AFD Enclosure Anchor Calcs
AFD Enclosure Anchor Calcs
AFD Enclosure Anchor Calcs
sm
_____________________________________________________________________________________________________________
ADF Enclosure Anchor Calculations
Component Information
ADF Enclosure Information [Pro/Dwg# 270979: Pg. 1]
Dry CG Height: CGh 48 in
Dry CG X-Distance: CGx 9 in
Anchor X-Spacing: dax 18 in
Operating Weight: W 1500 lbf
Overstrength Factor: Ω0 2.5 FP [ASCE 7-10: Tbl. 13.6-1]
Component Amplification Factor: ap 1.0 [2141-L: Tbl. 3]
W
CGh
Response Modification Factor: Rp 2.5
Component Importance Factor: Ip 1.5 [2141-L: Tbl. 4]
CGx
dax
Component Height in Structure: z 0.0 ft
Site Information
Spectral Acceleration: SDS 0.74 [2141-L: Tbl. 1]
Roof Height of Structure: h 52.25 ft [2141-L: Tbl. 2]
Seismic Design Force [ASCE 7-10: Eqn. 13.3-1]
Limits:
0.4 ap SDS W z Min.: FPmin 0.3 SDS Ip W 499.5 lbf
Full Tank: FP 1 2 266.4 lbf
Rp h
Max.: FPmax 1.6 SDS Ip W 2664 lbf
Ip
Use: FP 499.5 lbf
LRFD Anchor Forces (0.9 - 0.2SDS )D + 1.0E = 0.75D + 1.0E [ASCE 7-10: Sec. 12.4.2.3]
Overturning Check (Negative Result => No Overturning)
Full Tank: FP CGh 0.75 W CGx 1154.25 ft lbf
"Overturning Present!"
1/2
23 May 2022 18:05:35 - AFD Enclosure Anchor Calcs.sm
_____________________________________________________________________________________________________________
Maximum Anchor Forces (To be entered into PROFIS for anchorage check – attached)
Ω0 FP CGh 0.75 W CGx
Tension: Tu 1383.75 lbf
2 dax
Ω
0
FP
Shear: Vu 312.19 lbf
4
PROFIS Result
Anchorage: Use (4) 1/2Φ KWIK Bolt TZ-CS, 3.25" Min. Embed
2/2