Steam Generator: Manual
Steam Generator: Manual
Steam Generator: Manual
STEAM GENERATOR
STE-30-1/2 STE-45-1/2 STE-45-C1/3 STE-90-C1/3
STE-35-1/2 STE-50-1/2 STE-60-C1/3 STE-120-3
STE-40-1/2 STE-75-C1/3 STE-150-3
STE 2 STE 3
3,0 kW 4,5 kW 4,5 kW
3,5 kW 5,0 kW 6,0 kW
4,0 kW 7,5 kW
STE 6
9,0 kW
12,0 kW
15,0 kW
ENGLISH
TABLE OF CONTENTS
Before Installation...................................................................... 3
Steam Room Guidelines............................................................3
Steam Generator Parts..............................................................4
Instructions of Use...................................................................... 5
On/Off Mode............................................................................5
Illumination..............................................................................5
Standby Mode..........................................................................5
Session Time............................................................................6
Temperature.............................................................................6
Remote Switch.........................................................................6
Demand Button........................................................................6
Maintenance................................................................................ 7
Decalcification..........................................................................7
Level Probe Cleaning.................................................................8
Tank Cleaning...........................................................................8
Assembly and Installation.......................................................... 9
Plumbing..................................................................................9
Steam Generator.................................................................... 10
Water Supply.......................................................................... 10
Water Pressure....................................................................... 10
Connecting Water Filter and Softener....................................... 10
Steam Outlet.......................................................................... 11
Steam Guard Overflow............................................................ 11
Steam Head........................................................................... 11
Drain..................................................................................... 12
Technical Data........................................................................ 12
Power Wiring.......................................................................... 13
Electrical Diagram................................................................... 13
Installing the Temperature Sensor............................................ 17
Installing Control Unit............................................................. 18
Connection of SAWO Control to the PCB................................... 19
Terminal Connection of Demand Button (optional).................... 20
Jumper Connections in the Steam Generator PCB.................. 21
Steam Generator Series Connection......................................... 22
Troubleshooting........................................................................ 23
2 ENGLISH
Before Installing
Use the following information together with the consultation of your contractor, architect
or designer in determining all factors necessary in providing a suitable and safe steam
room.
Ensure that the steam generator kilowatt corresponds to the volume of your steam
room. Refer to Technical Data (See page 12).
WARNING!
The voltage of the light output is 230VAC. Sawo
recommends to use less than 50V for the steam
room lightning. Use appropriate transformer
for lower voltages. Sawo is not responsible of
damages caused by using higher voltage inside
the steam room.
ENGLISH 3
Steam Generator Parts
Relay
Terminal for Water Level Probe
steam generator
accessories Transformer
Power switch
Terminal for
incoming line Steam Outlet
Drain Valve
WARNING!
For illustrative purposes only.
Not for use for wiring. For
component identification only.
4 ENGLISH
Instructions of Use
There are three different operation modes in the unit: Off, On and Standby. The user can
easily switch between different modes, making the steam bathing more convenient with
less energy consumption.
To use steam room the control unit needs to be in the On mode. In the On mode, the
steamer is active, the temperature in the steam room will be kept in the preferred, set
temperature, with occasional discharge of steam.
However, if the steam room is not used constantly, the generator can be set to Standby
mode. The water in the tank is kept warm, with minimal energy usage. The generator is
able to produce steam shortly after the unit is switch back to On mode for the convenience
of the users or after Standby time expires. Room temperature is also kept warm during
Standby-mode. Setting for room temperature is from 30 to 55°C.
On/Off Mode
Press the On/Off button for ON /
OFF / STANDBY
Thermo knob
Short press the button to switch ON Rotate to set
and long press to switch OFF. minimum or
maximum room
When short press in ON mode, it temperature
goes to Standby.
ON steady light
OFF slow blink
STANDBY moderate blinking
ERROR fast blinking
Standby Mode
During the Standby mode the water in the steam generator tank is kept hot. This minimizes
the time to produce steam when generator goes to On mode after Standby time expires.
Standby-mode can be activated by any of the following methods when the unit is in On
mode:
1. Short press “On/Off” button
2. When session time expires.
Extra setting is available if wanting to have less than 10deg.C temperature while in
Standby mode. See jumper settings.
Standby mode can be disabled or enabled by a jumper setting on the STE board.
ENGLISH 5
To activate On-mode again short press the “On/Off” button or turn latch remote On.
To go Off-mode:
1. Short press “On/Off” button
2. Wait until remaining standby time expires.
3. Latched off remote on, if disabled standby.
Session time
Session time can be set by jumpers on the STE board. See page 21 for further details.
Temperature
Room temperature can be set by turning thermo knob. Setting is from 30 - 55deg.C
maximum.
Remote switch
Remote ON input can be lathing switch or 230VAC input. Jumper 13 can disabled interface
and room temperature dependence if placed. The main board will only follow commands
from Remote ON switch, Remote ON AC, and demand button. And will follow default
setting for room temperature. This setting is intended for WET sauna application or
SAUNA heater and Steam Generator tandem.
If remote ON Switch is latched ON or Remote ON AC has HIGH input it will cause the
following:
• Can’t turn to state “OFF” using ON/OFF button.
• Unlimited Session time
Demand Button
6 ENGLISH
Maintenance
1. Decalcification
Tap water contains impurities, for example lime, that can cause calcium deposit and
block the internal parts of the steam generator. To prevent this and prolong the lifetime
of steam generator it is recommended to have a water filter and water softener. They
are connected to the water source of the steam generator’s water inlet.
SAWO Decalcifying Solution can be used for decalcification. Follow these guidelines to
perform preventative maintenance of the steam generator.
STE with ECO Control:
WARNING! 1. Remove top cover and level probe. Before opening,
make sure that the generator is off. Use a flat head
Never add the Decalcifying screw driver or similar to poke the level probe to
Solution when the generator is dismount. Pour the solution into the water tank. Place
on, it can cause serious burns! level probe.
Steam Decalcifying
Generator Solution
(kW) (ml)
3-7,5 250
9-15 500
< 3 ºdH = very soft water, decalcification every 500 operation hours
3-6 ºdH = soft water, decalcification every 100 operation hours
6-9 ºdH = hard water, decalcification every 50 operation hours
9-18 ºdH = very hard water, decalcification every 30 operation hours
ENGLISH 7
2. Level probe cleaning
a. Turn switch OFF before opening the steam generator’s cover.
b. Rotate the probe as shown in the illustration. Note that probe’s enraved marking must
point to “unlock” sign.
c. Use a flat head screw driver or similar to poke the level probe to dismount. Clean tip
of the pins from impurities using sandpaper. Don’t damage plastic coating on pins. If
coating is damaged, replace level probe. Return back the level probe to its original
position when done.
Engraved Marking
WARNING!
Make sure that wire terminals
must not touch each other to
avoid short circuit.
8 ENGLISH
Assembly and Installation
1. Location of the steam generator has to be near the steam room. Place it within 7.5
meters to the steam room.
2. Steam generator has to be installed outside the steam room.
3. The steam generator must not be installed outdoors or areas that may damage the
unit due to climate conditions.
4. Do not install the steam generator or plumbing lines in unheated attic or any locations
where water could freeze.
5. The steam generator must not be installed in areas near flammable or corrosive
materials or chemicals such as gasoline, paint thinners, chlorine or the like.
6. Provide a level surface to install steam generator. Side hole slots are provided for wall
mounting. Make sure that the steam generator is secured and is level when mounted
on the wall.
7. The steam generator has to be installed in an upright position only.
8. Install water filter and softener or alike when necessary.
9. Leave enough space for service and maintenance of the generator.
Minimum Space for Service and Maintenance Wall Installation
CEILING
Interchangeable
bracket.
min. min. 0mm Screw to the wall.
300mm 38
300mm
STEAM ROOM
WALL
min. 240mm
300mm
WALL
min.150mm FLOOR
Steam Generator
Control unit
Temperature sensor
Power supply Water inlet
Over
Pressure
Steam Line Demand
Button
Steam
generator
Drain
Drain
Steam Head
Plumbing
The plumbing has to be done by a qualified licensed plumber. Plumbing should be in
accordance with national or local codes. Use unions for piping connections. Use only
prescribed brass piping or copper tubing. Never use black or galvanized pipe for the
plumbing as it can easily crack or damage.
ENGLISH 9
Steam Generator
3,0 kW | 3,5 kW | 4,0 kW | 4,5 kW | 5,0 kW
4,5 kW | 5,0 kW | 6,0 kW |7,5 kW Side view
NOTE!
If facing the wall there should be showing element
at least 100mm allowance. access panel
525mm Water Inlet
Thread:
3/4” BSP
Power
Switch
Steam
Outlet Valve
Overpressure
Valve
410mm
Drain Valve
Thread:
1/2” BSP
Power
525mm Switch
Water Inlet
Thread:
3/4” BSP
Steam
Outlet Valve
Overpressure
Valve
410mm
Drain Valve
Thread:
1/2” BSP
NOTE!
Refer to Technical Data for specifications.
Water Supply
Provide a shut off valve on the water source for the steam generator. Turn off the inlet
water line before installing the unit. Refer to the water filter’s manual for the pressure
requirement when installing. Maximum water pressure without water filter/softener is 8
bar. The water flow range must be at minimum of 4 liters per minute. Water softener is
recommend to use.
Water Pressure
The water pressure required for the STE steam generators is 2-8 bar or 30-120psi. Below
or above the pressure requirement may lead to damage or malfunction of the water inlet.
Connecting Water Filter and Softener
For illustrative purposes only.
Water Filter /
Softener
10 ENGLISH
Steam Outlet
The steam must move in a continuous flow to the steam room. Do not install valves on
the steam line. Use insulated, rated 120ºC or higher, brass pipe or copper tubing for
steam line to connect to the steam head as permitted by codes (see table below). Slope
the steam line height by 20mm per meter towards the steam head to avoid trapping of
the condensate and eliminate steam trap that blocks the flow of the steam.
Steam Guard Overflow
The overflow safety guard activates when there is an overpressure in the steam line. It
automatically opens and releases the pressured steam. When this happens, please check
your steam line for servicing.
Steam Head
Place the steam head on a safe area where bathers cannot get in contact with it as it can
get very hot. It is recommended that the steam head must be facing downwards. A teflon
tape or equivalent needs to be used on the thread for tightening it. Avoid using a wrench
to tighten the steam head as it might get scratched.
Running the steam line down and then up will create
a “steam trap” blocking the flow of the steam.
(kW) Steam
Line
3-7,5 3/4”
9 and above 3/4”
Place a Sealant or
Silicone to fill in the
300mm
gaps.
min. 3mm
Steam room wall
ENGLISH 11
Drain
Drain valve is provided for maintenance. Set drain connection for your steam generator
according to national or local plumbing requirements. Use only 1” pipe for drain to avoid
water clogged up.
Technical Data
Steam
Model kW Room Heating Element Voltage Current Phase Wire Size of Steam Generator Weight
Size
Volume Type Length Width Height
(m³) (kW) Number (V) (A) mm² (mm) (kg)
STE-30-1/2 3,0 3 max 2 x 1,5 kW STG-150 220 - 240 / 14 1N / 2,5 525 175 410 9
380 - 415 8 2N 2,5
STE-35-1/2 3,5 3,5 max 1 x 1,5 kW STG-150 220 - 240 / 19 1N / 2,5 525 175 410 9
1 x 2,0 kW STG-200 380 - 415 9 2N 2,5
STE-40-1/2 4,0 4 max 2 x 2,0 kW STG-200 220 - 240 / 18 1N / 4,0 525 175 410 9
380 - 415 10 2N 2,5
STE-45-1/2 4,5 2-5 1 x 2,0 kW STG-200 220 - 240 20 1N / 4,0 525 175 410 9
1 x 2,5 kW STG-250 380 - 415 12 2N 2,5
STE-50-1/2 5,0 2-6 2 x 2,5 kW STG-250 220 - 240 22 1N / 4,0 525 175 410 9
380 - 415 8 2N 2,5
STE-45-C1/3 4,5 2-5 3 x 1,5 kW STG-150 220 - 240 / 20 1N 4,0 525 200 410 10
220 - 240 / 12 3 2,5
380 - 415 7 3N 2,5
STE-60-C1/3 6,0 3 - 10 3 x 2,0 kW STG-200 220 - 240 / 26 1N 6,0 525 200 410 10
220 - 240 / 16 3 2,5
380 - 415 9 3N 2,5
STE-75-C1/3 7,5 4 - 15 3 x 2,5 kW STG-250 220 - 240 / 13 1N 8,0 525 200 410 10
220 - 240 / 20 3 4,0
380 - 415 11 3N 2,5
STE-90-C1/3 9,0 8 - 20 6 x 1,5 kW STG-150 220 - 240 / 40 1N 8,0 525 290 410 13
220 - 240 / 23 3 4,0
380 - 415 13 3N 2,5
STE-120-3 12,0 15 - 28 6 x 2,0 kW STG-200 380 - 415 18 3N 4,0 525 290 410 13
STE-150-3 15,0 22 - 40 6 x 2,5 kW STG-250 380 - 415 22 3N 6,0 525 290 410 13
NOTE!
This table is for steam rooms built with light walls (tempered glass or acrylic). Steam rooms with
thick walls or ventilation, please use higher kilowatt steam generators.
12 ENGLISH
Power Wiring
Only a qualified electrician should do the Electrical wiring connections.
Check the power supply before installing your unit. Single Phase connection, a 220-240V
supplied is required. Use two-wire supply source and equipment grounding wire of single
phase connection.
A 90ºC / 600V (HO7RN-F) rated insulated copper wire is required for SAWO steam
generators. Check size of wires in Ampere Chart in accordance with the National Electrical
Code and local electrical code.
The installation must include switch for all pole disconnection. Circuit breaker with 3mm
control gap is recommended.
Electrical Diagrams
1 PHASE / 2 PHASE 3,0 kW | 3,5 kW | 4,0 kW | 4,5 kW | 5,0 kW
Water Feed
Water
Level
S Solenoid Valve
Remote ON AC
Probe
Advance
Control
SLAVE
6 Poles IDC
1 2 3 1 2 3
ECO Control
1 2 3 1 2 3
Switch
24 VAC OUT
PL
12V Temperature
DC Switch Sensor
H1
Fuse
G N L1 L2 H2
380-415V
Remote ON Switch
2N~
Heating
Elements
G N L
220-240V
1N~
ENGLISH 13
CONVERTIBLE
Water Feed
Water
Level
S Solenoid Valve
Remote ON AC
Probe
Advance
Control
SLAVE
6 Poles IDC
1 2 3 1 2 3
ECO Control 1 2 3 1 2 3
Switch
24 VAC OUT
PL
12V Temperature
DC Switch Sensor
H3
Fuse
H2
G N L1 L2 L3
380-415V
NTC 2 Tank sensor
Remote ON Switch
H1
3N~
Heating
Elements
Copper
Jumper
G L1 L2 L3
220-240V
3~
G N L
220-240V
1N~
14 ENGLISH
CONVERTIBLE
9,0 kW
Water Feed
Water S Solenoid Valve
Level Remote ON AC
Probe
Advance
Control
SLAVE
1 2 3 1 2 3
6 Poles IDC
ECO Control 1 2 3 1 2 3
Switch
24 VAC OUT
PL
H1
12V Temperature
DC Switch Sensor
H2
Fuse
H3
G N L1 L2 L3
380-415V H4
NTC 2 Tank sensor
Remote ON Switch
3N~ H5
H6
Copper
Jumper Heating
Elements
G L1 L2 L3
220-240V
3~
G N L
220-240V
1N~
ENGLISH 15
3 PHASE
12,0 kW | 15,0 kW
Water Feed
Water
Level S Solenoid Valve
Probe Remote ON AC
Advance
Control
SLAVE
6 Poles IDC
1 2 3 1 2 3
ECO Control
1 2 3 1 2 3
Switch
24 VAC OUT
PL
H1
12V Temperature
DC Switch Sensor
H2
Fuse
H3
G N L1 L2 L3
380-415V H4
Remote ON Switch
3N~
H5
H6
Heating
Elements
16 ENGLISH
Installing the Temperature Sensor
Before installation main supply of the generator must be switch off from the
circuit braker.
The temperature sensor comes along with the SAWO steam generator. It is recommended
to use only Sawo temperature sensor with Sawo generator as it may otherwise not function
correctly.Temperature sensor wiring should not be routed near power cables or hot areas
as it may cause electronic interference or damage to the wires.
The sensor has an integrated 9-meter cable. If longer cable is
needed use 2 x 0,5 mm2 to 2 x 1,0 mm2 cable for extension. For illustrative purposes only.
Temperature
Sensor
Fig. 3
4. Insert the temperature sensor through the steam
room wall. Do not apply staples or other material
that may damage the cable.
Wall
Silicone Sealant
Never attempt to modify or to fix the steam control. Ask your licensed technician or your
nearest service centre for repair.
Before installation, main supply of the generator must be switch off from the circuit
breaker.
Installation Instructions
Check the most suitable area to place your steam generator control. The control and the
steam generator should be accessible for the user and maintenance. Do not install the
control unit inside the steam room! The cable of the control is 7,5 meters.
Mount the control in the wall, according to the specifications given below. Follow
NOTE!
If the control is attached to a concrete wall,
provide a control holder or equivalent to
mount the control into it.
Wall
illustration.
Insert the metal casing
into the hole. Poke the
spikes with a screw driver
to secure it to the hole. If
not possible because of
a thick wall, screw the
casing into the wall.
18 ENGLISH
Connection of SAWO Control to the PCB
Before installation make sure that the generator is disconnected from the mains by
switching off the circuit breaker.
1. Unscrew top cover of the steam generator to get access on the PCB.
2. Guide the RJ11 control cable through the cable lead-in hole on the side of the
generator as described in the drawing below to reach RJ jacks on the STE board.
3. Note that there are four black RJ jacks on the board. Make sure to connect the RJ
cable to “Control B” jack. Connection cannot be interchanged. Other jacks are for
Features, Classic 2.0 control and for Slave connection.
FEATURES
BOARD
CONTROL A
SLAVE
CONTROL B
ECO Control
5. Turn the mains on and switch on the power switch in the back of the generator.
ENGLISH 19
Terminal Connection of Demand
Button (optional)
Before installation make sure that the mains
is disconnected from the generator by turning
off the circuit breaker.
1. Open the top cover of the generator.
2. Guide the cable through cable lead-in on
the side of the generator.
3. Connect the wires to their designated
places in the terminal block.
4. If the demand button has light connect the
light wire on the “ILL” labeled terminal.
20 ENGLISH
Jumper Connections in the Steam Generator PCB
JUMPER
TEMP
(CLOSE)1 STBY SESSION SLAVE OPTIONS
1 2 3 1 2 3 4 M 1 2 1 2 3 4 5
JUMPER
(OPEN)
0
When High Temperature feature is ON (1), the An example is that when the steam generator is used
steam tank temperature is maintained until to increase the humidity of the sauna. The control of
87deg. Celsius. the sauna heater will be the primary host of the steam
21
generator.
ENGLISH
Steam Generator Series Connection
1 2 3 4
RJ11 Cable JUMPER JUMPER JUMPER JUMPER JUMPER
M = OFF M = ON M = ON M = ON M = ON
1 = OFF 1 = OFF 1 = ON 1 = OFF 1 = ON
2 = OFF 2 = OFF 2 = OFF 2 = ON 2 = ON
22 ENGLISH
Troubleshooting
If an error occurs, the steam generator will be switched off. There will be a
warning beep to alarm the user every 2 seconds. The code for the error will be
displayed blinking on the STE board. See table below.
If error happens in slave, by pressing on/off this problem slave will deactivate.
Rest of the steam generator will continue normal function.
If error occurred in any of the master or slaves, only the four LED indicators on
the power controller board of damage board will blink, see table 15. The LED 1 of
other board will blink to indicate state “OFF”.
The activation and deactivation of master and slave can be set by the jumpers on
the power controller board of basic steam generator.
ERROR
Code Problem Solution
1 2 3 4
E1 Temperature sensor 1 Check the wire between the sensor and the 0 0 0 1
not connected. control unit.
E4 Temperature sensor 2 0 1 0 0
short circuit.
E5 Temperature fuse defect. Check the wire between the fuse and the control 0 1 0 1
unit. Fuse has probably overheated. The reason
for it needs to be discovered before using the
steam generator again. A new fuse is needed.
E7 Communication failure. Check the RJ12 cable. If the area where cable 0 1 1 1
is located has many other cables, it can cause
EMC problems.
If no problem can be found, contact the retailer.
ENGLISH 23
Subject to change without notice.
STE_ML_(En1020)
www.sawo.com | info@sawo.com