LG Ceiling Duct-Type Fan Coil Unit: Installation Manual
LG Ceiling Duct-Type Fan Coil Unit: Installation Manual
LG Ceiling Duct-Type Fan Coil Unit: Installation Manual
LG Ceiling Duct-Type
Fan Coil Unit
INSTALLATION MANUAL
LOW STATIC PRESSURE FCU MODELS
IMPORTANT
• Please read this installation manual carefully and
thoroughly before installing and operating the unit.
• Please retain this installation manual for future reference
after reading it thoroughly.
• Installation work must be performed in accordance with
the national wiring standards by authorized personnel
only.
Fan Coil Unit Installation Manual
TABLE OF CONTENTS
FOR YOUR RECORDS
Safety Precautions.................3 Write the model and serial numbers here:
Model #
Care and maintenance...........8 Serial #
Before you call for service ..10 You can find them on a label on the side of each unit.
Dealer's Name
Installation ............................11
Date Purchased
■ Staple your receipt to this page in the event you need it
to prove date of purchase or for warranty issues.
PRECAUTION
• Contact the installer for installation of this unit.
• The unit is not intended for use by young children or
invalids without supervision.
• Young children should be supervised to ensure that
they do not play with the unit.
• When the power cord is to be replaced, replacement
work shall be performed by authorized personnel only
using only genuine replacement parts.
• Installation work must be performed in accordance
with the National Electric Code by qualified and
authorized personnel only.
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions
must be followed.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
WARNING
■ Installation
Do not use a defective or For electrical work, contact Always ground the product.
underrated circuit breaker. the dealer, seller, a qualified
Use this appliance on a electrician, or an Authorized
dedicated circuit. Service Center.
• There is risk of fire or electric • Do not disassemble or repair the • There is risk of fire or electric
shock. product. There is risk of fire or shock.
electric shock.
Always install a dedicated Use the correctly rated Do not modify or extend the
circuit and breaker. breaker or fuse. power cable.
• Improper wiring or installation • There is risk of fire or electric • There is risk of fire or electric
may cause fire or electric shock shock. shock.
Installation Manual 3
Safety Precautions
■ Operation
Do not let the unit run for a long Take care to ensure that power Do not place anything on the
time when the humidity is very high cable could not be pulled out or power cable.
and a door or a window is left open. damaged during operation.
• Moisture may condense and wet • There is risk of fire or electric • There is risk of fire or electric
or damage furniture. shock. shock.
Do not plug or unplug the Do not touch(operate) the Do not place a heater or
power supply plug during product with wet hands. other appliances near the
operation. power cable.
• There is risk of fire or electric • There is risk of fire or electrical • There is risk of fire and electric
shock. shock. shock.
Do not store or use flammable Do not use the product in a When flammable gas leaks, turn off
gas or combustibles near the tightly closed space for a the gas and open a window for
product. long time. ventilation before turn the product on.
• There is risk of fire or failure of • Oxygen deficiency could occur. • Do not use the telephone or turn
product. switches on or off.
There is risk of explosion or fire
Gasolin
If strange sounds, or small Stop operation and close the When the product is soaked
or smoke comes from window in storm or cyclone. (flooded or submerged),
product. Turn the breaker off If possible, remove the contact an Authorized
or disconnect the power product from the window Service Center.
supply cable. before the cyclone arrives.
• There is risk of electric shock or • There is risk of property damage, • There is risk of fire or electric
fire. failure of product, or electric shock. shock.
Be cautious that water could Ventilate the product from Turn the main power off
not enter the product. time to time when operating when cleaning or
it together with a stove, etc. maintaining the product.
• There is risk of fire, electric shock, • There is risk of fire or electric • There is risk of electric shock.
or product damage. shock.
Installation Manual 5
Safety Precautions
CAUTION
Installation
After installing, the water Install the drain hose to Keep level even when
leakage test should be ensure that water is drained installing the product.
perfrmed. away properly.
• A bad connection may cause • A bad connection may cause • To avoid vibration or water
water leakage. water leakage. leakage.
90°
Use two or more people to lift and transport Do not install the product where it will be
the product. exposed to sea wind (salt spray) directly.
• Avoid personal injury. • It may cause corrosion on the product. Corrosion,
particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient
operation.
Operation
Do not expose the skin Do not use the product for Do not block the inlet or
directly to cool air for long special purposes, such as outlet of air flow.
periods of time. preserving foods, works of
(Don't sit in the draft.) art, etc. It is a consumer air
conditioner, not a precision
refrigeration system.
• This could harm to your health. • There is risk of damage or • It may cause product failure.
loss of property.
Use a soft cloth to clean. Do Do not touch the metal parts Always insert the filter
not use harsh detergents, of the product when securely. Clean the filter
solvents, etc. removing the air filter. They every two weeks or more
are very sharp! often if necessary.
• There is risk of fire, electric shock, • There is risk of personal injury. • A dirty filter reduces the efficiency
or damage to the plastic parts of of the air conditioner and could
the product. cause product malfunction or
damage.
x
Wa Thinner
Do not insert hands or other Do not drink the water Use a firm stool or ladder
objects through the air inlet drained from the product. when cleaning or
or outlet while the product is maintaining the product.
operated.
• There are sharp and moving parts • It is not sanitary and could cause • Be careful and avoid personal
that could cause personal injury. serious health issues. injury.
Installation Manual 7
Care and maintenance
Indoor Unit
Turn the system off before cleaning. To clean, Never use any of the followings:
wipe with a soft, dry cloth. Do not use bleach or • Water hotter than 40°C
abrasives. Could cause deformation and/or
Note: discoloration.
Supply power must be disconnected before • Volatile substances
cleaning the indoor unit. Could damage the surfaces
of the air conditioner.
SI
N N ER
S CO
U R IN G
Be C LB
n z ene A RG E R
1 Operate the unit on Air circulation mode for ■ Check that the air inlet and outlet of the
2 to 3 hours. unit are not blocked.
Operation Tips
Do not overcool the room. Keep blinds or curtains Make sure that the doors
closed. and windows are shut tight.
This is not good for the health Do not let direct sunshine Avoid opening doors and
and wastes electricity. enter the room when the unit windows as much as possible
is in operation. to keep the cool air in the
room.
Installation Manual 9
Before you call for service...
The unit does not operate. • Has the fuse blown or has the circuit breaker
been tripped?
The room has a peculiar odor. • Check that this is not a damp smell exuded by
the walls, carpet, furniture or cloth items in the 4
room.
Does not cool or heat effectively. • Is the air filter dirty? See air filter cleaning
instructions.
• The room may have been very hot when the
unit was first turned on. Allow time for it to cool 4, 5, 7
down.
• Are the indoor unit's air inlet or outlet vents
obstructed?
Installation
Selection of the best location
Install the fan coil unit in the location that satisfies the
following conditions. Top view Rear
(unit: mm)
• The place shall easily bear a load exceeding four 300
times the unit’s weight.
• The place shall be able to inspect the unit as the
figure.
• The place where the unit shall be leveled.
600 600
1000
• The place shall allow easy water drainage.(Suitable
dimension “H” is necessary to get a slope to drain as Front
figure.)
• The place where the unit is not affected by an
electrical noise. Front view
• There should not be any heat source or steam near
the unit
Service Space
Installation Manual 11
Installation
CAUTION:
1. Install declination of the unit is very important for the drain of the duct type unit.
2. Minimum thickness of the insulation for the connecting pipe shall be 20mm.
Front of view
• The unit must be horizontal or declined to the drain hose connected when finished installation.
Ceiling
1- 3 m m
1- 3 m m
CORRECT INCORRECT
CORRECT
INCORRECT
Insulation, others
Insulate the joint and tubes completely.
THERMAL INSULATION All thermal insulation must comply with local requirement
the thickness min 20mm.
50/60
YL
WH WH
Capacitor
MED
38296001
2 1
3
50/60
YL
5 4
WH WH
Capacitor
6
YL
WH WH
MED
Capacitor
YL
WH WH
Capacitor
6 5 4 3 2 1
50/60
YL
WH WH
Capacitor
YL
WH WH
MED
Capacitor
3
Installation Manual 15
Installation
CAUTION
The power cord connected to the unit should be Install Power Cord
complied with the following specifications (Rubber
insulation, type H05RN-F approved by HAR or SAA). L 1 m
NORMAL CROSS-SECTIONAL
GN
AREA 1.25mm2
/YL
T/B Cover
20
mm
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
CAUTION: Make sure that the screws of the terminal fixed tightly.
Water Quality
The standards for cooling water quality
The influence of water quality
Index Item Standards
Corrosion The formation of scale
PH[25°C] 6.5~8.0 O O
Electric cOnductivity[25°C](µs/cm) Below 800 O O
Standard ChlOride iOn(mgCl-/L) Below 200 O
Item Sulfate iOn (mgSO42-/L) Below 200 O
Acid cOnsumptiOn[PH4.8](mgCaCO3/L) Below 100 O
Calcium hardness(mgCaCO3/L) Below 150 O
Turbidity Below 20 O O
Fe(mgFe/L) Below 1.0 O O
Reference
AmmOnium iOn(mgNH4+/L) Below 1.0 O
Item
IOnic phases silica(mgSiO2/L) Below 50 O
SaturatiOn index 0.0~1.0 O O
PH[25°C] 6.5~8.0
Electric conductivity[25°C](µs/cm) Below 200
Chloride ion(mgCl-/L) Below 50
Standard Item
Sulfate ion (mgSO42-/L) Below 50
Acid consumption[PH4.8](mgCaCO3/L) Below 50
Calcium hardness(mgCaCO3/L) Below 50
Turbidity Below 50
Fe(mgFe/L) Below 50
Reference Item
Ammonium ion(mgNH4+/L) Below 50
Ionic phases silica(mgSiO2/L) Below 50
Installation Manual 17
Installation
Circuit Breaker
Use a recognized circuit breaker between the power source and the unit.
A disconnecting device to adequately disconnect all supply lines must be fitted.
Capacity of the Circuit Breaker must lie between MCA and MOP
- MCA = 1.25 x Current of Motor
- MOP = 2.25 x Current of Motor
Installation Manual 18