L&T Acb Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

Air Circuit Breakers

About us
Larsen & Toubro is a technology-driven USD 7 billion company
that infuses engineering with imagination. The Company offers a
wide range of advanced solutions in the field of Engineering,
Construction, Electrical & Electronics, Machinery and Information
Technology.

L&T Switchgear, which forms part of the Electrical & Automation


business, is India's largest manufacturer of low voltage
switchgear, with the scale, sophistication and range to meet global
benchmarks. With over four decades of experience in this field,
the Company today enjoys a leadership position in the Indian
market with growing presence in international markets.

It offers a complete range of products including controlgear,


powergear, motor starters, energy meters, wires and host of other
accessories. Most of our product lines conform to international
standards, carry CE markings and are certified.

Switchgear Factory, Mumbai


L&T’s Air Circuit Breakers (ACBs) are specially designed for extreme
tropical conditions, and have a proven track of record of more than 30 years.
Presently more than 3,00,000 Air Circuit Breakers supplied by L&T are being used
for diverse applications. The Air Circuit Breakers provide technologically
driven solutions to meet customer needs.

Complete selectivity
Unique feature of lcu=lcs=lcw for 1 second across the entire range. This ensures
complete selectivity for system with time based discrimination.

Perfect for Indian conditions


Inherent design to perform in extreme tropical conditions. Typical site conditions like
high ambient temperature and humid, dusty environment are best handled
by ACBs without compromising on performance and safety.

Optimal compactness
Designed to ensure
lLow inherent temperature rise
lAdequate interface clearances

Widest choice of over current protection releases


lAdvance micro-controller based with option of communication & metering-SR71
lMicro processor based releases-SR21i/SR18/SR18G
lThermo-magnetic release-DN1

Elegant design & rugged construction


l Common door cutout for entire range
l Left aligned cutout for all ratings
l Uniform height and depth for ACBs up to 4000 Amp

Range to meet every customer’s need


Various options to choose from
lBreaking capacity from 35 kA to 100 kA
l3 Pole or 4 Pole configuration
lFixed or Drawout version
lAuto or Manual reset mechanism
lIndependent manual or stored energy type manual or electrically
operated mechanism
lDifferent terminal orientations : Flat, Horizontal and Vertical

1
User friendly features

Front accessible over current release settings, telescopic racking


l

handle and various racking interlocks; no need to open the panel door
Unique ‘Maintenance position’ in drawout type ACBs to facilitate
l

maintenance & inspection without removing ACB from the panel


Multitap Cts for enhancing protection range for example, 3200 Amp.
l

ACB can be set to have a thermal protection from 800 Amp.


Wide variety of Amperemetric and Voltmetric releases
l

Fully rated neutral pole for the entire range


l

Lockable sliding shutters to prevent unauthorized access to “TRIP”


l

and “CLOSE” push buttons


Can be used as an ON / OFF Load Isolator
l

Extendable Electrical Life:


l

- By replacing the arcing contacts at site, for all ratings


- Without changing pole assembly
Programmable SICs: Auxiliary contacts in drawout ACBs are programmable
l

for only Service, Only Test, Test and Service, and All Positions
Unique gasket for IP54 protection
l

Protection releases are easily interchangeable at site


l

Facility for site conversion of manually operated ACBs to electrically operated ACBs
l

Safety

“CE’’ marked for C & H ranges


l

Superior quality engineering grade plastics used for insulation purpose;


l

conforms to Glow wire test (Ref: IEC 60695-2-1)


In-built mechanical anti-pumping for electrically operated ACBs prevent
l

auto reclosing of ACB on fault


In-built rating error preventor in drawout ACBs ensure correct rating of
l

drawout porton in corresponding cradle


Safety shutters prevent accidental contact with live cradle terminals
l

Variety of Safety Interlocks (Refer to page no. 14)


l

Easily removable arc chutes without use of any tool


l

Operating voltage ranges from 10% Un to 110% Un for shunt release


l

ensures intentional tripping even at high voltage drops during short circuit

Conformance to standards

IEC 60947 - 2
l

IS 13947: Part 2
l

IEC 60695 - 2 - 1
l

BS EN 60947 - 2
l

2
A Commitment to Quality

3
Technical Data Sheet

Rating (A) 400 630 800 1000

Type Designation E E S1 E S1 C H E S1 C H E

Rated current (A) at 40°C In 400 630 800 1000


*
Rated operational voltage (V), 50/60Hz U e 415 415 415 415

Rated insulation voltage (V), 50/60Hz Ui 1000 1000 1000 1000

No. of poles 3 3 3/4 3 3/4 3 3/4 3

Rated ultimate short circuit breaking Icu 380/415/500 V 50 50 50 50 50 50 65 50 50 50 65 50

capacity 50/60Hz (kA rms) 660/690 V - - - - - 35 50 - - 35 50 -

Rated service short circuit breaking Ics 380/415/500 V 50 50 50 50 50 50 65 50 50 50 65 50

capacity 50/60Hz (kA rms) 660/690 V - - - - - 35 50 - - 35 50 -

Rated short time 0.5 sec 50 50 50 50 50 50 65 50 50 50 65 50

withstand capacity Icw** 1 sec 50 50 42 50 42 50 65 50 42 50 65 50

50/60Hz (kA rms) 3 sec - - - - - 35 50 - - 35 50 -

Rated making capacity Icm 380/415/500 V 105 105 105 105 105 105 143 105 105 105 143 105

50/60Hz (kA peak) 660/690 V - - - - - 73.5 105 - - 73.5 105 -

Rated impulse withstand voltage Uimp 8 8 12 8 12 12 12 8 12 12 12 8

of main circuit (kV)

Rated impulse withstand voltage Uimp 4 4 4 4 4 4 4 4 4 4 4 4

of aux. circuit (kV)

Typical opening time (ms) 40 40 40 40 40 40 40 40 40 40 40 40

Typical closing time (ms) 60 60 60 60 60 60 60 60 60 60 60 60

Utilization category B B B B B B B B B B B B

Suitability for isolation PPPPPPPPPPPP

Fixed PPx Px PPPx PPP

Draw out x x Px PPPx PPPx

Manual PPPPPPPPPPPP

Electrical x x Px PPPx PPPx



Electrical & Mechanical life (operating cycles) 15000 15000 15000 20000 15000 20000

Electrical life without maintenance 6000 6000 6000 6000 6000 8000 8000 6000 6000 8000 8000 6000

Dimensions Fixed H 385 385 - 385 - 394 385 - 394 385

3 Pole 316 316 - 316 - 326 316 - 326 316


W
4 Pole - - - - - 414 - - 414 -

D 423.5 423.5 - 423.5 - 431 423.5 - 431 423.5


Draw out H - - 468 - 468 - 468 -

3 Pole - - 399 - 399 - 399 -


W
4 Pole - - 487 - 487 - 487 -

D - - 587 - 587 - 587 -

* Please consult us for application at dc voltages & higher operational voltage upto 1000V ac
4 ** Icw values are indicated based on thermal considerations. While selecting a breaker please ensure that Icw requirement for the application is not more than Ics / Icu at the point of installation.
1250 1600 2000 2500 3200 4000 5000 6300

S1 C H E S1 C H E S1 C H S1 C H S1 H0 H1 H0 H C C

1250 1600 2000 2500 3200 4000 5000 6300

415 415 415 415 415 415 415 415

1000 1000 1000 1000 1000 1000 1000 1000

3/4 3 3/4 3 3/4 3/4 3/4 3/4 3/4 3/4

50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 75 100 75 100 95 95

- 35 50 - - 35 50 - - 40 65 - 40 65 - 65 85 65 85 DD

50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 75 100 75 100 95 95

- 35 50 - - 35 50 - - 40 65 - 40 65 - 65 85 65 85 DD

50 50 65 50 50 50 65 50 50 55 75 60 60 75 60 75 100 75 100 95 95

42 50 65 50 42 50 65 50 42 55 75 55 60 75 60 75 100 75 100 95 95

- 35 50 - - 35 50 - - 50 65 - 55 65 - 70 85 70 85 DD

105 105 143 105 105 105 143 105 105 121 165 132 132 165 132 165 220 165 220 209 209

- 73.5 105 - - 73.5 105 - - 84 143 - 84 143 - 143 187 143 187 DD

12 12 12 8 12 12 12 8 12 12 12 12 12 12 12 12 12 12 12 12 12

4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40

60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

B B B B B B B B B B B B B B B B B B B B B

PPPPPPPPPPPPPPPPPPPPP

x PPPx PPPx PPx PPx PPPPx x

PPPx PPPx PPPPPPPPPPPPP

PPPPPPPPPPPPPPPPPPPPP

PPPx PPPx PPPPPPPPPPPPP

20000 20000 20000 20000 10000 10000 5000 5000

6000 7000 7000 6000 6000 7000 7000 4500 4500 5000 5000 4500 5000 5000 4500 5000 5000 5000 5000 2500 2500

- 394 385 - 394 385 - 394 - 394 - D D - -

- 326 316 - 326 316 - 482 - 482 - D D - -

- 414 - - 414 - - 628 - 628 - D D - -

- 431 423.5 - 431 423.5 - 431 - 431 - D D - -

468 - 468 - 468 468 468 468 468 468 583 583

399 - 399 - 399 555 555 555 701 701 913 913

487 - 487 - 487 701 701 701 909 909 1182 1182

587 - 587 - 587 587 587 587 587 587 691 691

Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear.
D
Please consult us. 5
Protection releases

Microprocessor-based, Communication-capable Release - SR71

Salient Features

Micro-controller based RMS sensing


l
Offers comprehensive protection for overload, short circuit,
l
instantaneous, earth fault and neutral overload
High resolution backlit LCD display
l
Intelligent Pre-trip alarm to prevent system shutdown
l
Password protected setting and commands
l
MODBUS RTU protocol
l
Intrinsic RS 485 Port
l
Total breaker control and monitoring through PC
l
LED indication for POWER ON, different fault and Pre-trip alarm
l
2 sets of storable protection setting
l
Non-volatile memory to store last 5 trips history
l
128 Event recording with time & date stamping
l
3 programmable contacts-1 for micro controller failure, 2 for basic
l
fault annunciation
4 relay contacts for indication of maximum demand exceed, Pre-trip
l
alarm, and control on breaker (closing and opening)
Auto-doubling features to prevent nuisance tripping
l
Selectable I2t based current for short-time and earth fault zones
l
Thermal reflectivity enables faster tripping on recurrent overloads
l
Intelligent discrimination
l
Self-diagnostic and monitoring with tri-colour LED indication
l
Conformance to EMC standards
l

Parameter Screen Details Factory


Abbreviation Settings
Overload Current Settings (A), Ir = In x .... PICKUP 0.4 to 1.0 In in steps of 0.05 In 1.0 In
(Phase) Time Delay, Tr (sec) at 6 x Ir TMS-tr 0.5-1-2-4-6-12-18-24-30 30 sec
Pre-trip Alarm Settings PREALAR 0.5 to 0.95 Ir in steps of 0.05 Ir 0.95 Ir
Thermal Reflectivity THM-MEM ON / OFF OFF
Function FUNC Enable / Disable
Neutral Fault Current Settings (A), In = Irx .... PICKUP 0.5-1.0 1.0 Ir
Time Delay (sec) DELAY Same as 'Overload (Phase)' 30 sec
Short Circuit Current Settings (A), Is = In x .... PICKUP 2 to 10 In in steps of 0.5 In 10 In
Time Delay, Ts (msec) at 10 x In l2t OFF DELAY 20-100-200-300-400 400 msec
2
l t ON DELAY 20-100-200-300-400 400 msec
Pre-trip Alarm Settings PREALAR 0.5 to 0.95 Is in steps of 0.05 Is 0.95 Is
2 2
lt lt ON / OFF
Cold-load Pickup COLDPIC Enable / Disable Disable
Cold-load Pickup Delay CP_DLY 0.1 to 10 sec in steps of 0.1 sec 0.1 sec
Instantaneous Function FUNC Enable / Disable Enable
Current Settings (A), Ip = In x .... PICKUP 2 to 16 In in steps of 0.1 In 16 In
Earth Fault Function FUNC Enable / Disable Enable
Current Settings (A), Ig = In x .... PICKUP 0.1 to 0.6 in steps of 0.05 In for l2t ON 0.6 In
0.1 to 0.6 in steps of 0.01 In for l2t OFF
Time Delay (sec), Td DELAY 100 to 400 msecs in steps of 100 msec for l2t ON 3 sec
2
0.1 to 5 sec in steps of 100 msec for l t OFF
Pre-trip Alarm Settings PREALER 0.5 to 0.95 Ig in steps of 0.05 Ig 0.95 Ig
2 2
lt lt ON / OFF OFF
Cold-load Pickup COLDPIC Enable / Disable Disable
Note: Both Protection Groups 1 & 2 carry the same factory settings.
6
Additional Protections

Parameter Screen Details Factory


Abbreviation Settings

Under Current Function FUNC Enable / Disable Disable


Current Setting(A) x In PICKUP 15% to 80% in steps of 5% in 0.8 In
Time Delay (secs) DELAY 1 to 255 in steps of 1 second 1 second
Trip / Alarm MODE Either / Both Alarm
Current Unbalance Function FUNC Enable / Disable Disable
Current Setting (A) x In PICKUP 10% to 95% in steps of 5% in 0.2 In
Time Delay (secs) DELAY 1 to 10 in steps of 5 secs 2.0 secs
Over Voltage# Function FUNC Enable / Disable Disable
Voltage Setting (V) Vs = Vn x .. PICKUP 105% to 150% in steps of 5% Vn 1.2 Vn
Time Delay (secs) DELAY 0.1 to 100 in steps of 0.1 secs 5.0 secs
Reset Voltage RSTSET 85% to 98% in steps of 1% Vs 0.95 Vs
Trip / Alarm MODE Either / Both Alarm
Under Voltage# Function FUNC Enable / Disable Disable
Voltage Setting(V) Vn x .. PICKUP 45% to 65% in steps of 5% Vn 0.6Vn
Time Delay (secs) DELAY 0.1 to 5 in steps of 0.1 secs 1 second
Reset Voltage RSTSET 102% to 115% in steps of 1% Vs 1.02Vs
Trip / Alarm MODE Either / Both Alarm
Under Frequency# Function FUNC Enable / Disable Disable
45 to 50 Hz for 50 Hz in steps of 0.01 Hz 48.0Hz
Frequency Setting (Hz) PICKUP
57 to 60 Hz for 60 Hz in steps of 0.01 Hz 59.0 Hz
Time Delay (secs) DELAY 0.1 to 100 secs in steps of 0.1 Second 0.2 secs
Drop Off Frequency DRPOFF 0.02 to 0.10 Hz in steps of 0.1 Hz 0.1 Hz
Trip / Alarm MODE Either / Both Alarm
Over Frequency# Function FUNC Enable / Disable Disable
50 to 55 Hz for 50 Hz in steps of 0.01 Hz 52.0 Hz
Frequency Setting (Hz) PICKUP
60 to 62 Hz for 60 Hz in steps of 0.01 Hz 61.0 Hz
Time Delay (secs) DELAY o.1 to 100 secs in steps of 0.1 second 0.2 secs
Drop Off Frequency DRPOFF 0.02 to 0.10 Hz in steps of 0.1 Hz 0.1 Hz
Trip / Alarm MODE Either / Both Alarm
Reverse Power# Function FUNC Enable / Disable Disable
Settings (kW) PICKUP 0.02 to 0.4 in steps of 0.01 Pn 0.2Pn
Time Delay (secs) DELAY 1 to 100 in steps of 0.1 secs 2.0 secs
Trip Alarm MODE Either / Both Alarm
Phase Sequence# Function FUNC Enable / Disable Disable
Settings PICKUP 123-132 123
Time Delay (secs) DELAY 0 to 5 in steps of 0.5 secs 2 secs
Trip / Alarm MODE Either / Both Alarm
Breaker Failure Function FUNC Enable / Disable Disable
Time Delay (secs) DELAY 0.05 to 2 secs in steps of 0.01 secs 1.0 second
Maximum Demand Function FUNC Enable / Disable Disable
Exceed Settings (kW) PICKUP 40-1600 kW 100kW
Step DELAY 10 kW - 1000 10kW
i -Discrimination i -Discrimination Disable

# Requires SR71-PM module


8
Metering

Parameter Screen Abbreviation Details


Current I Phase, Earth and Neutral
Imax Maximum running Current per Phase
%Load Percent Loading
Voltage# V Phase-Neutral
Vph-Vph Phase-Phase
Frequency# F System Frequency
Power Factor# PF System Power Factor
Power# kW Active Power per Phase and Total (kW)
kVAr Reactive Power per Phase and Total (kVAr)
kVA Apparent Power per Phase and Total (kVA)
kW Maximum Demand (kW)
Energy# kWh Total Active Energy (kWh)
kVArh Total Reactive Energy (kVArh)
kVAh Total Apparent Energy (kVAh)
Harmonic-Current I1HAR R-Phase Current Harmonics
I2HAR Y-Phase Current Harmonics
I3HAR B-Phase Current Harmonics
Harmonic-Voltage# V1HAR R-Phase Voltage Harmonics
V2HAR Y-Phase Voltage Harmonics
V3HAR B-Phase Voltage Harmonics
Display High Resolution Backlit LCD
# Requires SR71-PM module

Additional Features
Parameter Details
LED Indications Auxiliary Power On P
Overload P
Short Circuit P
Instantaneous P
Earth Fault P
Neutral Fault P
Trip P
Alarm P
Auxiliary Supply 24V DC
Digital Inputs 4 Nos.
Output Relays 3 Internal + 4 External Relays
240V AC/5A, 30V DC/5A (resistive load)
Rating Plug In Multiplier 630-800-1000-1250-2000-3200-5000
Communication Protocol MODBUS RTU
Link used RS 485
2
Maintenance Indication I t based
Event Records Pickup, Alarm, Trip, Date, Time and Cause of Event
Trip Records Last 5 records with date and time stamping,
voltage and current readings in all phases
Testing Self-Diagnostic Test P
Relay Module 4 Relay Outputs
Supplementary Modules Power Supply Module 24V DC Output
Communication Module MODBUS RTU
No. of Storable Settings 2
9
Protection releases

Microprocessor Based Release - SR21i

Salient Features

l Self-powered

l True RMS sensing

l Zone selective interlocking on short circuit and ground faults reduces


dynamic and thermal stress on the system

l Self-diagnostic and self-correcting facility to monitor its own


performance

l Facility for default protection setting

l Switchable thermal memory takes care of residual heat in case of


repetitive overloads

l Multi-state LED to indicate


- Power ON condition
- Test mode
- Microprocessor unhealthy condition

l Individual fault annunciation through LEDs

l On load testing release possible through ‘TEST’ button


(without tripping the breaker)

l AN1 module for remote fault indication through LEDs with changeover
contact for each kind of fault

l Direct tripping of breaker-reliable tripping with minimum time delay


test kit available for testing the release (SRT-2)

l Realistic hot and cold curves which take into account integrated
heating effect

l Conformance to EMI/EMC standards

Type of Setting Range


Protection Pick-up Current Time Delay

Ir - 0.5 to 1.0 times In 0.2 to 30 sec. at 6 times Ir


Long Time Steps : 0.50, 0.60, 0.65, 0.70, Steps : 0.2, 0.5, 1, 1.5, 2, 3.5,
0.75, 0.80, 0.85, 0.9, 0.95, 1.00 6, 12, 17, 30 Sec

20 ms to 600 ms
Short Time 2 to 10 times In Steps : 20, 60, 100, 160, 200,
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 260, 300, 400, 500, 600 ms

2 to 16 times In -
Instantaneous Steps : 2, 3, 4, 6, 8, 10, 12,
14, 16 One position as infinity.

0.2 to 0.6 times In 100 to 400 ms.


Ground Fault
Steps : 0.2, 0.3, 0.4, 0.5, 0.6 Steps : 100, 200, 300, 400 ms
& infinity

In 3 phase, 4 wire system, Neutral CT is required for ground fault protection.

11
Protection releases

Microprocessor Based Release - SR18 & SR18G

Salient Features

l Self-powered

l True RMS sensing

l Comprehensive protection
- SR18; Long Time and Short Time
- SR18G; Long Time, Short Time and Ground fault protection

l True Hot & Cold characteristics

l Switchable thermal memory takes care of residual heat in case of


repetitive overloads

l Facility to have default protection settings

l Suitable for 800A to 6300A

l Multi-state LED to indicate


- Power ON condition
- Test mode
- Microprocessor unhealthy condition

l Individual fault annunciation through LEDs

l On load testing of release possible through ‘TEST’ button


(without tripping the breaker)

l Test kit (SRT-2) available for testing the releases

l Direct tripping of breaker-Reliable tripping with minimum time delay

l Conformance to EMI/EMC standards

Type of Setting Range


Protection
Pick-up Current Time Delay

Long Time Ir - 0.5 to 1.0 times In 2.5 sec at 6 times Ir


Steps : 0.50, 0.60, 0.65, 0.70,
0.75, 0.80, 0.85, 0.9, 0.95, 1.00

Short Time 2 to 10 times Ir Inst. to 400 ms.


Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 Steps: 20, 60, 100, 160, 200,
260, 300, 400, 500, 600 ms

Instantaneous 6 & 12 In -

Ground Fault* 0.2 to 0.5 times In 100 to 400 ms.


Steps : 0.2, 0.3, 0.4, 0.5, 0.6 Steps: 100, 200, 300,
400 ms & OFF

* Available in SR18G release only


In 3 phase, 4 wire system, Neutral CT is required for ground fault protection.

12
Protection releases

Thermo-magnetic Over Current Release Type - DN1

DN1 is CT-operated thermo-magnetic release, which offers reliable


protection against overload, short circuit and ground faults.

Protection
Overload Protection
lContinuously & individual phase adjustable dial settings
from 75% to 100% of CT tap

l Inverse Time Characteristics

Short Circuit Protection


lTwo taps available to select operating threshold

Ground Fault Protection


lOffered with auxiliary earth fault release (20% to 50% In)

Salient Features
l True RMS sensing

l Ambient temperature compensated from -50C to 500C

l Wide range of overload & short circuit settings possible with


multitap CTs

l Each phase can be individually adjusted for overload &


short circuit settings

l Fixed minimum impulsion time of 25 ms on short circuit


to prevent nuisance tripping due to transients

l Trip test facility available

13
Accessories

Locks/Interlocks

Type Data

Lockable Trip Push Mounted in place of normal trip push button. With this, ACB can be locked
Button (LTPB)
in trip condition. For interlocking, LTPBs are offered in the following
combinations:
l 4 different types of keys i.e. AA, BB, CC and DD suitable for 2 incomers
and 1 bus coupler schemes
l Combination of L, M, N, LM and MN locks, which are suitable for three
incomer and two bus coupler schemes
l Combination of K, L, MN, KL, LM and MN locks, Which are suitable for
four incomer and three bus coupler schemes
l Combination of J, K, L, M, N, JK, KL, LM and MN locks, which are
suitable for five incomer and four bus coupler schemes

View of the Cradle Locking in Isolated Position (LIP)


The facility of locking the ACB in Isolated position is available in Drawout
ACBs. This is useful to achieve interlocking between Main & Standby
source. Similar lock is available as LOCK IN ANY POSITION.

Door Interlock
This ensures:
Door Racking Locking in lUnless the panel door is closed, breaker cannot be racked in or out
Interlock Inerlock ‘Isolated’ lUnless the breaker is in Isolated Position, it is not possible to open the
Position panel door

Racking Interlock
This ensures that breaker cannot be racked in/out unless the ACB is in
tripped/open condition.

Mechanical Interlock It is possible to provide ‘Mechanical Interlock’ between two breakers of


the same or different ratings in vertical or horizontal configurations.
Mechanical interlock is available for ACBs up to 4000A. Mechanical
interlocking for ACBs in vertical configuration can be provided by links or
by flexible cables. Same for horizontal configuration can be provided by
flexible cables.

14
Accessories

Signaling

Type Data
C1
Common indication of tripping due to overload, short
circuit and ground faults.
l Provided by microswitch C1 fitted inside the ACB
l Available as an option in all releases

C2
Separate indication of tripping due to overload, short
circuit and ground faults.
l For release type DN1,this is provided by microswitch C1 & C2
(C2 fitted inside release)
l Available through in-built fault indicators in SR18, SR18G,
SR21i & SR71 releases

AN1-Annunciator Module
Remote indication of tripping due to overload, short circuit
and ground faults.
lCan be used with releases type SR18/SR18G/SR21i
lIndividual fault indication provided by three separate LEDs for
- Long time faults
- Short time fault/instantaneous fault
- Ground fault one potential free contact rated 5A at 230V AC
available for each type of fault
lFlush mounting on panel (H-W-D=92mm x 46mm x 105mm)
lOperating voltage: 240V AC/110V DC/220V DC (other
Voltages available on request)

C2
Indication for operation of shunt release or under voltage
release.
l Provided by microswitch C5 fitted on the shunt release

15
Accessories

Control

Type Data Technical Data

Shunt Release
For remote tripping of the
l Type Nominal Power Operation
of voltage consume- Limit
breaker
Release Uc (V) option at
Shunt release coil is short time
l 50Hz pick up
rated and is disconnected from
EA1 240 AC 800 VA 10-130%
the circuit by an auxiliary
415 AC 800 VA Uc
contact when the ACB trips
(Refer to wiring diagram) EA 24V DC 32 W 65-130%
Low power consumption
l
48V DC 125 W Uc
110 DC 45 W
Two types available:
l
220 DC 30 W
- EA for DC application
Note : Other voltages available on request
- EA1 for AC application

Undervoltage Release
Two types available: Parameter Specification
lType MV With no intentional
Nominal 240V & 415V: 50Hz
time delay voltage (Uc) 220V & 415V: 60Hz
lType MVR With fixed time
delay of 3+1.5 sec. to prevent Pick up (V) 80% Uc
nuisance tripping against Drop off (V) 35-65% Uc
momentary voltage dips
(VA) Consumption Pick up - 23 VA
Hold on - 10 VA
Notes: When undervoltage
release is provided, the ACB can Watt loss 6W
be closed only when supply is
available to the undervoltage
release.

Auxiliary Contacts
Two combinations available: Electrical Voltage Rated current
l2 NO + 2 NC circuit (V) (A)

l6 NO + 6 NC Resistive 24 to 415 AC 16
250V AC 1.2

Non- 24 to 415 AC 16
resistive 250V AC 1.0 #

# L/R = 15ms with two contacts in series

Operation Counter lOperates mechanically


lDisplay total number of breaker
operation cycles

16
Overall Dimensions: Fixed Breakers

For 630A to 2500A 3P/4P C/H


for Metallic Components

to Remove
340 min Arc Chute
for Insulating Sheet

200 min
7

140 min
Door

100 min
20 min Bezel
36 min 36 min 9
A 27
26 58 264 26

385

256
33
394
309

22
16

68.8
27
30 230
104

Earthing Terminal 35
20 301 54
2 Holes-Ø6.3 2.6 min
21 16 405 86 10

D E F E D

Ratings Dimensions (mm) Weight (kg.)


CN - CS
A D E F Manual Electrical
630/800/1000A C/H 3P 326 57 102 - 50 57
1250/1600A C/H 3P 51 58
630/800/1000A C/H 4P 414 56 98 98 54 61
1250/1600A C/H 4P 55 62
2000/2500A C/H 3P 482 83 154 - 69 76
2000/2500A C/H 4P 628 82 150 156 77 84

For CN-CS...E 400A-2000A 3P


340 min
Insulator

40 min 316+1.0 40 min


100 min

20 min

23.5
58 102 102 56
Rating
Type X Y

400E -
1250E 5 150
X
1600/ 15 140
2000E
385

4 Holes
325

Ø12 X
286

227

216
20 20
32

298
22 137.5
402 21
179.5

Note : All Dimensions are in mm.


17
Overall Dimensions: Fixed Breakers

Terminal

2 Holes-Ø13 3 Holes-Ø13

30 15 30 15

12.5 25 50 25
25

50 100

400 to 2000 E & 800/1000/1250/1600 C/H 2000/2500 C/H

Terminal Connections
23.5

23.5
10 15

10 15
227
227

140
145

Terminal for 800/1000 C/H Terminal for 1250/1600/2000/2500 C/H

Bezel Fixing Plan for all Fixed Breakers

305
12 Holes-Ø4 101
332

Hinge Hinge
112
112

363
325

112

5.5
91

11 min 59 294 15 min

Door Cutout Door Drilling for Bezel


Bezel Fixing Plan

Note: All dimensions are in mm.


18
Overall Dimensions: Drawout Breakers

For 630A to 3200A C/H 3P/4P, 3200H1/4000H 3P


for Metallic Components
75 Isolated Position
A
380 min
51 Test Position

200 min
122 for Insulating Sheet
40 max 7

100 min
94.5 264 Service Position
Door
40 64.5 26 Bezel

*5

256
468

397.5
404

68.8
M 10

160
46 28
4 74
6 10 54
17.5 min.
199.5 20
6 18.9 max.
538 8.9 min. 18 245

*Terminal For 630/800/1000 C/H/S1,


1250/2500 S1 & 2000 C/H
D E F E D
64.5 Earthing Terminal 40 65 60
5 25 15
15 15

308.5
308.5

308.5

221.5
221.5
221.5

*Terminal for *Terminal for *Terminal for


1250/1600/2500 C/H for 3200 S1 3200 H0/H1
& 800/1000H & 4000 H0/H

Ratings Dimensions (mm)


CN - CS
A D E F
630/800/1000A C/H/S1 3P
2000A S1 3P 399 97.5 102 -
1250/1600A C/H/S1 3P
630/800/1000A C/H 4P
2000A S1 4P 487 96.5 98 98
1250/1600A C/H 4P
2000/2500A C/H 3P
555 123.5 154 -
2500/3200A S1 3P
2000/2500A C/H 4P
701 122.5 150 156
2500/3200A S1 4P
3200A H0/H1 3P
701 148.5 202 -
4000A H0/H 3P
3200A H0/H1 4P
909 151.5 202 202
4000A H0/H 4P

Note : All Dimensions are in mm.


19
Overall Dimensions: Drawout Breakers

Flat Terminal Connections 63


50 100
25
25 30 30
19
12.5 10.2 20
10.2 10.2
4 slots 4 Slots 6 Slots

58.4

58.4
58.4

38

38
8.5 x 9.5 8.5 x 9.5
38

8.5 x 9.5

8.5 8.5 8.5

630 - 1000C & 630 - 1250S1 800 - 1000H, 1250/1600 C/H & 1600/2000 S1 2000 C

106 106 160


25 25 25 25 25
33 33 33 33 6 Holes-Ø14
17.5
20 100 20
12 12

70
6 Holes-Ø14 6 Holes-Ø14

50
67

25
67
43

43
62
38

12.5
2500 C/H & 2000 H 2500 S1 3200S1 3200 H0/H & 4000H0/H1

For 5000C/6300C 3P
for Metallic Components
75 Isolated Position
A 400 min 51 Test Position
200 min

124 for Insulating Sheet


Service
20 max 7
100 min

96.5 264 Position Door


102 26 Bezel

256
404

467

68.8
M 10
160

46 28
6 5 74
10 54
199.5 10 17.5 min 20
5 18.9 max.
615 8.9 min. 18 245

D E F E D 8 Holes-Ø14

217

28
63
683

17.5

40 50 40 43.5
42
Terminal Connections
64.5
Earthing Terminal 5000C/6300C

Dimensions (mm)
Ratings
A D E F
5000A C 3P 913 187.5 269 -
6300A C 3P 913 187.5 269 -
5000A C 4P 1182 187.5 269 269
6300A C 4P 1182 187.5 269 269

Note : All Dimensions are in mm.


20
Overall Dimensions: Mounting Details

Mounting Details: For Horizontal Mounting of all Draw-out Breakers


For 630A to 3200A C/H 3P/4P 3200 H0/H1, 4000 H0/H 3P/4P
107.5 367.5 40 10 Holes-Ø11
24

G
Ratings Type
(mm)
800A - 1600A 3P C/H 280.3
*G

FRONT 630A - 2000A 3P S1 280.3


800A - 1600A 4P C/H 368.3
630A - 2000A 4P S1 368.3
2000/2500A 3P C/H 436.3
24
64.1 2000/2500A 4P C/H 582.3
2500/3200 3P S1 436.3
20 481 37
2500/3200 4P S1 582.3
3200A 3P H0/H1 582.3
For 5000C/6300C 3P/4P
592 3200A 4P H0/H1 790.3
10 Holes-Ø11
522 4000A 3P H0/H 582.3
25
4000A 4P H0/H 790.3
5000A/6300A 3P C 863
5000A/6300A 4P C 1132

25

50
108.5
184.5

Bezel Fixing Plan for all Draw-out Breakers


12 Holes-Ø4 305 332

Hinge Hinge
224
412

450
199

1 5.5
Base of
Cradle

20.5 min A 294 5 min

Door Cutout

Note: For 5000C/6300C 3P ACB, A = 81.5


For other Drawout Breakers A = 79.5

21
Overall Dimensions

Horizontal Terminals Rear Side


80 80 80 80
10

10
15

15
308.5

221.5
800 - 1000 C 1250 - 1600 C/H 2000 C 2500 C/H
& 800/1000 H & 2000 H

2 Holes-Ø14 3 Holes-Ø14 4 Holes-Ø14 6 Holes-Ø14


12.5

20
12.5

15

25 25 25
16.5

33
160
100
50

63
25

33
16.5

12.5 25 12.5 30
12.5 25 12 43

Vertical Terminals
V S W

U 40.0

4 Holes-ØT O P Top

R
N
M
387.5
X

308.5
221.5

Side View Rear View

Ratings M N P Q R S T U V W X
800A/1000A C 10.2 38 20 25 29.2 5 9 65 95 10 58.4
1250/1600A C/H 20 40 20 25 29.2 5 9 65 95 10 80
800/1000A H
2000A C 20 40 20 40 29.2 22.5 14 80 110 15 80
2500A C/H
2000A H 20 40 20 40 33.5 7.5 14 80 110 15 80

Note : 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations.
22
Switchgear Training Centres

Pune Lucknow

Coonoor

‘Train & Gain’ - This concept underlies L&T’s commitment to its


customers and the Indian switchgear industry. To this end, L&T
has set up Switchgear Training Centers equipped with a wide
range of education facilities at Pune, Lucknow & Coonoor.
Specially designed ‘Hands-On’ training programs on the
operation & maintenance of switchgear are conducted for
engineers and technicians from different industry segments.
The centers have state-of-the-art training facilities,
well-equipped workshops and testing systems.

23
Notes
Electrical Standard Products (ESP) Branch Offices:

REGISTERED OFFICE AND L&T House, Group MIG - 5 Plot No. 518
HEAD OFFICE Padmanabhpur 4th Main Road
L&T House, Ballard Estate Durg 491 001 K. K. Nagar
P. O. Box 278 Tel: 0788-2213833 / 14 / 28 / 29 Madurai 625 020
Mumbai 400 001 Fax: 0788-2213820 Tel: 0452-2537404, 2521068
Tel: 022-6752 5656 Fax: 0452-2537552
Fax: 022-6752 5858 A1/11, Astronauts Avenue e-mail: esp-mdu@LNTEBG.com
Website: www.Larsentoubro.com Bidhan Nagar
Durgapur 713 212 EBG North Wing Office - 2
Tel: 0343-2536891 / 8952 / 7844 Powai Campus
ELECTRICAL STANDARD PRODUCTS (ESP) Fax: 0343-2536493 Mumbai 400 072
501, Sakar Complex I e-mail: esp-dgp@LNTEBG.com Tel: 022-67052874 / 2737 / 1156
Opp. Gandhigram Rly. Station Fax: 022-67051112
Ashram Road Milanpur Road, Bamuni Maidan e-mail: esp-bom@LNTEBG.com
Ahmedabad 380 009 Guwahati 781 021
Tel: 079-66304007-11 Tel: 0361-2651297 8B, Farmland
Fax: 079-26580491 Fax: 0361-2551308 Ramdaspeth
e-mail: esp-ahm@LNTEBG.com e-mail: esp-gau@LNTEBG.com Behind Hotel Radhika
Nagpur 440 010
38, Cubbon Road, Post Box 5098 II Floor, Vasantha Chambers Tel: 0712-2420641 / 24
Bangalore 560 001 5-10- 173, Fateh Maidan Road Fax: 0712-2420619
Tel: 080-25020100, 25593613 Hyderabad 500004 e-mail: esp-ngp@LNTEBG.com
Fax: 080-25580525 Tel: 040-66720250
e-mail: esp-blr@LNTEBG.com Fax: 040-23296468 32, Shivaji Marg
e-mail: esp-hyd@LNTEBG.com P. O. Box 6223
New Delhi 110 015
131/1, Zone II
Tel: 011-41419500 / 1, 41419515
Maharana Pratap Nagar D-24, Prithvi Raj Road, C-Scheme
Fax: 011-41419600
Bhopal 462 011 Jaipur 302 001
e-mail: esp-del@LNTEBG.com
Tel: 0755-4233906, 4233907 Tel: 0141-2385913 / 19
Fax: 0755-2769264 Fax: 0141-2373280 L&T House
e-mail: esp-bho@LNTEBG.com e-mail: esp-jai@LNTEBG.com P. O. Box 119
191/1, Dhole Patil Road
Plot No. 559, Annapurna Complex Akashdeep Plaza, 2nd Floor Pune 411 001
Lewis Road P. O. Golmuri Tel: 020-26135048, 26135611
Bhubaneswar 751 014 Jamshedpur 831 003 Fax: 020-26129586, 26124910
Tel: 0674-6451342, 2436696 Jharkhand e-mail: esp-pnq@LNTEBG.com
Fax: 0674-2537309 Tel: 0657-2340864
e-mail: esp-bbi@LNTEBG.com Fax: 0657-2341250 3rd Floor
e-mail: esp-jam@LNTEBG.com Vishwakarma Chambers
SCO 32, Sector 26-D Majura Gate, Ring Road
Madhya Marg, P. O. Box 14 Skybright Bldg. M. G. Road Surat 395 002
Chandigarh 160 026 Ravipuram Junction, Ernakulam Tel: 0261-2473726
Tel: 0172-4646841 to 7 Kochi 682 016 Fax: 0261-2477078
Fax: 0172-4646802 Tel: 0484-4409420 / 427 e-mail: esp-sur@LNTEBG.com
e-mail: esp-chd@LNTEBG.com Fax: 0484-4409426
e-mail: esp-cok@LNTEBG.com Radhadaya Complex
10, Club House Road Old Padra Road
Chennai 600 002 3-B, Shakespeare Sarani Near Charotar Society
Tel: 044-28462072 / 4 / 5 Kolkata 700 071 Vadodara 390 015
Fax: 044-28462102 Tel: 033-44002572 / 3 / 4 Tel: 0265-6613610 / 11 / 12
e-mail: esp-maa@LNTEBG.com Fax: 033-22822589 Fax: 0265-2336184
e-mail: esp-ccu@LNTEBG.com e-mail: esp-bar@LNTEBG.com
67, Appuswamy Road
Post Bag 7156 A28,Indira Nagar, Faizabad Road 48-8-16, Dwarakanagar
Opp. Nirmala College Uttar Pradesh, Visakhapatnam 530 016
Coimbatore 641 045 Lucknow 226 016 Tel: 0891-6620411-4
Tel: 0422-2588120 / 1 / 5 Tel: 0522-2312904 / 5 / 6 Fax: 0891-6620416
Fax: 0422-2588148 Fax: 0522-2311671 e-mail: esp-viz@LNTEBG.com
e-mail: esp-cbe@LNTEBG.com e-mail: esp-Lko@LNTEBG.com

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Electrical Standard Products


Larsen & Toubro Limited
Powai Campus, Mumbai 400 072
Customer Interaction Center (CIC)
BSNL / MTNL (toll free) : 1800 233 5858
Reliance (toll free) : 1800 200 5858
Tel : 022 6774 5858
Fax : 022 6774 5859
E-mail : cic@LNTEBG.com
Website : www.LNTEBG.com

SP 50437(R2) 040209