Npa422d Pfs3 E19 v3.3 Manual
Npa422d Pfs3 E19 v3.3 Manual
Npa422d Pfs3 E19 v3.3 Manual
Operating Manual
Revision History
SL. No. Date Ver Change Details
th
1 20 Aug 12 V1.0 Initial Release
2 22nd Aug 12 V1.1 Spelling & Grammatical corrections
3 5th Sept 12 V1.2 Relay photo changed
4 15th Jun 13 V1.3 Communication details for IEC60870-5-103 is added
5 31st Aug 13 V1.4 CB Fail, Fault history and event record details added
6 31st Dec 13 V2.0 IDMT with ARR wiring diagram included
7 5th Oct 15 V2.1 Correction in TC description
8 3rd Oct 18 V2.2 Grammatical Correction
9 6th Nov 19 V3.0 DI setting, supervision, ER are revised
rd
10 3 Sept 2020 V3.1 ARR timing diagram included and some correction is the
functionality is done.
11 1st Jun 22 V3,2 Directional relay feature added
12 29th Sept 22 V3.3 Some minor correction in formatting is added
Contents
1. Introduction
2. Features
3. User interface
4. Communication
5. Terminal diagram
6. Standard Compliance
V3.3 Page 2 of 20
Operating Manual NPA 422D
1. Introduction
The Inverse Definite Minimum Time (IDMT) Relay is used to provide time graded over current and
earth fault protection. The protection is required for Feeders, Transformers, Motors, Capacitors etc.,
The relay measures the true RMS current of each line and compares with user selected threshold, if
line current exceeds the threshold, fault picks up and operating time starts. After expiry of operating
time relay initiate trip signal to circuit breaker. Various parameters of the relay can be selected by
the user
The protection setting range for phase over current & earth fault elements are different. The low set and
high set settings are independently selected for phase over current & earth fault protection elements,
Relay has been tested for different applicable IEC standards, listed in standard compliance section.
NPA 422D is microprocessor based Numerical Relay, the internal block diagram is shown below. The
current input from the line CT is scaled down to a level where it can be measured by electronic circuitry
without changing its profile. The scaled down input is fed to analog circuitry which will do the filtering
and signal conditioning. The filtered signal is feed to microprocessor for converting in to corresponding
digital values. The proven protection algorithms are stored in the microprocessor.
The algorithm calculates true RMS value of each line current then calculates operating time based on the
fault current. After completion of operating time microprocessor initiate output contacts, potential free
output contacts are used to operate trip circuit of the circuit breaker, interlocking and alarming purpose.
The internal power supply unit converts the applied aux. supply in to different voltage levels which are
required for electronic circuitry. The proper isolation between input and output is provided. The power
supply unit is provided with special filtering circuits required for stable performance in substation
environment.
V3.3 Page 3 of 20
Operating Manual NPA 422D
2. Features
2.1 Over current Protection
Relay has three level of over current protection, O/c IDMT (I>) Protection, High set 1 (I>>) Protection with
definite time delay and Instantaneous High set 2 (I>>>). The settings are site programmable. The O/c I>
protection can be programmed for definite time delay OR IDMT characteristic. The TMS required for IDMT
to provide time graded protection is adjustable. The relay has inbuilt inrush blocking algorithm.
V3.3 Page 4 of 20
Operating Manual NPA 422D
2.4 Inverse Definite Minimum Time (IDMT).
Relay operating time depends on the magnitude of fault current; the operating time is inversely
proportional to magnitude of fault current. NPA 422 is provided with different types of IEC operating
characteristics as listed below.
Where
t : Operating time in secs
T : Time multiplier setting (TMS)
t = (k * T) / (I/IRef) α – 1 I : Input current / Fault current
IRef : Set current
k & α are Curve constants (Refer table below)
Operating time in seconds at TMS 1.00 for different Curves at different multiples of set value.
2 x Set 5 x Set 10 x Set 20 x Set
Curve
In sec In sec In sec In sec
3.0s Normal Inverse 10.0 4.28 2.97 2.27
1.3s Normal Inverse 4.35 4.00 1.29 0.98
0.6s Normal Inverse 2.01 0.86 0.59 0.45
1.5s Very Inverse 13.50 3.38 1.50 0.71
0.8s Extremely Inverse 26.67 3.33 0.81 0.20
0.6s Extremely Inverse 20.0 2.50 0.61 0.15
13.3s Long inverse 120.0 30.0 13.33 6.32
V3.3 Page 5 of 20
Operating Manual NPA 422D
V3.3 Page 6 of 20
Operating Manual NPA 422D
2.5 Directional Over current / Earth fault feature
NPD 422D Provide directional protection for over current and earth fault protection element. The relay
needs voltage input to decide the direction of operation. The torque angle for over current and ear fault
are independently settable. The directional feature can be enabled / Disabled.
The direction element of particular phase over current will decided based on the respective overcurrent
and voltage element of other two phase, similarly for other over current elements. (ex. For R phase over
current directional element will utilize Y-B voltage). The Open delta voltage required to decide the
directional zone for Earth fault element will be derived internally. Operating for Over current and Earth
fault element will be indicated by respective LED’s. Dedicated one common N/O contact is provided to
indicate Phase reversal, Input Voltage fail (any or all) and Voltage connected in reversal along with
dedicated LED indication.
Two digital inputs (DI) are used to sense the Breaker status through (52a/52b) aux. contact and Breaker
spring charge status, which are required before CB closing. The DI rating is to be specified during ordering.
DI5 and DI6 are dedicatedly used for Auto reclose.
V3.3 Page 7 of 20
Operating Manual NPA 422D
The relay has dedicated lockout contact; the relay will operate lockout contact on following status.
V3.3 Page 8 of 20
Operating Manual NPA 422D
V3.3 Page 9 of 20
Operating Manual NPA 422D
2.10 Programmable Output Contacts / Digital Output
Relay is provided with max of nine contacts out of which seven output contacts are programmable;
Different contact combinations are available. The required contact combination is to be specified during
ordering. The contact functions are described in user interface. Default relay contacts are programmed as
below.
Contact Durability
Loaded 1,00,000 operations
Un-loaded 10,000,000 operations
Contact Rating
Contact Make & Carry Breaking
2500VA, Maximum 10A or 250V AC
C1, C2, C3, C4 2500VA, Maximum 10A or 250V AC
300W(Resistive), Maximum 10A or 220V DC
& Supervision 1000W, Maximum 10A or 220V DC
150W(Inductive), Maximum 10A or 220V DC
1250VA, Maximum 5A or 250V AC
C5, C6, C7, C8 1250VA, Maximum 5A or 250V AC
100W(Resistive), Maximum 5A or 220V DC
& Alarm 300W, Maximum 5A or 220V DC
50W(Inductive), Maximum 5A or 220V DC
V3.3 Page 10 of 20
Operating Manual NPA 422D
These DI’s can be used to monitor the transformer fault status, as trip circuit supervision, as Master Trip
relay coil monitoring, other protection device trip status etc. the status of DI can be monitor in HMI which
required at time of commissioning. Each DI has setting of operate delay and reset delay.
The relay recognizes the DI after the expiry of selected respective operated delay after DI energize. The
relay will reset if the DI is de-energized. Similarly, the relay recognizes the DI after the expiry of selected
respective reset delay after DI de-energize. The relay will reset if the DI is energized.
Fault history consists of Type of fault, Date & time of fault, and O/c and Earth fault value during the fault.
The fault value can be downloaded through front USB port and Rear Modbus port.
V3.3 Page 11 of 20
Operating Manual NPA 422D
On pressing <Down> key at “Monitoring Mode” relay shows total trip counts and followed by fault
history, On pressing <Enter> key all phase current values will be displayed, as shown below.
R: 0A Y: 0A
B: 0A E: 0A
TOTAL TRIPS
F1 G1 12:00:44 R: 52A Y: 0A
EF > 08/01/20 B: 0A E:
Event records consist of Type of event, Date & time of event, the event records can be downloaded
through front USB port and Rear Modbus port. All events are viewed at LCD through navigation. The
event status is recorded in bit format event type Digital input, LED Indication, Contacts Indication Optional
Feature Pick-up and Trip status are stored in pickup and drop off information, pickup indicated by “1” and
drop off indicated by “0”
On pressing <Up> key at “Monitoring Mode” relay shows event history. On pressing <Enter> key all
functional events will be displayed.
R: 0A Y: 0A
B: 0A E: 0A
V3.3 Page 12 of 20
Operating Manual NPA 422D
Sl. No. Identification Event detail
1 Power-On-Reset On powering the relay unit
2 Device-Reset Device Reset on fault
3 Setting-Change Protection Setting-Change
4 Password-Change Password-Change
5 R-Ph O/c R Phase O/c fault pickup / drop off
6 Y-Ph O/c Y Phase O/c fault pickup / drop off
7 B-Ph. O/c B Phase O/c fault pickup / drop off
8 E/F Earth fault pickup / drop off
9 Trip I> IDMT Trip condition
10 Trip I>> High set -1 Trip condition
11 Trip I>>> High set -2 Trip condition
12 TC-Fail / TC-Healthy Trip circuit fault status
13 CB-Fail Protection element Operated
14 Lockout Lockout contact operated
15 DI-1 to DI-6 Digital Input DI1 to DI6 Applied / Removed
16 C2 to C8 Output contact operation C1 to C8 Operated/Release
Contacts Indication C C8 C7 C6 C5 C4 C3 C2
2
Optional feature OP LO BF TC
Event display information has 6 different statuses, each event contains all above-mentioned status.
Event Types Indication Details
Digital input 1 Represents Pickup of respective Event type
LED Indication
Contacts Indication
0 Represents Drop off of respective Event type
Optional feature _ Resents there is no change in event with respective to
Pick-up and Trip (underscore) previous respective event type.
In gen events only indication will be 0 or 1, it does not contain No change
General Events
Indication
V3.3 Page 13 of 20
Operating Manual NPA 422D
2.19 Technical specifications
Current In 1A or 5A
Ratings
Auxiliary supply 18 to 60V DC or 80 to 265V AC/DC
V3.3 Page 14 of 20
Operating Manual NPA 422D
3. User interface
Relay provides user friendly Human Machine Interface (HMI), relay has six snap switches used to navigate
settings, accept settings, test output contacts etc., the alphanumeric 2-line LCD provides easy
understanding of settings and operations. The relay displays the acceptable setting ranges on left-bottom
corner of respective setting window. Relay will not accept the setting beyond the specified range and
resolution.
V3.3 Page 15 of 20
Operating Manual NPA 422D
R: 0A Y: 0A
B: 0A E: 0A
A B
V3.3 Page 16 of 20
Operating Manual NPA 422D
A B
“Monitoring Mode” (Where the relay displays the all phase current values)
<EDIT> : To enter into “Setting Mode”
<UP> : To view the Event records,
<DOWN> : To view Trip count and to view Fault History,
<ENTER> : To change / select Active group (G1/G2),
<TEST> : To test the selected output contacts of the relay to operate.
(Selected output contacts will be operated for a duration of 5 to 7 sec)
<RESET> : To reset the entire relay from its present operation
“Setting mode” (Where the relay setting options / values appears)
<EDIT> : To exit from “Setting Mode”
<UP> : To select / scroll the setting Options / Change the setting values
(On pressing once, value increment by one unit, on pressing continuously,
value increment by multiples)
<DOWN> : To select / scroll the setting Options / Change the setting values
(On pressing once, value decrement by one unit, on pressing continuously,
value decrement by multiples)
<ENTER> : To accept selected Option / Changed values.
<RESET> : To reset the entire relay from its present operation
V3.3 Page 17 of 20
Operating Manual NPA 422D
4. Communication
4.1 USB communication
NPA 422 is provided with Front USB port for uploading and downloading relay settings, downloading relay
fault history and event records. A dedicated software avana- Quick Connect is to be installed to access
the relay details.
V3.3 Page 18 of 20
Operating Manual NPA 422D
5. Terminal diagram
V3.3 Page 19 of 20
Operating Manual NPA 422D
6. Standard Compliance
IEC 60255-5; 2000: Insulation requirement test
500V DC for 1min to each circuit and exposed conductive parts & Independent circuits
2kV AC for 1min between each circuit and exposed conductive parts & Independent circuits
5kV peak, 5 positive and 5 negative Impulses of wave shape 1.2/50 use for 10 secs
V3.3 Page 20 of 20