BS en 50200-2006
BS en 50200-2006
BS en 50200-2006
50200:2006
12&23<,1*:,7+287%6,3(50,66,21(;&(37$63(50,77('%<&23<5,*+7/$:
BS EN 50200:2006
National foreword
Summary of pages
This document comprises a front cover, an inside front cover, the EN title page,
pages 2 to 29 and a back cover.
The BSI copyright notice displayed in this document indicates when the
document was last issued.
© BSI 2006
English version
This European Standard was approved by CENELEC on 2006-03-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, the Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
© 2006 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Foreword
This European Standard was prepared by Working Group 10 of the Technical Committee CENELEC TC 20,
Electric cables. This edition is a consolidation of the original text of EN 50200:2000 approved on 1999-08-01
and the text of the draft amendment prepared by WG 10 and agreed at 115 BT (D115/055, confirmed by
D116/162 at 116th Technical Board (BT)) to go forward to the Unique Acceptance Procedure at which a
positive vote was achieved.
This consolidated text was submitted to the formal vote and was approved by CENELEC as EN 50200 on
2006-03-01.
This European Standard was originally prepared under Mandate M/117, given jointly to CEN and CENELEC
by the Commission of the European Communities and the European Free Trade Association, and supports
Essential Requirement No.2 "Safety in case of fire" of the Construction Products Directive.
The cable is tested in a representative installed condition, under conditions of minimum bending radius, and
the test is based upon a constant temperature attack at a minimum test temperature of 830 °C. This is
typical of the gas temperature reached after 30 min exposure to the time/temperature conditions prescribed
in EN 1363-1.
The test method in this document includes exposure to fire with mechanical shock under
specified conditions and satisfies the requirements of Mandate M/117 for the PH classification.
The standard also includes (Annex E) a means of applying a water spray to the cable during the
test, which is not required under Mandate M/117.
–3– EN 50200:2006
Contents
1 Scope ............................................................................................................................4
2 Normative references ...................................................................................................4
3 Definitions ....................................................................................................................4
4 Duration of survival ......................................................................................................5
4.1 Time......................................................................................................................5
4.2 Point of failure .......................................................................................................5
5 Test environment ..........................................................................................................5
6 Test apparatus ..............................................................................................................6
6.1 Test equipment......................................................................................................6
6.2 The wall and its mounting ......................................................................................6
6.3 Continuity checking arrangement ...........................................................................6
6.4 Source of heat .......................................................................................................7
6.5 Shock producing device .........................................................................................7
7 Verification procedure for source of heat ....................................................................8
8 Test sample ..................................................................................................................8
8.1 Sample preparation ...............................................................................................8
8.2 Sample mounting...................................................................................................9
9 Cable test procedure ....................................................................................................9
9.1 General .................................................................................................................9
9.2 Procedure for different cable types.........................................................................9
9.3 Ignition and shock production...............................................................................11
9.4 Electrification or optical monitoring.......................................................................11
9.5 End-point ............................................................................................................11
10 Test report ..................................................................................................................11
Bibliography .....................................................................................................................29
Figure 1 - Schematic of test wall .........................................................................................12
Figure 2 - Plan view of fire test equipment (not to scale) ......................................................13
Figure 3 - End elevation of fire test equipment (not to scale) ................................................14
Figure 4 - Typical rubber bush (hardness: 50-60 shore A) for fastening wall .........................15
Figure 5 - Burner face .........................................................................................................15
Figure 6 - Schematic diagram of an example of a fuel control system using rotameters ........16
Figure 7 - Temperature measuring arrangement ..................................................................17
Figure 8 - Example of method of mounting a sample for test ................................................17
Figure 9a - Basic circuit diagram - Electric power and control cables
with rated voltage up to 600/1 000 V..................................................................18
Figure 9b - Basic circuit diagram - Electric data and communication cables
with no rated voltage .........................................................................................19
Figure E.1 – Water spray tube.............................................................................................27
Figure E.2 – Water spray application ...................................................................................28
EN 50200:2006 –4–
1 Scope
This European Standard specifies the test method for cables designed to have intrinsic resistance to fire
and intended for use as emergency circuits for alarm, lighting and communication purposes.
This standard is applicable to cables, for emergency circuits, of rated voltage not exceeding 600/1 000 V,
including those of rated voltage below 80 V, and for emergency circuit optical cables.
NOTE Although test procedures for electronic data and communication cables and optical fibre cables are given in
this document, these areas are under active development and the given procedures may be subject to future review.
This standard is not applicable to cables intended for use in public telecommunications networks.
The test method is limited to cables with an overall diameter not exceeding 20 mm.
The test method, which is based on the direct impingement of flame from a propane burner giving a
constant temperature attack of a notional 842 °C, can be used for cables for emergency circuits required to
comply with Subclause 4.3.1.4.6 (a) of the Interpretative Document for Essential Requirement No. 2 'Safety
in Case of Fire' (94/C62/01) of the Construction Products Directive (89/106/EEC). In such cases the test
method only applies, for metallic conductor cables, to those with conductor sizes up to and including
2,5 mm2. For optical cables, only the 20 mm diameter limit applies.
This standard includes (Annex D) a means of linking the measured survival time to the fire resistance
classification for these cables, as required by Subclause 4.3.1.4.6(a) of 94/C62/01.
The standard also includes (Annex E) a means of applying a water spray to the cable during the test.
Although there is no requirement under the Construction Products Directive for cables to withstand water
spray when assessing resistance to fire, such a requirement may be a feature of particular product
standards.
2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments) applies.
HD 60269-3-1 Low-voltage fuses Part 3-1: Supplementary requirements for fuses for use by
unskilled persons (fuses mainly for household and similar applications)
Sections I to IV: Examples of types of standardized fuses
(IEC 60269-3-1:2004, modified)
EN 60695-4 Fire hazard testing - Part 4: Terminology concerning fire tests (IEC 60695-4)
IEC 60793-1-4 1995 Optical fibres - Part 1: Generic specification - Section 4: Measuring methods
for transmission and optical characteristics
3 Definitions
For the purposes of this standard the definitions given in EN 60695-4 apply.
–5– EN 50200:2006
4 Duration of survival
4.1 Time
The duration of survival, measured in minutes, to the point of failure shall be recorded for each cable tested
up to a maximum survival time of 120 min.
1) The voltage is not maintained during the test duration, as indicated by fuse failure or by
interruption of the circuit breaker.
2) A conductor ruptures during the test duration, as indicated by the lamp extinguishing.
NOTE The test procedure given in 9.2.1 connects the neutral core to earth. This may not be appropriate if the cable
is designed for use on systems where the neutral is not earthed. If required by the cable standard, it is permissible for
the neutral conductor to be tested as if a phase conductor. Where a metallic sheath, armour or screen acts as a
neutral conductor, it shall always be connected to earth.
1) The voltage is not maintained during the test duration, as indicated by fuse failure or by
interruption of the circuit breaker.
2) A conductor ruptures during the test duration, as indicated by the lamp extinguishing.
1) The maximum increase in attenuation exceeds the value given in the cable standard during the
test duration.
In the case of cables in a) and b), failure by either one of the criteria listed shall be sufficient to show a
failure for that cable.
5 Test environment
The test shall be carried out in a suitable chamber with facilities for disposing of any noxious gases resulting
from the burning. Sufficient ventilation shall be available to sustain the flame for the duration of the test.
The chamber and test apparatus shall be at (25 ± 15) °C at the start of each test.
The same ventilation and shielding conditions shall be used in the chamber during both the verification and
cable test procedures.
NOTE 1 The test given in this standard may involve the use of dangerous voltages and temperatures. Suitable
precautions should be taken against shock, burning, fire and explosion risks that may be involved and against any
noxious fumes that may be produced.
NOTE 3 Shields, such as those as described in EN 61034-1, may need to be placed in an appropriate position to
protect the burner from draughts that may influence the flame geometry.
EN 50200:2006 –6–
6 Test apparatus
a) a vertical wall, on to which the cable is mounted, comprising a board manufactured from heat
resisting non-combustible material fastened to steel supports as described in 6.2;
The wall consists of a board of heat resisting non-combustible and non-metallic material fastened rigidly to
two horizontal steel supports, one at the top of the board and the other at the bottom. Vertical supports may
also be used. The board is approximately 900 mm long, 300 mm high and 9 mm thick, and the total mass
of the wall (i.e. board and steel supports) shall be (10 ± 0,5) kg. Ballast, if required, shall be placed inside
the steel supports.
Guidance on the choice of suitable material for the wall is given in Annex A.
NOTE 1 Supports made from square section steel tube approximately 25 mm x 25 mm and approximately 1 m long
have been found to be suitable
NOTE 2 The top support should be fastened to the board so that its upper face is slightly above the upper edge of the
board, so that the shock producing device impacts on the support and not the board.
Each support shall have a horizontal hole at each end, the exact position and diameter being determined by
the particular supporting bush and supporting framework used. The wall shall be fastened to a rigid support
by four bonded rubber bushes fitted between the horizontal steel supports of the wall and the support
framework, as shown in Figure 1, so as to allow movement under impact.
NOTE 3 A typical rubber bush which has been found to be suitable is shown in Figure 4.
In order to check the mounting of the wall, the static deflection following application of a load to the centre of
the upper support of the wall shall periodically be measured.
The values of load and deflection shall comply with the following:
6.3.1 Electric power and control cables with rated voltage up to 600/1 000 V
During the test a current for continuity checking is passed through all conductors of the cable and this shall
be provided by a three phase star connected or single phase transformer(s) of sufficient capacity to maintain
the test voltage up to the maximum leakage current allowable.
NOTE 1 Due note should be taken of the fuse characteristics when determining the power rating of the transformer.
This current is achieved by connecting, at the other end of the sample, a suitable load and indicating device
(e.g. lamp) to each conductor, or group of conductors.
–7– EN 50200:2006
NOTE 2 A current of 0,25 A at the test voltage, through each conductor or group of conductors, has been found to be
suitable.
During the test a current for continuity checking is passed through all conductors of the cable and this shall
be provided by a three phase star connected or single phase transformer(s) of sufficient capacity to maintain
the test voltage up to the maximum leakage current allowable.
NOTE 1 Due note should be taken of the fuse characteristics when determining the power rating of the transformer.
This current is achieved by connecting, at the other end of the sample, a suitable load and indicating device
(e.g. lamp) to each conductor, or group of conductors.
NOTE 2 A current of 0,25 A at the test voltage, through each conductor or group of conductors, has been found to be
suitable.
At the conclusion of the test, check each fibre (or those fibres indicated in the relevant cable specification as
fire resistant) for continuity.
The source of heat shall be a ribbon type propane gas burner with a nominal burner face length of 500 mm
with Venturi mixer. A centre-feed burner is recommended. The nominal burner face width shall be 10 mm.
The face of the burner shall have three staggered rows of drilled holes, nominally 1,32 mm in diameter and
drilled on 3,2 mm centres, as shown in Figure 5. Additionally, a row of small holes milled on each side of
the burner plate, to serve as pilot holes for keeping the flame burning, is permitted.
Mass flow meters should be used as the means of controlling accurately the input flow rates of fuel and air
to the burner.
NOTE Rotameter type flow meters may be used as an alternative, but are not recommended. Guidance on their use,
and the application of appropriate correction factors, may be found in Annex B. Figure 6 shows an example of a
rotameter type system.
By reference to the wall the burner shall be positioned centrally at a horizontal distance of (40 ± 2) mm from
the burner face to the wall as shown in Figures 2 and 3. The burner shall be positioned in the test chamber
such that it is at least 200 mm above the floor of the chamber or any solid mounting table and 500 mm from
any chamber wall.
The flow rates used for the test at reference condition (1 bar and 20 °C) shall be as follows:
The burner and control system shall be subject to verification following the procedure given in Clause 7.
For the purposes of this test, the air shall have a dew point not higher than 0 °C.
The shock producing device consists of a mild steel round bar (25 ± 0,1) mm in diameter and (600 ± 5) mm
long. The bar is freely pivoted about an axis parallel to the wall, which is in the same horizontal plane as,
and (200 ± 5) mm away from, the upper edge of the wall. The axis divides the bar into two unequal parts of
length (400 ± 5) mm and approximately 200 mm respectively; the longer section impacting the wall. The bar
drops under its own weight from an angle of 60° to the horizontal to strike the upper steel support of the wall
at its midpoint as shown in Figure 1 and Figure 3.
EN 50200:2006 –8–
Position the burner (40 ± 2) mm horizontally from the wall and (65 ± 10) mm vertically below the centre line
of the thermocouple as shown in Figure 3.
Ignite the burner and adjust the gas and air supplies to those given in 6.4.
7.2 Monitor the temperature as recorded by the thermocouples over a period of 10 min to ensure
conditions are stable.
a) the average of the readings from the two thermocouples over the 10 min period falls
within the requirement of (830 + 40, -0) °C and
b) the maximum difference between the averaged readings for each of the two
thermocouples over the 10 min period does not exceed 40 °C.
At least one measurement shall be made on each thermocouple every 30 sec in order to obtain the
average.
NOTE The actual method of obtaining the average thermocouple reading over the period is not specified but it is
recommended that a recorder with averaging facilities is used in order to damp the variability caused by point
measurement.
7.4 If the verification is not successful, the flow rates shall be altered within the tolerances given in 6.4
and/or distances altered within the tolerances given in 7.1 and a further verification carried out.
7.5 The positions established for successful verification shall be recorded (see 9.1.2).
7.6 If no successful verification can be achieved within the tolerances given, then the burner system shall
be considered as incapable of providing the source of heat required by this standard.
8 Test sample
8.1.1 Electric power and control cables with rated voltage up to 600/1 000 V
The sample to be tested shall be a piece of cable not less than 1 200 mm long with approximately 100 mm
of sheath and outer coverings removed at each end. At each end of the cable, each conductor shall be
suitably prepared for electrical connections, and the exposed conductors shall be spread apart to avoid
contact with each other.
The sample to be tested shall be a piece of cable not less than 1 200 mm long with approximately 100 mm
of sheath or outer coverings removed at each end. At each end of the cable, each conductor shall be
suitably prepared for electrical connections, and the exposed conductors shall be spread apart to avoid
contact with each other.
The sample to be tested shall be a piece of cable (at least 5 m) sufficiently long that the two ends emerge
from the test chamber, with approximately 100 mm of sheath or outer coverings removed at each end. For
–9– EN 50200:2006
multi-fibre cables, one fibre shall be selected from the outermost layer of the cable. At each end of the
cable sample, lengths of identical optical fibre shall be connected, if necessary, to give a total length
appropriate to the optical measuring method used.
The cable shall be bent to form an approximate 'U' shape. The internal radius of each bend shall be the
manufacturer's declared minimum bending radius and the overall distance between the vertical portions of
the cable shall be approximately 475 mm as shown in Figure 8.
The cable shall be mounted centrally on the wall using metal clips, as recommended by the manufacturer
for the cable under test, for example, copper P clips. The clips, which shall be earthed, shall support the
cable at either end of the radiused section and in the centre as shown in Figure 8. The type of clips used
shall be detailed in the Test Report.
NOTE By agreement between the user and manufacturer of the cable alternative clips may be used for the testing of
multicore cable, but in this case the test shall only be considered valid for cable installed with such clips.
9.1 General
9.1.1 Remove the thermocouple assembly and position the cable test sample on the wall as described in
8.2.
9.1.2 Position the burner (40 ± 2) mm horizontally from the wall, and at the same vertical distance below the
bottom line of the cable as determined in the verification procedure for the distance between burner and
thermocouple centre lines.
9.1.3 Fuses used in the test procedures in 9.2.1 and 9.2.2 shall be Type DII complying with HD 60269-3-1.
Alternatively, a circuit breaker with equivalent characteristics may be used.
Where a circuit breaker is used, its equivalent characteristics shall be demonstrated by reference to the
characteristic curve shown in Annex C.
9.2.1 Electric power and control cables with rated voltage up to 600/1 000 V
At the transformer end of the sample, earth the neutral conductor and any protective conductor. Any metal
screens, drain wire or metallic layer shall be interconnected and earthed. Connect the transformer(s) to the
conductors, excluding any conductor which is specifically identified as intended for use as a neutral or a
protective conductor, as shown in the circuit diagram (Figure 9a).
Where a metallic sheath, armour or screen acts as a neutral or protective conductor, it shall be connected
as shown in the circuit diagram (Figure 9a), as for a neutral or protective conductor.
For single, twin-or three-phase conductor cables, connect each phase conductor to a separate phase of the
transformer(s) output with a 2 A fuse or circuit breaker with equivalent characteristics in each phase.
For multicore cables having four or more conductors (excluding any neutral or protective conductors), the
conductors shall be divided into three roughly equal groups, ensuring that adjacent conductors are, as far as
possible, in different groups.
For multipair cables the conductors shall be divided into two equal groups, ensuring that the a-core of each
pair is connected to one phase and the b-core of each pair is connected to another phase (L1 and L2 of
Figure 9a). Quads shall be treated as 2 pairs.
EN 50200:2006 – 10 –
For multitriple cables the conductors shall be divided into three equal groups, ensuring that the a-core of
each triple is connected to one phase, the b-core of each triple to another phase and the c-core of each
triple to the third phase of the transformer. (L1, L2 and L3 of Figure 9a)
Connect the conductors of each group in series and connect each group to a separate phase of the
transformer output with a 2 A fuse or circuit breaker with equivalent characteristics in each phase.
NOTE For cable constructions not specifically identified above, the test voltage should be applied, as far as is
practicable, to ensure that adjacent conductors are connected to different phases.
- connect each phase conductor, or group of conductors, to one terminal of the load and indicating
device (as described in 6.3.1), the other terminal being earthed;
- connect the neutral conductor and any protective conductor to one terminal of the load and indicating
device (as described in 6.3.1), the other terminal being connected to L1 (or L2 or L3) at the
transformer end (see Figure 9a).
At the transformer end of the sample, earth any earth conductor. Any metal screens, drain wire or metallic
layer shall be interconnected and earthed. Connect the transformer(s) to the conductors, excluding any
conductor which is specifically identified as intended for use as an earth conductor, as shown in the circuit
diagram (Figure 9b).
For multicore cables, the conductors (excluding any earth conductor) shall be divided into two roughly equal
groups, ensuring that adjacent conductors are, as far as possible, in different groups.
For multipair cables the conductors shall be divided into two equal groups, ensuring that the a-core of each
pair is connected to one phase and the b-core of each pair is connected to another phase (L1 and L2 of
Figure 9b). Quads shall be treated as 2 pairs.
For multitriple cables the conductors shall be divided into three equal groups, ensuring that the a-core of
each triple is connected to one phase, the b-core of each triple to another phase and the c-core of each
triple to the third phase of the transformer. (L1, L2 and L3 of Figure 9b).
Connect the conductors of each group in series and connect each group to a separate phase of the voltage
source output with a 2 A fuse or circuit breaker with equivalent characteristics in each phase.
NOTE For cable constructions not specifically identified above, the test voltage should be applied, as far as is
practicable, to ensure that adjacent conductors are connected to different phases.
- connect each conductor, or group of conductors, to one terminal of the load and indicating device (as
described in 6.3.2) the other terminal being earthed;
- connect any earth conductor to one terminal of the load and indicating device (as described in 6.3.2),
the other terminal being connected to L1 (or L2 or L3) at the transformer end (see Figure 9b).
Connect the fibre(s) (or those fibres indicated in the relevant cable specification) to an optical apparatus to
monitor and/or measure the change in optical transmittance in accordance with IEC 60793-1-4, method
C10. Unless otherwise stated in the appropriate standard, the test shall be carried out at the declared
nominal wavelength of operation.
– 11 – EN 50200:2006
Ignite the burner and adjust the propane and air flow rates to those obtained during the verification
procedure (see Clause 7).
Immediately after igniting the burner, switch on the electricity supply as indicated in 9.4, activate the shock
producing device and start the test duration timer. The shock producing device shall impact the wall after
5 min ± 10 s from activation and subsequently at 5 min ± 10 s intervals
9.4.1 Electric power and control cables with rated voltage up to 600/1 000 V
For electric power and control cables of rated voltage up to and including 600/1 000 V, switch on the
electricity supply and adjust the voltage to the rated voltage of the cable (subject to a minimum voltage of
100 V a.c.), i.e. the test voltage between conductors shall equal the rated voltage between conductors and
the test voltage from conductor to earth shall equal the rated voltage from conductor to earth.
For electric data and communication cables with no rated voltage, switch on the electricity supply and
unless otherwise stated in the appropriate standard adjust the voltage to (110 ± 10) V a.c. phase to earth.
For optical fibre cables, switch on the optical apparatus and monitor the attenuation.
9.5 End-point
NOTE A particular cable standard may require an alternative survival time and/or measure of the point of failure. In
such cases no classification against the Construction Products Directive shall be claimed.
10 Test report
The test report shall include the following information:
Dimensions in millimetres
(Dimensions are approximate)
Key
Dimensions in millimetres
(Dimensions are approximate)
This figure is purely representational and does not indicate nor imply relative sizes or dispositions of
components of the test
Key
Dimensions in millimetres
(Dimensions are approximate except where toleranced)
Key
Figure 4 - Typical rubber bush (hardness: 50-60 shore A) for fastening wall
Key
Dimensions in millimetres
(Dimensions are approximate except where toleranced)
Key
Key
1 Metal clips
R = minimum bending radius of cables
Key
Key
Annex A
(informative)
A commercially available burner face meeting the requirements of this standard is the AGF burner insert 11-
55, and a suitable 500 mm burner including the specified burner face is available from AGF, reference
1857B.
AGF
American Gas Furnace Company
PO Box 496
Elizabeth
New Jersey 07207
USA
Commercially available mass flow meters suitable for use in carrying out tests according to this standard are
supplied by, amongst others:
Examples of materials which have been found to be suitable for the wall are:
Commercially available bushings which have been found to be suitable for mounting the wall include:
The chamber must have a sufficient volume such that fire effluents released during combustion do not alter
the test conditions. Experience has shown a chamber similar to the 3 m cube specified in EN 61034-1 to be
suitable. Windows may be installed in the walls of the chamber in order to observe the behaviour of the
cable during the test. Fume exhaust should be by means of natural draught through a chimney located at
least 1 m from the burner. A damper may be used for adjustment of ventilation conditions. The use of
forced ventilation is not recommended.
Air inlet to the chamber should be through orifices located near the base of the chamber. Air inlets and an
exhaust chimney should be located in such a way that the burner flame remains stable during the
verification procedure and test.
EN 50200:2006 – 22 –
Annex B
(informative)
When using the rotameter type flowmeters to monitor the supply rate of the gases, two factors need to be
considered in order to use them correctly. It is important
a) to know what the flowmeter is indicating when used under the actual operating conditions;
b) to know under what conditions of temperature and gas pressure the flowmeter was calibrated, and
under what conditions it was designed to operate.
Considering point (a), most flowmeters are designed to indicate the volumetric flow rate at atmospheric
temperature and pressure, i.e. 20 °C and 1 bar. However, considering point (b), not all flowmeters are
calibrated and designed to work at the same temperature and pressure, and care should be taken to ensure
that the temperature and pressure of the gas flowing through a flowmeter are correct for that particular
meter. Working the flowmeter at temperatures and pressures different from these conditions requires
application of a correction factor such as provided hereafter.
B.2 Example
B.2.1 General
Assume that an air flow rate of 80 l/min at 1 bar and 20 °C is required at the burner:
Flowmeter 1 : Calibrated to operate at 2,4 bar absolute and 15 °C, but to indicate
l/min at 1 bar and 15 °C
Assume that the air supply pressure up to and including the flowmeters is altematively at 1 bar (see B.2.2)
or at 2,4 bar (see B.2.3), and 20 °C.
P1 T 2
C= ×
P2 T1
where
Flowmeter 1
This will require a correction factor to be used since the meter is operating in conditions removed from its
designed operating conditions:
2,4 293
C= × = 1,56
1 288
Thus to set a flow rate of 80 l/min at reference conditions a reading on this flowmeter of 125 l/min
(80 x 1,56) is required.
Flowmeter 2
Since this meter is operating under its design conditions, the required flow rate of 80 l/min can be read
directly from the meter with no correction factor necessary.
Flowmeter 1
This will require a correction factor for temperature, but not for pressure since the meter is operating at its
design pressure:
2,4 293
C= × = 1,01
2,4 288
Thus to set a flow rate of 80 l/min at reference conditions, a reading of 81 l/min (1,01 x 80) on this flowmeter
is required.
Flowmeter 2
This will also require a correction factor since it is operating in conditions removed from its design
conditions:
P1 = 1 bar T1 = 20 °C = 293 K
P2 = 2,4 bar T2 = 20 °C = 293 K
1 293
C= × = 0,65
2,4 293
Thus to set a flow rate of 80 l/min at reference conditions, a reading of 52 l/min (0,65 x 80) on this flowmeter
is required.
EN 50200:2006 – 24 –
Annex C
(normative)
Current I p
– 25 – EN 50200:2006
Annex D
(informative)
The purpose of this annex is to provide guidance as to the derivation of the fire resistance classifications for
continuity of power supply or signal, as included in the Interpretative Document no. 2 of the Construction
Products Directive, from test data.
The ability of electrical cables or optical cables to maintain a reliable form of power supply or signal from the
source to the safety installation(s) when exposed to fire.
Classification
Two results in which the measured duration of survival equals or exceeds the stated classification
(i.e. 15, 30, 60, 90 or 120 min) are needed to obtain classification.
Range of classification
A range of cables of the same general construction and materials and differing only in conductor or fibre
size or number of conductors may be classified on the basis of the following tests:
Classification Category 1 - Single core electric power and control cables of a particular rated voltage
Classification Category 2 - Multicore electric power and control cables of a particular rated voltage
Test the smallest conductor size having the largest number of cores and also test the largest
conductor size having the smallest number of cores.
Classification Category 3 - Multipair/multitriple electric power and control cables of a particular rated voltage
Test as for Category 2 except that a test on screened pairs/triples covers unscreened types but not
vice versa and a test on multitriples covers multipairs but not vice versa.
Test the smallest number of fibres in the range and test the largest number of fibres in the range.
EN 50200:2006 – 26 –
Annex E
(informative)
Guidance for using optional water spray protocol
E.1 General
There is no requirement under the Construction Products Directive to withstand a water spray
when assessing resistance to fire, but such requirements may be features of national standards
or codes of practice or particular product standards.
Where the water spray requirement is needed, the requirements given in Clauses 4 to 10 of this
Standard shall apply with the modifications in E.2.
Subclause 4.1
The duration of survival, measured in minutes, to the point of failure shall be recorded for each
cable tested up to a maximum survival time of 30 min, with the water spray being applied for the
last 15 min of the test.
The water spray bar shall consist of a metallic tube (copper or stainless steel) of nominal thickness 1,00 mm
and overall diameter (15,5 ± 1,0 ) mm, closed at one end and open at the other to allow the inflow of water.
The tube shall have one row of 17 holes of nominal 0,85 mm diameter drilled on 30 mm centres as shown in
Figure E.1.
The bar shall be positioned centrally with respect to the test sample as shown in Figure E.2.
The output of water from the bar shall be at a flow rate of (0,80 ± 0,05) l/min. This shall be verified by
volumetric measurement.
The tube shall be capable of adjustment such that the resulting water spray is centralised around the burned
portion of the test sample.
The use of a metal plate device over the burner to avoid ingress of water is permitted. If a plate is used, the
calibration shall be carried out with the metal plate in place.
NOTE 1 A steel plate of suitable thickness extending horizontally approximately 12 mm from the burner face and
fixed approximately 12 mm vertically above the centre line of the burner has been found to be satisfactory
NOTE 2 If the metal plate device is not used the flame is likely to be extinguished. In such cases the gas supply
should be turned off and a new test carried out.
Subclause 9.3
Ignite the burner and adjust the propane and air flow rates to those obtained during the verification
procedure (see Clause 7).
– 27 – EN 50200:2006
Immediately after igniting the burner, switch on the electricity supply as indicated in 9.4, activate the shock
producing device and start the test duration timer. The shock producing device shall impact the wall after
5 min ± 10 s from activation and subsequently at 5 min ± 10 s intervals.
After 15 min and with the flame and shock still being applied, the water spray shall be started. The
application of water shall continue until the end-point of the test.
Subclause 9.5
Clause 10 add
Key
Key
Bibliography
Revisions
British Standards are updated by amendment or revision. Users of
British Standards should make sure that they possess the latest amendments or
editions.
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: +44 (0)20 8996 9000. Fax: +44 (0)20 8996 7400.
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: +44 (0)20 8996 9001.
Fax: +44 (0)20 8996 7001. Email: orders@bsi-global.com. Standards are also
available from the BSI website at http://www.bsi-global.com.
In response to orders for international standards, it is BSI policy to supply the
BSI implementation of those that have been published as British Standards,
unless otherwise requested.
Information on standards
BSI provides a wide range of information on national, European and
international standards through its Library and its Technical Help to Exporters
Service. Various BSI electronic information services are also available which give
details on all its products and services. Contact the Information Centre.
Tel: +44 (0)20 8996 7111. Fax: +44 (0)20 8996 7048. Email: info@bsi-global.com.
Subscribing members of BSI are kept up to date with standards developments
and receive substantial discounts on the purchase price of standards. For details
of these and other benefits contact Membership Administration.
Tel: +44 (0)20 8996 7002. Fax: +44 (0)20 8996 7001.
Email: membership@bsi-global.com.
Information regarding online access to British Standards via British Standards
Online can be found at http://www.bsi-global.com/bsonline.
Further information about BSI is available on the BSI website at
http://www.bsi-global.com.
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means – electronic, photocopying, recording or otherwise – without prior written
permission from BSI.
This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
BSI written permission of BSI must be obtained.
389 Chiswick High Road Details and advice can be obtained from the Copyright & Licensing Manager.
London Tel: +44 (0)20 8996 7070. Fax: +44 (0)20 8996 7553.
Email: copyright@bsi-global.com.
W4 4AL