1.Checklist :
1) Is the cable between the indoor unit and outdoor unit connected correctly?
2) Isn't the power cable and communication cable cross?
Restart after power off.
2. Troubleshooting procedure
YES
NO
Is the connection of power cable
Correct the wrong cable.
and communication cable normal?
YES
NO
Is the communication error Terminate the service.
occurred again?
YES
1.Checklist :
1) Is the cable between the indoor unit and outdoor unit connected correctly?
2) Isn't the power cable and communication cable cross?
2. Troubleshooting procedure
Restart after power off.
YES
NO
Is the connection of power cable
Correct the wrong cable.
and communication cable normal?
YES
NO
Is the power is normal?
Exchange the PBA of no power unit
(check the LED Lamp)
YES
NO
Is the communication error Terminate the service.
occurred again?
YES
12-3
Indoor temperature sensor error
1.Checklist :
1) Is the indoor units temperature sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
Sensor Replace
Is the sensor resistance value #1-#2
NO Sensor resistance value : 20℃ - 12.09kohm
10kohm±3% at the room
30℃ - 8.31kohm
temperature
35℃ - 6.94kohm
of 25℃
40℃ - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the indoor PBA
NO
YES
12-4
Indoor Eva-in temperature sensor error
1.Checklist :
1) Is the indoor units temperature sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
Sensor Replace
Is the sensor resistance value #3-#4
NO Sensor resistance value : 20℃ - 12.09kohm
10kohm±3% at the room
30℃ - 8.31kohm
temperature
35℃ - 6.94kohm
of 25℃
40℃ - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the indoor PBA
NO
YES
12-5
When the Up/Down louver motor does not operate (Initial Diagnosis) (Not displayed)
1.Checklist :
1) Is the input power voltage normal?
2) Is the Up/Down louver motor properly connected with the connector? (CN61)
2. Troubleshooting procedure
Unplug the power cord and plug it after 30seconds
later.
YES
NO
Is the connected louver wire? Connect the wire PBA to louver motor
YES
NO
YES
12-6
When the remote control is not receiving
1.Checklist :
1) Check if the connector was normally assembled.
2) Check the battery in remote control
3) All the lights out and check again : Change electronic typed to a fluorescent light
4) Put the set in operation and check the voltage of display PBA
5) Replace the display PBA
12-7
Indoor fan motor speed detecting error (AC fan)
1.Checklist :
1) Is the indoor units fan motor properly connected with the connector(CN72)?
2) Is the AC voltage correct?
3) Is the HALL IC(feedback sensing) in indoor fan motor properly connected with the connector(CN44)?
4) Is the running capacitor(CR71) properly connected with PBA?
2. Troubleshooting procedure
After unplugging out the power cord should be
reconnected with in 5 seconds
YES
YES
YES
Test location Normal NO
Is the supply
+ voltage of- the fanvoltage PBA should be
PBA is out of order
motor sufficient? replaced
SS71- SS71- 12V
12-8
Outdoor temperature sensor error (A*V**PSB*)
1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
Is the sensor connector(CN251) NO
2. Troubleshooting
connected correctlyprocedure
in accordance Reconnect the sensor connector.
with a color(BLU,6PIN)?
YES
Sensor Replace
Is the sensor resistance value #1-#2
NO Sensor resistance value : 20℃ - 12.09kohm
10kohm±3% at the room
30℃ - 8.31kohm
temperature
35℃ - 6.94kohm
of 25℃
40℃ - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA
NO
YES
12-9
Outdoor Coil temperature sensor error (A*V**PSB*)
1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
YES
Sensor Replace
Is the sensor resistance value #5-#6
NO Sensor resistance value : 20℃ - 12.09kohm
10kohm±3% at the room
30℃ - 8.31kohm
temperature
35℃ - 6.94kohm
of 25℃
40℃ - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA
NO
YES
12-10
Outdoor Discharge temperature sensor error (A*V**PSB*)
1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
Is the sensor connector(CN251) NO
2. Troubleshooting
connected correctlyprocedure
in accordance Reconnect the sensor connector.
with a color(BLU,6PIN)?
YES
Sensor Replace
Is the sensor resistance value #3-#4
NO Sensor resistance value : 20℃ - 242kohm
200kohm±3% at the room
30℃ - 166ohm
temperature
35℃ - 138ohm
of 25℃
40℃ - 115kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA
NO
YES
12-11
OLP sensor error/OLP over heat (A*V**P*A*)
1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
5) Check the compressor locking or gas leak
YES
Sensor Replace
Is the sensor resistance value #3-#4
NO Sensor resistance value : 20℃ - 242kohm
200kohm±3% at the room
30℃ - 166ohm
temperature
35℃ - 138ohm
of 25℃
40℃ - 115kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA
NO
12-12
Outdoor Discharge over temperature error (A*V**PSB*)
1.Checklist :
1) Check the discharge temperature in the outdoor unit
2) Check the compressor locking or gas leak
3) Download the EEPROM data
2. Troubleshooting procedure
Restart after power off.
YES
The condition is too poor for air conditioner to
operate
Wait until discharge temperature is decreased
Restart after power off
NO
Is the discharge over temperature
sensor error appeared again? Terminate the service
YES
NO
Is the discharge over temperature
Terminate the service
sensor error appeared again?
YES
12-13
Outdoor Fan motor error (A*V**PSB*)
1.Checklist :
1) Are the input power voltage and the power connection correct?
2) Is the motor wire connected to the outdoor PBA correctly?
3) Is there no assembly error or none-assembly in the terminal of motor wire connector?
4) Is there no obstacle at the surrounding of motor and propeller?
2. Troubleshooting procedure
Restart after power off.
YES
Reassemble the fan wire and input the power again Is there short among each pin YES Exchange the Fan
#1~#6 motor
NO Terminate the NO
Is the fan error appeared again?
service
YES
NO
Is the voltage of CN901 #1-#3 over Follow the check procedure of outdoor unit power
250Vdc supply error check
YES
YES
12-14
Compressor starting error
1.Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
NO
Is the restart error occurred again? Terminate the service
YES
NO
Is the connection of compressor
wire is normal? Connect the comp wire normally
YES
NO
Is the restart error occurred again? Terminate the service
YES
YES
Is the compressor body and
Exchange the Outdoor PBA
interphase resistance insulated?
NO
12-15
Compressor wire missing error/rotation error
1.Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
NO
Is the restart error occurred again? Terminate the service
YES
YES
NO
Is the restart error occurred again? Terminate the service
YES
YES
Is the compressor body and
Exchange the Outdoor PBA
interphase resistance insulated?
NO
12-16
O.C(Over Current) error
1.Checklist :
1) Is the IPM Shunt(R451,R452,R453) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
NO
Is the O.C error occurred? Terminate the service
YES
NO
Is the connection of compressor
wire is normal? Connect the comp wire normally
YES
NO
Is the O.C error occurred again? Terminate the service
YES
YES
YES Is the O.C error NO Terminate the
occurred again? service
YES
NO
12-17
DC_link voltage sensor error
1.Checklist :
1) Is the input voltage of outdoor terminal block is normal?
2) Is the reactor wire connected?
3) Is the DC_link capacitor(CE101,CE102,CE103) assembled in accordance the specification? (Outdoor PBA)
4) Is the DC_link resistor(R104,R106,R107,R108) value is normal?
2. Troubleshooting procedure
Is the connected of reactor wire? NO
Connect the reactor wire
(PBA-Reactor)
YES
YES
YES
NO
Is the reactor insulation damaged? Exchange the Outdoor PBA
YES
1.Checklist :
1) Is the input voltage of outdoor terminal block is normal?
2) Is the input voltage is higher than 300Vac?
3) Is the reactor wire connected?
4) Is the DC_link capacitor(CE101,CE102,CE103) assembled in accroance the specification? (Outdoor PBA)
5) Is the DC_link resistor(R104,R106,R107,R108) value is normal?
2. Troubleshooting procedure
YES
YES
YES
YES
NO
Is the reactor insulation damaged? Exchange the Outdoor PBA
YES
12-19
I_trip error, PFC over current
1.Checklist :
1) Is the PFC Shunt(R062,R063) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
YES
Is the I_trip error NO Terminate the
YES occurred again? service
YES
YES
12-20
Current sensor error/Input current sensor error
1.Checklist :
1) Is the PFC Shunt(R062,R063) resistance value correct? Check the resistor is opened
2) Is the IPM Shunt(R451,R452,R453) resistance value correct? Check the resistor is opened
3) Is there no short or open around IC451?
2. Troubleshooting procedure
Restart after power off.
Is the PFC shunt and IPM shunt NO Exchange the Outdoor PBA
resistance value correct?
YES
YES
12-22
Heatsink sensor error/Heatsink over heat
1.Checklist :
1) Are there screws assembly in PBA-heatsink?
2) Is the gap PBA-heatsink
3) Is the fan operation normal?
4) Is the cover assembly in conrol-box normal?
YES
YES
12-23
Comp Vlimit error/Comp current limit error
1.Checklist :
1) Is the IPM Shunt(R451,R452,R453) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
NO
Is the O.C error occurred? Terminate the service
YES
NO
Is the connection of compressor
wire is normal? Connect the comp wire normally
YES
NO
Is the O.C error occurred again? Terminate the service
YES
YES
YES Is the O.C error NO Terminate the
occurred again? service
YES
NO
12-24
EEPROM error/OTP error
1.Checklist :
1) Is there a short around micom?
2) Is there a short around IC502(A*V**PW*) IC202(A*V**PS*)?
3) Did you download or insert EEPROM IC, after changing outdoor PBA?
YES
12-25
AC zero cross signal error
1.Checklist :
1) Check the power condition at customer's house (Is there any power noise?)
2) Have been there power failure?
2. Troubleshooting procedure
Restart after power off
YES
12-26
Operation condition secession error (A*V**PSB*)
1.Checklist :
1) Check the temperature around the outdoor unit.
2. Troubleshooting procedure
Restart after power off
YES
YES
12-27
Capacity miss match error (A*V**PSB*)
1.Checklist :
1) Check the Btu between indoor and outdoor unit
2) Check the indoor unit option and outdoor unit EEPROM data
2. Troubleshooting procedure
Is the rated Btu between indoor NO Exchange the one of them according to the exact
unit and outdoor unit? model spec
YES
YES
YES
12-28
Gas leak error (A*V**PSB*)
1.Checklist :
1) Is the position of indoor Eva_in sensor normal?
2) Check the pipe crack
3) Check the EEV valve connection in Outdoor unit
4) Check the refrigerant was charged
2. Troubleshooting procedure
YES
YES
YES
YES
YES
12-29
4
01230