L&T Acb Manual
L&T Acb Manual
L&T Acb Manual
About us
Larsen & Toubro is a technology-driven USD 7 billion company
that infuses engineering with imagination. The Company offers a
wide range of advanced solutions in the field of Engineering,
Construction, Electrical & Electronics, Machinery and Information
Technology.
Complete selectivity
Unique feature of lcu=lcs=lcw for 1 second across the entire range. This ensures
complete selectivity for system with time based discrimination.
Optimal compactness
Designed to ensure
lLow inherent temperature rise
lAdequate interface clearances
1
User friendly features
handle and various racking interlocks; no need to open the panel door
Unique ‘Maintenance position’ in drawout type ACBs to facilitate
l
for only Service, Only Test, Test and Service, and All Positions
Unique gasket for IP54 protection
l
Facility for site conversion of manually operated ACBs to electrically operated ACBs
l
Safety
ensures intentional tripping even at high voltage drops during short circuit
Conformance to standards
IEC 60947 - 2
l
IS 13947: Part 2
l
IEC 60695 - 2 - 1
l
BS EN 60947 - 2
l
2
A Commitment to Quality
3
Technical Data Sheet
Type Designation E E S1 E S1 C H E S1 C H E
Rated making capacity Icm 380/415/500 V 105 105 105 105 105 105 143 105 105 105 143 105
Utilization category B B B B B B B B B B B B
Manual PPPPPPPPPPPP
Electrical life without maintenance 6000 6000 6000 6000 6000 8000 8000 6000 6000 8000 8000 6000
* Please consult us for application at dc voltages & higher operational voltage upto 1000V ac
4 ** Icw values are indicated based on thermal considerations. While selecting a breaker please ensure that Icw requirement for the application is not more than Ics / Icu at the point of installation.
1250 1600 2000 2500 3200 4000 5000 6300
S1 C H E S1 C H E S1 C H S1 C H S1 H0 H1 H0 H C C
50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 75 100 75 100 95 95
- 35 50 - - 35 50 - - 40 65 - 40 65 - 65 85 65 85 DD
50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 75 100 75 100 95 95
- 35 50 - - 35 50 - - 40 65 - 40 65 - 65 85 65 85 DD
50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 75 100 75 100 95 95
42 50 65 50 42 50 65 50 42 55 75 55 60 75 60 75 100 75 100 95 95
- 35 50 - - 35 50 - - 50 65 - 55 65 - 70 85 70 85 DD
105 105 143 105 105 105 143 105 105 121 165 132 132 165 132 165 220 165 220 209 209
- 73.5 105 - - 73.5 105 - - 84 143 - 84 143 - 143 187 143 187 DD
12 12 12 8 12 12 12 8 12 12 12 12 12 12 12 12 12 12 12 12 12
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40
60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60
B B B B B B B B B B B B B B B B B B B B B
PPPPPPPPPPPPPPPPPPPPP
PPPPPPPPPPPPPPPPPPPPP
6000 7000 7000 6000 6000 7000 7000 4500 4500 5000 5000 4500 5000 5000 4500 5000 5000 5000 5000 2500 2500
468 - 468 - 468 468 468 468 468 468 583 583
399 - 399 - 399 555 555 555 701 701 913 913
487 - 487 - 487 701 701 701 909 909 1182 1182
587 - 587 - 587 587 587 587 587 587 691 691
‡
Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear.
D
Please consult us. 5
Protection releases
Salient Features
Additional Features
Parameter Details
LED Indications Auxiliary Power On P
Overload P
Short Circuit P
Instantaneous P
Earth Fault P
Neutral Fault P
Trip P
Alarm P
Auxiliary Supply 24V DC
Digital Inputs 4 Nos.
Output Relays 3 Internal + 4 External Relays
240V AC/5A, 30V DC/5A (resistive load)
Rating Plug In Multiplier 630-800-1000-1250-2000-3200-5000
Communication Protocol MODBUS RTU
Link used RS 485
2
Maintenance Indication I t based
Event Records Pickup, Alarm, Trip, Date, Time and Cause of Event
Trip Records Last 5 records with date and time stamping,
voltage and current readings in all phases
Testing Self-Diagnostic Test P
Relay Module 4 Relay Outputs
Supplementary Modules Power Supply Module 24V DC Output
Communication Module MODBUS RTU
No. of Storable Settings 2
9
Protection releases
Salient Features
l Self-powered
l AN1 module for remote fault indication through LEDs with changeover
contact for each kind of fault
l Realistic hot and cold curves which take into account integrated
heating effect
20 ms to 600 ms
Short Time 2 to 10 times In Steps : 20, 60, 100, 160, 200,
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 260, 300, 400, 500, 600 ms
2 to 16 times In -
Instantaneous Steps : 2, 3, 4, 6, 8, 10, 12,
14, 16 One position as infinity.
11
Protection releases
Salient Features
l Self-powered
l Comprehensive protection
- SR18; Long Time and Short Time
- SR18G; Long Time, Short Time and Ground fault protection
Instantaneous 6 & 12 In -
12
Protection releases
Protection
Overload Protection
lContinuously & individual phase adjustable dial settings
from 75% to 100% of CT tap
Salient Features
l True RMS sensing
13
Accessories
Locks/Interlocks
Type Data
Lockable Trip Push Mounted in place of normal trip push button. With this, ACB can be locked
Button (LTPB)
in trip condition. For interlocking, LTPBs are offered in the following
combinations:
l 4 different types of keys i.e. AA, BB, CC and DD suitable for 2 incomers
and 1 bus coupler schemes
l Combination of L, M, N, LM and MN locks, which are suitable for three
incomer and two bus coupler schemes
l Combination of K, L, MN, KL, LM and MN locks, Which are suitable for
four incomer and three bus coupler schemes
l Combination of J, K, L, M, N, JK, KL, LM and MN locks, which are
suitable for five incomer and four bus coupler schemes
Door Interlock
This ensures:
Door Racking Locking in lUnless the panel door is closed, breaker cannot be racked in or out
Interlock Inerlock ‘Isolated’ lUnless the breaker is in Isolated Position, it is not possible to open the
Position panel door
Racking Interlock
This ensures that breaker cannot be racked in/out unless the ACB is in
tripped/open condition.
14
Accessories
Signaling
Type Data
C1
Common indication of tripping due to overload, short
circuit and ground faults.
l Provided by microswitch C1 fitted inside the ACB
l Available as an option in all releases
C2
Separate indication of tripping due to overload, short
circuit and ground faults.
l For release type DN1,this is provided by microswitch C1 & C2
(C2 fitted inside release)
l Available through in-built fault indicators in SR18, SR18G,
SR21i & SR71 releases
AN1-Annunciator Module
Remote indication of tripping due to overload, short circuit
and ground faults.
lCan be used with releases type SR18/SR18G/SR21i
lIndividual fault indication provided by three separate LEDs for
- Long time faults
- Short time fault/instantaneous fault
- Ground fault one potential free contact rated 5A at 230V AC
available for each type of fault
lFlush mounting on panel (H-W-D=92mm x 46mm x 105mm)
lOperating voltage: 240V AC/110V DC/220V DC (other
Voltages available on request)
C2
Indication for operation of shunt release or under voltage
release.
l Provided by microswitch C5 fitted on the shunt release
15
Accessories
Control
Shunt Release
For remote tripping of the
l Type Nominal Power Operation
of voltage consume- Limit
breaker
Release Uc (V) option at
Shunt release coil is short time
l 50Hz pick up
rated and is disconnected from
EA1 240 AC 800 VA 10-130%
the circuit by an auxiliary
415 AC 800 VA Uc
contact when the ACB trips
(Refer to wiring diagram) EA 24V DC 32 W 65-130%
Low power consumption
l
48V DC 125 W Uc
110 DC 45 W
Two types available:
l
220 DC 30 W
- EA for DC application
Note : Other voltages available on request
- EA1 for AC application
Undervoltage Release
Two types available: Parameter Specification
lType MV With no intentional
Nominal 240V & 415V: 50Hz
time delay voltage (Uc) 220V & 415V: 60Hz
lType MVR With fixed time
delay of 3+1.5 sec. to prevent Pick up (V) 80% Uc
nuisance tripping against Drop off (V) 35-65% Uc
momentary voltage dips
(VA) Consumption Pick up - 23 VA
Hold on - 10 VA
Notes: When undervoltage
release is provided, the ACB can Watt loss 6W
be closed only when supply is
available to the undervoltage
release.
Auxiliary Contacts
Two combinations available: Electrical Voltage Rated current
l2 NO + 2 NC circuit (V) (A)
l6 NO + 6 NC Resistive 24 to 415 AC 16
250V AC 1.2
Non- 24 to 415 AC 16
resistive 250V AC 1.0 #
16
Overall Dimensions: Fixed Breakers
to Remove
340 min Arc Chute
for Insulating Sheet
200 min
7
140 min
Door
100 min
20 min Bezel
36 min 36 min 9
A 27
26 58 264 26
385
256
33
394
309
22
16
68.8
27
30 230
104
Earthing Terminal 35
20 301 54
2 Holes-Ø6.3 2.6 min
21 16 405 86 10
D E F E D
20 min
23.5
58 102 102 56
Rating
Type X Y
400E -
1250E 5 150
X
1600/ 15 140
2000E
385
4 Holes
325
Ø12 X
286
227
216
20 20
32
298
22 137.5
402 21
179.5
Terminal
2 Holes-Ø13 3 Holes-Ø13
30 15 30 15
12.5 25 50 25
25
50 100
Terminal Connections
23.5
23.5
10 15
10 15
227
227
140
145
305
12 Holes-Ø4 101
332
Hinge Hinge
112
112
363
325
112
5.5
91
200 min
122 for Insulating Sheet
40 max 7
100 min
94.5 264 Service Position
Door
40 64.5 26 Bezel
*5
256
468
397.5
404
68.8
M 10
160
46 28
4 74
6 10 54
17.5 min.
199.5 20
6 18.9 max.
538 8.9 min. 18 245
308.5
308.5
308.5
221.5
221.5
221.5
58.4
58.4
58.4
38
38
8.5 x 9.5 8.5 x 9.5
38
8.5 x 9.5
630 - 1000C & 630 - 1250S1 800 - 1000H, 1250/1600 C/H & 1600/2000 S1 2000 C
70
6 Holes-Ø14 6 Holes-Ø14
50
67
25
67
43
43
62
38
12.5
2500 C/H & 2000 H 2500 S1 3200S1 3200 H0/H & 4000H0/H1
For 5000C/6300C 3P
for Metallic Components
75 Isolated Position
A 400 min 51 Test Position
200 min
256
404
467
68.8
M 10
160
46 28
6 5 74
10 54
199.5 10 17.5 min 20
5 18.9 max.
615 8.9 min. 18 245
D E F E D 8 Holes-Ø14
217
28
63
683
17.5
40 50 40 43.5
42
Terminal Connections
64.5
Earthing Terminal 5000C/6300C
Dimensions (mm)
Ratings
A D E F
5000A C 3P 913 187.5 269 -
6300A C 3P 913 187.5 269 -
5000A C 4P 1182 187.5 269 269
6300A C 4P 1182 187.5 269 269
G
Ratings Type
(mm)
800A - 1600A 3P C/H 280.3
*G
25
50
108.5
184.5
Hinge Hinge
224
412
450
199
1 5.5
Base of
Cradle
Door Cutout
21
Overall Dimensions
10
15
15
308.5
221.5
800 - 1000 C 1250 - 1600 C/H 2000 C 2500 C/H
& 800/1000 H & 2000 H
20
12.5
15
25 25 25
16.5
33
160
100
50
63
25
33
16.5
12.5 25 12.5 30
12.5 25 12 43
Vertical Terminals
V S W
U 40.0
4 Holes-ØT O P Top
R
N
M
387.5
X
308.5
221.5
Ratings M N P Q R S T U V W X
800A/1000A C 10.2 38 20 25 29.2 5 9 65 95 10 58.4
1250/1600A C/H 20 40 20 25 29.2 5 9 65 95 10 80
800/1000A H
2000A C 20 40 20 40 29.2 22.5 14 80 110 15 80
2500A C/H
2000A H 20 40 20 40 33.5 7.5 14 80 110 15 80
Note : 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations.
22
Switchgear Training Centres
Pune Lucknow
Coonoor
23
Notes
Electrical Standard Products (ESP) Branch Offices:
REGISTERED OFFICE AND L&T House, Group MIG - 5 Plot No. 518
HEAD OFFICE Padmanabhpur 4th Main Road
L&T House, Ballard Estate Durg 491 001 K. K. Nagar
P. O. Box 278 Tel: 0788-2213833 / 14 / 28 / 29 Madurai 625 020
Mumbai 400 001 Fax: 0788-2213820 Tel: 0452-2537404, 2521068
Tel: 022-6752 5656 Fax: 0452-2537552
Fax: 022-6752 5858 A1/11, Astronauts Avenue e-mail: esp-mdu@LNTEBG.com
Website: www.Larsentoubro.com Bidhan Nagar
Durgapur 713 212 EBG North Wing Office - 2
Tel: 0343-2536891 / 8952 / 7844 Powai Campus
ELECTRICAL STANDARD PRODUCTS (ESP) Fax: 0343-2536493 Mumbai 400 072
501, Sakar Complex I e-mail: esp-dgp@LNTEBG.com Tel: 022-67052874 / 2737 / 1156
Opp. Gandhigram Rly. Station Fax: 022-67051112
Ashram Road Milanpur Road, Bamuni Maidan e-mail: esp-bom@LNTEBG.com
Ahmedabad 380 009 Guwahati 781 021
Tel: 079-66304007-11 Tel: 0361-2651297 8B, Farmland
Fax: 079-26580491 Fax: 0361-2551308 Ramdaspeth
e-mail: esp-ahm@LNTEBG.com e-mail: esp-gau@LNTEBG.com Behind Hotel Radhika
Nagpur 440 010
38, Cubbon Road, Post Box 5098 II Floor, Vasantha Chambers Tel: 0712-2420641 / 24
Bangalore 560 001 5-10- 173, Fateh Maidan Road Fax: 0712-2420619
Tel: 080-25020100, 25593613 Hyderabad 500004 e-mail: esp-ngp@LNTEBG.com
Fax: 080-25580525 Tel: 040-66720250
e-mail: esp-blr@LNTEBG.com Fax: 040-23296468 32, Shivaji Marg
e-mail: esp-hyd@LNTEBG.com P. O. Box 6223
New Delhi 110 015
131/1, Zone II
Tel: 011-41419500 / 1, 41419515
Maharana Pratap Nagar D-24, Prithvi Raj Road, C-Scheme
Fax: 011-41419600
Bhopal 462 011 Jaipur 302 001
e-mail: esp-del@LNTEBG.com
Tel: 0755-4233906, 4233907 Tel: 0141-2385913 / 19
Fax: 0755-2769264 Fax: 0141-2373280 L&T House
e-mail: esp-bho@LNTEBG.com e-mail: esp-jai@LNTEBG.com P. O. Box 119
191/1, Dhole Patil Road
Plot No. 559, Annapurna Complex Akashdeep Plaza, 2nd Floor Pune 411 001
Lewis Road P. O. Golmuri Tel: 020-26135048, 26135611
Bhubaneswar 751 014 Jamshedpur 831 003 Fax: 020-26129586, 26124910
Tel: 0674-6451342, 2436696 Jharkhand e-mail: esp-pnq@LNTEBG.com
Fax: 0674-2537309 Tel: 0657-2340864
e-mail: esp-bbi@LNTEBG.com Fax: 0657-2341250 3rd Floor
e-mail: esp-jam@LNTEBG.com Vishwakarma Chambers
SCO 32, Sector 26-D Majura Gate, Ring Road
Madhya Marg, P. O. Box 14 Skybright Bldg. M. G. Road Surat 395 002
Chandigarh 160 026 Ravipuram Junction, Ernakulam Tel: 0261-2473726
Tel: 0172-4646841 to 7 Kochi 682 016 Fax: 0261-2477078
Fax: 0172-4646802 Tel: 0484-4409420 / 427 e-mail: esp-sur@LNTEBG.com
e-mail: esp-chd@LNTEBG.com Fax: 0484-4409426
e-mail: esp-cok@LNTEBG.com Radhadaya Complex
10, Club House Road Old Padra Road
Chennai 600 002 3-B, Shakespeare Sarani Near Charotar Society
Tel: 044-28462072 / 4 / 5 Kolkata 700 071 Vadodara 390 015
Fax: 044-28462102 Tel: 033-44002572 / 3 / 4 Tel: 0265-6613610 / 11 / 12
e-mail: esp-maa@LNTEBG.com Fax: 033-22822589 Fax: 0265-2336184
e-mail: esp-ccu@LNTEBG.com e-mail: esp-bar@LNTEBG.com
67, Appuswamy Road
Post Bag 7156 A28,Indira Nagar, Faizabad Road 48-8-16, Dwarakanagar
Opp. Nirmala College Uttar Pradesh, Visakhapatnam 530 016
Coimbatore 641 045 Lucknow 226 016 Tel: 0891-6620411-4
Tel: 0422-2588120 / 1 / 5 Tel: 0522-2312904 / 5 / 6 Fax: 0891-6620416
Fax: 0422-2588148 Fax: 0522-2311671 e-mail: esp-viz@LNTEBG.com
e-mail: esp-cbe@LNTEBG.com e-mail: esp-Lko@LNTEBG.com
Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.
SP 50437(R2) 040209