Differential Pressure Switch PASXX
Differential Pressure Switch PASXX
Differential Pressure Switch PASXX
PASxx
Stable switching
points
PASxx differential air flow switches are intended for use in air handling Long-term stability of switching
systems for the monitoring of air ducts, filters and fans. points through trapezoidal bead
The enclosure is plastic with a rating of IP54. A set-point adjustment is diaphragm
provided under the clip-on clear plastic cover.
Supplied complete with mounting adaptor ring, two straight duct APPLICATIONS
probes and a 6-foot length of clear tubing. • High pressure monitoring • Filter monitoring
78.5 (3.09)
52 (2.05)
P2 16 (0.63)
• Horizontal with cover facing
60 (2.36)
44.4 (1.75)
downward
25 (0.98)
18 (0.71)
P1
6.5 (0.26) 8 (0.32)
(switching setpoint 0.4” WC
9.1 (0.36)
3.4 (0.13) lower than scale)
16 (0.63) • Horizontal with cover facing
upward
(switching setpoint 0.4” WC
2.2 (0.09) higher than scale)
*
WIRING
49.7
2
(1.96
)
1
0.18
4.5 (
3
80.8 (3.18)
4.
5
53.7 (2.11)
88 (3.46)
(0
56 (2.20)
65 (2.56)
.1
8) 1 = COM (Common)
2 = NC Contact (Normally Closed)
15.5º
)
(2.11
53.7
FUNCTIONALITY
The pressure switch has two separate pressure chambers, each with
its own connection. The switch operates when the setpoint is either
exceeded or not reached.
Vacuum Monitoring
Connect the pressure switch via P2. Do not connect P1. Leave P1 open.
Make sure that debris cannot get into P1.
High Pressure Monitoring
Connect the pressure switch via Pa. Do not Connect P2. Leave P2 open.
Make sure that debris cannot get into P2.
Filter Monitoring
Connect P1 before the filter and P2 after it.
Fan Monitoring
Connect P1 after the fan (in blowing direction) and P2 before the fan.
ORDERING INFORMATION
PART NUMBER DESCRIPTION PRESSURE RANGE ACCESSORIES
PAS01 0.08 to 1.2 in. WC (20 to 300 Pa) Static-04 Pick-up - 4” Duct Static
PAS02 Differential Air 0.2 to 2.0 in. WC (50 to 500 Pa) Pickup Probe (AA06)
Pressure Switch AA06 AA07
PAS03 0.4 to 4.0 in. WC (100 to 1000 Pa) Static-08 Pick up - 8” Duct Static
PAS04 2.0 to 8.0 in. WC (500 to 2000 Pa) Pickup Probe) (AA07)