REF542plus Om 755869 ENd
REF542plus Om 755869 ENd
REF542plus Om 755869 ENd
1MRS755869
Multifunction Protection and Switchgear Control Unit
Issued:
Version:
REF 542plus
Operator's manual
01.11.2002
D/14.02.2008
Contents
Copyrights ................................................................................. 7 1. Introduction..............................................................9
1.1. 1.2. 1.3. 1.4. 1.5. This manual.............................................................. 9 Use of symbols ......................................................... 9 Intended audience ..................................................... 9 Product documentation ............................................. 10 Document revisions.................................................. 10
4. Behavior at power up .............................................. 19 5. Changing the language displayed ............................ 21 6. Control modes........................................................ 25
6.1. Available control modes ............................................ 25 6.2. Changing the control modes ...................................... 25
9. Viewing measurements ........................................... 31 10. Viewing events ....................................................... 33 11. Viewing and changing the protection settings ........... 35
11.1. Viewing the protection settings................................... 11.2. Changing the protection settings ................................ 11.2.1. Changing the protection key mode.................. 11.2.2. Changing the protection parameters................ 11.2.3. Changing the active parameter set ................. 11.2.4. Viewing and changing control parameters ........ 35 35 35 36 38 39
12. Setting the time and date......................................... 41 13. Command page ...................................................... 43 14. REF 542plus commissioning mode........................... 45
14.1. 14.2. 14.3. 14.4. Binary input commissioning page ............................... Binary output commissioning page ............................. Analog input commissioning page .............................. Analog output 4- 20 mA commissioning page ............... 46 47 48 50
3
REF 542plus
1MRS755869
14.5. Analog input 4-20 mA commissioning page.................. 51 14.6. Optical inputs commissioning page ............................. 52 14.7. Optical output commissioning page............................. 53
16. Troubleshooting...................................................... 61
16.1. Error messages ....................................................... 61 16.2. Clearing the configuration inside the unit ..................... 66 16.3. Primary objects incorrect visualization ......................... 67
17. Terminology ........................................................... 69 18. Abbreviations ......................................................... 71 19. Appendix A: Connection diagrams ........................... 73
19.1. Analog Inputs.......................................................... 19.2. Binary inputs and outputs.......................................... 19.2.1. Static ......................................................... 19.2.2. Electromechanical........................................ 19.2.2.1. BIO3 ........................................... 19.3. Other connections.................................................... 19.3.1. Analog outputs 0/4-20 mA ............................. 19.3.2. Analog inputs 4-20 mA ................................. 19.3.3. Communication module ................................ 19.3.4. Power supply .............................................. 19.3.5. Time synchronization.................................... 19.3.6. HMI ........................................................... 20.1. 20.2. 20.3. 20.4. 20.5. 20.6. Commands ............................................................. Reset page............................................................. Protection ............................................................... Control................................................................... Test ....................................................................... Service page........................................................... 20.6.1. Statistics .................................................... 20.6.2. Versions ..................................................... 20.6.3. Hardware identification.................................. 20.6.4. Communication ........................................... 20.6.4.1. IEC 103 communication page.......... 75 78 78 79 79 80 80 81 82 82 82 83 85 85 87 87 87 87 88 88 89 91 92
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
20.6.4.2. LON communication page............... 94 20.6.4.3. SPA communication page ............... 95 20.6.4.4. Modbus communication page .......... 95 20.6.4.5. CAN communication page .............. 96 20.6.4.6. HMI communication page ............... 99 20.6.4.7. Ethernet IP page ..........................100 20.6.4.8. Ethernet communication page ........101 20.6.5. Char map .................................................. 110 20.6.6. LCD contrast.............................................. 110 20.6.7. Load flow direction ...................................... 111 20.7. Test page .............................................................. 111 20.7.1. Test HMI ................................................... 111 20.7.2. Test primary object...................................... 112
21. Appendix C: Tripping time indication...................... 113 22. Appendix D: Self Supervision ................................ 115 23. Appendix E: Telnet protocol................................... 125
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Copyrights
The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document. In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document. This document and parts thereof must not be reproduced or copied without written permission from ABB Oy, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. Copyright 2005 ABB. All rights reserved.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
1.
1.1.
Introduction
This manual
Before attempting any operation with REF 542plus, read this manual carefully first. This manual describes how to use the interface of REF 542plus (LD HMI, Local Detached Human Machine Interface). Note that HMI views and pictures are to be considered exemplary. Do not make any changes to the REF 542plus configuration unless you are authorized to do it and familiar with REF 542plus and its Operating Tool. This might result in malfunction and loss of warranty.
1.2.
Use of symbols
This publication includes the following icons that point out safety-related conditions or other important information: The electrical warning icon indicates the presence of a hazard which could result in electrical shock.
The warning icon indicates the presence of a hazard which could result in personal injury.
The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
The information icon alerts the reader to relevant facts and conditions.
Although warning hazards are related to personal injury, it should be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.
1.3.
Intended audience
This manual is intended for operators, supervisors and administrators to support normal use of the product.
9
REF 542plus
1MRS755869
1.4.
Product documentation
Name of the Manual Product Guide Configuration Manual iButton Programmer User Manual Manual Part 3, Installation and Commission Manual Part 4, Communication Motor Protection with ATEX Certification, Manual SCL Tool Configuration Manual Protection Manual Technical Reference Manual Technical Reference Modbus RTU Web Manual, Installation Web Manual, Operation IEC 61850 Protocol Implementation extra Information for Testing (PIXIT) IEC 61850 Conformance Statement IEC61850 Tissues conformance statement Document ID 1MRS756269 1MRS755871 1MRS755863 1 VTA100004 1VTA100005 1MRS755862 1MRS756342 1MRS755860 1MRS755859 1MRS755868 1MRS755865 1MRS755864 1MRS756360 1MRS756361 1MRS756362 Real Time Clock Synchronization, IRIG-B Input Time Master 1MRS755870
1.5.
Document revisions
Version 1VTA100172-Rev 1, en 1VTA100172-Rev 2, en 1VTA100172-Rev 3, en 1VTA100172-Rev 4, en A IED Revision number Date 01.11.2002 22.10.2003 03.05.2004 04.04.2005 28.02..2006 History First release Updated to version 4D02 Updated Updated Document updated * language * layout Updated to software version V4E03x Updated to software version V4E04x Updated
B C D
Applicability
This manual is applicable to REF 542plus Release 2.5 SP3, software version V4E04x.
10
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
2.
Safety information
Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected. Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed. The frame of the device has to be carefully earthed.
The device contains components which are sensitive to electrostatic discharge. Unnecessary touching of electronic components must therefore be avoided.
11
12
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
3.
HMI features
The REF 542plus is shown in Fig. 3.-1. This HMI features a back-illuminated LCD, 8 push buttons, several LEDs and an electronic key sensor. This new international HMI is a part of the product release of REF 542plus release 2.5. The resolution of the display is 320x240 (QVGA) and the display supports full Unicode character set. Consequently, all languages, for example Chinese, can be displayed clearly. With this HMI two different languages can be handled simultaneously. The local language can be defined as the first language with the related operating tool. Then, the second language becomes automatically English. The language on the HMI can be changed from one to the other very easily.
A051327
Fig. 3.-1
The LCD in the SLD view provides a graphical representation of the primary objects controlled or monitored by REF 542plus in the switchgear. The right half of the LCD is for plain text visualization such as measurements and protection events. The contrast level is automatically controlled for an optimum reading, it can also be adjusted as wanted. The HMI panel is organized in three main areas.
3.1.
Control area
The left side of the HMI panel is for primary objects control. The command buttons and the information related to the switchgear control are placed on this area
13
REF 542plus
1MRS755869
A051328
Fig. 3.1.-1
This section of the display shows the Single Line Diagram (SLD) of the controlled panel and the measurement bars. Text can be added in this section to improve the understanding of SLD.
*
Command buttons
The Primary Object Control can be performed with the following push buttons to allow operating the primary objects if configured as selectable. The command push buttons for local operation of the switching devices are:
Open: to open the selected object. Close: to close the selected object. Select: to select the object. The selected object appears highlighted. CB Fast Opening: to allow opening of the circuit breaker independently from the selected control mode. When pressed simultaneously with the normal open button, this button allows opening the circuit breaker independently from the selected control mode. This feature must be enabled in the unit with the Operating Tool.
*
E-Keys Sensor: this is the sensor for the electronic keys. The sensor automatically detects which key has been inserted. The two keys are usually labelled Protect and Control to distinguish them. Protection key: is specialized to the protection environment allowing changing of parameters and other functions related to the protection. Control Key: this is dedicated to the control modes. It allows changing the operating mode of REF 542plus. The different operating modes discipline the access to the primary objects by the different REF 542plus interfaces (HMI and SCADA). When required, a Super User key to access both modes can be
14
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
provided. The Super User key is also needed to access the commissioning test mode. The password codes stored in the key can be customized in each REF 542plus for access restriction purposes. SLD view: this is the graphical part of the LCD. This part shows the single line diagram of the switchgear. The status of the primary objects is dynamically updated after every operation. If for example the circuit breaker has been opened, its representation will reflect it.
3.2.
A051333
Fig. 3.2.-1
*
Menu Navigation: these push buttons allow navigation trough the REF 542plus menus.
Pressing this button, the unit goes back to the former menu. The up direction push button. The down direction push button. The enter push button to enter into the selected menu or to select the highlighted submenu.
Commands: this menu shows the configured FUPLA commands. E-Key status: to display and change the unit modes with the electronic keys. Alarms: it displays the indication LEDs status. Measurements: it displays the available measurements. Resets: to acknowledge alarms and other quantities.
15
REF 542plus
1MRS755869
* *
Events: to display protection starts and trips events. Protection: it displays the protection functions installed in the unit, and allows displaying and changing their settings. Control: it displays the control functions list installed in the unit and allows displaying and changing their settings. Service: relevant information on the HW and SW configurations and basic setting of REF 542plus. Tests: to access the test mode for the HMI and the primary objects. Access to a few submenus is allowed only in some modes.
LED bars: The three LED bars are available to show the most relevant measurements acquired by REF 542plus for a quick inspection of the switchgear load situation. The three bars are marked M1, M2, and M3. Each bar is composed of twelve LEDs, ten green and two red ones. The ten green LEDs are normally dedicated to display between 0% and 100% of the nominal value of the configured measurement. Each LED corresponding then to 10% of the nominal value. The two red LEDs indicate an overload condition of 20%. The measurements displayed by the bars are set with the Operating Tool. Indication LEDs: 8 freely programmable, three-color LEDs are available for indications. There are 4 pages of these LEDs. As a result, a total of 32 indication options can be programmed for events and status regarding protection, control, monitoring, binary inputs and so on. The assignment of the LED to a specific condition is done with the Operating Tool. Infrared (IrDa) interface: This is the IrDa serial interface port to connect REF 542plus to a personal computer. By using the appropriate cable and the Operating Tool, the following actions are possible: * Download a configuration into the unit. * Upload the current configuration from the unit. * After a fault, upload the fault recorder data. This is possible only if the fault recorder has been previously enabled with the Operating Tool.
Upload other information (measurements, binary inputs status, binary output status). Do not make any changes to the REF 542plus configuration unless you are familiar with REF 542plus and the Operating Tool. This might result in malfunction and loss of warranty.
16
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
3.3.
A051338
Fig. 3.3.-1
1 2 3 4
Ready: Operation status of the unit IBB Error: Network communication status Alarm: Indication according to the programmed alarm condition Interlocking: Indication for inadmissible control action
Ready. This green LED is turned on when the unit is in the operational state. The LED is switched off when the auxiliary power is not present or when the unit is not operational (FUPLA is not running). IBB(interbaybus) Error. This LED is meaningful only when the REF 542plus is equipped with a communication module. When the configured communication module is detected the LED turns on to green. If the module is not detected or fails, the LED turns red. When a Modbus communication module is installed, the LED becomes orange if the communication error rate increases. It becomes red when the communication error rate prevents good communication. The LED comes back to green when no communication errors occur or by resetting the module status registers (see the Modbus technical reference). When there is no communication module, the LED is always switched off. * Alarm: this LED turns to red when the user defined alarms become true. Several arbitrary alarm conditions can be defined and configured with the Operating Tool. Alarm conditions could be the trip of a protection function, loss of SF6 in the circuit breaker and so on. When this LED is on, it is not possible to close the circuit breaker or to download a new configuration. The alarm must be acknowledged first. * Interlocking Error: this LED is usually green. It turns temporarily to red when the user attempts an operation that would violate the programmed interlocking conditions; for example switching a disconnector with the circuit breaker in closed position.
17
18
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
4.
Behavior at power up
Before energizing the switchgear, verify that the REF 542plus protection functions are properly set and that the unit is properly working (READY LED green).
At power up, the HMI unit shows on the LCD for a few seconds the following:
A051339
Fig. 4.-1
After that, the LCD left part shows the switchgear single diagram while the right part shows the default menu. When the initialization is completed and the unit is operational, the ready LED is on.
19
20
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
5.
A060408
Fig. 5.-1
The following Fig. 5.-2 shows how to change the active language on the HMI. The prerequisite is that there is a local language defined. Do as follows:
* * *
Go to the main menu by pressing MENU . Press UP and DOWN simultaneously to get to the Language page. Press ENTER to execute the language change.
21
REF 542plus
1MRS755869
A060409
Fig. 5.-2
The former HMI of the REF 542plus (HMI Version V4) can still be applied together with the base unit having the new firmware of release 2.5. provided the firmware of the HMI is upgraded accordingly. After upgrading the firmware the HMI V4 behaves almost the same as the new international HMI V5. Due to the low resolution of the LCD on the former HMI, the displaying certain languages, such as Chinese, is not possible. Other languages, such as Russian with cyrillic characters, can be used as the first language.
With release 2.5 SP1, an optional Ethernet module for the IEC 61850 communication protocol can be applied. Therefore, new menu items appear on the HMI display. Because of the limitation of the existing memory, the use of the HMI version V4 is not reasonable and it is not recommended anymore.
The design of the new international HMI V5 has been improved by extending the existing memory on the related mainboard. The information files for both languages are stored on the HMI after the download of the configuration file by the operating tool. The display of the language file is immediately available after the language change. In case of HMI V4 the language files are stored in the base unit. If the
22
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
display shall be changed, the relating language file must first be uploaded. After reset of the LCD the requested language will be displayed.
23
24
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
6.
6.1.
Control modes
Available control modes Local Control
It is possible to control the circuit breaker and other primary objects from the HMI using the object control buttons. Open and close operations are possible only if the interlocking logic programmed into the unit allow them. Remote control from the SCADA is inhibited. Uploading and downloading the configuration via the optical interface is possible.
Remote Control
The control of the circuit breaker and other primary objects from the HMI is inhibited. The control is possible only remotely. Uploading and downloading the configuration via the optical interface is possible.
No Control
It is not possible to control the circuit breaker and other primary objects both from the HMI and remotely. Any kind of operation apart from the protection trip is inhibited. Uploading and downloading the configuration via the optical interface is possible.
6.2.
25
REF 542plus
1MRS755869
A051340
Fig. 6.2.-1
26
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
7.
27
28
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
8.
8.1.
A051341
Fig. 8.1.-1
Alarm visualization
8.2.
Resetting alarms
At first, the reset menu must be selected. Select the reset menu with the navigation . buttons. Highlight the reset alarm line in the menu and then press ENTER
29
REF 542plus
1MRS755869
Some alarms might not be reset before the cause that generated it has been removed. For example, an alarm due to an error in the tripping circuit (coil supervision) cannot be reset before the tripping coil is replaced. Whereas an alarm generated by a trip of a protection function is normally reset with this procedure.
A051342
Fig. 8.2.-1
Resetting alarms
30
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
9.
Viewing measurements
REF 542plus offers complete measurements set to the user. To view the measurements, select the measurement menu with the navigation button. Use the UP and DOWN buttons to browse the measurement pages. The available measurements depend upon the unit configuration. In the maximum configuration, the following measurements are displayed:
* * * *
* *
* * * * *
IL1, IL2, IL3, in A; line currents, measured values U1E, U2E, U3E, in kV; phase to earth voltages, measured values UL12, UL23, UL31, in kV; phase-to-phase voltages, computed values.1) IL1 mean, IL2 mean, IL3 mean, in A; mean currents in the observation period, computed values IL1 max, IL2 max, IL3 max, in A; maximum peak currents in the observation period, computed values Frequency, in Hz; measured values Active power, in kW; reactive power in kVAr, apparent power in kVA, computed values Power factor, computed value Active energy in MWh, reactive energy in Mvarh; computed values Operating hours, in hours. This is the total working hours of the unit Switch cycle, number the circuit breaker close-open cycles Added switched current, in kA; sum of the interrupted currents by the circuit breaker THD (total harmonic distortion) The observation period is set with the Operating Tool. It can be from 0 minutes up to 30 minutes. If the observation period is set to 0, the corresponding measurements are disabled.
The refresh time for the displayed measurements is about half second.
1)
REF 542plus can also use phase-to-phase voltage transformers. When used, phase-to-phase voltages are measured and phase to earth voltages are computed.
31
REF 542plus
1MRS755869
A051343
Fig. 9.-1
Measurements visualization
The available measurements depend upon the analogue input module type and the unit configuration.
32
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
10.
Viewing events
REF 542plus records the last 30 protection events (start, trips, block and other). This internal memory is managed as a circular buffer, for example the 31st event overwrites the 1st oldest one. In case of a power loss, events are kept because they are stored in the non-volatile memory. For each event, the following information is recorded: involved protection function, event type, relevant measurement (current, voltage, frequency), date and time (up to milliseconds). Events are displayed using the full screen; the single line diagram is thus not visible.
A051344
Fig. 10.-1
Events display
To display the protection events, select the Start/Trip menu with the navigation and DOWN to browse through the events. buttons. Use UP
33
34
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
11.
11.1.
A051345
Fig. 11.1.-1
and DOWN to highlight the desired protection function and press . Then, the protection parameters will be displayed in one or more
11.2. 11.2.1.
Set: It is possible both to visualize and to change the protection settings. Operational: It is possible to visualize the protection settings but it is not possible to modify them.
In both modes, the protection functions are active. In the operational mode, parameterization of the protection functions is also possible by a SCADA when present. In the set mode, parameterization from a SCADA is inhibited.
35
REF 542plus
1MRS755869
The procedure to change the protection mode is identical to changing the control mode. At first, the menu E-Key must be selected. Then the protection key must be placed in the electronic key sensor. Select then the required protection mode by and DOWN until it is highlighted. Confirm the selection by using UP . After having pressed ENTER push button, the E-key pressing ENTER status menu will appear again. Verify that the required protection mode has been properly set in the unit, looking in the HMI lower left corner.
A051346
Fig. 11.2.1.-1
11.2.2.
36
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051347
Fig. 11.2.2.-1
Press again to leave the protection functions menu. The unit will then ask what to do with the changes: The following screen will appear:
A051348
Fig. 11.2.2.-2
37
REF 542plus
1MRS755869
Select the desired choice with Up or Down and then press ENTER confirm it. The meaning of the choices is as follows:
to
Store permanently: The new parameters are stored in the unit internal memory. They will be used immediately and for all the next starts. Save temporarily: The new parameters are used immediately but are not saved in the unit internal memory. Next starts will use the old parameters. Discard changes: The new parameters are discarded. There are no effects. Do not switch off the Base Unit power supply during parameter storing. The whole unit configuration might be corrupted and a new configuration download might be necessary.
11.2.3.
A051349
Fig. 11.2.3.-1
38
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
11.2.4.
A051350
Fig. 11.2.4.-1
39
40
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
12.
A051351
Fig. 12.-1
The time is edited by using UP , DOWN and then ENTER to confirm. The complete date and time must be inserted: year, month, day, hour, minutes and seconds. Unit connected to a master clock: When the unit is connected to a master clock (typically a clock which receives its signal from a GPS), only the year can be set. The remaining part of the date and time is received from the master clock. Unit connected to a SCADA system: Usually, the SCADA transmits to the unit the date and time according to the used protocol services. There are some differences depending upon the used protocol. IEC 60870-5-103 protocol: The IEC 60870-5103 module is the time master. Setting the time and date from the HMI is inhibited. LON LAG 1.4 protocol: The LON module is the time master. Setting the time and date from the HMI is inhibited. SPA bus and Modbus protocols: usually, the SCADA sets the date and time, nevertheless setting the time and date from the HMI is allowed.
41
42
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
13.
Command page
From this page, it is possible to access the HMI command objects configured in the application software of REF 542plus. For more information on these objects, refer to Operating Tool user manual.
A051352
Fig. 13.-1
Command page
the command is
43
44
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
14.
Switch off the REF 542plus Base Unit. Place the super user key on the e-key sensor and keep it contacted. Switch on the Base Unit.
When the Base Unit starts the e-key is detected. The commissioning mode is entered. Verify this reading on the start-up status line COMMISSIONING MODE. When this text is visible, the e-key can be unplugged from the e-key sensor. This mode allows driving directly the binary outputs of the Base Unit. If they are connected to primary objects, operations are thus possible. The interlocking functions are disabled. Before accessing this mode, put the switchgear in safe conditions.
45
REF 542plus
1MRS755869
A051353
Fig. 14.-1
14.1.
46
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051354
Fig. 14.1.-1
14.2.
47
REF 542plus
1MRS755869
A051355
Fig. 14.2.-1
14.3.
48
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Channel descriptor Channel number : Values Analog input x, where x addresses the analog input channel. CT (1-5 A) Rated secondary current related to the current input. CT (0,2 A) Rated secondary current. VT (100 V) Rated secondary voltage (Volt). Sensor Voltage output of the sensor (Volt).
A051356
Fig. 14.3.-1
Analog inputs commissioning page for the 3CT, 3VT, 1VT, 1CT module
With sensor inputs, the displayed values are the voltages read by the analog channels. For example, by using the voltage divider 10.000/1 applying 20 kV on the sensor, the measurement will show 2 Volt. For the current sensor 80 A/150 mV, applying 80 Amp on the sensor the measure will be 0.150 Volt.
49
REF 542plus
1MRS755869
A051357
Fig. 14.3.-2
Analog inputs commissioning page for the 6 sensor module connected to 3 voltage divider and 3 Rogowski coils
14.4.
50
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051358
Fig. 14.4.-1
14.5.
51
REF 542plus
1MRS755869
Channel descriptor Channel number : Values General 4-20 mA sensor General sensor Trafag Density, Temperature x. Where x addresses the analog input channel. General Sensor 4-20 mA, for Trafag the density and the temperature.
A051359
Fig. 14.5.-1
14.6.
Values:
52
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051360
Fig. 14.6.-1
14.7.
, DOWN
53
REF 542plus
1MRS755869
A051361
Fig. 14.7.-1
54
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
15.
15.1.
Connection to PC
Infrared (IrDa) to RS232 converter cable
A special cable with an optical infrared (IrDa) interface is needed to connect REF 542plus to a serial port of a PC. This cable is available from ABB.
Fig. 15.1.-1
A060412
Fig. 15.1.-2
Interface on the HMI for the serial cable with optical infrared (IrDa)
15.2.
Null-modem cable
If there is no HMI applied or a direct connection to the base unit is preferred, a standard null-modem cable can be used to connect the base unit via the so called RS 232 service interface (X72) to the PC.
55
REF 542plus
1MRS755869
15.3.
Downloading a configuration
When the connection is set up with the appropriate cable, it is possible to download the configuration into REF 542plus with the Operating Tool. Connect the infrared (IrDa) converter to the foreseen connector on the HMI and the D-sub connector to the PC. Start the Operating Tool on the PC and select the serial port to be used inside the program.
A051363
Fig. 15.3.-1
56
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
15.3.1.
A051364
Fig. 15.3.1.-1
Select the COM port where the RS232/Infrared (IrDa) cable or RS232 null-modem cable is plugged in. Apply the following settings: Appplication with the new international HMI V5 or connection with a null-modem cable directly to the base unit:
Baud rate Data bits Stop bits Parity 115,200 8 1 None
57
REF 542plus
1MRS755869
19,200 8 1 Even
After the download of the configuration file using the service or the debug port, press ENTER key on the PC keyboard to end the download process.
Base Unit slave address: This number can be from 1 to 254. When several Base Units are connected to the same HMI, this number uniquely identifies the Base Unit. The default address is 99. To configure or to change the Base Unit slave address there are two methods:
*
Open the application file with the Operating Tool and change it in the hardware settings.
A051365
Fig. 15.3.1.-2
*
Via the HMI menu > Service page > Communication > HMI PORT
58
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051366
Fig. 15.3.1.-3
Please note: When the ALARM LED is on, the download is inhibited. The configuration download starts as soon as the relevant push button on the Operating Tool is clicked. The previous configuration inside REF 542plus is destroyed and overwritten by the new one. REF 542plus is fully operational during the download. After the download, REF 542plus starts to write the new configuration in the non-volatile with a low priority task in background. This task might take several seconds. Do not switch off Base Unit power supply during the storing. The whole unit configuration might be corrupted and a new configuration download might be necessary.
The download is possible in all control modes, provided the status of the protection is switched by the corresponding electronic key in operational mode. Communication to the SCADA system is operational during the download. After the download, REF 542plus automatically starts with the new configuration.
59
REF 542plus
1MRS755869
When the download is completed, the unit may change the operational status of the output relays due to the new logic configured in the application file. It is strongly recommended to put the switchgear in safe conditions before performing the download.
15.4.
15.5.
fault recorder file binary input status binary output status measurements software version
All this data is accessible with the Operating Tool from the transfer menu. Refer to the Operating Tool manual for more details.
60
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
16.
16.1.
Troubleshooting
Error messages Base Unit not responding, communication corrupted or wrong slave address
When the HMI is not able to communicate with the Base Unit, the following information appears on the LCD:
A051367 2
Fig. 16.1.-1
Solution: Check that the Base Unit is powered and regularly working. Look at the status LED on the connector panel (Slot X7). The LED close to the analog inputs is related to the watchdog. When the Base Units is working this LED is on with a weak light. The other LED is related to the communication with the HMI. When the communication is properly working, this LED is blinking. When the communication is not working, the LED can be either ON or OFF. It depends on when the communication is interrupted. Check that the connection cable between the HMI and the Base Unit is inserted both in the HMI and in the Base Unit (Base Unit connector X73 and HMI connector X20) and properly tighten. Check the slave address of the connected Base Unit to be polled. The address is configured in the application file. If you do not know you can enter the following page by pressing ENTER.
61
REF 542plus
1MRS755869
Power Up Operations
After pressing the key the Power Up Operation menu is shown as in the following Fig. 16.1.-2.
A051437 2
Fig. 16.1.-2
If the older version of the HMI V4 is used, the menu of the Power Up Operations is slightly different in accordance to the menu in the former release 2.0. The menu is as shown in the following Fig. 16.1.-3.
A060410
Fig. 16.1.-3
Select HMI <-> Base Unit address scanning menu item and press ENTER. The HMI will start polling all the addresses to find the connected Base Units. When a unit is found, its address and the feeder name are reported.
62
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051438 2
Fig. 16.1.-4
Select the HMI <-> Base Unit address to change the address to be polled.
A051439 2
Fig. 16.1.-5
Press ENTER
63
REF 542plus
1MRS755869
A051440 2
Fig. 16.1.-6
A051441 2
Fig. 16.1.-7
Solution: Download the configuration into the unit by using the serial cable and the Operating Tool.
64
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051442 2
Fig. 16.1.-8
Solution: Try to download the configuration again. If after two or three attempts the error remains, contact ABB.
Wrong configuration
The following message appears when a not correct configuration has been downloaded in the Base Unit. This message can also appear when the configuration contains protection functions that exceed the unit functionality level.
A051443 2
Fig. 16.1.-9
The WRONG CONFIGURATION can also be caused by other reasons. The error handling will be described in Appendix D, where the Self Supervision is explained.
65
REF 542plus
1MRS755869
* * *
WRONG COM CONFIG WRONG TCP-IP CONFIG WRONG MODTCP CONFIG WRONG WEBREF CONFIG WRONG SMS CONFIG WRONG COMBOARD CONF WRONG COMBOARD TYPE WRONG COMBOARD VERS COMBOARD NOT INSTALL COMBOARD NOT DETECT COMBOARD NOT CONFIG
Invalid file format Invalid TCP-IP configuration or version not compatible Invalid MODTCP configuration or version not compatible Invalid WEBREF configuration or version not compatible Invalid SMS configuration or version not compatible Invalid COM board configuration COM board configured does not match with the one detected COM board configuration version does not match with the one handled by the installed COM board COM board configured but not installed. It is physical check on DPM presence. COM board configured but not detected or the COM is present but it doesn't work properly COM board detected but it has not been configured
* * *
16.2.
Switch off the Base Unit power supply (disconnect the X10 connector from the Base Unit). Press simultaneously the UP and DOWN buttons on the HMI and keep them pressed. Switch on the Base Unit again.
After this procedure, REF 542plus is without configuration. Download a new configuration in the unit. This procedure deletes the configuration stored inside REF 542plus. The configuration cannot be recovered. Upload the configuration and save it before deleting it from the unit.
66
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
16.3.
A051444
Fig. 16.3.-1
REF 542plus has no voltage at both inputs indicating the primary object position
The primary object is visualized both in open and close positions when both contacts are closed (REF 542plus has voltage at both its contact inputs).
A051445
Fig. 16.3.-2
REF 542plus has voltage at both inputs indicating the primary object position
Solution: Check the wiring of the primary object. Verify that REF 542plus connectors are properly inserted and tightened.
67
REF 542plus
1MRS755869
Note: When the primary object in such an undefined positions, issuing an open command will activate the open coil on the circuit breaker. The open operation is never blocked. The close operation with the object in the undefined position is blocked. A close command will be discarded and will turn the interlocking error LED on.
68
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
17.
Terminology
Term Ethernet Modbus Description Physical communication network to transfer Internet data of the REF 542plus to the PC and back. By extension, communication board implementing the Modbus protocol for REF 542plus.
69
70
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
18.
Abbreviations
Abbreviation BIO CAN CB CT EEPROM FUPLA GPS HMI HW IBB ID IEC IP LAG LCD LD LED LON MC PC RAM SCADA SLD SNTP SPA TCP VT Description Binary input and output board Controller area network Circuit-breaker Current transformer Electrically Erasable Programmable Read-Only Memory Function block programming language; Functional programming language; Function plan; Function chart Global positioning system Human-machine interface Hardware Interbaybus Identifier; identification International Electrotechnical Commission Internet protocol Lon application guide Liquid crystal display Logical device Light-emitting diode Local operating network Micro controller Personal computer Random access memory Supervision, control and data acquisition Single-line diagram Simple Network Time Protocol Data communication protocol developed by ABB Transmission Control Protocol Voltage transformer
71
72
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
19.
A051446
Fig. 19.-1
REF 542plus wide housing connections plate with mixed analog input connector
73
REF 542plus
1MRS755869
A051447
Fig. 19.-2
REF 542plus standard housing connections plate with mixed analog input connector
Connectors
Meaning Base Unit power supply First BIO, input First BIO, output Second BIO, input Second BIO, output Third BIO, input Third BIO, output 4-20 mA analog outputs, 4-20 mA analog inputs 4-20 mA analog input RS 232 service interface 4-20 mA analog CAN service interface Modbus RS 485, channel 2; COM L-COM I TX; SPABUS RX Modbus RS 485, channel 1; COM L-COM I RX; SPABUS TX Modbus optical, RX channel 1 Modbus optical, TX channel 1 Modbus optical, RX channel 2 Modbus optical, TX channel 2 Optical LC connector on the Ethernet module Optical LC connector on the Ethernet module Electrical RJ-45 connector on the Ethernet module Electrical RJ-45 connector on the Ethernet module Ethernet 10 Mb/s RJ-45 CAN Open ISO11898 connector
74
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Connector X72 X73 X74 X75 X76 X77 X80 X81 X82 X83 X84 X85 X86 X87 X88
Meaning Mainmodule RS232 service or debug interface HMI connection Time synch input HSTS Input HSTS Input HSTS Output Analog inputs Sensor 1 Sensor 2 Sensor 3 Sensor 4 Sensor 5 Sensor 6 Sensor 7 Sensor 8
19.1.
Analog Inputs
REF 542plus can have a maximum of 8 analog input channels. These inputs are divided into three measurement groups:
* * *
Measurement Group 1: channel 1, channel 2, channel 3 Measurement Group 2: channel 4, channel 5, channel 6 Measurement Group 3: channel 7, channel 8
Group 1 and group 2 have to be homogeneous, which means they can measure 3 currents or 3 voltages. For example, measurements of 1 current and 2 voltages are not allowed. Group 3 can get any type of signals: 2 currents, 2 voltages, 1 current and 1 voltage and so on. Group 1 and group 2 can be used for homogeneous current or voltage measurements both from instrument transformers and non-conventional sensors. Group 3 can be used in a heterogeneous way. Channel 7 and 8 in group 3 can be used for earth-fault current with CT type input; residual voltage, or for the synchrocheck function with VT or sensor type input. The input CT 0.2A is commonly used with a toroidal transformer for sensitive earthfault current measurement. Instrument current transformers can have secondary windings ratio /1 A or /5 A. The primary nominal current (for example 400 A) is selected with the Operating Tool. The secondary current (for example /5 A) is automatically selected connecting the right wire to the analog input module.
75
REF 542plus
1MRS755869
The Rogowsky coil can be used for current sensing. The correct ratio of the Rogowsky coil is selected with the Operating Tool. The resistive divider can be used for voltage sensing. The ratio is selected with the Operating Tool. The physical input on the unit is the same both for voltage and current sensing, the selection is done via the Operating Tool. Therefore, it is possible for example to use 6 Rogowsky coils, 6 voltage dividers, or 3 Rogowsky coils and 3 voltage dividers. To detect which analog input module is present inside the unit, look in the identification label stick on the unit itself, or on the HMI service page under the HW identification submenu.
A051450
Fig. 19.1.-1
The analog input for sensor is the same both for voltage and current sensing. To find out whether an input is for current or for voltage, the Operating Tool is needed. X81 corresponds to analog input 1 (sensor 1 in the Operating Tool), X82 to analog input 2 (sensor 2 in the Operating Tool) and so forth.
A051451
Fig. 19.1.-2
The connector for conventional instrument transformer has twenty-four pins. The following Table 19.1.-1 defines which input is connected to what:
Table 19.1.-1
1 2 3 4 5 6 7 8 9 10 11 T1/R T8/R
76
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
T8/1 T4/3 T2/2 T6/3 T7/2 T4/2 T2/3 T6/2 T7/3 T4/1 T2/1 T6/1 T7/1 T7/B T7/A
B: Black wire for voltage transformer. R: Red wire for voltage transformer. 1: 1 A input for current transformer. 2: Common input for current transformer. 3: 5 A input for current transformer. Example: To determine the pins for the analog input module 1VCF750170R0817: 3CTs, 3VTs, 1CTs; used with transformers with 1 A on the secondary windings. The following connection must be done: Analog input 1; the current transformer for phase 1 must be connected on pins 11 and 3 (common). Analog input 2; the current transformer for phase 2 must be connected on pins 22 and 14 (common). Analog input 3; the current transformer for phase 3 must be connected on pins 10 and 2 (common). Analog input 4; the voltage transformer for phase 1 to earth must be connected on pins 21 and 17. Analog input 5; the voltage transformer for phase 2 to earth must be connected on pins 5 and 1. Analog input 6; the voltage transformer for phase 3 to earth must be connected on pins 23 and 19. Analog input 7, for the toroidal transformer for the residual current must be connected on pins 24 and 16 (common).
77
REF 542plus
1MRS755869
A051453
Fig. 19.1.-3
The picture above shows the connector for the mixed analog input module when both sensors and conventional instrument transformers are used. To find out which connector is used for what, identify the module code from the identification label stick on the unit and see Table 19.1.-1.
19.2.
19.2.1.
Static
In the static module, digital inputs are implemented with optocouplers and digital outputs are implemented with power transistors. Two different module types are available, with control coil continuity and without. Each module features: 14 digital inputs, 3 power outputs, 4 normal outputs, 2 signal outputs, 1 watchdog output and optionally 2 coil supervision circuits. For more information, refer to the REF 542plus Technical Reference Manual.
78
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051454 2
Fig. 19.2.1.-1
Two static binary input and output modules with and without coil continuity check
19.2.2.
Electromechanical
In the electromechanical module, digital inputs are implemented with optocouplers and digital outputs are implemented with electromechanical relays. REF 542plus can be equipped with electromechanical module type BIO3.
19.2.2.1.
BIO3
Twelve different types of BIO3 are available depending upon the supply voltage and other features.
Table 19.2.2.1.-1
BIO3 Code 1VCF750132R0801 1VCF750132R0803 1VCF750132R0801 1VCF750132R0803 1VCF750132R0802
79
REF 542plus
1MRS755869
Description Binary I/O3 - 80..250 VDC/50 VDC Standard with Static Channel Binary I/O3 - 80..250 VDC/50 VDC Standard with interconnected '-' on inputs Binary I/O3 - 80..250 VDC/50 VDC Standard with Static Channel and with interconnected '-' on inputs Binary I/O3 - 80..250 VDC/72 VDC Standard Binary I/O3 - 80..250 VDC/72 VDC Standard with Static Channel Binary I/O3 - 80..250 VDC/143 VDC Standard Binary I/O3 - 80..250 VDC/143 VDC Standard with Static Channel
A051455
Fig. 19.2.2.1.-1
19.3. 19.3.1.
80
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051457
Fig. 19.3.1.-1
19.3.2.
81
REF 542plus
1MRS755869
A051458
Fig. 19.3.2.-1
Only passive sensors, for example those that are powered from the loop can be connected to the 420 mA analog input module.
19.3.3.
Communication module
The communication module uses connectors from X60, X61, X62, X63, X64 and X65 depending on the physical media type (RS 845, glass or plastic fiber).
19.3.4.
Power supply
Power supply for the Base Unit is X10.
19.3.5.
Time synchronization
The optical input for time synchronization is X74.
82
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
19.3.6.
HMI
A051459
Fig. 19.3.6.-1
HMI connectors
Fig. 19.3.6.-1 shows the back side of the HMI. The connector for the HMI power supply is X10, which is located on the right-hand side of the Fig. 19.3.6.-1. The serial cable for the connection to the base unit is to place on the other connector X20 on the left-hand side. Respect the right polarity on the HMI power supply to avoid damages to the unit.
83
84
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
20.
A051460
Fig. 20.-1
The access to some submenus to change parameters or to reset indication depends on the actual operating modes. The operating mode is set with two different electronic keys. With the CONTROL key the following operation modes are selectable:
* * * *
20.1.
Commands
The command in this submenu can be activated if the active mode is Local or Local & Remote. In other modes the activation will be denied.
20.2.
Reset page
From this page, it is possible to reset alarms and other quantities. Some reset actions are possible only if REF 542plus is in the proper mode. The possibility of reset in the different submenus is described in the following:
85
REF 542plus
1MRS755869
Reset alarm: the LED's alarm indication can be reset in this submenu, independent of the active mode
A051461
Fig. 20.2.-1
and DOWN
to
A051462
Fig. 20.2.-2
86
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Reset alarm: can only be reset, if there is no active alarm present anymore. An attempt to reset an alarm caused for example by an interrupted open coil is impossible as long as the coil is not replaced. Reset max. values: this sub menu resets the maximum and mean current values in the observation period. Also the sum of switched off current is reset from here. Reset is only possible in Local or Local & Remote modes. Reset energy values: all the energy values (active, reactive, apparent) are reset from here. Reset is only possible in Local or Local & Remote modes. Reset CB cycles: a circuit breaker cycle is a close operation and the subsequent open operation. The unit sums the cycles. This cycle number is reset from here. Reset is only possible in Local or Local & Remote modes. Reset fault recorder: the fault recorder data is cleared from here. Reset is only possible in Local or Set Local modes. Reset events: the events are cleared from here, if the mode is in Set Local. Reset counters: the unit working hours are reset from here. Reset is only possible in Local or Local & Remote modes.
20.3.
Protection
The parameter of the Protection submenus, Active set page and Protection, can only be changed in mode Set Local by applying the protection electronic key.
20.4.
Control
The parameter of the Control submenus can only be changed in mode Set Local by applying the protection electronic key.
20.5.
Test
The test of the primary object can only be performed in local mode.
20.6.
Service page
The service page menu is composed of several submenus. Browse through the and DOWN buttons. Press ENTER to enter the submenus with UP selected submenu.
87
REF 542plus
1MRS755869
A051463
Fig. 20.6.-1
20.6.1.
Statistics
This submenu shows the FUPLA cycle time and other information related to the current configuration in the unit.
A051464
Fig. 20.6.1.-1
Statistics submenu
20.6.2.
Versions
This submenu displays information on the firmware versions loaded inside the unit.
88
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051465
Fig. 20.6.2.-1
Versions submenu
20.6.3.
Hardware identification
This submenu shows the reference information of the hardware modules installed into REF 542plus.
A051466
Fig. 20.6.3.-1
Hardware identification
89
REF 542plus
1MRS755869
A051467
Fig. 20.6.3.-2
When the information from the module is not available the following page is displayed.
A051468
Fig. 20.6.3.-3
When the information stored on the module is corrupted, the following page is displayed.
90
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051469
Fig. 20.6.3.-4
When the module is not present or the module is not able to publish the HW identification data, the following page is displayed.
A051470
Fig. 20.6.3.-5
20.6.4.
Communication
This subpage displays the information related to the communication ports available and configured in REF 542plus.
91
REF 542plus
1MRS755869
A051641
Fig. 20.6.4.-1
When the port is not installed or configured, the following page will be displayed.
A051642
Fig. 20.6.4.-2
20.6.4.1.
92
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051645
Fig. 20.6.4.1.-1
In this subpage, it is possible to block the monitoring direction of the module. For more information, refer to the Communication Module User Manual.
A051646
Fig. 20.6.4.1.-2
The IEC Test mode menu allows setting and resetting the test mode of the IEC module. For more information, refer to the Communication Module User Manual.
93
REF 542plus
1MRS755869
A051647
Fig. 20.6.4.1.-3
20.6.4.2.
A051643
Fig. 20.6.4.2.-1
94
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
20.6.4.3.
A051648
Fig. 20.6.4.3.-1
It is not possible to modify the SPA bus slave address of the unit on this page.
20.6.4.4.
A051644
Fig. 20.6.4.4.-1
REF 542plus
1MRS755869
By selecting the row related to port 1 or 2 and pressing the port communication address.
, it is possible to change
20.6.4.5.
A051649
Fig. 20.6.4.5.-1
Only channel 1 is currently available. To enter the next subpage, select Channel 1 . The following page is displayed. and press ENTER
96
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051650
Fig. 20.6.4.5.-2
A051651
Fig. 20.6.4.5.-3
97
REF 542plus
1MRS755869
A051652
Fig. 20.6.4.5.-4
98
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A051653
Fig. 20.6.4.5.-5
20.6.4.6.
99
REF 542plus
1MRS755869
A051654
Fig. 20.6.4.6.-1
20.6.4.7.
Ethernet IP page
This page shows the current settings of the Ethernet communication subsystem. Here, it is possible to visualize the IP and MAC address. The IP and MAC addresses cannot be changed from this page.
A051655
Fig. 20.6.4.7.-1
100
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
20.6.4.8.
A070398
Fig. 20.6.4.8.-1
The next Fig. 20.6.4.8.-2 shows a case where there is no Ethernet module present.
101
REF 542plus
1MRS755869
A070399
Fig. 20.6.4.8.-2
In normal situation where the Ethernet module is installed, the following subpage appears when you select another submenu, as shown in Fig. 20.6.4.8.-3:
102
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A070400
Fig. 20.6.4.8.-3
To select the desired subpage, click the UP and DOWN buttons. The subpages are divided into two categories for value settings and info.
103
REF 542plus
1MRS755869
A070401
Fig. 20.6.4.8.-4
A070402
Fig. 20.6.4.8.-5
104
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
To move from one subpage to another click the UP , and DOWN buttons. You can go back to the FB COM Ethernet page from each subpage by clicking the button. MENU
TCP/IP subpage
The TCP/IP subpage consists of two pages for each configured communication port, port1 or port2. The following two figures Fig. 20.6.4.8.-6 and Fig. 20.6.4.8.-7 show the TCP/IP Settings subpage and the TCP/IP INFO subpage.
A070403
Fig. 20.6.4.8.-6
105
REF 542plus
1MRS755869
A070404
Fig. 20.6.4.8.-7
At the moment, you can use either port 1 or port 2. If you apply port 2 , the subpages shown in the two following figures are displayed.
106
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A070405
Fig. 20.6.4.8.-8
A070406
Fig. 20.6.4.8.-9
107
REF 542plus
1MRS755869
SNTP subpage
The SNTP subpage displays whether SNTP is enabled or disabled.
A070407
Fig. 20.6.4.8.-10
SNTP disabled
If SNTP is enabled, the related subpage consists of two different subpages, as shown in the following two figures Fig. 20.6.4.8.-11 and Fig. 20.6.4.8.-12.
108
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A070408
Fig. 20.6.4.8.-11
A070409
Fig. 20.6.4.8.-12
109
REF 542plus
1MRS755869
You can move from one subpage to another by clicking the UP , and DOWN buttons. You can go back to the FB COM Ethernet subpage by clicking the MENU button.
20.6.5.
Char map
This page shows the active char map used by the HMI. Refer to the Operating Tool User Manual on how to change it.
A051656
Fig. 20.6.5.-1
20.6.6.
LCD contrast
The LCD screen contrast can be adapted to different light condition from this submenu.
A051657
Fig. 20.6.6.-1
110
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
20.6.7.
FORWARD: the power is flowing from the switchgear to the load (outgoing feeder). BACKWARD: the power is flowing into the switchgear (incoming feeder).
A051658
Fig. 20.6.7.-1
20.7.
Test page
This submenu allows testing the HMI and the primary part of the switchgear.
20.7.1.
Test HMI
When the test HMI is selected, all its features will be tested by switching them on and off. HMI buttons are not available during the test. The displayed information on the HMI does not reflect the switchgears actual status. REF 542plus is protecting the switchgear during the HMI test. The HMI test takes a few seconds.
111
REF 542plus
1MRS755869
A051659
Fig. 20.7.1.-1
20.7.2.
112
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
21.
A051660
Fig. 21.-1
Start/Trip events
Event number 21: The Overcurrent Instantaneous protection function detects the system fault condition on phase L1 at the absolute time 25/05/2006, 07:45:15.859. The time stamp is indicated by arrow 1, see Fig. 21.-1. Event number 22: The Overcurrent Instantaneous protection function detects the system fault condition on phase L3 at the same absolute time 25/05/2006, 07:45:15.859. Event number 23: The trip by the above-mentioned protection function is released at the absolute time 25/05/2006, 07:45:15.862, which is indicated by arrow 3, see Fig. 21.-1. As long as the current is not interrupted, the start signal remains active. Arrow 2 indicates that the current is flowing for a time duration of 73 ms.
113
114
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
22.
FUPLA (functions sequence) WIRE (functions connection) LCU (HMI display configuration) COM (communication configuration)
REF 542plus is a scalable system. Optional modules can be used according to project requirements. The following list provides a definition of the terminology used when defining the state of an optional module:
*
"Installed" indicates that the module is physically inserted in the REF 542plus housing. "Configured" indicates that the module has been configured in REF542CONF by a REF 542plus engineer. "Detected" indicates that the REF 542plus start-up procedure has made a successful detection check of the module.
Software supervision
Software faults require different kinds of handling and these can be modelled by defining a level that identifies the faults critical nature:
*
Level 1 Level 1 faults are irrecoverable fatal errors. After fault detection, the system is not able to guarantee safe execution of the protection and control functions. The irrecoverable fault forces REF 542plus to stop any activities and it can only be restarted after a power-switch cycle (power off/on) or after a configuration download (if possible).
Level 2 Level 2 faults are recoverable fatal errors. They are similar to level 1 faults except that REF 542plus, instead of stopping any activities, resets and therefore automatically restarts and signals the reset cause.
Level 3 Level 3 faults are errors that do not affect safe execution of the protection and control functions. In general, they are handled by signalling the fault via an HMI error message and a SPA event.
115
REF 542plus
1MRS755869
HMI LEDs * Ready: * Black Protection and control functions not active
*
Amber Some communication error on the line (handled only by MODBUS and ETHERNET module)
Alarm Led and Interlocking errors are handled by the programmable logics HMI error message
*
If an error message has been displayed in the MMI, no other message is displayed until: a local/remote reset command has been given * completion of a configuration download SPA event
*
Supervision by bootloader
REF 542plus has an on-chip bootloader that handles the software upgrade and the entering into Factory test mode. The bootloader supervises RAM (Random Access Memory) and FLASH (MC non-volatile memory) application program correctness. At normal start-up, it performs a simple RAM test that verifies the presence of the RAM chip and its memory size. The exhaustive RAM test has to be performed if the Factory test mode is activated. If the RAM test is passed, the bootloader verifies the presence and the correctness of the application program which is stored in FLASH. The presence is verified through a pre-defined pattern check in a fixed FLASH location and the correctness is verified through application program checksum calculation. The following table presents the bootloader fault descriptions:
116
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Signalling DEBUG port message "RAM error has been detected" DEBUG port message "RAM error has been detected" "RAM addressing error (?) - size too small: xx" DEBUG port message "No valid application found - card resetting"
Level 2
Reset
REF 542plus performs a complete and deep analysis of the last reset cause. The reset can be the result of a normal situation or a HW/SW fault detection. A normal situation can be either of the following two:
*
Power-switch cycle REF 542plus power is switched OFF and than ON.
Commissioning test end REF 542plus is in commissioning test mode and the user exits from the commissioning test HMI menu.
HW watchdog A HW watchdog supervises the SW execution. The required refresh time is about 80 ms (fault-time detection). This is the worst reset cause because the reset is beyond SW control which means that the real fault root cause in principle is unknown. The cause can be either SW or HW related and in any case there is no possibility to obtain a SW reference or description of the fault. The fault analysis depends on the fault reproducibility in laboratory. If the fault is not reproducible, a special REF 542plus SW can be built that is able to make a trace log of all the activities executed by the SW (interrupts, tasks switching, events, semaphore, etc.). This trace log is stored in the internal memory and can be displayed in the DEBUG port after a watchdog reset. The trace log contains the last operation performed by the system before the fault and it can be the starting point for further analysis to identify the real fault cause. That is, if the fault was HW or SW related, and, in case of SW, in which SW module the fault occurred or what sequence of events that produced the fault.
SW exceptions The internal processor supervises all instruction executions and memory access instances. In case it detects an exception, it prepares an exception stack frame and raises a SW exception interrupt. The REF 542plus exception handler stores all the information contained in the exception stack frame in the internal memory and sets the reset cause to SW exception. The SW exception always produces a HW reset. At start-up, the SW exception is signalled through a HMI and SPA event.
117
REF 542plus
1MRS755869
Moreover, the exception stack frame data, which includes very important information needed when analysing the real root cause of the SW exception, is available on the DEBUG port. Examples of SW exceptions are: access error address error * illegal instruction Fatal errors
* *
Fatal errors are faults detected by the internal error checking functionality that, if it fails, compromises the system reliability (e.g. RTOS errors). The REF 542plus fatal error handler stores a fatal error description string in the internal memory. The description string contains a reference to the SW function that generated the fatal error and a description of the cause. Fatal errors always produce a HW reset. At start-up, the fatal error is signalled through a HMI and SPA event. The following table describes signalling/handling of the reset faults:
Faults/Errors HW watchdog Signalling HMI event Reset!! Watchdog" SPA event 0E37 DEBUG port command 4 shows SW trace logs before reset (Special REF542 SW) HMI event Reset!! SW exception" SPA event 0E37 DEBUG port command 1 shows SW exception stack frame data HMI event Reset!! Fatal error" SPA event 0E37 DEBUG port command 1 shows fatal error description string Level
SW exception
Fatal Error
Configuration
The configuration is stored in FLASH. At start-up or after a configuration download, REF 542plus makes a consistency check on it. It consists of:
*
Version checking There are separate versions for protection and control functions (FUPLA) and COM configuration functions.
Function checking Every installed function must be implemented in the firmware and must have the expected configuration data/parameters format.
Hardware checking If a function requires a hardware component, this has to be installed and detected by the start-up procedure.
118
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Note that all version checks are performed by REF542CONF before configuration download. Therefore, the fault can occur only after a REF 542plus firmware upgrade/downgrade or after FLASH configuration data corruption. The following table describes signalling/handling of the configuration faults:
Faults/Errors No configuration Incompatible Version COM configuration file format Signalling HMI error message "Waiting new config." HMI error message "Software changed" HMI error message "WRONG COM CONFIG." SPA event 102E60 Level 1 1 3 3 3 3 3
COM TCP-IP incompatible HMI error message "WRONG TCP-IP CONFIG." version SPA event 102E61 COM MOD-TCP incompatible version COM WEBREF incompatible version COM SMS incompatible version HMI error message "WRONG MODTCP CONFIG." SPA event 102E62 HMI error message "WRONG WEBREF CONFIG." SPA event 102E63 HMI error message "WRONG SMS CONFIG." SPA event 102E61
COM module incompatible HMI error message "WRONG COMMODULE version CONF." SPA event 102E61 Functions checking Hardware checking HMI error message "WRONG CONFIGURATION" SPA event 0E43 Protection functions: See 2.4 DSP AI20mA functions: See 2.6 AI20mA
DSP version It is used to verify communication at start-up and to check SW version compatibility.
DSP Analogue Inputs calibration factors The data is retrieved from the Analogue Input module. If the data is not present or if it is corrupted, the system will be stopped because it is not able to guarantee reliable measurements and safe protection executions.
DSP configuration The DSP configuration is built by the MC from the Analogue Input and Protections configuration. It is sent to the DSP that performs a consistency check on it.
119
REF 542plus
1MRS755869
DSP SW watchdog It is based on a flag-toggle mechanism. The DSP is faulty if it does not toggle a flag for 1 second.
MC-DSP communication The DSP is faulty if the number of consecutive fault requests reaches a predefined counter (15). Note that, during normal operation, the DSP measurements are requested every 100ms which means that the worst fault-time detection of a DSP fault is 1.5 sec.
COM module version COM configuration data version COM module type The COM start-up supervision verifies that the configured COM module type matches with the one detected.
The COM module type detected is different from the one configured in REF542CONF The COM module has been configured in REF542CONF but it is not installed in the REF 542plus housing The COM module has been configured in REF542CONF but it has not been detected due to an internal COM module fault (the detection timeout is 30 sec.) The COM module has been detected but it has not been configured
120
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
COM module alive state Based on the update of a life cycle counter. If the COM module does not update the life cycle counter for 500 ms, it is considered to be faulty. NOTE: Up to release 2.5, this mechanism is implemented by the MODBUS and ETHERNET modules.
COM module not installed Network communication led becomes RED HMI error message "COMMODULE NOT INSTALL" SPA event 102E68 COM module not detected Network communication led becomes RED HMI error message "COMMODULE NOT DETECT" SPA event 102E69 COM module not configured COM module not alive Network communication led becomes RED HMI error message "COMMODULE NOT CONFIG." SPA event 102E70 Network communication led becomes RED
3 3
AI20mA version A common pre-defined pattern is used for AI20mA module detection and, if detected, an internal version number is used to perform the compatibility check.
AI20mA configuration
121
REF 542plus
1MRS755869
The AI20mA configuration is built by the MC from the AI20mA sensors and Warnings configuration. It is sent to the AI20mA that performs a consistency check on it.
*
AI20mA-MC configuration The MC does not start normal operation if the AI20mA is configured but not detected at start-up.
MC-AI20mA communication The AI20mA sensor measurements and warnings status are requested every FUPLA cycle and so this time has to be considered as the worst fault time detection.
AI20mA communication HMI error message "AI20MA NOT READY" (command failure) SPA event 102E54
FLASH data
REF 542plus uses a FLASH device to store non-volatile data/configuration. The MC supervises every FLASH erase/write operation checking that the FLASH status registers. In order to protect the FLASH data against erroneous write/erase attempts, the FLASH is write-protected which means that erroneous access will raise a SW exception (address error). The write-protection is disabled only when valid FLASH write/erase has to be performed. Moreover, in order to guarantee data integrity, all data stored in FLASH is validated with size-check and checksum verification. The following table describes signalling/handling of the FLASH faults:
122
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
Faults/Errors Memory full error Ready error Writing byte error Block erase error Vpp low error Block locked error
Signalling SPA event 102E1 SPA event 102E2 SPA event 102E3 SPA event 102E4 SPA event 102E5 SPA event 102E6
Level 3 3 3 3 3 3
123
124
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
23.
A070410
Fig. 23.-1
In the above figure, the PC Ethernet port is configured to communicate with the address 192.168.2.203 and with subnet 255.255.255.0. The subnet value must match the subnet value set in the Ethernet module, while only the first three digits of the IP address must match with the ones of the Ethernet module, the fourth digit must be different. After that it is possible to verify a remote connection with a ping command. To perform the ping command, select Run in the PC Start menu. Then type the ping command by specifying the Ethernet board IP address, as illustrated in the following Fig. 23.-2:
125
REF 542plus
1MRS755869
A070411
Fig. 23.-2
In the example above, the PC sends a ping command to an Ethernet board connected to the net with the address 192.168.2.106. If the connection is correct, the following window appears after the execution of the ping command:
A070412
Fig. 23.-3
Now, it is possible to establish a connection with the Telnet server of the Ethernet module. As before, use the Run command in the PC Start menu. After that, type the telnet command specifying the Ethernet board IP address as displayed in the following figure:
A070413
Fig. 23.-4
126
1MRS755869
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
A070414
Fig. 23.-5
A connection with the Ethernet board Telnet server is now established. The Ethernet module Telnet server allows different logging levels to enable different functions and commands. You can access Telnet without any log in operation by simply pressing the Enter key twice. Note that the Telnet connection is automatically closed if it stays inactive for more than two minutes. Access to Telnet as a basic user allows functions to monitor the Ethernet board status and general information.
Specific commands
Specific commands allow getting information on:
* * * * *
Ethernet connection configurations disks contents SNTP module state internal interface state Dual Channel state (if the option is enabled)
The Ethernet connection configurations display the current Ethernet configuration. Two commands are available:
127
REF 542plus
1MRS755869
ep
shows the configuration parameters of the ports: topology * protocol type * MAC address (for port1 and port2) * IP address (for port1 and port2) * subnet mask (for port1 and port2) * gateway IP address (for port1 and port2)
*
es
The disks contents display the contents of the Flash disk (C:) and Ram disk (D:). Three commands are available:
fl fp fs allows to see the content of the selected disk (C: or D:) allows to select the current disk and path to look at shows the disk usage statistics for the current disk
You can check the SNTP module state by using the following five commands:
sc ss st sa sk sx shows the state of the SNTP client shows the state of the SNTP server shows the result of the last transaction shows some information regarding the running SNTP algorithm shows information regarding the SNTP clock module shows all information reported with the previous commands
You can check the internal interface state with the command:
ii internal interface information display
The dual channel state is not available at the moment. In this context, you can use the following set of commands to check the state of the Dual Channel operation modality. The available commands are:
dv dc ds dn da shows the Dual Channel module release version shows the current Dual Channel configuration shows statistics about Dual Channel communication shows the table list of the nodes connected used to print out all the information of the above commands
128
ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa FINLAND +358 10 22 11 +358 10 22 224 1094 http://www.abb.com/substationautomation
1MRS755869 EN 2/2008