Troubleshooting

9.1 Indoor Unit Error Display

Display LED STATUS

E0 EEPROM parameter error

E1 Indoor / outdoor units communication protection

E2 Zero-crossing signal error

E3 Indoor fan speed out of control

E5 Open or short circuit of outdoor temperature sensor

E6 Open or short circuit of room or evaporator temperature sensor

E7 Outdoor fan speed out of control

P0 IBM malfunction or IGBT over-strong current protection

P1 Over voltage or too low voltage protection

P2 Temperature protection of compressor top.

P4 Inverter compressor drive error

Note: E4 & P3: Reserved function.

36
9.2 Diagnosis and Solution

9.2.1 EEPROM parameter error diagnosis and solution

Shut off the power supply and turn on it 5s later

The problem comes out again

No
Is the EEPROM chip plugged in indoor PCB well? Correct the connection

Replace the main PCB of indoor unit

37
9.2.2 Indoor / outdoor units communication protection error diagnosis and solution

Turn off the power supply, after 1 minute, connect the


power supply , turn on the unit with remote controller

The unit does not work normally.

Check the wiring between indoor and outdoor


No
unit. Is the connection of L, N, S and GND good? Reconnect and retest

Yes

Is the LED4(red) bright and LED1(yellow) Yes Replace indoor


blinking on outdoor PCB?
PCB and repower

No The unit does not


work normally.

The power supply for outdoor PCB is fail.


Check the wiring on outdoor PCB Yes
comparing with wiring plate. Is the Replace outdoor e-box.
connection good?

No

Correct the connection

38
9.2.3 Fan speed out of control diagnosis

Shut off the power supply and turn on it 5s later

The unit does not work normally

Turn off the unit, rotate the cross No Disassemble the connection between
fan.Does it rotate freely? fan and motor, check if the bearing is
normal. If not, change the bearing.If
yes, follow the below step.
Yes

Is the fan motor connector and


connection good?

Yes

Is the voltage being applied to the fan


Yes
motor? Replace the fan motor

No

Replace the PCB

9.2.4 Open or short circuit of temperature sensor diagnosis and solution.

Check the connections between


the sensors and the PCB. Are the
connections good?

Yes

Replace the sensor and check if Yes


Replace outdoor PCB
the errors happen again?

39
9.2.5 IGBT over-strong current protection diagnosis and solution.

Check whether the connections between


outdoor PCB and IPM are good?

Yes

Check whether the IPM is fixed to radiator No


Fastening the IPM to the radiator
tightly

The unit does not work normally


Replae the IPM Replace the compressor

9.2.6 Over voltage or too low voltage protection diagnosis and solution.

No
Is the power supply good? Make sure the power supply is normal.

Yes

Replace the outdoor e-box.

9.2.7 High temperature protection of compressor top diagnosis and solution.

Does compressor operate? No No


Is the connection good? Reconnect it

Yes
Yes

Is refrigerant circulation
No
volume normal? Is protector normal? Replace it

No,
Charge refrigerant Yes

Is abnormality the same


after gas charging? Replace the outdoor PCB.

There is block(Such as capillary or


welded points of the pipes.)

40
9.2.8 Inverter compressor drive error diagnosis and solution.

Is the connection of compressor good?


No
Is the wiring sequence right? The voltage
Reconnect and retry.
range proper?

Yes

No
Replace the outdoor PCB Replace inverter compressor.

9.2.9 Zero crossing detection error


When such failure occurs, the main control board must have fault.