayed if the solenoid valve EVXX (XX = 01, 02 or 03) driver is shorted.
Check if there is a short or low impedance between the negative of one of the coils and –Batt.
If not, the driver circuit is damaged and the controller must be replaced.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 261 (322)
NSP Service Manual
This warning is displayed if one of the solenoid valve’s EV (XY1 or XY2) coils is shorted.
Check if there is a short or low impedance between the negative of the EV coil and +Batt. If
not, the controller is damaged and must be replaced.
This alarm indicates that the maximum current gain parameters are at their default values,
meaning that the maximum current procedure has not been carried out.
This fault is not related to external components, so when it appears, replace the traction
controller.
This alarm occurs when the conversion of the analogue inputs provides frozen values.
If the alarm occurs permanently, replace the traction controller.
This alarm indicates that there is a mismatch between the H&S input and the tiller input.
In such a case, check the harness related to CAN#1 and CAN#29 with a voltmeter. If the state
of these inputs is OK, the problem is in the traction controller, which must be replaced.
This alarm indicates that the software is not compatible with the controller.
In case of this alarm, flash new software to the controller. If the alarm occurs permanently
replace the traction controller.
This alarm is displayed if the solenoid valve driver is damaged or the solenoid valve coil
impedance is too low.
In such a case, check the following:
• Solenoid valve coil impedance
• Wiring
If the solenoid valve driver circuit is damaged, replace the controller.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 262 (322)
NSP Service Manual
This alarm occurs when lifting and lowering demands are active at the same time.
Use a tester to check the possible reasons for this alarm. If both demands are active at the
same time, check the switches and wiring.
If no lifting and lowering signals are active at the same time outside the controller, the problem
is in the traction controller.
This alarm indicates that the lift lever voltage is out of range.
In such a case, check the following:
• Teach the lift lever values again.
• Check that the connectors and cables are in order.
• Replace the lift lever and teach the new values.
This alarm occurs when the lift lever output voltage differs from the values acquired at
calibration.
In such a case, check the functionality of the lift lever. Perform the lift lever calibration wizard
function.
This alarm indicates that the driver of the electromagnetic brake coil is not able to drive the
load.
The driver inside the traction controller is damaged, so the controller has to be replaced.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 263 (322)
NSP Service Manual
This alarm is displayed where there is no CAN message from the Curtis display.
This alarm can be caused by a CAN bus malfunction, which blinds the traction-display
communication. If not, it is an internal problem in the traction controller or in the Curtis display.
This warning indicates that the output of the controller thermal sensor is out of range.
This fault is not related to external components, so when it appears, replace the traction
controller.
At startup, the controller checks the battery voltage and verifies that it is within a certain
window around the nominal value. If this is not the case, this alarm is displayed.
In such a case, do the following:
• Check that the controller’s SET BATTERY parameter value matches the battery nominal
voltage.
• Check from the tester menu that the BATTERY VOLTAGE parameter shows the same
value as the battery voltage measured with a voltmeter. If it does not match, perform the
ADJUST BATTERY function.
• Replace the battery.
When adjusting the battery voltage, voltage should be measured from the key line, after the
reverse polarity protection diode. A good measuring point is, for example, the emergency stop
button terminal. If the battery voltage is measured anywhere else, it will cause invalid operation
of the battery discharge indicator.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 264 (322)
NSP Service Manual
The outputs of the amplifiers (used to measure the traction motor voltage) are checked to be
within a certain range. This alarm occurs when the voltage signals exceed 3 V or fall below 2 V
at the startup.
This fault is not related to external components, so when it appears, replace the traction
controller.
This alarm indicates that there is an error in the chosen slip profile parameters.
Check the value of those parameters in the HARDWARE SETTING menu.
This alarm indicates that the driver of the magnetic brake is shorted.
Check if there is a shortcut between XA1 A/4 and –Batt. Otherwise, the driver in the traction
controller is damaged and the controller has to be replaced.
Copyright© 2013 by MCFE. All rights reserved. Revision: B Document ID: 616838 265 (322)