NETWORK DEPARTMENT
Chalkokondyli 22, 10432 ATHENS - Tel.: 210-5292030, Fax: 210-5239301
CONTENTS
1. SCOPE
2. KEYWORDS
3. OPERATING CONDITIONS
4. STANDARDS – SPECIFICATIONS
5. DESCRIPTION
6. TESTS
7. NAMEPLATES – MARKING
8. PACKING
9. ANNEXES – DRAWINGS
PPC TECHNICAL DESCRIPTION ND - 180/04.09.2006
1. SCOPE
2. KEYWORDS
Modular panel with external metallic enclosure, modular – type panel, M.V.
customers, 20 kV substation.
3. OPERATING CONDITIONS
3.1.1 Installation
Panels compliant to this T.D. are intended for use in Medium Voltage distribution
networks; they shall be suitable for indoor installation, at ground, underground or
other floors of buildings, to allow supply to medium voltage customers by PPC.
Panel installation shall be done according to the requirements of paragraph 10.2
of ΕΝ 62271-200 and Drawing 5 of the present. Clearance between the back side
of the panels and the Substation (S/S) wall shall be 100 mm. The minimum
height of the panel installation room (channels not included) shall be 2500 mm.
The panels shall be installed on concrete foundation, as shown in Drawing 5 of
the present; fastening shall be carried out from the operating position at the front
side.
Manufacturers shall take into account that the maximum free height of the top
surface of the concrete foundation (panel base) above the S/S floor that cannot
be trenched, is 0,5 m. Hence, terminations shall be installed at a suitable height
and position so that cables can be freely routed to any direction, with bend radius
of each single core cable 890 mm.
Furthermore, in any case terminations shall not protrude below the foundation
plane of the panel. In addition, it is desirable that live panel components are
situated at a minimum distance of 500 mm from the panel floor.
Each panel shall be accompanied by all fittings necessary for mounting on the
above mentioned foundation, e.g. angular profile bars, bolts etc.
Manufacturer at its own expense shall allocate specialized personnel for the
installation of the first 5 panel groups (Athens, Thessaloniki, Patra, Lamia or
elsewhere as instructed).
1
3.2. System Characteristics
The material is intended for use on three - phase, three conductor distribution
networks with earthed neutral node at the feeding point through a resistor
limiting the maximum earth fault current to 1000 Α.
Material shall be of 24 kV rated voltage, of frequency 50 Hz and suitable for
installation at networks with the following characteristics:
4. STANDARDS – SPECIFICATIONS
2
- EN 62271-105:2003: High-voltage switchgear and controlgear - Part 105:
Alternating current switch-fuse combinations.
Note: In case requirements of this T.D. contradict the provisions of any of the above
Standards / Specifications, the provisions of this Description shall prevail.
5. DESCRIPTION
The present T.D. sets out requirements for the supply of modular type, Medium
Voltage panels with external metallic enclosure, intended for earthing according
to paragraph 5.3.1.10 of the present.
Panels use atmospheric air under atmospheric pressure as the main dielectric
between live parts, according to paragraph 5.3.1.1. of the present. Load break
switches shall utilize sulfur hexafluoride (SF6) as a dielectric under pressure,
according to standard ΕΝ 60376 and circuit breakers shall be of vacuum
technology in accordance with the European standard ΕΝ 62271-100:2001 and
the paragraph 5.4.2.1. of the present.
This T.D. refers to standard panels fitted with equipment as described in
paragraph 5.2 of the present.
These panels are combined to constitute panel groups, as specified in the
following paragraph 5.1 of the present.
All chambers where SF6 gas is present shall be fitted with filters to retain
moisture and SF6 by-products; these shall be warranted for the entire lifetime of
the equipment as no inspection or replacement is specified.
Manufacturers shall declare filter quantity and absorbency.
Panel diagrams for the S/S of medium voltage customers are the following:
- Type Ι in radial system. (Drawing 2a)
- Type Ι in ring main system. (Drawing 3a)
- Type II in radial system. (Drawing 2b)
- Type II in ring main system. (Drawing 3b)
Each of the above diagrams constitutes a group of panels and includes the
following standard panels:
3
- Two line “load break switch” panels, according to paragraph 5.2.2.
- One MV customer protection panel, type I, according to paragraph 5.2.3.
- One voltage transformers' panel, according to paragraph 5.2.5.
- One meter panel, according to paragraph 5.2.6.
This panel is used for cable arrival of network in radial system. It includes the
following:
5.2.1.4 One voltage presence test indicating device on the cable side according
to paragraph 5.3.1.3.6.
These panels shall be of identical dimensions with the line “load break switch”
panels; their doors shall be interlocked with the earthing switch, to allow opening
of the door only after it is closed.
This panel shall be suitable for future integration of equipment necessary for
remote control and remote signaling with 48 V dc supply voltage; it shall include
the following apparatus and devices:
4
5.2.2.1 Busbar Compartment: Special (tool-based) accessible compartment
in accordance with paragraph 3.107.3 of ΕΝ 62271-200.
This panel shall not be fitted with remote control equipment; instead, it shall be
suitable for future integration of equipment necessary for remote control and
remote signaling with 48 V dc supply voltage.
5
5.2.3.2.3 One earthing - short circuiting device, according to paragraphs 5.4.5
and 5.2.1.3.
5.2.3.3.1 Three 200 Α fuse bases for fuse links of high breaking power,
according to paragraph 5.4.8.
Note: Earthing - short circuiting devices located on both opposite sides of high voltage
fuses shall be operated by a common control handle.
5.2.3.4.2 One test terminal box with locking capability by wire and seal, similar
to the one the Corporation purchases under Specification GR-107 Α,
allowing the short circuiting of current transformers and the isolation of
voltage transformers - for testing purposes - and the connection of
instruments to perform measurements. This box shall be installed in
the meter panel.
Note 1: Locating the disconnector at the line “load break switch” and type Ι and II
protection panels serves three purposes:
- Establishing an isolating gap between busbars and the remainder of the main
circuit.
- Establishing safe conditions in the interior of the panel when busbars are live.
- Preventing permanent connection to busbars of apparatus or apparatus
components requiring regular maintenance (paragraph 5.3.1.8).
Note 2: 75-150/5 current transformers, shall be the same as current transformers of
paragraph 5.2.4.3.4., with two secondary windings.
This panel shall not be fitted with remote control equipment; instead, it shall be
suitable for future integration of equipment necessary for remote control and
remote signaling with 48 V or 24 V dc power supply voltage.
This panel shall include the following apparatus and devices:
6
5.2.4.1.1 400 Α busbars, according to paragraph 5.4.1.
5.2.4.4.1 Two test terminals boxes, one intended for measurement and the
second for protection, according to paragraph 5.2.3.4.2. These boxes
shall be installed in the meter panel.
7
5.2.5.3 Voltage transformers - fuses compartment: Operator (interlock-
based) accessible compartment, LSC2A, PM or PI in accordance with
paragraphs 3.107.1 and 3.131.1 of ΕΝ 62271-200.
5.2.5.3.1 Three M.V. fuse bases and fuse links suitable for voltage transformer
protection, installed downstream of panel disconnector (para.
5.2.5.2.1).
Note: Panels can also be ordered with 6000-20000/100 transformers, if this is reported at
the Call for Tenders.
5.2.5.4.1 One bipolar L.V. miniature circuit breaker (MCB) for the L.V. side of
voltage transformers.
The opening of this L.V. MCB shall cause illumination of indicating
lamps on a type Ι protection panel and it shall produce opening of the
L.V. MCB on type II protection panels. Electric lamps shall be power
supplied from the L.V. of the customer. The L.V. MCB shall be placed in
a box whose cover has the ability of sealing. The lamp layout is shown
in Drawing 6.
This panel shall have width of 500 mm and height as the other panels of the
group; it shall be divided into two independent parts. Each part shall have an
independent door that can be secured with padlock. The lower part shall be used
by the Corporation for the installation of one energy meter (kWh), one reactive
power meter (kVAR) and one peak demand recorder. The upper part (whose
height is in the level of 600 mm) can be used to install protection instruments,
e.g. relays. Manufacturer shall perform the wiring and the configuration of these
panels for the connection of the above mentioned instruments, taking into
account the instrument arrangement shown in Drawing 7.
8
covered with solid insulating material on condition that this insulating material is
in permanent contact with busbars.
Solid insulating materials used shall be self-extinguishing, ensuring an insulation
level equal to the rated insulation level of the panel (paragraph 5.3.2.2. of the
present). Maximum allowed partial discharge level of insulating materials is 50
pC. All panels of a group, of the same manufacturer, shall have the same height
and depth not greater than 1950 mm for height and 1250 mm for depth.
Individual panels of a group, of the same manufacturer, can be of different
widths, however this shall not exceed 750 mm. The total width of a ring main
system panel group shall not exceed 2750 mm (including the meter panel). All
panels of each group shall be separated by metallic partitions extending
throughout the whole depth of panels and reaching upwards up to the separating
cover of busbars.
Note: Minor variations from the above panel dimensions, resulting from requirements for
withstand to internal arc testing, as well as to facilitate easy access can be accepted at
PPC’s discretion. Such changes shall not cause the overall width of the group to exceed
3000 mm or 2500 mm (including meter panel) for ring main system or radial system
respectively.
Panels shall have external metallic enclosure covering all their parts even from
the bottom, providing protection of persons against accidental contact with live
parts, IΡ3Χ minimum degree of protection, as this is defined in paragraph
5.102.1 of ΕΝ 62271-200. External wiring between panels is not permitted.
Works mentioned below shall be carried out by person standing in front of the
panel, while the enclosure provides degree of protection ΙΡ3Χ in accordance with
paragraph 5.3.1.2. of the present.
5.3.1.3.1 Closing and breaking (ON-OFF) operations by the main breaking device
Note: The term "main breaking device" in this Technical Description, refers to the load
break switch or the circuit breaker.
9
All parts of the section of the panel where an operation is being carried out,
having conductive connections to circuit elements which are out of this area, shall
be earthed and short circuited.
Verification of earthing - short circuiting shall also be performed visually. If
because of the panel design, moving contacts of the earthing device are not
visible, such verification must be performed under other indisputably reliable
criterion, as specified in paragraph 5.3.1.3.3 above.
Note: The above do not refer to main busbars, i.e. busbars which are common to adjacent
panels.
This test shall be carried out using voltage divider that supplies power to low
voltage glow lamps or equivalent illuminating devices of more recent technology,
permanently installed at the front of the Panel.
Voltage presence indicating device shall be capable of detecting voltage from 3
kV up to 24 kV and shall be safe for the operator.
This test shall be carried out using devices similar to the ones used for testing for
voltage presence.
Note: Phase correspondence portable devices shall be provided - one per each panel
group.
5.3.1.4 Works performed following disconnecting of the main circuit and the
opening of the door, with live main busbars
All the above mentioned operations shall be carried out from the panel's front
side.
Intervention shall be easy and safe and replacement shall not require extensive
disassembly works.
10
circuits outgoing from the operations area. In this case, the circuit shall be
earthed upstream and downstream of the M.V. fuse.
Note: The term “mandatory earthing" refers to the fact that the opening of panel door
shall not be allowed prior to this earthing.
5.3.1.6 Interlocks
The interlocks mentioned below shall be obtained through simple and direct
mechanical arrangements (using keys for such purpose is not allowed).
As connection to busbars is carried out using a disconnector, the necessary
interlocks (ΕΝ 62271-200, paragraph 5.11) shall be the following:
5.3.1.6.1 Operation of the main isolating device shall not be possible when the
main breaking device is closed.
5.3.1.6.2 Operation of the main breaking device shall not be possible, only
unless the isolating device is completely closed or open.
5.3.1.6.3 Operation of the earthing – short circuiting device shall not be
possible, unless after the isolation from the busbars has been
performed.
5.3.1.6.4 The isolating device shall not be possible to close, unless earthing has
been removed.
5.3.1.7 Access
Access to the panel interior shall be prevented through suitable interlocks so that
access shall only be possible when the conditions of paragraph 5.3.1.5.2 are met.
When the panel interior has been accessed, the following shall apply:
5.3.1.7.1 Free operation of the cable's earthing - short circuiting device shall be
possible after a deliberate removal (violation) of the respective
interlock.
5.3.1.7.2 Closing of the isolating device from the busbars shall not be possible,
as well as non-deliberate removal of the busbars’ cover.
11
5.3.1.9 Measurements and testing on cables
After earthing - short circuiting of the cable ends, its removal shall be possible in
order to perform dielectric tests or measurements on cables, (see paragraph
5.3.1.7.1).
In case cable ends are not directly approachable e.g. due to the kind of
insulation, manufacturer shall provide suitable bushing adaptors for application,
at each phase, of test voltage with regard to earth either 20 kV ac (rms value) or
49 kV dc for 15 minutes for both cases.
Manufacturer shall provide one such bushing adaptor for each panel group.
The provisions of the respective paragraphs 5.6 and 5.7, of ΕΝ 60694, where
applicable, shall apply to the energy storage and operation of the opening/closing
commands of the breaking devices.
Removable covers and doors are parts of the external enclosure; they shall be
metallic, they shall provide ΙΡ3Χ degree of protection and they shall be in
accordance with paragraph 5.102.2 of ΕΝ 62271-200.
Inspection windows shall be made from safety glass (e.g. Securit type) or
equivalent material; they shall be durable (tested according to paragraph 6.2.14
12
of the present); they shall be firmly fixed to the external metallic enclosure and
they shall comply with paragraph 5.102.4 of ΕΝ 62271-200.
These openings and outlets shall meet the requirements of paragraph 5.102.5 of
ΕΝ 62271-200.
Access to a voltage transformer panel shall be carried out only under the
following conditions:
- Mandatory disconnection of transformers from MV, ensured through
suitable mechanical interlocks,
- full coverage of live parts that remain live, through a permanent or
automatically installed shutter.
Following the opening of the panel interior access door, the closing of
disconnectors and removal of busbar covers shall be prohibited (by interlocks).
Alternatively, voltage transformers can be installed on a withdrawable truck;
thus, the isolation on both the MV and the LV side shall be carried out by the
above truck movement and the respective disconnector is omitted. In this case,
voltage transformers shall be accessible when the truck has overridden the
isolating position and the fixed contacts which are live are automatically covered.
Replacement of fuse links shall be possible only when circuits upstream and
downstream of MV fuse links are earthed. The downstream earthing of fuses
towards the transformer’s side can be omitted in case another device is installed,
ensuring that it will not be reverse power supply of the transformer from the LV
side, when the transformer panel door is open.
13
5.3.1.19 Supplementary materials, instruments and tools
Manufacturer shall include the following materials, instruments and tools in his
offer:
- All panel mounting material for installation, according to paragraph 3.1.1
of the present.
- One kit for each standard ring or radial type substation; this shall include
tools, removable control handles, devices and proprietary apparatus or
arrangements, provided that these are necessary for service operations
and maintenance works.
- All materials required for construction and fixing of cable terminations for
each panel.
This panel shall be certified for protection against internal faults (IAC
Classification), AFL type in accordance with ΕΝ 62271-200, Annex A, paragraph
2.
All necessary measures for protection of personnel against internal faults shall be
implemented by proof, in accordance with the ΕΝ 62271-200, paragraph 5.101
and for 10 kA short circuit for 1 sec. Furthermore, installation position of panels
in accordance with Drawing 5 and paragraph 3.1.1 shall be taken into account.
Independent exhausting ducts shall be provided at the back of panels, used to
evacuate gases produced in case of internal arc; they shall be routed upwards or
downwards (cable area).
Panels shall withstand the internal arc test as stand-alone units without using
walls as part of the channel or as part of any other element of the installation
area (e.g. cable duct).
Panels’ construction shall be complete, including the above mentioned channels
for the case of electric arc.
The Supplier is obliged to furnish all the relevant technical data (description of
protection measures, test results) with his offer.
14
b) Withstand to lighting impulse voltage, full wave (1,2/50 μs).
5.3.2.4 Rated short-time withstand current and rated duration of short circuit:
10 kA, 1s
5.4.1 Busbars
Panel busbars shall have all the electrical characteristics specified in paragraph
5.3.2. of the present; additionally, their rated current shall be equal to 400 Α.
5.4.2.1 Description
The circuit breakers shall be of vacuum technology in accordance with EN 62271-
100.
Vacuum circuit breakers shall be suitable to break the magnetizing currents of
20/0.4kV transformers, constructed according to valid CENELEC standards, and to
break the inductive fault currents, for faults occurring after the 20/0.4 kV
transformer. Manufacturing material of contacts of vacuum circuit breakers shall
be an alloy of appropriate composition to ensure the low chopping current, thus
preventing the development of hazardous overvoltage and re-ignition.
Vacuum circuit breakers shall be of sealed pressure type, warranted for 30 years
expected operating life, in accordance with the effective valid European Standard
mentioned above.
Circuit breakers shall have all the electrical characteristics specified in paragraph
5.3.2 of the present, as well as the following:
5.4.2.4 Rated short circuit making capacity: 2,5 times the rated symmetrical
breaking current in kΑ, of the respective voltages as specified in the
above paragraph 5.4.2.3. This value denotes the peak value.
15
5.4.2.5 Rated total break time: 100 ms at 100% of the breaking capacity
specified in the above paragraph 5.4.2.3.
5.4.3.1 Description
5.4.3.3.1 Rated closed loop breaking current: equal to the rated normal current
of the switch (paragraph 5.4.3.1. of the present).
5.4.3.3.2 Rated mainly active load breaking current: equal to the rated normal
current of the switch (paragraph 5.4.3.1. of the present).
5.4.3.3.3 Rated no-load line and cable charging current: at least equal to 10 A.
16
5.4.3.3.4 Minimum rated transformer off-load breaking current:
- 10 Α for 400 A switches
- 4 Α for 200 A switches
5.4.4 Disconnectors
5.4.4.1 Description
These shall comply with ΕΝ 62271-102, they shall meet the requirements of ΕΝ
62271-200 and shall have all the electrical characteristics as specified in
paragraph 5.3.2 of the present; they shall feature an independent manual
operation as specified in ΕΝ 62271-102.
Regarding customers’ protection panels of type Ι and with respect to the second
earthing switch (downstream of fuses) the respective values of paragraphs
5.3.2.4. and 5.3.2.5. are revised as follows:
a) Rated short-time withstand current and rated duration: 2 kΑ, 1 sec
b) Rated peak withstand current: 5 kA
On customer protection panels of type Ι, earthing-short circuiting devices
installed on both opposite sides of high voltage fuses shall have a common
control handle.
17
Note: The earthing switch shall not open by itself and shall not be damaged after the flow
of the short circuit current.
Current transformers shall be designed for a rated thermal current equal to 1,2
times the rated primary current specified in paragraph 5.4.6.2. The respective
current errors and phase displacements shall extend up to that value.
5.4.6.6 Instrument security factor & accuracy limit factor: F<=5 for instrument
current transformers and 5-Ρ-10 for protection transformers.
5.4.6.8 Dimensions
It is desirable that current transformer dimensions do not exceed 250X210 mm
and their height is not greater than 270 mm.
18
5.4.6.9 Partial discharges requirements
The permissible partial discharges level for all current transformers is 50 pC.
Voltage transformers shall be two (2) double pole independent units, or shall be
contained in the same external enclosure, connected between phases according
to the 'V' or 'W' scheme.
These transformers shall be in accordance with EN 60044-2 for metering
transformers and they shall be of dry insulation type and located in the panels at
such a position which will facilitate service interventions thereto. They shall have
the following characteristics:
Resin used for transformers insulation construction shall be of proven premium
quality, suitable for such applications. Manufacturer shall furnish product design
data to demonstrate the absence of manufacturing faults as well as their long -
term reliability.
6000 - 20000/100
15000 - 20000/100
20000/100
5.4.7.6 Dimensions
It is desirable that voltage transformers’ dimensions do not exceed 310X180 mm
and their height is not greater than 310 mm.
5.4.8.1 Bases
19
5.4.8.1.2 Rated insulation level: as paragraph 5.3.2.2. of the present.
Note 1: Quantities from each fuse category are defined in the Tender.
Note 2: Manufacturer has the obligation to give prices for fuse links of all the rated
currents mentioned above. PPC reserves the right to select suitable fuse links based on
their characteristics and as well as to revise quantities of each type of fuse link.
5.4.9 Voltmeter
It shall comply with ΕΝ 60051-1, ΕΝ 60051-2 and ΕΝ 60051-9, and shall have
the following characteristics:
- Accuracy class: 1,5
- Type: Flush-mounted
- Dimensions: External dimension > 65 mm for installation heights up to
1,90 m, otherwise > 130 mm for greater heights.
- Scale: Triple scale: 4800 - 7200 V
12000 - 17500V
16000 - 24000V
Digital voltmeters can be accepted as well.
5.4.10 Terminations
Terminations shall already be tested and widely used, which shall be proven by
the submission of references.
5.4.10.1 Terminations for line arrival panels and line “load break switch” panels
These terminations are intended for terminating three single core 12/20kV
aluminum cables, XLPE insulated, PVC sheath and Al earthing conductor
20
contained within a lead sheath, in accordance with Technical Description DECOD -
182/15.11.94 and its Supplement 1/14.03.02, with the following characteristics:
These terminations are intended for terminating single core copper cables, XLPE
insulated and screened by copper strands and tapes and furthermore a PVC
protective sheath, of type N2XSY.
21
5.4.10.3 Manufacturer shall provide all materials necessary for the construction
of the termination assembly, as well as for cable connections and mounting.
Terminations shall be successfully subjected to tests according to European
Standard CENELEC HD 629.1S1:1996+A1:2001 and ΕΝ 61442:2005.
22
5.4.11.6 Indications
Relays shall feature separate indicative signals for time - delay operation, for
instantaneous operation as well as position indication under voltage. A total of 5
indicative signals shall be provided. Alternatively, the above mentioned
indications can be displayed on - screen. Furthermore, additional contacts shall
be provided for the remote signaling of their functions.
5.4.11.7 Reset
The relay shall support auto reset i.e. self - reverting to idle state, ready for a
new operation when the cause of the initial pick - up has been eliminated,
whereas operation indicators will remain in a pick-up state. The resetting of these
indicators shall be performed manually and it shall be possible without removing
the lock of relay housing.
5.5.1 The line “load break switches” shall be electrically driven (equipped with a
motor) with remote control - remote signaling capabilities under 48 V dc.
Indication of switch position, including the earthing switch, shall be conducted
through suitable cam contacts or other equivalent layouts.
Each switch shall be fitted with pressure switches (ON-OFF button) for local
operation, while the panel group shall include a single selector switch for local
operation - remote operation (LOCAL - REMOTE). Furthermore a device shall be
provided for the remote indication of voltage presence in busbars regarding all
operations and in every case the interlocks specified in this Technical Description
shall be followed.
5.5.2 All mechanical interlocks shall also be realized electrically as well with
proper connection at each panel's terminal strip.
5.5.3 All panel outgoing signals shall end to a terminal strip in the form of dry
contacts.
5.5.4 At least 2 contact pairs to the terminal strip shall be provided for each
control handle for the indication of its position.
5.5.5 In case the LOCAL-REMOTE switch is set to LOCAL position, electrical
interlocks shall be removed as well.
5.5.6 The 48 V dc source does not constitute part of the present Technical
Description.
All manufacturers shall declare the following data with regard to the 48 V dc
source:
- Power consumption requirements (in diagram form) of all components to
be battery - powered (opening and closing of the load break switches,
tripping coil consumption, consumption of indicating devices supplied by
48 V dc etc.)
- Proposed battery capacity in Ah, sufficient for power requirements
specified above for:
- total number of 20 complete operations, at minimum, as well
23
as any other operation for a minimum time of 48h.
- total number of 10 complete operations, at minimum, as well as
any other operation for a minimum time of 8h.
6. TESTS
For the requirements of the present Technical Description tests on the panels are
distinguished into type tests and routine tests.
Individual panel components covered by separate International Standards shall
be tested according to these Specifications. Instead of these tests, test
certificates can be accepted at the discretion of PPC, where such certificates are
issued by an accredited laboratory.
In particular, with regard to current and voltage transformers, the following tests
shall be carried out during each contract:
a) Visual inspection of all voltage and current transformers for possible
manufacturing defects (marking, suitability of connectors, cast resin quality,
possible cracks etc), as well as measurement of their accuracy class.
b) All the current and voltage transformers shall be tested regarding their
accuracy at PPC’s laboratories (MS/ND) where they shall be transported at the
manufacture’s expense. Alternatively the test of the mentioned transformers can
be performed in any other laboratory provided that the following conditions are
met:
- The laboratory where accuracy tests are carried out shall be accredited by
EN/ISO17025:2005
- All the certificates issued for each T/F shall be submitted to Metering
Section/ND (MS/ND) for examination, as described in the Management
and Transactions Code.
- Sample tests shall be performed, with the following sampling program
according to PPC’s Technical Specification ΤΚ 02.01/11.11.87 «Sampling
procedures and tables for the inspection of the percentage of defectives by
attributes»: Single sampling, Special inspection level S4 for tightened
inspection and AQL = 1.0%. These samples shall be transported to MS/ND
to be tested for their accuracy, at the contractor’s expense and
responsibility.
c) Preferably 3 current transformers and 3 voltage transformers shall be tested at
the PPC laboratories to verify conformance to the requirements of the present
and the relevant ΕΝ or IEC standards. In case 2 or 3 transformers fail these tests,
the lot shall be rejected. In case 1 transformer fails, a new sample of 3
transformers shall be taken and all three shall be successfully tested.
Not applicable.
24
operation conditions, at all times, fully compliant to the operational requirements
specified and its intended purpose.
At the discretion of PPC, it is possible to accept certificates, which are issued by
an accredited laboratory, for panels of identical design manufactured by the same
manufacturer.
The following type tests shall be performed in accordance with the provisions of
ΕΝ 62271-200:
These tests only refer to components or apparatus fitted with compact solid
insulation (partitions and shutters included) and shall be carried out in
accordance with ΕΝ 62271-200 and ΕΝ 60270. The maximum allowable partial
discharge level is 50 pC.
Note: Where current transformers or fuses are fitted in panels, such components shall be
short circuited and the test shall be performed with current equal to the panel rated
nominal current.
Moreover, the type I protection panel shall be tested using a 63 Α fuse link and allowing
passage of 50 Α current (30% higher than the maximum nominal current of the 1000 kVA
transformer) with the current transformers short circuited.
6.2.4 Short - time withstand current and peak withstand current tests
25
6.2.8.2 Measurement of leakage currents
This test shall be carried out in accordance with paragraph 6.106 of ΕΝ 62271,
type A (F,L), for 10 kA short circuit for 1 sec, in all panel areas; all the criteria of
paragraph Α – 6 of ANNEX Α of ΕΝ 62271-200 standard shall be met. The place of
the installation of the panel is defined in paragraph 3.1.1.
Panels under testing shall be well secured and subject to mechanical impact using
a pendulum hammer. The pendulum arm shall consist of a steel tube 100cm long,
10mm outer diameter and 1mm wall thickness.
The side subject to impact shall be placed vertically in such a way that impact
occurs vertically to a point located at the swing plane of the pendulum.
The hammer shall weigh 500 gr and shall be left to fall 40cm above the point of
impact. The hammer head shall be round - shaped with a radius of 25mm. Each
side of the panel shall be subject to 3 impacts at its weakest point.
Following the test, the panel enclosure shall not present any deformation that will
eliminate its protective properties or influence the efficient performance of the
panel.
Surface defects i.e. paint scratching, breaking of cooling louvers and the
compression at small extend can be ignored.
After the completion of the test, the protection degree shall not be reduced, no
damages or malfunction of the apparatus and instruments of the panel or
reduction of the dielectric strength of the panel, shall occurred. The above is
verified through respective tests in case of doubt raised during visual
examination.
Not applicable.
26
The Inspector, at his discretion can perform any of the following routine tests on
a random sample of the product in order to verify data in test protocols.
Routine tests shall be carried out to ensure that the product is compliant to the
equipment on which type tests have been performed.
This measurement shall be carried out under the same conditions as with the
respective type test; the measured value shall not exceed 120% of the
corresponding value in type test before the temperature rise test.
These tests refer to components and apparatus fitted with compact, solid
insulation (e.g. insulators for supporting busbars, voltage dividers etc.). They
shall be performed according to ΕΝ 62271-200 and ΕΝ 60270.
The maximum permitted partial discharge level is 50 pC.
Not applicable.
7. NAMEPLATES – MARKING
Each panel shall be fitted with the following nameplates on the front side:
These nameplates shall comply with the provisions of paragraph 5.10 of ΕΝ
62271-200.
27
Contract number and PPC code material
Nominal voltage
Nominal current of busbars and main circuits
Year of manufacture
7.1.3 Nameplate indicating panel group name (identity) and relative position in
the network
Under the nameplate specified in paragraph 7.1.2., a housing shall be provided
for the placement by PPC of group identification nameplate as well as its relative
position in the M.V. network.
This diagram shall automatically indicate the "closed", "open" position of the main
breaking device, of the disconnector and of the earthing switch.
7.3. Markings
7.3.1 Terminations
7.3.2 Busbars
L.V. wiring shall be carried out using insulated, stranded copper conductors, of a
minimum cross section of 2,5 mm2 and they shall be fitted with numbered rings
with an encoded indication, of the circuit they belong, at the ends and throughout
their length, approximately every 30 cm, as described below:
Numbers 1,2,3,0 are used to signify 3 phases and neutral respectively.
28
4 denotes the wiring of the protection current transformer.
5 denotes the wiring of the measurement current transformer.
6 denotes the wiring of the measurement voltage transformer.
Code numbers shall include two digits, e.g.
16: first phase of the measurement voltage transformer
04: neutral of the protection current transformer.
Marking of other wiring components - if applicable - shall be performed at the
Manufacturer's discretion. Such marking shall be designated in the assembly
instruction and maintenance handbooks, as these are provided by the
manufacturer according to the requirements of Annex 3.
8. PACKING
8.3. The manufacturer has the obligation to submit instructions and installation
drawings in Greek, as well as operation, maintenance and safety instructions
according to paragraph 10 of ΕΝ 62271-200. The manufacturer has the obligation
to submit panel installation instructions, indicating panel installation for safe
operation in case an internal electric arc occurs, in accordance with paragraph
10.2 of ΕΝ 62271-200.
In particular, with regard to relays, an operating manual and suitable software on
CD shall be provided to allow an interface of the above mentioned relays to a PC.
One copy of the above mentioned instructions shall be delivered in conjunction
with the accessories of each protection panel. Furthermore, these instructions
shall be submitted for approval of their completeness, alongside with the sample
inspection.
29
9. ANNEXES – DRAWINGS
9.1.1 ANNEX 1
Catalogue of Electronic Processing Data of the T.D.
9.1.2 ANNEX 2
Conditions for participation to the Call for Tenders
9.1.3 ANNEX 3
Data to be submitted with the offer.
9.2.1 DRAWING 1
Legend of diagrams of Drawings 2 and 3
9.2.2 DRAWING 2
Diagrams of groups of panels in radial system
9.2.3 DRAWING 3
Diagrams of groups of panels in ring main system
9.2.4 DRAWING 4
Protection diagram
9.2.5 DRAWING 5
Indicative diagram for the installation of panels
9.2.6 DRAWING 6
Arrangement for the indication of voltage loss in auxiliary circuits
9.2.7 DRAWING 7
Arrangement of the instruments on metering panel
30
ANNEX 1
3. List of tests
3.1. Design tests
Not applicable
Not applicable
Not applicable.
31
ANNEX 2
Manufacturers shall have the following, in order to participate in the Call for
Tenders (unless otherwise specified in the Inquiry):
- Quality Assurance System certified to ISO 9001 or 9002 for the offered
material
- experience in the manufacturing of the said materials which shall have
been installed and operated successfully for a three (3) years period in a
quantity greater than or equal to half the quantity requested according the
Call for Tenders.
To allow assessment of the above, bidder shall submit the following with its offer:
32
ANNEX 3
Supplier shall accompany its offer with all data necessary for the offer’s
evaluation e.g. certificates, drawings, descriptive documentation etc.
These data shall definitely include the following:
1. Detailed drawings indicating the layout of the apparatus inside the panels,
dimensions etc.
2. Drawings similar to Drawing 5 of the present, showing dimensions Α, Β, Ε, F,
Η1, Η2 as well as any other dimension useful to determine the space
required for panel installation and maintenance.
3. The table shown in Annex 3 of the present, duly completed, containing all the
characteristics of the individual parts of the apparatus of the offered panel as
specified in paragraph 5.4. These characteristics shall be confirmed through
respective prospectuses issued by the manufacturer of the respective
apparatus, or through relevant test certificates.
4. Detailed information on panel construction features.
Specified Offered
33
4.11. Description of corrosion protection Para. 5.3.1.20
which shall be used
4.12. Designation of packing method Para. 8
4.13. Description of measures Para. 5.3.1.21
implemented to avoid internal faults
and test results
4.14. Partial discharges Para. 5.3.1.1.
5. The manufacturer shall ultimately report with details any deviations of the
offered material from the provisions of this Specification, which has not been
included in the above paragraphs.
It is mandatory for manufacturers to provide the above information.
It is recommended that the requested information is explicitly stated, avoiding
plain yes/no responses. Offers that don’t include all the above data will not be
taken under consideration.
34
TABLE
1. BUSBARS
2. CIRCUIT BREAKERS
35
a) Load break switches for line “load 400 A
break switch” panels
b) Load break switches for protection 200 A
panels of type I
3.5. Rated breaking currents
3.5.1. Rated mainly active load breaking As per above para.3.4
current
3.5.2. Rated closed loop breaking As per above para.3.4
current
3.5.3. Rated no-load line and cable 10 Α
charging current, minimum
4. DISCONNECTORS
36
5. EARTHING - SHORT CIRCUITING
DEVICE
6. CURRENT TRANSFORMERS
37
7. VOLTAGE TRANSFORMERS
7.1. Type, manufacturing and tests ΕΝ 60044-2
7.2.Rated insulation level According to ΕΝ 60044-
2, table 4, for 24 kV
rated voltage
7.3. Connection V, W
7.4. Transformer ratio 6000-20000/100
15000-20000/100
20000/100
7.5. Rated output power 75 VA each
7.6. Rated voltage factor 1,2 for continuous
operation
7.7. Accuracy class 0,5
7.8. Insulation type Dry insulation
7.9. Requirement in partial discharges 50pC
9. VOLTMETER
9.1. Manufacturing and tests ΕΝ 60051-1,
ΕΝ 60051-2,
ΕΝ 60051-9
9.2. Accuracy class 1,5
9.3. Type Flush – mounted
9.4. Dimensions, minimum (mm) 65 at 1,90 m height
130 for height greater
than 1,90 m
38
9.5. Triple scale 4800-7200 V
12000-17500 V
16000-24000 V
10. TERMINATIONS
39
PUBLIC POWER CORPORATION S.A.
NETWORK DEPARTMENT
Chalkokondyli 22, 10432 ATHENS - Tel.: 210-5292030, Fax: 210-5239301
SUPPLEMENT Νο 1 / 26.02.08
TECHNICAL DESCRIPTION ND - 180/04.09.06
22 Chalkokondyli Str, 104 32 Athens, Τel. : 210 5292030, FAX : 210 5239301,
www.dei.gr
PUBLIC POWER CORPORATION S.A.
NETWORK DEPARTMENT
Chalkokondyli 22, 10432 ATHENS - Tel.: 210-5292030, Fax: 210-5239301
SUPPLEMENT Νο 2 / 04.08.08
TECHNICAL DESCRIPTION ND - 180/04.09.06
At paragraphs 5.1.2. «Type I panel groups - ring main system» and 5.1.4.
«Type II panel groups - ring main system» the following text is added:
« One of the two line «load break switch» panels shall be equipped with a
fault passage indicator (FPI) according to Technical Description ND-
325/28.1.08. For the evaluation of the FPI, the data requested in the
Technical Description ND-325/28.1.08, shall be submitted. »
PUBLIC POWER CORPORATION S.A. Distribution
Network Department
SUPPLEMENT Νο 3 / 19.11.08
TECHNICAL DESCRIPTION ND - 180/04.09.06
b) All the current and voltage T/F shall be tested for their accuracy at a
laboratory specialized in testing metering T/F, which has the following:
ISO 9001 for manufacturing voltage and current T/F.
Calibration certificate, from an independent authority, of the
instruments used for the T/F accuracy tests.
Alternatively the test for the accuracy of the mentioned T/F can be
performed:
At PPC’s laboratories (MS/ND) where all the T/F will be transported at
the manufacture’s expense.
At a laboratory accredited according to EN 17025 at which all the T/F
shall be tested, at the manufacture’s expense.