Mural - Samsung AQV09PSBN

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

Communication error (A*V**P*A*)

Outdoor display ⊙ ● ● 1min. Time out Comm.


○ ○ ●
Abnormal Communication
○ ● ●

1.Checklist :
1) Is the cable between the indoor unit and outdoor unit connected correctly?
2) Isn't the power cable and communication cable cross?
Restart after power off.

2. Troubleshooting procedure

Is the communication error NO


Terminate the service.
occurred again?

YES

NO
Is the connection of power cable
Correct the wrong cable.
and communication cable normal?

YES

Exchange the indoor unit PBA.

NO
Is the communication error Terminate the service.
occurred again?

YES

Exchange the outdoor unit PBA.

Samsung Electronics 12-2


Communication error (A*V**PSB*)

Indoor display ○ ⊙ ⊙ Communication error

Outdoor display ⊙ ● ● 1min. Time out Comm.


○ ○ ●
Abnormal Communication
○ ● ●

1.Checklist :
1) Is the cable between the indoor unit and outdoor unit connected correctly?
2) Isn't the power cable and communication cable cross?

2. Troubleshooting procedure
Restart after power off.

Is the communication error NO


Terminate the service.
occurred again?

YES

NO
Is the connection of power cable
Correct the wrong cable.
and communication cable normal?

YES

NO
Is the power is normal?
Exchange the PBA of no power unit
(check the LED Lamp)

YES

Exchange the indoor unit PBA.

NO
Is the communication error Terminate the service.
occurred again?

YES

Exchange the outdoor unit PBA.

12-3
Indoor temperature sensor error

Indoor room temp sensor


Indoor display ○ ⊙ ○
error

1.Checklist :
1) Is the indoor units temperature sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?

Detach the assembled sensor


2. Troubleshooting from the PBA sensor
procedure
connector and measure the sensor resistance with
ohmmeter(tester)

Sensor Replace
Is the sensor resistance value #1-#2
NO Sensor resistance value : 20℃ - 12.09kohm
10kohm±3% at the room
30℃ - 8.31kohm
temperature
35℃ - 6.94kohm
of 25℃
40℃ - 5.83kohm

YES

Connect the sensor to PBA connector (4piin)


supply power and measure the voltage of #1-#2 in
the connector

YES
Below 0.5V or Over 4.5V? Exchange the indoor PBA

NO

Micom error or connector check

YES

Exchange the indoor PBA

12-4
Indoor Eva-in temperature sensor error

Indoor Eva-in temp sensor


Indoor display ⊙ ⊙ ○
error

1.Checklist :
1) Is the indoor units temperature sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?

Detach the assembled sensor


2. Troubleshooting from the PBA sensor
procedure
connector and measure the sensor resistance with
ohmmeter(tester)

Sensor Replace
Is the sensor resistance value #3-#4
NO Sensor resistance value : 20℃ - 12.09kohm
10kohm±3% at the room
30℃ - 8.31kohm
temperature
35℃ - 6.94kohm
of 25℃
40℃ - 5.83kohm

YES

Connect the sensor to PBA connector (4piin)


supply power and measure the voltage of #3-#4 in
the connector

YES
Below 0.5V or Over 4.5V? Exchange the indoor PBA

NO

Micom error or connector check

YES

Exchange the indoor PBA

12-5
When the Up/Down louver motor does not operate (Initial Diagnosis) (Not displayed)

1.Checklist :
1) Is the input power voltage normal?
2) Is the Up/Down louver motor properly connected with the connector? (CN61)
2. Troubleshooting procedure
Unplug the power cord and plug it after 30seconds
later.

NO Check the as in the procedure.


Is the lamp blinking?
No power.

YES

NO
Is the connected louver wire? Connect the wire PBA to louver motor

YES

Does operation start when swing YES


button of the remote control unit Normal
pushed?

NO

Is the voltage changeable at the NO


pin#2~#5 of CN61(louver Exchange the PBA
connector)?

YES

Up/Down louver motor is faulty.

12-6
When the remote control is not receiving

1.Checklist :
1) Check if the connector was normally assembled.
2) Check the battery in remote control
3) All the lights out and check again : Change electronic typed to a fluorescent light
4) Put the set in operation and check the voltage of display PBA
5) Replace the display PBA

12-7
Indoor fan motor speed detecting error (AC fan)

Indoor display ○ ○ ⊙ Indoor fan error

1.Checklist :
1) Is the indoor units fan motor properly connected with the connector(CN72)?
2) Is the AC voltage correct?
3) Is the HALL IC(feedback sensing) in indoor fan motor properly connected with the connector(CN44)?
4) Is the running capacitor(CR71) properly connected with PBA?

2. Troubleshooting procedure
After unplugging out the power cord should be
reconnected with in 5 seconds

YES

Does the operation lamp blink? NO


Check as in the procedure " No power parts"

YES

Does the solid state relay(SS71) NO PBA should be


Micom is out of order
work properly? replaced

YES
Test location Normal NO
Is the supply
+ voltage of- the fanvoltage PBA should be
PBA is out of order
motor sufficient? replaced
SS71- SS71- 12V

Motor fan-capacitor is Motor fan capacitor


out of order should be replaced
YES
Test location Normal
PBA CN72 Condition voltage Fan motor
Fan motor is out of order
Fan About AC should be replaced
pin #3~#5
operate 180V

12-8
Outdoor temperature sensor error (A*V**PSB*)

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor temperature sensor


Outdoor display ⊙ ○ ⊙
error

1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
Is the sensor connector(CN251) NO
2. Troubleshooting
connected correctlyprocedure
in accordance Reconnect the sensor connector.
with a color(BLU,6PIN)?

YES
Sensor Replace
Is the sensor resistance value #1-#2
NO Sensor resistance value : 20℃ - 12.09kohm
10kohm±3% at the room
30℃ - 8.31kohm
temperature
35℃ - 6.94kohm
of 25℃
40℃ - 5.83kohm

YES

Connect the sensor to PBA connector (6piin)


supply power and measure the voltage of #1-#2 in
the connector

YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA

NO

Micom error or connector check

YES

Exchange the Outdoor PBA

12-9
Outdoor Coil temperature sensor error (A*V**PSB*)

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor display ⊙ ● ⊙ Outdoor Coil temperature sensor error

1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?

Is the sensor connector(CN251) NO


2. Troubleshooting procedure Reconnect the sensor connector.
connected correctly in accordance
with a color(BLU,6PIN)?

YES
Sensor Replace
Is the sensor resistance value #5-#6
NO Sensor resistance value : 20℃ - 12.09kohm
10kohm±3% at the room
30℃ - 8.31kohm
temperature
35℃ - 6.94kohm
of 25℃
40℃ - 5.83kohm

YES

Connect the sensor to PBA connector (6piin)


supply power and measure the voltage of #5-#6 in
the connector

YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA

NO

Micom error or connector check

YES

Exchange the Outdoor PBA

12-10
Outdoor Discharge temperature sensor error (A*V**PSB*)

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor Discharge temperature sensor


Outdoor display ⊙ ⊙ ○
error

1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
Is the sensor connector(CN251) NO
2. Troubleshooting
connected correctlyprocedure
in accordance Reconnect the sensor connector.
with a color(BLU,6PIN)?

YES
Sensor Replace
Is the sensor resistance value #3-#4
NO Sensor resistance value : 20℃ - 242kohm
200kohm±3% at the room
30℃ - 166ohm
temperature
35℃ - 138ohm
of 25℃
40℃ - 115kohm

YES

Connect the sensor to PBA connector (6piin)


supply power and measure the voltage of #3-#4 in
the connector

YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA

NO

Micom error or connector check

YES

Exchange the Outdoor PBA

12-11
OLP sensor error/OLP over heat (A*V**P*A*)

Outdoor display ⊙ ○ ● OLP over heat


⊙ ⊙ ○ OLP sensor error

1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
5) Check the compressor locking or gas leak

Is the sensor connector(CN251) NO


2. Troubleshooting procedure Reconnect the sensor connector.
connected correctly in accordance
with a color(WHT,2PIN)?

YES
Sensor Replace
Is the sensor resistance value #3-#4
NO Sensor resistance value : 20℃ - 242kohm
200kohm±3% at the room
30℃ - 166ohm
temperature
35℃ - 138ohm
of 25℃
40℃ - 115kohm

YES

Connect the sensor to PBA connector (2piin)


supply power and measure the voltage of #1-#2 in
the connector

YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA

NO

The condition is too poor for air conditioner to


operate
Wait until OLP temperature is decreased
Restart after power off
YES

Exchange the Outdoor PBA

12-12
Outdoor Discharge over temperature error (A*V**PSB*)

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor Discharge over temperature


Outdoor display ⊙ ○ ●
error

1.Checklist :
1) Check the discharge temperature in the outdoor unit
2) Check the compressor locking or gas leak
3) Download the EEPROM data

2. Troubleshooting procedure
Restart after power off.

after 30min ~ 1Hr

Is the discharge over temperature NO


Terminate the service
sensor error appeared again?

YES
The condition is too poor for air conditioner to
operate
Wait until discharge temperature is decreased
Restart after power off

NO
Is the discharge over temperature
sensor error appeared again? Terminate the service

YES

Download the EEPROM data

NO
Is the discharge over temperature
Terminate the service
sensor error appeared again?

YES

Exchange the Outdoor PBA

Exchanged the Compressor

12-13
Outdoor Fan motor error (A*V**PSB*)

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor display ● ○ ○ Outdoor fan error

1.Checklist :
1) Are the input power voltage and the power connection correct?
2) Is the motor wire connected to the outdoor PBA correctly?
3) Is there no assembly error or none-assembly in the terminal of motor wire connector?
4) Is there no obstacle at the surrounding of motor and propeller?

2. Troubleshooting procedure
Restart after power off.

NO Power off and Separate the Fan motor wire from


Does the fan rotate?
CN901 on Outdoor PBA

YES

Reassemble the fan wire and input the power again Is there short among each pin YES Exchange the Fan
#1~#6 motor

NO Terminate the NO
Is the fan error appeared again?
service

YES

NO
Is the voltage of CN901 #1-#3 over Follow the check procedure of outdoor unit power
250Vdc supply error check

YES

Is the voltage of CN901 #3-#5 and NO


#3-#6 with in 1Vdc~15Vdc during Exchange the Outdoor PBA
the operation?

YES

PBA problem or Motor problem


Change the PBA first and check the operation

Exchange the Fan motor

12-14
Compressor starting error

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor display ○ ⊙ ○ Comp starting error

1.Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?

2. Troubleshooting procedure
Restart after power off.

NO
Is the restart error occurred again? Terminate the service

YES

NO
Is the connection of compressor
wire is normal? Connect the comp wire normally

YES

Download the EEPROM data

NO
Is the restart error occurred again? Terminate the service

YES

YES
Is the compressor body and
Exchange the Outdoor PBA
interphase resistance insulated?

NO

Exchange the compressor

12-15
Compressor wire missing error/rotation error

Indoor display ⊙ ○ ⊙ Outdoor error

Compressor wire missing error/rotation


Outdoor display ● ○ ●
error

1.Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?

2. Troubleshooting procedure
Restart after power off.

NO
Is the restart error occurred again? Terminate the service

YES

Is the connection of compressor NO


wire is normal? (PBA and Connect the comp wire normally
Compressor)

YES

NO
Is the restart error occurred again? Terminate the service

YES

YES
Is the compressor body and
Exchange the Outdoor PBA
interphase resistance insulated?

NO

Exchange the compressor

12-16
O.C(Over Current) error

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor display ○ ○ ⊙ Comp starting error

1.Checklist :
1) Is the IPM Shunt(R451,R452,R453) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?

2. Troubleshooting procedure
Restart after power off.

NO
Is the O.C error occurred? Terminate the service

YES

NO
Is the connection of compressor
wire is normal? Connect the comp wire normally

YES

NO
Is the O.C error occurred again? Terminate the service

YES

Is the condition of indoor/outdoor NO


Restart after returning to the normal load
temperature normal load?

YES
YES Is the O.C error NO Terminate the
occurred again? service

Is the position of temperature NO


Correct the sensor position or exchange the sensor
sensor and sensing value normal?

YES

Is the compressor body and YES


Exchange the Outdoor PBA
interphase resistance insulated?

NO

Exchange the compressor

12-17
DC_link voltage sensor error

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor display ● ⊙ ⊙ DC_link voltage sensor error

1.Checklist :
1) Is the input voltage of outdoor terminal block is normal?
2) Is the reactor wire connected?
3) Is the DC_link capacitor(CE101,CE102,CE103) assembled in accordance the specification? (Outdoor PBA)
4) Is the DC_link resistor(R104,R106,R107,R108) value is normal?

2. Troubleshooting procedure
Is the connected of reactor wire? NO
Connect the reactor wire
(PBA-Reactor)

YES

Restart after power off.


Start the operation (cooling mode or heating mode)

Is the DC_link voltage (CE101) is NO


normal in operation mode? Check the power input
Normal range(280Vdc~320Vdc)

YES

Is the DC_link sensing voltage(R104) NO


is normal in operation mode? Exchange the Outdoor PBA
Normal range (0.2Vdc~2.8Vdc)

YES

NO
Is the reactor insulation damaged? Exchange the Outdoor PBA

YES

Exchange the Reactor


DC_link voltage under/over error, Over voltage protection error/PFC over load

Indoor display ⊙ ○ ⊙ Outdoor error

DC_link voltage under/over error


Outdoor display ○ ● ⊙ Over voltage protection error
PFC over load

1.Checklist :
1) Is the input voltage of outdoor terminal block is normal?
2) Is the input voltage is higher than 300Vac?
3) Is the reactor wire connected?
4) Is the DC_link capacitor(CE101,CE102,CE103) assembled in accroance the specification? (Outdoor PBA)
5) Is the DC_link resistor(R104,R106,R107,R108) value is normal?
2. Troubleshooting procedure

Is the connected of reactor wire? NO


Connect the reactor wire
(PBA-Reactor)

YES

Restart after power off.

Is the the input voltage is nomal? NO


Check the input power in the powercord.
Normal range(180Vac ~ 270Vac)

YES

Restart after power off.


Start the operation (cooling mode or heating mode)

Is the DC_link voltage (CE101) is NO


normal in operation mode? Check the input power
Normal range(280Vdc~320Vdc)

YES

Is the DC_link sensing voltage(R104) NO


is normal in operation mode? Exchange the Outdoor PBA
Normal range (0.2Vdc~2.8Vdc)

YES

NO
Is the reactor insulation damaged? Exchange the Outdoor PBA

YES

Exchange the Reactor

12-19
I_trip error, PFC over current

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor display ● ⊙ ● I_trip error, PFC over current

1.Checklist :
1) Is the PFC Shunt(R062,R063) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?

2. Troubleshooting procedure
Restart after power off.

Is the condition of indoor/outdoor NO


Restart after returning to the normal load
temperature normal load?

YES
Is the I_trip error NO Terminate the
YES occurred again? service

Is the position of temperature NO


sensor and the sensing value Correct the sensor position or exchange the sensor
normal?

YES

Is the connection cable for the NO


compressor and power terminal Correct the cable connection
normal?

YES

Exchange the Outdoor PBA

12-20
Current sensor error/Input current sensor error

Indoor display ⊙ ○ ⊙ Outdoor error

Current sensor error/Input current


Outdoor display ⊙ ⊙ ●
sensor error

1.Checklist :
1) Is the PFC Shunt(R062,R063) resistance value correct? Check the resistor is opened
2) Is the IPM Shunt(R451,R452,R453) resistance value correct? Check the resistor is opened
3) Is there no short or open around IC451?

2. Troubleshooting procedure
Restart after power off.

Is the PFC shunt and IPM shunt NO Exchange the Outdoor PBA
resistance value correct?

YES

Is the current sensor error NO


Terminate the service
appeared again?

YES

Exchange the Outdoor PBA

12-22
Heatsink sensor error/Heatsink over heat

Indoor display ⊙ ○ ⊙ Outdoor error

Heatsink sensor error/Heatsink over heat


Outdoor display ○ ⊙ ⊙
(A*V**PW**)
⊙ ⊙ ● Heatsink sensor error (A*V**PS**)
⊙ ● ⊙ Heatsink over heat (A*V**PS**)

1.Checklist :
1) Are there screws assembly in PBA-heatsink?
2) Is the gap PBA-heatsink
3) Is the fan operation normal?
4) Is the cover assembly in conrol-box normal?

Restart after power


2. Troubleshooting off.
procedure

Are there screws in PBA-heatsink? NO Fastening the screw


(4 screws)

YES

NO Check the fan connection


Is the fan operation normal?
Change the Fan motor

YES

Exchange the Outdoor PBA

12-23
Comp Vlimit error/Comp current limit error

Indoor display ⊙ ○ ⊙ Outdoor error

Comp Vlimit error/Comp current limit


Outdoor display ⊙ ● ○
error

1.Checklist :
1) Is the IPM Shunt(R451,R452,R453) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?

2. Troubleshooting procedure
Restart after power off.

NO
Is the O.C error occurred? Terminate the service

YES

NO
Is the connection of compressor
wire is normal? Connect the comp wire normally

YES

NO
Is the O.C error occurred again? Terminate the service

YES

Is the condition of indoor/outdoor NO


Restart after returning to the normal load
temperature normal load?

YES
YES Is the O.C error NO Terminate the
occurred again? service

Is the position of temperature NO


Correct the sensor position or exchange the sensor
sensor and sensing value normal?

YES

Is the compressor body and YES


Exchange the Outdoor PBA
interphase resistance insulated?

NO

Exchange the compressor

12-24
EEPROM error/OTP error

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor display ○ ● ○ EEPROM error


● ○ ⊙ OTP error

1.Checklist :
1) Is there a short around micom?
2) Is there a short around IC502(A*V**PW*) IC202(A*V**PS*)?
3) Did you download or insert EEPROM IC, after changing outdoor PBA?

power off and download


2. Troubleshooting EEPROM data
procedure
(or. Insert the service EEPROM IC)

Restart after power off NO Terminate the service


Is the error appeared again?

YES

Exchange the Outdoor PBA

12-25
AC zero cross signal error

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor display ● ● ⊙ AC zero cross signal error

1.Checklist :
1) Check the power condition at customer's house (Is there any power noise?)
2) Have been there power failure?

2. Troubleshooting procedure
Restart after power off

Is the AC line zero cross signal error NO Terminate the


appeared again? service

YES

Exchange the Outdoor PBA

12-26
Operation condition secession error (A*V**PSB*)

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor display ● ⊙ ○ AC zero cross signal error

1.Checklist :
1) Check the temperature around the outdoor unit.

2. Troubleshooting procedure
Restart after power off

Is the operation condition secession NO Terminate the


error appeared again? service

YES

* Heating mode * * Cooling mode *


Is the outdoor temperature over Is the outdoor temperature under -
40℃ or under -30℃? 7℃

YES

The temperature condition is too poor to operate.


Wait until temperature is changed

12-27
Capacity miss match error (A*V**PSB*)

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor display ⊙ ○ ○ Capacity miss match error

1.Checklist :
1) Check the Btu between indoor and outdoor unit
2) Check the indoor unit option and outdoor unit EEPROM data
2. Troubleshooting procedure

Is the rated Btu between indoor NO Exchange the one of them according to the exact
unit and outdoor unit? model spec

YES

Reset the option code again at indoor unit

Is the capacity miss match error NO


Terminate the service
appeared again?

YES

Download the EEPROM data

Is the capacity miss match error NO


Terminate the service
appeared again?

YES

Exchange the Outdoor PBA


Exchange the Indoor PBA

12-28
Gas leak error (A*V**PSB*)

Indoor display ⊙ ○ ⊙ Outdoor error

Outdoor display ● ● ○ Gas leak error

1.Checklist :
1) Is the position of indoor Eva_in sensor normal?
2) Check the pipe crack
3) Check the EEV valve connection in Outdoor unit
4) Check the refrigerant was charged

2. Troubleshooting procedure

Is the position of indoor eva_in NO


Indoor sensor take the normal position
sensor normal?

YES

Restart after power off

after 20minutes later

Is the gas leak error appeared NO


Terminate the service.
again?

YES

Check the EEV valve operation.

Is the EEV valve connection NO


Connect the EEV valve.
normal?

YES

Is the EEV valve is operation? NO


Check the sound of EEV valve after Change the EEV valve.
power on.

YES

Is the pressure of refrigerant NO Check the pipe crack.


normal? Fill up the refrigerant.

YES

Exchange the Indoor PBA


Exchange the Outdoor PBA

12-29