Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Control and Relay Panel Feb 2021

Download as pdf or txt
Download as pdf or txt
You are on page 1of 53

CONTROL AND RELAY

PANEL

Feb 2021

Engineering Department

WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

Regd. Office: Vidyut Bhawan, Block – DJ, Sector-II, Bidhannagar, Kolkata – 700091.
CIN: U40101WB2007SGC113474; Website: www.wbsetcl.in

WBSETCL : Feb 2021 Page 1 of 53 Control & Relay Panel


TECHNICAL SPECIFICATION FOR CONTROL & RELAY PANEL
FOR 400KV, 220 KV, 132 KV AND 33 KV SYSTEMS

1.00 SCOPE:
1.01 The specification covers design, engineering, manufacture, testing & supply delivery at site of Control
and relay Board and protection relay panels inclusive of internal wiring and with arrangement for
external connection to various Switchyard equipments and Control room building equipments as
necessary. The Contractor has to design the Schematics for protection and Control of all equipments
including monitoring indications, visual and audible alarm, interlocking schemes between different
equipment. Any other requirement which are not specifically covered here but which are necessary
for successful commissioning of the Sub-station are also within the scope of the Contract. The same
shall be indicated by the bidder with their price for WBSETCL's consideration.

1.02 The equipment manufactured should conform to the relevant standards and of highest quality of
engineering design and workmanship. The equipment manufactured shall ensure satisfactory and
reliable performance throughout the service life.

2.00 STANDARDS:
2.01 Unless otherwise specified, all equipment and material shall conform to the latest IS applicable
standards. Equipment complying with other internationally recognised standards will also be
considered, if it ensures performance equivalent or superior to Indian standards. In the event of
supply of equipment conforming to any international/ internationally recognised standards other than
the standard listed below, the salient features of comparison shall be brought out and furnished along
with the bid. One copy of such standard specification in English language shall be enclosed with the
tender.

2.02 The equipment provided shall also comply with the latest revisions of Indian Electricity act and Indian
Electricity rules and any other applicable Statutory provisions, rules and regulations.

2.03 All equipment provided under the specification shall generally conform to the latest issue of the
following:
IEC/Indian Standard No. Title

IS 3231 & IEC-255 Electrical relays for power system protection


IS 1248 & IS 2419 Indicating Instrument
IS 6236 Recorders
IS 722, IS 14697, IS 15959 Energy meters
IEC 679 Static TVM
IEC 337 & 337-1 Control Switches (LV Switching devices for control and auxiliary
circuit)
IS 2705, IS 16227 Current Transformers
IS 3156 Voltage Transformer
IS 4237 General requirement for Switch gear and Control gear for voltage
not exceeding 1 KV.
IS 375 Marking and arrangement for Switchgear Bus bars, main connection
and auxiliary wiring.
IS 8686 Specification for static protective relays

WBSETCL : Feb 2021 Page 2 of 53 Control & Relay Panel


3.00 QUANTITIES:
Quantities of Control, Relay & Protection panels are to be assessed by the bidders from the Schedule
enclosed with this specification/ LOA. However, if any corridor in the switchyard layout is left for
future use in between two proposed bays included in the project, blank panels without any
equipment, relays etc but only with matching mimic are to be supplied.

4.00 TECHNICAL PARTICULARS FOR DESIGN OF CONTROL, RELAY AND PROTECTION PANELS:
4.01 SYSTEM DETAILS:
400KV 220KV 132KV 33KV
a) Nominal System 400KV 220KV 132KV 33KV
Voltage
b) Highest System 420KV 245KV 145KV 36KV
Voltage
c) Number of Phases <-------------------------- Three ------------------------->

d) Frequency <-----------------------50 Hz +/- 3% ------------------->

e) Grounding < -------- Effectively Earthed------------->through E.Tr.

f) Maxm.fault 50KA 40KA 31.5KA -


Current (rms) (rms) (rms)

4.02 AUXILIARY SUPPLY:


D.C. Supply voltage shall be normally fed from Battery charger and battery connected in parallel
which is 220V +/- 10%. In case of failure of the AC supply to battery charger, DC Supply voltage will
be available automatically from Battery. The D.C Supply voltage may vary from -10% to + 10%. The
D.C. system shall be 2 wire with necessary positive earth fault and negative earth fault annunciation
scheme. The ripple content in the D.C. supply from charger will be less than 2%.

AC Auxiliary supply voltage for the C&R panel shall be 230V, 1-phase, 50Hz grounded with +/- 10%
voltage variation.

5.00 INDICATING INSTRUMENT RANGE:


Indicating instruments (Ammeter, Voltmeter, MW meter, MVAR meter) shall have site settable/
programmable CTR and the range of CT ratios shall be in line with final approved drawing of the
respective equipment for the particular project.

Voltmeter Range: -

400kV 0-500kV
220kV 0-250kV
132kV 0-150kV
33kV 0 – 40kV

6.00 PANEL DESCRIPTION, CONSTRUCTION AND FORMATION:


6.01 GENERAL REQUIREMENT:
a) The protection, control and relay board panels for 400KV system shall be duplex/simplex type (as per
the Project LOA) so as to accommodate all the control equipment, breaker relays, meters etc. and the
protective relays and its aux. relays/accessories as necessary for completeness of the
protection/control scheme without overcrowding and cramping.

WBSETCL : Feb 2021 Page 3 of 53 Control & Relay Panel


b) The control and relay board panel for 220KV system and 132KV system shall be duplex/simplex type
(as per the Project LOA) for accommodating all relays and aux. relays for protection of respective
circuit along with control equipment, meters etc. as necessary for completeness of the
protection/control scheme without overcrowding and cramping.
c) The 33KV C&R board panels shall be simplex type for accommodating all the control, protection and
metering equipment properly.
d) Size of individual panel shall be as stated below :
Type Depth (mm) Width (mm) Height (mm)
Duplex 1982 as necessary but limited to 1000 mm 2312 including channel base.
Simplex 610 -do- 2250 including channel base
There shall be a corridor of 762 mm wide and access doors of 1900 mm height with latch at two ends
of duplex panel board for inspection. The door with door frame shall be detachable type so that the
same can be fitted to newly erected panel of similar design if any new C&R panel is added. The
access door for the simplex type panel shall be at the back side and of 1900 mm height.
e) The front and rear parts of duplex type C&R panel shall be detachable and all interconnection
between front and rear panels shall be through terminal connector and preferably underneath the top
cover. The interconnection between the simplex type control and relay panel and duplex type
respective C&R panels where applicable will be made through cables to be laid in the cable trenches
under those panels.
f) The complete panel shall incorporate all necessary instruments, meters, relays, auxiliary relays,
control switches, indicating lamps, mimic, annunciators, audible alarms, horizontal and vertical wiring
trough, wiring supports, interior lighting system, terminal blocks fuses and links etc.

6.02 CONSTRUCTIONAL FEATURES:


a) The control & relay board shall comprise of cubicle type panels placed in juxta position to form a
continuous board for each system voltage. If the panels are required to be aligned in right angular
formation, the tenderer shall be required to arrange dummy/covering plates for the uniform
formulation without any extra price.
b) The tenderer shall ensure that the equipment specified and such unspecified complementary
equipment required for completeness of protection/control scheme be properly accommodated in the
panels without congestion and if necessary to provide panels with larger width. No price increase at a
later date on this account shall be allowed.
c) Panels shall be completely metal enclosed and shall be dust, moisture and vermin proof. The
enclosure shall provide a degree of protection not less that IP-31 in accordance with IS-2147.
d) Panels shall be free standing, floor mounting type and shall comprise structural frames enclosed
completely with specially selected smooth finished, cold rolled sheet steel of thickness not less than
3mm for weight bearing members of panels such as base frame, front sheets and door frames and
not less than 2mm for sides, door, top & bottom portions. There shall be sufficient reinforcement to
provide level surfaces, resistance to vibration and rigidity during transportation and installation.
e) All doors, removable covers and panels shall be gasketed all around with neoprene gaskets.
Ventilating covers, if provided shall have screens and filters. The screens shall be made of either
brass or GI wire mesh.
f) Design, material selection and workmanship shall be such as to result in neat appearance, inside and
outside with no welds, rivets or bolt head apparent front outside, with all exterior surfaces tune and
smooth.
g) Cable entries to the panel shall be from the bottom. The bottom plates of the panel shall be fitted
with removable gland plates and fixed with cable glands. Total area of the gland plate may preferably
be divided into at least two nos. equal size gland plates for easy termination of Control cable in
future, if required. Necessary number of cable glands of sizes to suit external cables to the panels

WBSETCL : Feb 2021 Page 4 of 53 Control & Relay Panel


shall be supplied by the bidder. Cable glands shall be screwed type made of brass and shall be
suitable for PVC armoured cable.
h) Metal seals in the form of metal channels properly drilled shall be furnished by the Contractor along
with anchor bolts and necessary hardware for mounting the panels. Panels shall be mounted on the
other end of the channel.

6.03 MOUNTING:
a) All equipment on and inside the panels shall be mounted and completely wired to the terminal blocks
ready for external connection. The equipment of panel shall be mounted flush.
b) Equipment shall be mounted such that removal and replacement can be accomplished
individually without interrupting of service to adjacent devices and are readily accessible
without use of special tools. Terminal marking shall be clearly visible and of permanent
nature.
c) The contractor shall carry out cut out, mounting and wiring of the bought out items which are to be
mounted in the panel in accordance with the corresponding equipment manufacturer's drawings.
d) The centre line of switches, push buttons and indicating lamps shall be not less than 750mm from the
bottom of the panel. The centre line of relays and meters and recorders shall be not less than 450
mm from the bottom of the panel. However, the same shall be finalized during Detail Engineering.
e) The centre lines of switches, push buttons and indicating lamps shall be matched to give a neat and
uniform appearance. Likewise the top of all meters, relays and recorders etc. shall be in one line.
f) The control switches for circuit breakers and isolators shall be located on the mimic diagram
corresponding to their exact position of the controlled equipment in the single line drawing. The
location of the switches shall be within working height from the floor level for easy and comfortable
operation.
g) No equipment shall be mounted on the doors.
h) All the panels in the control room shall be matched with the other panels of the same C&R board in
respect of dimension, colour and appearance. Control equipment on front side of the panel shall be
similarly placed.
i) All the equipment connections and cabling shall be designed and arranged to minimise the risk of fire
and damage.

6.04 PAINTING:
a) All unfinished surface of the steel panels and frame work shall be sand blasted to remove rust, scale,
foreign adhering material or grease.
b) A suitable rust resisting primer shall be applied on the interior and exterior surfaces of the steel,
which shall be followed by of an under coat suitable to serve as base and binder for the finishing
coat. The finishing coat on the exterior of the panel & on the interior faces shall be as per following
table: -
Sl. No. Painting
1 a) External Colour shade Shade RAL 7032 (Pebble Grey)
b) Internal Colour shade White
Colour c) External Finish Texture Semi Glossy
d) Internal Finish Texture Semi Glossy
e) Base Frame Colour shade Black
2 Type of Painting Powder Coating
3 Thickness of Paint Average of Powder Coating 80-100 microns
4 Phosphating Sheet Steel shall be phosphated in accordance to IS 6005
5 Special Instruction Small quantity of paint shall be supplied for minor touchup work
required at site.

WBSETCL : Feb 2021 Page 5 of 53 Control & Relay Panel


6.05 PANEL INTERNAL WIRING:
a) All wiring shall be carried out with 1100V grade Single core, standard copper conductor wires with
PVC insulation conforming to IS 694 or equivalent International Standard.
b) The minimum size of the stranded copper shall be as follows :
i) All current transformer circuit : 2.5 sq mm per lead.
ii) Voltage transformer circuits : 2.5 sq mm per lead
iii) All other circuits : 1.5 sq mm per lead.
c) The following colour scheme shall be used for the wiring :
Circuit where used Colour of the wire
R - Y - B phase of Red, yellow and blue for
instrument transformer circuit. respective phases.
Neutral connections of the Black
instrument transformer circuit.
Earthing connection Green
AC control wiring circuit for
auxiliary AC supply. Black
D.C. control wiring circuit
using D.C. Battery supply. Grey
d) All wires directly connected to trip circuit breaker or device shall be distinguished by addition of red
colour unlettered ferrule.
e) All internal wiring shall be securely supported, neatly arranged, readily accessible and connected to
equipment terminals and terminal blocks. Wiring gutters & trough shall be used for this purpose. The
position of the PVC carrying troughs and having bunch of wires shall not give any hindrance for fixing
or removing relay casing, switches etc.
f) Interconnection to adjacent panels shall be brought to a separate set of terminal blocks located near
to the slots or holes to be provided at the top of the panel. The terminal blocks for the wires shall be
with isolating links. Arrangements shall be made for easy connections to adjacent panels at site and
wires for this purpose shall be provided and bunched inside the panel.
g) All wiring interconnecting the front cubicles with the near cubicles of duplex type panel over the
access corridor shall be wired in gutters held against the ceiling of the corridor by means of screws
and the interconnection shall be made through suitable terminal connectors securely fixed on the
panel.
h) Longitudinal troughs extending throughout the full length of the panel shall be used for inter panel
wiring. Inter connections to adjacent panels shall be brought out to a separate set of terminal blocks
located near the slot of holes meant for taking the interconnecting wires. All bus wiring for interpanel
connection shall be provided near the top of the panels running throughout the entire length of the
panels.
i) Wiring connected to the space heaters in the cubicles shall have porcelain beaded insulation over a
safe length from the heater terminals.
j) Wire termination shall be made with solder less crimping type and tinned copper lugs which firmly
grip the conductor and insulation, ensuring optimum contact surface and also ease of removal of
termination, if required. Insulated sleeves shall be provided at all the wire terminations. Engraved
core identification plastic ferrules marked to correspond with panel wiring diagram shall be fitted at
both ends of each wire. Ferrules shall fit tightly on the wire and shall not fall off when the wire is
disconnected for any purpose. Termination shall be such that no strand of a conductor shall left loose
or overhanging. Conductor termination shall be secured to the holding nuts/screws, terminal blocks
etc. with washers interposed between the terminals/holding nuts/screw heads. The terminals shall be
so connected that no conductor ferrule code gets masked due to overlay of conductors.
k) All spare contacts of relays shall be wired up to terminal blocks.

WBSETCL : Feb 2021 Page 6 of 53 Control & Relay Panel


6.06 TERMINAL BLOCKS:
a) All internal wiring to be connected to the external equipment shall terminate an terminal blocks,
preferably vertically mounted on the side of each panel. Terminal blocks shall be 1100 V grade and
have 10Amp continuous rating, moulded piece, complete with insulated barriers, stud type terminals,
washers, nuts and locknuts, inserts. The stud, washers, nuts, locknuts, inserts shall be tin plated
Brass/Brass. Terminal block design shall include markings of terminals and the terminals shall be
provided with transparent plastic, slip on/clip on terminal covers. Markings on the terminal strip shall
correspond to wire number and terminal numbers on the wiring diagram.
b) Terminal blocks for current transformer and voltage transformer secondary leads shall be provided
with test links and isolating facilities. Also current transformer secondary leads shall be provided with
short circuiting and earthing facilities of adequate rating.
c) Each terminal block shall be provided with at least 20% spare terminals on each panel and these
spare terminals shall be uniformly distributed on all terminal block.
d) In case of duplex panels, separate set of terminal blocks shall be provided with separate internal
cable entries for the front (control) and rear (relay) sections.
e) Terminal blocks shall be suitable for connecting the following conductors on each side.
i) All C.T. circuits. : Two of 4.0 sq.mm. copper.
ii) All P.T. circuits. : Four of 2.5 sq.mm. copper.
iii) AC/DC Power Supply Circuit : Four of 2.5 sq.mm. copper.
iv) All other circuits. : Four of 1.5 sq.mm. copper.
f) There shall be a minimum clearance of 250 mm between the first row of terminal blocks and the
associated cable gland plate. Also the clearance between two rows of terminal blocks shall be
minimum of 150mm.
g) The number & sizes of the multicore incoming cable will be as per approved scheme. All necessary
cable terminating accessories such as gland plates packing glands, crimp type tinned copper lugs,
supporting clamps and brackets, wiring troughs and gutters etc. for cable shall be included in
contractor's scope of supply.
g) All studs, nuts, screw etc. shall be threaded according to IS:7684 or equivalent International
Standards.

6.07 MIMIC DIAGRAM:


a) Coloured mimic diagram and symbols showing the exact representation of the system shall be
provided in the front of control panels.
b) Mimic diagram shall be made preferably of anodized aluminium or plastic of approved fast colour
material which shall be screwed on to the panel and can be easily cleaned. The mimic bus shall be
2mm thick. The width of the mimic bus shall be 10mm for bus bars and 7mm for other connections.
Indicating lamp, one for each phase for each bus shall be provided on the mimic of Bus coupler panel
of three Bus system or at Transfer bus panel of two bus system to indicate bus charged condition.
c) Colour scheme for mimic diagram.
KV Class Colour Shade Index as per ISS
400KV Dark Violet 796
220 KV Light orange 557
132 KV Signal Red 537
33 KV Brilliant green 221
11 KV Air Craft blue 108
400/230 V Black 309
Earth White -
110 V Canary yellow -

WBSETCL : Feb 2021 Page 7 of 53 Control & Relay Panel


d) LED Position Indicators, Round type, for all earth switches & isolators control switches and
discrepancy type control switch with flash type built-in indicating lamp, for circuit breakers shall be
mounted along the mimic diagram at appropriate location in 400KV, 220 KV and 132 KV duplex type
C&R panels.
In 33KV simplex type C&R panels, LED Position Indicators for the position indication of isolators, earth
switches and ON/OFF indication for such breaker shall be mounted along the mimic diagram at
appropriate location.

6.08 NAME OF IDENTITY PLATES:


a) All instruments, relays and such other similar electrical devices mounted on the control and relay
panel shall be provided with name plates bearing the manufacturer's name, serial identifying number
and the Electrical rating data.
b) 25mm wide plastic plates bearing suitable identification marks shall be fixed under the terminal wiring
at the test blocks, at the fuse blocks and at the cable terminals. Similar plates shall be fixed on the
exterior of the switch board in appropriate places to indicate function of control switches, push button
etc. such as isolator control switch, breaker control switch, DC fail test, accept reset etc. Suitable
identification marks shall be provided for individual casing part of the relays and other equipment.
c) 50mm wide plastic plate bearing suitable circuit description (which will be furnished after order is
placed) etched in 30 mm size letters shall be provided for each panel and mounted on the top of both
outer and inner sides of the front and rear panels. These plates shall be removable type.
d) Each unit of control and relay panel shall be provided with a label located at the bottom on the front
and shall contain the following details:
i) Manufacturer's name
ii) P.O.no. and date
iii) Drg. ref. no. that pertains to the panel.

6.09 CONTROL AND RELAY BOARD PANEL LIGHTING & ACCESSORIES:


a) Each unit of cubicle interior (both control and relay panel) shall be illuminated by LED connected to
230V single phase AC through individual switch for duplex type panel and through Door switch for
Simplex type panel. The illumination of the interior shall be free from hand shadows and shall be
planned to avoid any strain or fatigue to the wireman likely to be caused due to subnormal or non-
uniform illumination. One emergency D.C. light (LED) shall also be provided for each panel with
individual switch with proper identification mark.
b) Corridor of the duplex type control and relay board formation should be illuminated with adequate no.
of LEDs, AC operated, through door operated push button switch provided at both sides.
c) One 15 amps. 3 pin power socket outlets together with plug pins shall be provided at convenient
points in each panel with marking at the bottom for obtaining AC supply wherever required.
d) The above AC auxiliary supply and DC emergency lamp ckt. in each panel shall be HRC fuse and link
protected.

6.10 SPACE HEATERS:


Tubular space heater suitable for connection to the single phase AC supply in each panel (both
control and relay panel in case of duplex type) complete with switches and thermostat located at
convenient position shall be provided at the bottom side of the cubicle to prevent condensation of
moisture. The watt loss per unit surface temperature of the heater shall be low enough to keep
surface temperature well below allowable heat. The wattage of the heater shall be such as to keep
10℃ above average ambient temperature in the rainy season but the temperature shall not under
any circumstances damage the insulation of the wiring of the panel.

WBSETCL : Feb 2021 Page 8 of 53 Control & Relay Panel


6.11 SAFETY EARTHING:
a) All panels shall be provided with an earth bus securely fixed along with the inside base of the panel
extended throughout the length of the C&R board formation. The material and size of the earth bus
bar shall be 25mm x 6mm size copper. Provision shall be made for extending the earth bus bars at a
future date into new adjacent panels to be installed if any. Provision shall be made at the end panels
for connecting the same to the system earth grid mat.
b) Earthing of current free metallic parts or metallic bodies of the equipment provided in the switchboard
shall be done with soft drawn conductor of size not less than 2.5 sq.mm.
c) The neutral point of star connected LV winding of instrument transformers and one corner of the
open delta connected LV side of instrument transformers shall be similarly earthed with the main
earth bar of the switchboard earthing system.

6.12 FUSES AND LINKS:


H.R.C. Cartridge fuse and link of adequate current and voltage rating shall be provided inside the
cubicle in an easily accessible location. The selection of the main and sub circuit fuse ratings shall be
such as to ensure selective clearance of sub circuit faults. Fuses shall have operation indicators for
indicating blown fuse condition. Fuse carriers and bases shall have imprints of rating, voltage and
circuit designation.

7.00 INDICATING LAMPS AND SEMAPHORE:


a) These lamps shall be of LED type and suitable for being operated on S/S D.C. voltage or AC voltage
or P.T. secondary supply as and where applicable. All Lamps shall be interchangeable, panel
mounting type with rear terminal connection and shall afford easy replacement from the front of the
panel. Lamps shall have translucent lamp covers to diffuse lights and coloured Red, green, Amber,
clear white or blue as specified. The lamp cover shall be of screwed type, unbreakable and mounded
from heat resisting material. The indicating lamps with resistors shall withstand 120% of rated
voltage on a continuous basis.
b) No tools shall be required for replacing the bulbs and lenses.
c) The colour scheme of the signal lamps shall be as follows:
Function Colour lens
C.B. spring charged/compressor Blue
healthy indication
C.B. Trip circuit healthy Milky White
Alarm Bus and incoming D.C. fail Amber
indication.
P.T. supply healthy indication Red/Yellow/Blue
(Bus bar healthy indication).
C.B. ON-OFF Indication (33kV & below) Red/Green
d) LED type Semaphores are to be used for status indication of Circuit Breaker and Isolator.

8.00 CONTROL SWITCHES:


a) All control switches shall be of the rotary type provided with escutcheon plates clearly marked to
indicate status of the switch. They shall be semi flush mounted with only the switch front plate and
operating handle projected out. All such control switches shall be provided for remote operation of
isolators and circuit breakers.
b) All Control switches shall be wire connected at the back. The contact mechanism shall be cam
operated. The contacts shall be silver faced and designed for liberal rating of the duty involved. The
contacts shall be provided with dust and vermin proof removable protection cover. The protection

WBSETCL : Feb 2021 Page 9 of 53 Control & Relay Panel


cover shall preferably be of transparent, inflammable material made of moulded dielectric material.
Springs to be provided in the switch shall not be used as current carrying parts. The contacts
provided in the switch shall be suitable for easy assembly/disassembly during replacement of the
contacts. The control switch springs shall be strong to prevent any inadvertent operation due to a
light touch on the handle.
c) Control switches for 400KV, 220KV & 132KV circuit breakers shall be of discrepancy type with built in
pilot lamps and having two maintained contact positions for "ON" and "OFF" positions and two
momentary contact positions for "ON" and "OFF" impulse. The built-in pilot lamp shall give a steady
light when the position of the control switch corresponds to the position of the associated circuit
breaker. A flickering light shall be given by the same lamp when due to hand operation or due to
automatic tripping of the circuit breaker the position of the control switch does not coincide with that
of the corresponding circuit breaker. The arrangement to provide the flickering voltage for the above
purpose shall be made by the contractor. In order to avoid continuous burning of the aforesaid built-
in lamps associated with the control switches, the said lamp shall be connected through a switch. The
circuit should be such that irrespective of the position of the aforesaid switch winking of the lamp
shall not be affected by change in respective control switch position. The winking of the control switch
pilot lamp shall be followed by an alarm annunciation after a preset time adjustable between 0-10
secs. Switches complete with accessories for the above function shall be supplied.
d) Control switches for 33KV circuit breakers, 400KV, 220KV isolators, 132KV isolators shall be with
pistol grip type operating handle having "ON & OFF" monetary operating position and an automatic
return to normal neutral position on release from operated positions.
e) At bay level, Bay Control IEDs (if considered in respective LOA) shall provide all bay level functions
regarding control and monitoring, inputs for status indication and outputs for commands. Bay Control
IEDs shall not depend on any Numerical Protection IED or other equipment for the above functions.
f) Clear control priorities shall prevent operation of a single switch at the same time from more than
one of the various control levels, i.e. remote control centre, station HMI, bay level or apparatus level.
The priority shall always be on the lowest enabled control level.

9.00 SELECTOR SWITCHES AND CHANGE OVER SWITCHES:


a) Instrument selector switches shall be provided for indicating instruments while change over switches
shall be provided for selective operation of controls such as auto/ non auto reclose, trip circuit
transfer from main breaker to transfer breaker. Protection selector switches are to be provided in the
Bus transfer bay and shall be used for adopting the bus transfer bay protection during Bay transfer
condition, when line side C.T. operated protection of any bay develops any defect. All these switches
shall be stay put type.
b) Voltmeter selector switch shall be suitable for reading all line to line and line to neutral voltage for
effectively earthed system. This selector switch shall be of the rotary oval head or knob type.
c) Trip circuit transfer switch shall be of 3-position Normal-Inter-Transfer. Operating handle shall be
pistol grip, lockable at Normal position and key trapped at transfer position having one common key
for all 400KV, 220KV, 132KV and 33KV panels respectively for a particular Sub-station.
d) Protection selector in Bus Transfer bay shall be lockable type, two/three position depending upon
scheme requirement.
e) One four position selector switch for setting group selection in respect of distance relay in Bus
Transfer panel shall be provided.
f) One three position selector switch for setting group selection in respect of numerical over current &
earth fault relay in Bus Transfer panel shall be provided.
g) One five position Selector Switch for Earthing Transformer selection in each 33KV side transformer
C&R panel shall be provided.

WBSETCL : Feb 2021 Page 10 of 53 Control & Relay Panel


10.00 SYNCHRONISING SWITCH:
a) Synchronising switch with lock feature two positions, "ON & OFF" shall be provided on all control
panels except the 132/33KV Transformer panel and 33KV C&R panels. The switch shall be semi flush
mounting type.
b) The switch shall be wired back connected. It's operation in the "ON” position shall connect the
incoming and running bus potentials to the respective synchronising instrument and relay mounted in
a trolley, through a synchronising socket having sufficient nos. of ways. The wiring between the
synchronising switch, socket and the main breaker control switch shall be such that when the main
breaker control switch is operated to close position, the breaker shall not receive a close command
unless the synchronising switch is put to the 'ON' position and receives a synchronising command. If
the synchronising trolley is not within the scope of supply for a particular sub-station, the terminal of
the synchronising socket to be shorted through a plug to be provided to cover the socket.

11.00 PUSH BUTTON SWITCHES:


a) Push button switches, provided where required, shall be of the monetary contact type wired back
connected. They shall be semi flush mounted. They shall be provided with integral inscription plates
engraved with their functions.
b) All push buttons shall be with a set of NO/NC contacts as required to fulfill the scheme requirement.
The contact faces shall be silver plated and shall able to make/break and carry the rated current
appropriate to the duty of the desired function.

12.00 INDICATING INSTRUMENTS, RECORDERS & TRANSDUCERS:


All instruments, meters, recorders and transducers shall be enclosed in dust proof, moisture resistant,
black finished cases and shall be suitable for tropical use. All megawatt, megavar, Bus voltage and
frequency indicating instruments shall be provided with individual transducers and these shall be
calibrated along with transducers to read directly the primary quantities. They shall be accurately
adjusted and calibrated at works and shall have means of calibration check and adjustment at site.
The supplier shall submit calibration certificates at the time of delivery. However no separate
transducers are envisaged for digital bus voltmeters and digital frequency meters and the indicating
meters provided in the synchronising equipment. Necessary complete wiring arrangement for
Intelligent Electronic Meters along with supply of TTB & De-linked type Terminal Block shall be within
the scope of supply of the bidders.
For greenfield SAS substations without any control panel, for each bay one no. MFM is to be provided
in series with BCU Metering circuit at Relay panel.

12.01 INDICATING INSTRUMENTS:


a) Unless otherwise specified, all electrical indicating instruments shall be of digital type suitable for flush
mounting.
b) Instruments shall have 4-digit display; display height being not less than 25 mm
c) Instrument shall confirm to relevant IS and shall have an accuracy class of 0.5 or better. Watt and
Var meters shall have an indication of (+) and (-) to indicate EXPORT and IMPORT respectively.
d) Digital voltage and frequency meters shall be of class: 0.5 and shall have digital display of 5 and 4
digits respectively, with display size, not less than 25mm (height).
e) All indicating instruments shall preferably of size 72mm X 144mm.

12.02 TRANSDUCERS:
a) Transducers (for use with Indicating Instruments and Telemetry/Data Communication application)
shall in general conform to IEC:688-1
b) The transducers shall be suitable for measurement of active power and reactive power in three phase

WBSETCL : Feb 2021 Page 11 of 53 Control & Relay Panel


four wire unbalanced system.
c) The input to the transducers will be from sub-station current & potential transformers. The output
shall be in milli ampere D.C. proportional to the input & it shall be possible to feed the output current
directly to the telemetry terminal or indicating instruments.
d) The transducer characteristic shall be linear throughout the measuring range.
e) The transducer output shall be load independent.
f) The input & output of the transducer shall be galvanically isolated.
g) Each transducer shall be housed in a separate compact case and have suitable terminals for inputs &
outputs.
h) The transducers shall be suitably protected against transient high peaks of voltage & current.
i) The transducer shall withstand indefinitely without damage and work satisfactorily at 120% of the
rated voltage and 120% of the rated input current as applicable.
j) The active & reactive power transducer shall have dual output of 4-20mA.
k) The response time of the transducers shall be less than 1 second.
l) The accuracy class of transducers shall be 0.5 or better for watt/VAR transducer.
m) The transducers shall have a low AC ripple on output less than 1%.
n) The transducers shall be suitable for load resistance of 1000-1500Ω

13.00 TEST BLOCK:


Switch Board type, back connected, test blocks with contacts shall be provided with links or other
devices for shorting terminals of CT leads before interrupting the normal circuit for injection from
external source or for inserting testing instruments in the circuit without causing open circuit of the
CT. The potential testing studs shall preferably be housed in block molding insulation and partition
shall be provided to prevent accidental short circuit across the studs. Test blocks for meters, relays
shall be placed in front and rear panel respectively.

14.00 DC, AC AUXILIARY SUPPLY AND V.T. SECONDARY SUPPLY DISTRIBUTION SCHEME:
14.01 DC SYSTEM:
DC distribution in CRP panels shall be designed with the consideration that two sets of
batteries (220V), their respective chargers and DC boards shall be used for DC supply for
all new substations.

14.02 INCOMING DC SCHEME:


For CRP panels of different voltage class, the Incoming DC scheme shall be as mentioned below:
400kV Two DC incomers (220V) for
panels of each bay, as DC supply
- 1 and DC supply - 2.
220kV Two DC incomers (220V) for
panels of each bay, as DC supply
- 1 and DC supply - 2.
132kV Only two DC incomers (220V) as D.C. incoming buses of
DC supply - 1 and DC supply - 2 132KV Panel shall run
for the entire panel board. continuously in the panel
One suitably rated HRC fuse unit board. Individual panel D.C.
both at +ve and -ve side shall be supply shall be teed off in
provided for each D.C. incomer each panel from the two
in Bus Transfer (2 bus system)/ D.C. buses.
Bus Coupler (GIS or 3 bus AIS
system) panel.
33kV Only two DC incomers (220V) as D.C. incoming bus of 33KV
DC supply - 1 and DC supply – 2 CR Panel shall run

WBSETCL : Feb 2021 Page 12 of 53 Control & Relay Panel


for the entire panel board. continuously in the panel
One suitably rated HRC fuse unit board. Individual panel D.C.
both at +ve and -ve side shall be supply shall be teed off in
provided for each D.C. incomer each panel from the above
in Bus Transfer/ Bus Section (2 two D.C. buses.
bus system)/ Bus Coupler (3 bus
system) panel.
Necessary arrangement for Supervision of the both the incoming DC supplies shall be made in each
panel.

14.03 DC CIRCUIT IN 400kV, 220kV AND 132kV PANELS:


a) Following circuits for each bay shall be connected, as tabulated below:
Sr. Circuit Connection Duplex panel Simplex panel
No.
1. Power supply circuit of through separate Auto Changeover DC
individual IED suitable HRC fuses
2. LBB scheme (only in 220kV & through suitable Auto Changeover DC
132kV Bus Transfer/ Bus HRC fuses
Coupler panel, as applicable)
3. VT Selection circuit through MCB Auto Changeover DC
4. CB Aux. Relay circuit and CT through MCB Auto Changeover DC
Supervision circuit (only for SF6
CTs)
5. Transformer Supervision circuit through MCB Auto Changeover DC
6. GIS LCC Supervision circuit through suitable Auto Changeover DC
HRC fuses
7. D.C. emergency lamp circuit through suitable DC Supply – 1 Auto Changeover
HRC fuse DC
8. Metering circuit through suitable DC Supply – 2 Auto Changeover
HRC fuses DC
9. Isolator control circuit through MCB DC Supply – 1 N.A.
10. Synchronising circuit through suitable DC Supply – 1 N.A.
HRC fuses
11. Indication circuit through suitable DC Supply – 2 N.A.
HRC fuses
b) The above circuits, which are connected to Auto Changeover DC, will be automatically fed from
healthy DC Supply, in the event of failure of the Selected DC Supply. Necessary additional high speed
electrically set – reset type relays having high current carrying capacity and inductive breaking
capacity shall be considered to develop this auto Changeover scheme.
c) The above circuits, which are connected to DC supply – 1, will be fed from DC Supply – 2 in the event
of failure of DC Supply – 1 and vice versa. Changeover shall be Manual (by using two-position
Selector switch, DC - 1 / DC – 2)
d) DC supply – 1 & 2, drawn to each C&R panel, shall be divided into the following sub circuits through
suitable HRC Fuses.
i) CB Closing circuit
ii) CB Trip coil – 1 shall be fed from DC supply – 1.
iii) CB Trip coil – 2 shall be fed from DC supply – 2.
e) For 400kV system, DC Supply - 1 & 2 to Protection panel of a bay shall be fed from Relay panel of
that bay directly.
f) LBB protection scheme DC shall be formed in 220kV & 132kV Bus Transfer/ Bus Coupler panel, as
applicable, and shall run through all panels as bus wires. In individual panels this supply will feed the
LBB scheme through isolating links.

WBSETCL : Feb 2021 Page 13 of 53 Control & Relay Panel


g) In case of GIS substations, from Control/ Relay panel the DC supply - 1 & 2 will be teed off from the
resp. incomer D.C. bus to LCC panel. For remote operation of GIS equipment the operational DC will
generate from LCC through LOCAL/ REMOTE switch of LCC. Necessary separate relays shall be
considered for Supervision of both LCC DC Supply - 1 & 2.

14.04 D.C. CIRCUIT IN 33 KV C&R PANEL/ INTEGRATED SWITCHGEAR:


Following circuits for each bay shall be connected to Changeover DC supply:
CB Closing circuit through suitable HRC fuses
CB Trip coil – 1 through suitable HRC fuses
CB Trip coil – 2 through suitable HRC fuses
Power supply circuit of individual IED through suitable HRC fuses
Isolator control circuit through MCB
Transformer Supervision circuit through MCB
CB Aux. Relay circuit through MCB
Synchronising circuit through suitable HRC fuses
D.C. emergency lamp circuit, separately for through suitable HRC fuses
Control and Relay panel
Metering circuit through suitable HRC fuses
Indication circuit through suitable HRC fuses
Changeover shall be Manual (by using two-position Selector switch, DC - I / DC - II)

14.05 ANNUNCIATION D.C. CIRCUIT:


There shall be one DC incomer (220V) from DCDB to Bus Transfer (2 bus system)/ Bus Coupler (3
bus system) panel through 16A HRC Fuse (both +ve and –ve) as Annunciation DC supply. Necessary
arrangement for supervision of the incoming Annunciation DC Supply shall be made in Bus Transfer
(2 bus system)/ Bus Coupler (3 bus system) panel. D.C. annunciation bus shall be teed off from the
Bus Transfer (2 bus system)/ Bus Coupler (3 bus system) panel of each system for annunciation
system and the same shall run continuously through the entire C&R board for facia annunciation
system in respective panels.

14.06 AC CIRCUIT:
a) 230V, single phase 50Hz AC auxiliary supply to the control, relay and protection panel board of each
system voltage of 400KV, 220KV, 132KV and 33KV will be fed from AC distribution board through
separate 32Amp. switch fuse units provided there.
b) The supply shall be provided in Bus coupler/ Bus Transfer/ Bus Section panel for each voltage class.
One 16Amp rated HRC fuse unit shall be provided for the AC incomer. AC incoming bus shall run
continuously in each voltage class panel board.
c) Individual panel AC supply shall be teed off in each panel from the AC bus. A set of fuse and link
rated for 10Amps. for 3 pin plug circuit, cubicle lamp circuit, space heater circuit shall also be
provided in each control, relay and protection panel.
d) Door operated corridor illumination lamp circuit of duplex type panel shall be arranged from the
above incoming AC bus through suitably rated fuse and link.
e) AC circuit for incoming DC fail and Annunciation DC fail alarm scheme shall be provided in Bus
coupler/ Bus Transfer/ Bus Section panel for each voltage class. The above circuit shall be teed off
from the above respective panel AC bus through suitably rated fuse and link.
f) One supervision relay for incoming AC fail with test P.B. and reverse flag indication shall be provided
for monitoring of AC supply healthiness through D.C. operated facia annunciation in Bus coupler/ Bus
Transfer/ Bus Section panel for each voltage class.

WBSETCL : Feb 2021 Page 14 of 53 Control & Relay Panel


14.07 V.T.SECONDARY SUPPLY DISTRIBUTION SCHEME:
PT kiosk at switchyard may be considered with sufficient terminals, fuses, links etc for protection PT
secondary supply and for metering PT secondary supply to bus coupler panel through individual cable
for all voltage class in a substation.
a) The bus coupler panel shall receive protection VT secondary volts through fuses and links provided in
the respective VT kiosk. The protection VT supply shall run throughout entire board for each panel
through VT supply selection scheme.
b) The Bus Coupler panel shall also receive Metering VT Secondary volts by at least 25Sqmm Copper/
equivalent Aluminum per phase/neutral through fuses and links provided in the respective VT kiosk.
The Metering VT supply shall also run throughout entire board for each panel through VT supply
selection scheme.
c) VT secondary volts from all Protection cores and Metering core shall be first terminated to de-linked
type TBs in each bay panel before wiring to the VT selection scheme.
d) Selected VT secondary supply to the protective relays of each panel shall be fed through individual
fuses in individual phases and link in neutral in each panel. Necessary arrangement for supervision of
VT secondary supply shall be provided in numeric relay.
e) Selected VT secondary supply to metering and indicating instruments of each panel shall be fed
through MCB. Proper arrangement of supervision through MCB shall also be provided.
f) For 400KV/ 220KV system three sets VT selection relays shall be provided. In 132KV C&R panel,
where more than one set of 132KV PT is available or not, necessary 132KV PT selection scheme shall
be adopted and made ready for future use. Where more than one set of 33KV bus PT is available,
necessary 33KV PT selection scheme shall be adopted through switch at 33KV C&R panel.

15.00 ANNUNCIATION SYSTEM:

15.01 INCOMING DC FAIL AND ANNUNCIATION BUS DC FAIL ALARM SCHEME:

Each voltage class system shall have alarm scheme, as follows: -


i) Incoming DC-1/ DC-2 supervision shall be provided in each panel.
ii) In Bus bar protection panel, DC fail supervision shall be provided.
iii) Audible AC alarm shall be provided for Incoming DC/ Annunciation DC Fail.
iv) The "Annunciation Bus D.C. alarm scheme" shall be common to the entire C&R board and
operated from 230V single phase AC auxiliary supply for audible as well as visual alarm
through lamp and bell arrangement. This will be provided at the Bus Coupler/ Bus Transfer/
Bus Section panel.
The scheme shall comprise of D.C. supervision relays with test push buttons for Annunciation
bus DC system, AC operated alarm accept relays, indication lamp, AC operated hooter and
push button for cancellation of audible alarm, as necessary.
v) Annunciation DC and AC shall be supervised by the Annunciator through auxiliary AC supply /
DC supply resp. of the Annunciator in each panel.

15.02 OTHER TRIP AND NON-TRIP ALARM SCHEME:

a) Facia annunciation system shall be provided in each control panel by means of visual and audible
alarm to draw attention of the operator to the abnormal operation or operation of the protective
devices. The annunciation shall be divided into the following categories:
i) Trip annunciation
ii) Non Trip annunciation
The annunciator shall be suitable for operation with the sub-station AC/ DC voltage and potential free
initiation contact is to be provided. Annunciator must have communication port, suitable for SCADA/
SAS operation, and this connection is to be established during commissioning.

WBSETCL : Feb 2021 Page 15 of 53 Control & Relay Panel


b) The visual facia widow shall be flush mounted at a convenient position near top row of the control
panel and necessary switching relays for the same shall be mounted inside the panel or at the relay
side of the panel.
c) The annunciator facia shall be provided with translucent glass or plastic cover plates of white colour
with inscription in black colour. The size of facia window shall be 70mm x 35mm in general and the
size of the lettering shall not less than 5 mm. Alarm inscription shall be engraved not more than three
line of in each facia window and the same shall be prominently visible when facia light is ON. The
cover plates of the facia window shall be easily removable to facilitate replacement of lamp when
required. Annunciator of each bay must have minimum 5-6nos. spare windows available.
d) The transparency of cover and wattage of the lamp provided in the facia window shall be adequate to
ensure clear visibility of the inscription from the location of the operator's table in the control room
having high illumination intensity. Each facia window shall be provided with two lamps to ensure
safety against lamp failure. Long life lamp shall be used having resistor of adequate rating in series.
e) Annunciator should have in-built Accept, Reset and lamp Test push buttons for acknowledgment of
alarm, reset of visual indication and for checking perfectness of the lamps shall be provided below the
facia window in each panel. These push buttons shall be common for both trip and warning
annunciation. The sequence of operation of the annunciation shall be as follows:
Alarm Fault Visual Audible
Condition contact Annunciation Annunciation
Normal Open OFF OFF
Abnormal Close Flashing ON

Accept push button Close Steady ON OFF


is pressed. Open Steady ON OFF

Reset push button Close ON OFF


is pressed. Open OFF OFF

Lamp test push Open Steady ON OFF


button is pressed.
f) In case static annunciation system is used, care should be taken that no spurious alarm condition
arises due to external influences on the annunciator wiring and switching disturbances from the
neighboring circuits within the panels. The static relay shall be suitable for operation within a
temperature range from 0°C to 55°C.
g) The annunciation scheme should be such that momentary closing of any fault contacts shall also
cause operation of annunciation system as above.
h) The annunciation facia window shall be programmable between Trip annunciation and Non-trip
annunciation using DIP switches at site easily.

15.02. TRIP ANNUNCIATION:


01
Trip annunciation shall be used to draw attention of the operator when the circuit breaker is tripped
automatically through relay. One hooter is to be provided in each panel for audible annunciation.
Visual annunciation shall be provided by flickering of a facia window.

15.02. NON-TRIP ANNUNCIATION:


02
Non-Trip annunciation shall be used to draw attention of the operator to abnormal operating
condition of certain equipment for immediate action to avoid tripping of circuit breaker. One bell with

WBSETCL : Feb 2021 Page 16 of 53 Control & Relay Panel


different tone is to be provided in each panel for audible annunciation. Visual annunciation shall be
provided by flickering of a facia window.

16.00 RELAY:

GENERAL REQUIREMENT:
The main numerical protective relays shall be of Panel manufacturer’s own make or their principal
company’s make.

However, panel manufacturer, who are authorized by relay manufacturer to supply their
relay, may also be considered for supply of C&R panel. This acceptance is subject to strict
compliance to the following conditions: -
i) The panel manufacturer must be enlisted in WBSETCL maker’s list as on date of
NIT and meet all the Qualification Requirement to be eligible.
ii) The panel manufacturer should provide document/ certificate of guarantee from
the relay manufacturer.
Live demonstration of any offered relay has to be arranged by the Party at the laboratory of Central
Testing Department of WBSETCL prior to approval, if felt necessary by WBSETCL. The turn-key bidder
shall be required to make necessary arrangement without any extra price.

16.01 All shall conform to the requirement of IS: 3231 / IEC 255 and shall be suitable for operation within a
temperature range 0ºC to 55ºC and 50% to 95% relative humidity. Relays shall be suitable for flush/
semi flush mounting on the panel with connections from the rear, protected with dust tight cases for
tropical use and with transparent cover removable from the front.
16.02 All protective relays shall be in draw out case or plug-in/modular cases with proper built in testing
facilities. If testing devices are not incorporated in the relay itself separate test block and switches
shall be provided. The adjusting devices shall be accessible with the relay mounted on the panel
board. Flag type operating indicators and flag indicator reset devices shall be provided which shall be
suitable for operation from the front of the relay case without opening the cover.
16.03 All A.C. relays shall be suitable for operation at 50Hz.The current coils shall be rated for a continuous
current of 1 amp and the voltage coil for 110V normal. The contacts of the relays shall be properly
designed to prevent or minimise damage due to arcs which have to be broken successfully against
220 +/- 10% volt DC. When open the contacts shall withstand a voltage of 115% of the normal
circuit voltage. The relays shall be designed for satisfactory operation between 70% and 110% of
rated D.C. voltage of the sub-station. The voltage operated relays shall have adequate thermal
capacity for continuous operation.
16.04 Timers shall be of static type. Pneumatic timers are not acceptable.
16.05 The sub-stations may be required to run without air-conditioning plant. Therefore, the static relays
shall be designed for operating satisfactorily under the climatic conditions of ambient temperature and
relative humidity variation from 0ºC to 55ºC and 50% to 95% respectively. The static relays should
be capable to withstand the test voltages as stated in the relevant Indian standard or equivalent.
Stringent measures including shielding of long internal wiring should be taken to make the relays
insensitive to the voltage spikes. Insulation barriers shall be provided to ensure that transients
present in CT & VT connection due to extraneous sources do not cause damage to static circuits.
16.06 DC/DC converter shall be provided in the solid state protective relays wherever necessary in order to
provide a stable auxiliary supply for relay operation. Provision of D.C. Cells in the protective relays as
reliable standby power supply will however not be acceptable. The DC/DC converter shall have power
supply failure annunciation contact.

WBSETCL : Feb 2021 Page 17 of 53 Control & Relay Panel


16.07
a) The solid state relays shall be stable and suitably protected against transient/ induced over voltages
and noise signals. The bidder shall state clearly in the list of special requirement, if any, for D.C. input
arrangement or cabling considered necessary for satisfactory operation of proposed solid state relays.
b) All the Numerical Relays should have setting parameter access restriction. All the numerical relay
should have provision for setting all the features available in the relay and viewing those setting as
well as different other parameters through both built in display unit as well as through PC. The supply
of relay should be inclusive of necessary software and hardware for interfacing with a PC, to be
supplied by the bidder. The bidder/manufacturer has to make arrangement for communication with
all relays, along with supply of cables, connectors, communication port, converters etc. as necessary
for downloading the storage data for all microprocessor/ numeric relays, disturbance recorder and
fault locator etc. through a centralized PC. The necessary PC, window based Licensed software along
with operating system software and all the necessary hardware for establishing the Network in latest
IEC 61850, Ed - 2 platform to be considered in the scope of supply by the bidder.

The relays shall have the provision for Man to Machine Communication for local and remote control
and monitoring complete with software, ports and other hardware e.g. required numbers PC hook up
cable for direct communication, one for each type of relay.

Bidder shall arrange for such local man to machine communication facility for all the numerical relays
inclusive of all the necessary accessories as mentioned above complete through Local Area
Networking System for each 400KV, 220KV & 132KV substation wherever mentioned in the schedule.

For existing and new substations, provision is to be made for connectivity with the existing and/ or
future numerical relays through PC by providing external comport multiplier (e.g. Rocket port/Serial
sharer etc.).

The electronic devices on bay shall be connected to the communication infrastructure for data sharing
and meet the real-time communication requirements. The communication shall be made in fault
tolerant ring in redundant mode INCLUDING the links between individual bay IEDs to switch, such
that failure of one set of fiber shall not affect the normal operation. However failure of fiber shall be
indicated through alarm/ annunciation. Each fiber optic cable shall have four spare fibers.

The data exchange between the electronic devices on bay and station level shall be realized using
fiber optic cables, thereby guaranteeing disturbance free communication. The fiber optic cables shall
be run in suitable, preferably GI, conduit pipes. Data exchange is to be realized using latest IEC
61850, Ed - 2 protocol with a external managed switched optical Ethernet communication
infrastructure in decentralized ring configuration.

All the protective relays shall be numerical type and communication protocol shall be latest IEC
61850, Ed - 2 compatible with the following features:
i) All Numerical Protection IEDs as well as BCU shall be IEC 61850, Edition – 2 compliant.
ii) Peer-to-peer communication using GOOSE messages (latest IEC61850, Ed - 2) for
interlocking.
iii) Interoperability with third party IEC 61850, Ed - 2 (latest version) compliant devices.
iv) Generate XML file for integration/ engineering with vendor independent SCADA systems.
v) Should be directly connected to the inter bay bus on IEC 61850, Ed - 2 (latest version)
without the use of any gateways. Connections of bay protection IEDs to the IEC 61850, Ed - 2
bus (latest version) through the bay control units are not acceptable.
vi) All Numerical relays must be PRP compliant for SAS.

WBSETCL : Feb 2021 Page 18 of 53 Control & Relay Panel


vii) Numeric relays with non-programmable Inputs and non-programmable outputs are not
acceptable.
All the numerical relays shall have one front port for direct access with proprietary protocol, rear ports
with latest IEC 61850, Ed - 2 protocol (One no. mandatory FO port and another FO/RJ 45 port). The
main Numerical Protective Relays shall synchronise the internal clock with GPS based time
synchronising equipment directly through,
i) IRIG-B or
ii) SNTP protocol or
iii) Minute/Second pulse through Binary I/Ps
All numerical relays shall be provided with ‘Relay Failure Annunciation Contact’. Individual window is
to be assigned in annunciator for each Numerical relay.
c) One set of Special Tools and Tackles required for maintenance purpose, including but not limited to
the following items, must be supplied for each substation:
i) Test Jacks
ii) Wire Lugs
iii) Crimper
iv) Module Extractor
v) Wire Extractor
vi) Special type of Screw Driver
d) List of software for local parameterisation, settings, logic configuration, data retrieval, disturbance
evaluation, downloading of storage data and no. of license (minim. 3 for new 400KV & 220KV S/Stn,
& one each for other substations involved) shall be supplied by the bidder:
i) Graphical configuration tool having all the functions used in the relay and sufficient numbers
different logic gates in the inbuilt library (software)
ii) Basic application licensed software for setting change, service value monitoring etc., one each
for every substation where numerical relays shall have to be provided.
iii) Software for disturbance record & event logger collection and evaluation of those records in
COM TRADE format.
iv) Latest IEC 61850, Ed - 2 software for inter-operability, Goose message etc.
v) Any additional software if required for remote communication and for other facilities available
in the relay.
All the above tools/software should be WINDOWS 7/ WINDOWS 10 operating system compatible.
e) Interconnection architecture among the relays showing details identification of all intermediate
hardware including interfacing port of the monitoring PC and other hardware
f) Connectivity architecture of Disturbance recorder evaluation station of all numerical relays like
numerical distance relay, numerical differential relay etc. with time synchronisation unit.
g) Interface architecture involving multiple nos. of numerical relays of respective make, with the
monitoring PC.
h) Interface architecture of the above network with existing/future network of other make numerical
relays with monitoring PC, wherever applicable.
i) The bidder has to furnish the certificate for latest IEC 61850, Edition - 2 Compliance from
KEMA/CPRI, type test certificate from any Govt. recognized Test House and performance certificate
from Power Utilities in India.
j) Local area networking system: -
i) Shall be PRP and IEC 61850, Edition – 2 compliant.
ii) PC configuration for both local and remote end communication:
 CPU - i5 latest (3GHz Min)
 RAM – 4GB Min

WBSETCL : Feb 2021 Page 19 of 53 Control & Relay Panel


 HDD 500GB, 7200 rpm
 Internal DVD combo
 17” TFT monitor, Key board & optical mouse
 Minimum 2 nos COMPORT(RS232C)
 8 Nos. USB Port (2 Front & 6 Rear)
 Requisite quantity of interconnecting cable
 IRIGB port if required for time synchronization with GPS clock for date and time
stamping.
 Operating system – Windows 7/ WINDOWS 10
 Required software including but not limited to licensed latest version of latest Anti-Virus
software, MS Office etc.
iii) External comport (RS232C) multiplier to be interfaced with the comport of PC, having
minimum 8 nos interfacing port.
iv) UPS - ON LINE UPS for individual PC with minimum 15 min. battery backup.
v) Printer – Colour inkjet suitable for A3 size paper.
v) Required furniture for table top installation of PC along with Printer and two nos suitable
revolving chair
vi) Other particulars, if any.

17.01 BAY CONTROL UNIT/ BAY CONTROL & PROTECTION UNIT


[The IED should be latest IEC61850, Ed - 2 compliant having rear port compatible to
latest IEC 61850, Ed - 2 protocol.]
a) BCU shall be provided for supervision and control of each 132kV and above voltage class bay and
BCU/ BCPU (as per the Project LOA) shall be provided for supervision and control of 66kV and below
voltage class bay (a bay comprises of one circuit breaker and associated disconnector, earth switches
and instrument transformer). In such case, BCPU is considered for a bay, BCPU for each bay must
have six nos. Analog Current Input channels, (three nos. each for Metering core and Protection core).
b) Communication Port: BCU shall be PRP compliant for SAS with latest 61850, Ed - 2 protocol including
one front port for direct access with proprietary protocol.
c) Inputs: Sufficient opto-isolated inputs. Contact bouncing in Digital inputs shall not be assumed as
change of state.
d) Outputs: Sufficient potential free outputs.
e) All inputs and outputs must be user programmable. The bay control units shall be equipped with
sufficient number of programmable I/O modules for interfacing with the process inputs and outputs.
Extension should be possible with additional I/Os via fibre-optic communication and process bus.
f) The BCU shall meet the requirements for withstanding electromagnetic interference as per relevant
standard. Failure of any single component within the equipment shall neither cause unwanted
operation nor lead to a complete system breakdown.
g) The IEDs should be directly connected to the switchgear without any need for additional interposition
or transducers.
h) A graphic user interface (GUI) display shall be provided in each bay control unit. The GUI display in
the BCU shall display the status of the bay devices (breakers, isolators, switches etc) in real time. All
alarms related to the respective bay shall be displayed in the BCU through its LED’s or in its GUI
display as an alarm list/scroll.
i) Analog inputs for voltage and current measurements shall be connected directly to the voltage
transformers and the current transformers without intermediate transducers. The values of active
power (MW), reactive power (MVAR), Frequency (Hz) and the RMS values for Voltage and Current
shall be calculated.
j) Each bay control IED shall be independent from each other and its functioning shall not be affected
by any fault occurring in any of the other bay control units of the station. Bay Control IEDs shall not

WBSETCL : Feb 2021 Page 20 of 53 Control & Relay Panel


depend on any Numerical Protection IED or other equipment to perform control, protection, and
monitoring functions and for acquisition of any bay equipment associated data.
k) Connections from BCU to switchgear should not be terminated directly on I/O boards but should be
routed through Terminal Boards (TB). The bay unit shall acquire and process all data for the bay
(Equipment status, fault indications, measured values, alarms etc.) and transmit these to the other
devices in sub-station automation system.
l) The protection functions are independent of bay control function. The protection shall be provided by
separate protection IEDs (numerical relays) and other protection devices, guided by the respective
section of Relay & Protection.
m) Self-monitoring of components, modules and communication shall be incorporated to increase the
availability and the reliability of the equipment and minimize maintenance.
n) Functions for BCU:
i) Control mode selection
ii) Select-before-execute principle
iii) Command supervision
iv) Interlocking and blocking
v) Double command
vi) Synchro-check, voltage selection
(BCU of Bus Coupler bay must have six numbers Analog voltage Input Channels)
vii) Run Time Command cancellation
viii) Transformer Tap Changer Control (Raise & Lower of tap) (for Power Transformer bays)
ix) Operation counters for circuit breakers
x) Breaker position indication per phase
xi) Alarm annunciation
xii) Measurement display of Vrms, Irms, HZ, W, Var for each phase and for 3phase
xiii) Local HMI (local guided, emergency mode) with Graphic display
xiv) Interface to the station HMI.
xv) Data storage for at least 200 events
xvi) Capability to implement bay level interlocks
o) Bay wise Typical I/O requirement (not exhaustive) of BCU is tabulated here under. The exact number
and description of digital inputs shall be as per detailed engineering requirement because some of the
I/Os may be deleted or added during detailed engineering. Apart from the above mentioned I/Os,
50% spare I/Os BCU wise for all BCUs shall be kept spare for WBSETCL use in future.
Status DI Hard AI Hard DO Remarks
Wired Wired
Common status for each bay
220V DC -1 source fail
220V DC -2 source fail
220V LCC DC -1 source fail
220V LCC DC -2 source fail
Current -R Phase
Current -Y Phase
Current -B Phase
Current Neutral
CB Local Mode
CB Remote Mode
CB R-Ph Open position
CB R-Ph Close position
CB Y-Ph Open position
CB Y-Ph Close position
CB B-Ph Open position

WBSETCL : Feb 2021 Page 21 of 53 Control & Relay Panel


Status DI Hard AI Hard DO Remarks
Wired Wired
CB B-Ph Close position
CB Pole Discrepancy
operated
CB Spring Charged
CB SF6 Gas Pr. Low Alarm
CB lockout
CB Trip Coil-1 R-Ph Faulty
CB Trip Coil-1 Y-Ph Faulty
CB Trip Coil-1 B-Ph Faulty
CB Trip Coil-2 R-Ph Faulty
CB Trip Coil-2 Y-Ph Faulty
CB Trip Coil-2 B-Ph Faulty
CB Open Order 1
CB Open Order 2
CB Close Order
Sync OK
86-A Master trip Relay
Operated
86-B Master trip Relay
Operated
86-A Master trip Relay Faulty
86-B Master trip Relay Faulty
Reset Order for Master-86A
Reset Order for Master-86B
96 Trip Relay Operated
96 Trip Relay Faulty
Reset Order for 96
75A OPTD
75B OPTD
GIS Auxiliary Status e.g. gas (Exact nos. of signals
low and lockout of various need to be assessed
gas sections, L/R/E Switch from final approved
status, N/M Switch status, GIS LCC drawing)
MCB trip condition etc.
33kV Indoor Switchgear (Exact nos. of signals
Auxiliary Status e.g. Test need to be assessed
position, Service position, from final approved
Local mode, Remote mode, Indoor Switchgear
MCB Trip etc. drawing)
CB Auxiliary Status (Minimum For AIS CBs
8nos for 220kV and above,
minimum 6nos for 132kV and
below )
Relay Faulty status Separately for each
Numerical IED
PT MCB Trip Separately for each
Metering and
Protection circuit
Common status for each equipment

Isolator Local Mode


Isolator Remote Mode
Isolator Open position
Isolator Close position

WBSETCL : Feb 2021 Page 22 of 53 Control & Relay Panel


Status DI Hard AI Hard DO Remarks
Wired Wired
Isolator Open Order
Isolator Close Order
Earth Switch Open position
Earth Switch Close position
Earth Switch Interlock
permissive
SF6 CT R-Ph Gas Low For AIS SF6 CTs
SF6 CT Y-Ph Gas Low
SF6 CT B-Ph Gas Low
SF6 CT R-Ph Gas Lockout
SF6 CT R-Ph Gas Lockout
SF6 CT R-Ph Gas Lockout
Additional bay specific status
Bus Coupler bay/ Bus Transfer bay
Bus1 Voltage- R - Y Phase
Bus1 Voltage- Y - B Phase
Bus1 Voltage- B - R Phase
Bus1 Voltage - Neutral
Bus1 Frequency
Bus2 Voltage- R - Y Phase
Bus2 Voltage- Y - B Phase
Bus2 Voltage- B - R Phase
Bus2 Voltage - Neutral
Bus2 Frequency
All Bays except Bus Coupler bay/ Bus Transfer bay
Selected Bus R -Y Phase
Selected Bus Y - B Phase
Selected Bus B - R Phase
Selected Voltage Neutral
Line bay
Autoreclosure - CB Healthy
CVT Voltage Phase
CVT Voltage Neutral
Transformer bay
Other side Voltage Phase
Other side Voltage Neutral
Other side CB Open Order 1
Other side CB Open Order 2
WTI Temperature of each
winding
OTI Temperature
OLTC Main Supply ON
OLTC Main Supply OFF
OLTC Tap Position Indication
Tap Changer Out of Step
Tap Changer in progress
Tap Changer ON LOCAL
Tap Changer ON REMOTE
Tap Changer in Independent
mode
Tap Changer in master mode
Tap Changer in follower
mode

WBSETCL : Feb 2021 Page 23 of 53 Control & Relay Panel


Status DI Hard AI Hard DO Remarks
Wired Wired
OLTC Tap Raise
OLTC Tap Lower
Cooler control Main AC
Supply Fail
Cooler control S/By AC
Supply Fail
Cooler Control Auto
Cooler Control Manual
Cooler control Main Oil Pump
ON
Cooler control Main Oil Pump
OFF
Cooler control Main Oil Pump
STUCK
Cooler control S/By Oil Pump
ON
Cooler control S/By Oil Pump
OFF
Cooler control S/By Oil Pump
STUCK
Cooler control Main Fan ON
Cooler control Main Fan OFF
of each Fan
Cooler control S/By Fan ON
Cooler control S/By Fan OFF
Buchholz Trip
Buchholz Alarm
PRV Trip
OSR Trip
Oil Temp. High Trip
Oil Temp. High Alarm
Oil Level Low Alarm
Winding Temp. High Trip of
each winding
Winding Temp. High Alarm of
each winding
MOG Alarm
Diverter Tank MOG Alarm
RTCC in AUTO
RTCC in MANUAL

17.02 EVENT LOGGER:


[The IED should be latest IEC61850, Ed - 2 compliant having rear port compatible to
latest IEC 61850, Ed - 2 protocol.]
a) Stand-alone type Event logger to be considered with external triggering facility. The event list shall
contain events that are important for the control and monitoring of the substation.
b) The event logger shall be mounted in a separate Simplex type panel.
c) The events shall be registered in a chronological event list in which the type of event and its time of
occurrence are specified. It should be possible to get the chronological event list at any time for the
whole substation or sections of it. Filters for selection of a certain type or group of events shall be
available. The filters shall be designed to enable viewing of events grouped per:
i) Date & Time

WBSETCL : Feb 2021 Page 24 of 53 Control & Relay Panel


ii) Bay
iii) Device
iv) Functions e.g. Trips, Protection operations etc.
v) Alarm class
d) The chronological event list shall contain:
i) Position changes of Circuit Breakers, Isolators and Earthing devices
ii) Indication of Protective relay operations
iii) Fault signals from the switchgear
iv) Indication when analog measured values exceed upper and lower limits. Suitable provision
shall be available to define two level of alarm on either side of the value, which shall be user
defined for each measurands.
v) Loss of communication
e) Event Logger shall fetch events from IEDs (including BCU) through soft signals. It shall also fetch
events from potential free contacts through BI (5 inputs per bay + 20% spare).
f) All recorded/stored events shall be date and time tagged followed by a message describing the points
which have been operated. The time resolution shall be 1 milli second.
g) Number of time tagged events in the event list should be sufficient enough to record/store all possible
sorts of events of the switchyard, equipments, relays etc.
h) Event Recorder buffer memory shall be of non-volatile type and shall not require the use of batteries.
i) The printout of events shall contain at least the station & feeder identification, date and time (in hour,
minute, second and millisecond), event number and event description. The event list and its print out
may be available from S/S; PC and its printer to be supplied by the bidder for a complete S/Stn. The
timing of each event shall be as per GPS based time synchronising equipment to be supplied by the
bidder, wherever applicable & mentioned in the schedule..
All the necessary software for the event logger function and download the event list shall be within
the scope of the bid.

17.03 NUMERICAL TYPE DISTANCE PROTECTION SCHEME RELAY:


[The relay should be latest IEC61850, Ed - 2 compliant having rear port compatible to
latest IEC 61850, Ed - 2 protocol.]

a) The distance protection shall be a microprocessor based high speed non-switched distance relay
suitable for all phase to phase faults and phase to earth faults based on numerical principles.It shall
also have necessary phase selection and direction selection facilities. The relay shall be field
selectable for various permissive over reaching, permissive under reaching and for blocking/
intertripping through communication schemes.
b) The relay shall have polygonal/ quadrilateral characteristics with a facility to set resistance and
reactance characteristics independently.
c) The relay shall have three forward and one reverse zone of protection for each PH-PH & PH-E fault
loop with sufficient impedance or reactance and resistance reach of each zone. It shall have three
zone time stepped characteristics. The second and third zone elements shall provide backup
protection in the event of the carrier protection on the first zone element failing to clear the fault.
d) It shall be compatible with the PLCC equipment to be procured separately under separate contract.
The distance protecting scheme shall be suitable for any length (short length also i.e. Minimum
Settable value should be 1Ω Primary) of transmission line. Any limitation in this regard shall be clearly
specified by the bidder.
e) The relay shall have numerical filtering and measuring techniques. It shall have individual measuring
element for each phase to phase fault and each phase to earth fault. It should ensure a maximum
operating time from the relay to the trip coil of CB within 40 ms for all types of faults at 50% of the
set zone 1 relay reach with CVT being used on the line for a System Impedance Ratio (SIR) of 4 and

WBSETCL : Feb 2021 Page 25 of 53 Control & Relay Panel


the same shall be 45millisecond for an SIR of 15. However, a relaxation of 5millisecond is allowed for
the relays being used for 132 KV.
f) It shall be provided with continuous self supervision features along with self diagnostic feature,
having output IRF contact for annunciation purpose.
g) Shall have memory circuits with defined characteristics in all three phases to ensure correct operation
during close up three phase faults and other adverse conditions and shall operate instantaneously
when circuit breaker is closed to zero volt three phase faults.
h) It shall be suitable for single and three phase tripping mode to be scheduled by WBSETCL depending
upon their application along with necessary trip relays.
i) The scheme for 400KV & 220 KV system shall be suitable for single phase or/and three phase Auto-
reclosing. It shall have in built features of weak end in feed, switch on to fault, fuse failure
supervision and instantaneous blocking of voltage dependent protection in the event of fuse failure
and should remain inoperative for system earth fault, Power Swing blocking with zone selection
facility for such blocking, broken conductor detection and different indications for relay monitoring
operations.
j) The relay should have the facility to switch over to settable non-directional O/C during loss of voltage.
k) The relay shall have inbuilt single phase & three phase auto reclose scheme, disturbance recorder,
event logger facility and additional features shall also be indicated over and above the features
already specified.
l) The relay shall have online type fault location function along with built-in parallel line mutual
compensation facilities having accuracy of ±3% of line length. The above accuracy should not be
impaired in presence of severe CVT transient or high fault arc resistance.
m) Relay should be blocked in case of momentary dropping off of PT switching Relays to avoid
maloperation, if there be any. The VTF protection should be incorporated.
n) The numerical distance relay should have in built directional sensitive earth fault element for high
resistance fault.
o) The relay shall have suitable number of potential free contacts for carrier aided tripping, auto
reclosing, event logger, disturbance recorder and data acquisition system.
p) The relay shall have a continuous current rating of two times of rated current, the voltage shall be
capable of operation at 1.2 times rated voltage. The relay shall also be capable of carrying a high
short time current without damage for a period of 1sec.
q) The relay shall have at least 16nos (for upto 132kV) and 20nos (for 220kV and above) of individually
site selectable Binary Inputs and 20nos Binary Outputs (rating of Binary Input shall be 240V DC but
they should not pick up at less than 150V). Latching option for B/O shall have to be provided. Output
contact of the protective relay should operate single phase trip relay which will have sufficient contact
to give trip command to main breaker & TBC breaker & for LBB protection initiation and other
purpose.

17.03. AUTO-RECLOSE RELAY:


01
a) The scheme shall be compatible with the distance relaying scheme. It shall be suitable for single shot,
single and/or three phase auto-reclosing feature. The bidder shall coordinate the auto-reclose
relaying scheme with that of the circuit breaker so as to ensure satisfactory and reliable operation of
the auto reclosing scheme.
b) The auto reclose relays shall have independently adjustable dead timers for single phase and three
phase reclosures and an adjustable reclaim timer.
c) It shall also be possible to lock out the auto-reclosing scheme relays when the carrier protection
associated with distance protection scheme is out of service or faulty.
d) It shall have auto-reclose mode selection facilities as required.

WBSETCL : Feb 2021 Page 26 of 53 Control & Relay Panel


e) It shall have facilities for selecting check synchronising or dead line charging feature. It shall be
possible at anytime to change the required feature as required.
f) It shall be built-in with the main distance relay.
g) The autoreclose relay along with necessary check synchronising or dead line charging facilities and
other associated features shall be in built in the Main-1 & Main-2 protection. Any one shall be
activated during operation and the other shall be kept as stand by. The two inbuilt autoreclose relays
should be well coordinated so that autoreclose command/ definite trip command etc may be initiated
from either of the two units at the discretion of WBSETCL personnel. The autoreclose element of the
distance relay shall also be suitable for triggering from other external protections.
h) In One and Half breaker system, while reclosing the Main breaker & Tie breaker for the Line bay, a
priority shall be assigned. The Main breaker shall be allowed to reclose first and only after its
successful recloser, the Tie breaker shall be allowed to reclose. If the fault persists after reclosing of
the Main breaker, reclosing of the Tie breaker is blocked.

17.03. FAULT LOCATOR:


02
The distance to fault locator shall be provided for all 400KV, 220KV and 132KV lines. It shall comply
with the following requirements: -
a) Microprocessor based "on-line" type.
b) suitable for breaker operating time.
c) have built in display unit.
d) the display shall be directly in kilometers without requiring any further calculations.
e) have an accuracy of 3% of the line length for which the fault locator is installed or better for all type
of faults and fault levels.
f) the above accuracy should not be impaired under the following conditions:
i) presence of remote end in feed.
ii) Predominant d.c. component in fault current.
iii) high fault arc resistance.
iv) severe CVT transients.
g) have facility for remote data transmission.
h) shall be in-built in distance relay with facility for triggering from external protection.
i) shall have built in mutual compensation facility for using in double circuit lines and this parallel line
compensation shall not be used for protection purpose.

17.03. DISTURBANCE RECORDER:


03 [The DR should be latest IEC61850, Ed - 2 compliant having rear port compatible to latest
IEC 61850, Ed - 2 protocol.]

a) Disturbance Recorder shall be used for 400KV, 220KV and 132KV system to record the graphic forms
of instantaneous/ rms values of voltages and currents, in all phases, open delta voltage and neutral
current, open or closed position of relay/ breaker contacts just prior to, during and immediately after
a system disturbance to provide information necessary to ascertain the causes of disturbance and
performance of relays, breakers etc. The system shall start only on the occurrence of a system
abnormality.
b) The disturbance recorder shall be inbuilt function of numerical distance/ differential relay. The
channels and trigger sources shall be user configurable. Program for disturbance records and event
logger collection and evaluation of those records shall be provided. Also the software shall be capable
of carrying out Fourier /harmonic analysis of the current and voltage waveform. Disturbance shall also
be available in COMTRADE format.
c) Number of Channels required for each feeder bay :
i) Analog channel: 8 nos.

WBSETCL : Feb 2021 Page 27 of 53 Control & Relay Panel


ii) Digital channel: 32 nos.
d) The relay shall have the disturbance recording function with at least 8nos analog channels and 32nos
binary channels having total recording memory of at least 15secs divided in to 8 records, each having
at least a memory of 100ms for pre-fault analysis, and recording bandwidth may please be indicated.
It should have on line pre and post fault disturbance recording facility. There should be provisions for
interfacing all the digital channels both internally and externally.
e) The disturbance recorder shall be suitable for working with 220V DC available at the Sub-station.
f) Each Relay & Disturbance Recorder shall have the facility to synchronise the internal clock with GPS
based time synchronising equipment directly through,
a. IRIG-B or
b. SNTP protocol or
c. Minute/Second pulse through Binary I/Ps
g) The accuracy of the internal clock shall be indicated by the bidder. The drift is limited to 0.5sec per
day, if allowed to run without synchronisation. The recorder shall give annunciation in case of
absence of synchronising pulse within a specified time.
h) Substation where time synchronisation equipment is not available, time generator of any one of the
disturbance recorder can be taken as master and the time generator of other disturbance recorder
and event logger in the substation shall be synchronized to follow the master.
i) The recorder shall have facility for automatic uploading of, remote data transmission. Scan rate of D
R shall be at least 1KHZ per channel or better. Facility for triggering of disturbance recorder from
external protection shall also be provided. Acquisition units shall acquire the fault data for the prefault
and post fault period and can be transferred on demand to connected PC.

17.04 NUMERICAL TYPE LINE DIFFERENTIAL PROTECTION RELAY:


[The relay should be latest IEC61850, Ed - 2 compliant having rear port compatible to
latest IEC 61850, Ed - 2 protocol.]

a) Line Differential protection relay shall have phase segregated line differential protection.
b) It shall measure Differential as well as restrain current continuously and shall display the same as
measurement.
c) It shall communicate analogue as well as digital signals to remote end.
d) It shall have Line charging current compensation feature for better sensitivity.
e) Have backup built-in Distance protection functionality as specified for distance protection relay.
Distance protection function can be utilized as independent or as back up of Differential protection in
case of failure of remote communication.
f) It shall communicate time coordinated current signals for remote communication to execute Line
differential protection algorithm accurately. Time synchronization through GPS shall also be possible.
g) Have high immunity to electrical & electromagnetic interference.
h) Have DR with 8nos analog channel & 32nos binary channel.
i) Generate GOOSE message as per latest IEC 61850, Ed - 2 standards for interlocking and also to
ensure interoperability with third party relays.
j) be provided with necessary user friendly configuration tools to configure the relays and shall be
compatible with SCL/SCD files generated by a third party system. GOOSE signals shall be freely
configurable for any kind of signals using graphic tool/user friendly software. There shall be a facility
to have latest IEC 61850, Ed - 2 protocol inbuilt without use of any external converter.
k) Have the facility of setting parameter access restriction.
l) Have self supervision with fault diagnostics.
m) Be provided with necessary WINDOWS 7/ WINDOWS 10 based support software for setting
parameterisation, up & downloading data etc.
n) Have channel communication with continuous supervision facility and the facility for switching to
backup protection mode in the event of communication channel failure.

WBSETCL : Feb 2021 Page 28 of 53 Control & Relay Panel


o) Have cold start switching facility at every end.
p) Have phase segregated measurement and tripping facility.
q) Have a high set differential trip setting with tripping time of maximum 15ms.
r) Have a normal line differential trip time of maximum 35ms at 5 times of set value.
s) Provide high stability during external faults.

17.05 TIME SYNCHRONISATION EQUIPMENT:

The time synchronisation equipment shall receive the coordinated Universal Time (UTC) transmitted
through Geo Positioning Satellite system(GPS) and synchronise equipments to Indian Standard time in
a substation. It will also synchronise the substation PC through necessary software to be supplied by
the bidder.
a) Time synchronising equipment shall include antenna, all special cable and processing equipments&
the same shall be housed in a separate simplex type panel.
b) For all new substations, if specified in LOA, GPS shall be redundant, i.e. Two nos of Clock & Antenna
should be considered.
c) It shall be compatible for synchronisation of event loggers, disturbance recorder and SCADA at a
substation.
d) Equipment shall operate upto the ambient temperature of 50C and 100% humidity.
e) Equipment shall meet the requirement of IEC 60255 for storage and operation.
f) Equipment shall have real time display in hour, minute, sec (24 hr. mode)and have a separate time
display unit to be mounted on the top of the control panels or any suitable location having display
size of approximately 100mm height.
g) Equipment offered shall have six output ports .Various combinations of output ports shall be selected
by the customers, during detailed engineering from the following:
i) Voltage signal: Normally 0 – 5 V with 50ms minimum pulse duration. In case any other
voltage signal required it shall be decided during detailed engineering.
ii) Potential free contact (minm. pulse duration of 50ms).
iii) IRIG-B
iv) RS232C
h) The synchronisation equipment shall have 2micro second accuracy. Equipment shall give real time
corresponding IST (taking into consideration all factors like voltage and temperature variation,
propagation and processing delays etc.).
i) The output signal of each port shall be programmable at site for either one hour, half hour, minute or
second pulse, as per our requirement.
j) The equipment shall have a periodic time correction facility of one second periodicity.
k) The equipment shall be suitable to operate from 220V DC  10% as available at the substation.
l) The system shall be able to track the satellites to ensure no interruption of synchronisation signal.
m) Time synchronization equipment consisting of :
i) GPS antenna,
ii) GPS receiver with detail of output & ports,
iii) Requisite quantity of interconnecting cable with matching connector,
iv) Master clock with display unit, power supply unit,
v) Battery charger if required, time synchronization panel etc.
vi) Necessary converter arrangement for deriving Power supply DC voltage from 220V DC supply
from our substation battery.
vii) Synchronisation panel etc.
viii) Other particulars if any.

WBSETCL : Feb 2021 Page 29 of 53 Control & Relay Panel


17.06 TRANSFORMER DIFFERENTIAL RELAY:
[The relay should be latest IEC61850, Ed - 2 compliant having rear port compatible to
latest IEC 61850, Ed - 2 protocol.]
a) The protection shall be provided at the HV side panel of the transformers to be protected. It shall be
numerical type adjustable/variable percentage biased differential relay.
b) Necessary softwares, cables, connectors and other accessories as required in compatible with Sub-
station PC shall be provided by the Tenderer as described under clause 16.07 above.
c) The relay shall be very fast in operation with an operating time less than 30 40 millisec at 5 times
setting.
d) The relays shall be inherently stable for external through fault conditions (up to at least 10 times of
relay basic current) without affecting the speed of operation for internal faults.
e) The relay shall have built in facility of: -
i) Ratio and phase angle correction.
ii) Amplitude matching feature by means of reference power common to all winding.
iii) Zero sequence filtering of relay currents depending of relevant chosen vector group.
f) The relay shall be provided with 2nd harmonic restraint (having site selectable setting facilities of
10% to 40% of I2/I1) or any other inrush proof feature to prevent operation due to magnetising in
rush current when the transformer is charged either from HV or LV side. But this shall not affect the
speed of operation for internal fault.
g) It shall be provided with 5th harmonic restraint features (having site selectable setting facilities of
10% to 40% of I 5th/Ifund) to prevent operation due to possible over excitation of the transformer.
This shall also not affect the speed of operation for internal fault.
h) It shall have three instantaneous site selectable high set differential tripping facilities over
current units (8 to 15 times of relay basic current) for clearing heavy internal faults.
i) The bias-operating characteristic of differential protection device shall have at least two knees. The
relay shall have adjustable bias setting range 20% to 50% and adjustable operating setting range of
10% to 50% at zero bias.
j) The relay shall be with 3-bias winding for 400/220/33KV and 220/132/33KV transformers and 2-bias
winding for 220/33KV, 132/33KV and 10MVA and above 33/11KV transformers.
k) The relay shall be such that there will not be any necessity of changing the setting of the relay
whenever the transformer taps are changed.
l) The relay shall be provided with GPS based time synchronized disturbance recorder with date and
time tagged records with the facility of triggering from other external protective relays of the
transformer as well as date & time tagged event logger function. The disturbance recorder shall be
capable of recording graphic form of values of currents each phase, differential currents of each
phase etc. and store them in the memory which can be downloaded both from local and remote end
PC. Memory size and number of disturbances stored in the relay shall be clearly indicated in the offer.
m) The in-built disturbance recorder shall have the facility to record the following external digital signal
apart from the digital signals pertaining to differential relay.
i) REF protection operated
ii) Over flux relay operated
iii) Dir/ Non-Dir O/C relay operated
iv) HV breaker status(Main & Tie)
v) LV breaker status
vi) Buchholz/OLTC Buchholz alarm/trip
vii) WTI/OTI/PRD alarm/trip of transformer
n) The relay shall have the disturbance recording function with at least 12nos analog channels and
16nos digital channels having total recording memory of at least 15secs divided in to 8 records, each
having at least a memory of 100ms for pre-fault analysis, and recording bandwidth may please be

WBSETCL : Feb 2021 Page 30 of 53 Control & Relay Panel


indicated. It should have on line pre and post fault disturbance recording facility. There should be
provisions for interfacing all the digital channels both internally and externally.
o) The relay shall have at least 8nos of individually site selectable Binary Inputs and 8nos Binary Outputs
(rating of B/I shall be 240V DC but they should not pick up at less than 150V). Latching option for
B/O shall have to be provided. Output contact of protective relay should operate trip relay which will
have sufficient contact to give trip command to main breaker, TBC breaker & for LBB protection
initiation and other purposes.
p) The relay shall have 4 - 20mA Analog Input card having sufficient provision to record the data from
one no. OTI, three nos. WTI and Tap Position Indicator.
Necessary hardware and software for downloading the data captured by disturbance recorder to the
personal computer available in the substation shall be included in the scope.

17.07 RESTRICTED EARTH FAULT PROTECTION:

The Relay shall comply with the following requirements: -


a) stand-alone Numerical type. Shall be current or voltage operated and high impedance type.
b) shall have three nos. voltage coils to identify the faulty phase.
h) tuned to the system frequency.
e) have suitable nonlinear resistor to limit the peak voltage.
f) operating time shall be less than 20 45 ms.
g) have suitable stabilizing resistor to prevent mal-operation during external faults.

17.08 CIRCULATING CURRENT PROTECTION:

The protection shall be responsive for both phase and earth fault of the transformer and reactor
winding. The relay shall comply with the following requirements: -
a) stand-alone Numerical type. Shall be current or voltage operated and high impedance type.
b) shall have three nos. voltage coils to identify the faulty phase.
c) tuned to the system frequency.
d) have suitable nonlinear resistor to limit the pick voltage.
e) operating time shall be less than 20 45 msec.
f) have suitable stabilizing resistor (in each phase) to prevent mal-operation during external faults.

17.09 OVER FLUXING PROTECTION:


The relay shall comply with the following requirements: -
a) Stand alone Numerical type.
b) The relay shall operate on the principle voltage to frequency ratio.
c) It shall have characteristics compatible with transformer over fluxing withstand capability.
d) Input shall be 110V, 50Hz, Auxiliary Volt 220V DC ± 20%
e) Over Flux relay characteristics should be suitable for: -
i) 110% continuous
ii) 125% for 1min.
iii) 140% for 5sec.
f) Alarm : - Settable between 100% - 130% with Definite Time delay, settable from 0.5 – 30 sec.
g) Drop Off/ Pick Up ratio should not be less than 98%.
h) The relay shall have the disturbance recording function with at least 4nos analog channels and 8nos
digital channels.

WBSETCL : Feb 2021 Page 31 of 53 Control & Relay Panel


17.10 OVER LOAD PROTECTION:
This protection shall be used for 400/220/33kV & 220/132/33kV Auto-transformer and shall be
located at HV side protection panel of respective transformer. The relay shall comply with the
following requirements: -
a) definite time, single pole type.
b) have a variable and continuously adjustable current setting range of 50% to 200% of rated current
and variable time setting 2.5 to 25sec. of the timer unit.
c) included hand reset flag indicator.
d) the relay shall provide alarm only.
e) have a drop off/pick up ratio greater than 95%.
f) May be in built feature of numerical differential relay.

17.11 OVER VOLTAGE PROTECTION:


This protection shall be used for 400kV Feeder. The relay shall comply with the following
requirements: -
a) stand-alone type & connected to Line CVT.
b) monitor all three phases.
c) be connected between Phase to Phase in Delta configuration.
d) have two stages.
e) have an adjustable setting range of 100 - 170% of rated voltage with an adjustable time delay range
of 1 to 60secs for the first stage .
f) have an adjustable setting range of 100 – 170% of rated voltage with a delay of 100 – 200msec for
the second stage .
g) have power frequency filters.
h) have a drop off to pickup ratio greater than 99%.
i) provide separate output contact for each ‘Phase’ and stage for breaker trip relays, event logger and
other scheme requirement.

17.12 NUMERICAL DIRECTIONAL/NON-DIRECTIONAL OVER CURRENT & EARTH FAULT


PROTECTION:
The relay shall comply with the following requirements: -
a) Minimum two characteristics, one IDMT of 3sec and the other one of definite time characteristic with
instantaneous high set and the same should be site selectable.
b) Wide range of time and current setting in very small steps without sacrificing the relay characteristics.
c) There should be provision for configuring the output contacts and LEDs as latched or unlatched
individually. Reset of the outputs and LEDs shall be possible from a logic input and the front panel
operator interface.
d) Continuous self supervision along with self diagnostic feature for faults within the relay and the relay
should have potential free ‘change over’ contact for annunciation in the event of internal failure.
e) DC auxiliary voltage – 220V±20%, 110v. ±20%
f) Rated current – 1A.
g) Frequency – 50Hz.
h) Digital input voltage range shall be identical to the DC voltage range.
i) Thermal withstand capability – 100A for 1Sec/ 4A continuous.
j) Output contacts having sufficient current rating to directly energize trip coil of circuit breaker.
k) LED indication facility for visual annunciation of different type of faults including phase identification.
Fault indication should be displayed in the stand-by screen.
l) Individually site selectable both binary Output & Input and latching option for binary Output.
m) Relay should show fault current with time stamping.

WBSETCL : Feb 2021 Page 32 of 53 Control & Relay Panel


n) The relay shall have more than one selectable setting group.
o) The setting group can be changed by binary inputs.
p) The relay shall have a non volatile memory for -
i) Event recorder - shall have the facility of recording up to 75 events with time stamping.
ii) Setting values.
iii) Disturbance recorder data - Recorded data of 5 last events with time stamp. The disturbance
recording function is triggered either by any of programmed threshold or by an external
input. All logic and analog information can be transferred using communication port to an
external data analyzer. Current waveforms shall be captured.
q) Fault records - At least five nos fault records shall be available with the following indications:
i) Fault indication.
ii) Current values.
iii) Tripping time.
r) Measurement -Instantaneous three phase current values and residual current value. All the measured
and derived values can be displayed on the front panel LCD.
s) No of output contact required – 8 nos
No. of digital input required – 8 nos
t) The numerical directional shall have built in feature for derivation of zero sequence voltage internally.
The MTA of numerical directional relay shall be 45ºlag for earth fault and 45ºlead for over current.
Any extra feature like time synchronization, LAN compatibility with other numerical relays shall be
mentioned specifically.

17.13 CURRENT UNBALANCE PROTECTION:


This protection shall be used for 33kV Capacitor bank. The relay shall comply with the following
requirements: -
a) Shall be stand-alone Numerical type.
b) Shall have SEF element suitable for capacitor bank (double star) unbalance current protection.
c) SEF (unbalance current) element should be settable up to 2 times rated current. This element will be
fed from neutral CT of low primary current rating (eg. 2A).
d) SEF (unbalance current) element shall have minimum 2 stages with definite time characteristics.
e) Shall have three phase current based overload protection element. This element shall be used for
overload protection of capacitor bank due to over voltage as well as harmonic content of current.
f) Over load protection element should operate considering the current, without suppression of
harmonics.
g) Characteristics of over load element shall be definite time. Setting range should cover up to 2 times
relay rated current.
h) Shall have built-in three-phase under-current element (fed from phase current) with definite time
characteristics to prevent closing operation of circuit breaker, immediately after tripping, to allow
discharging of capacitor bank. Time setting range of this element shall be minimum 10 minutes.

17.14 OVER VOLTAGE AND UNDER VOLTAGE PROTECTION:


This protection shall be used for 33kV Capacitor bank. The relay shall comply with the following
requirements: -
a) Shall be stand-alone Numerical type.
b) Shall be connected between Phase to Phase in Delta configuration and monitor all three phases.
c) Both the under-voltage element and the over-voltage element shall have two stages.
d) Over voltage element shall have an adjustable setting range of 100 - 170% of rated voltage with an
adjustable time delay range of 0 to 60secs for both stages.

WBSETCL : Feb 2021 Page 33 of 53 Control & Relay Panel


e) Under voltage element shall have an adjustable setting range of 10 - 90% of rated voltage with an
adjustable time delay range of 0 to 60secs for both stages.
f) Shall have power frequency filters.
g) Shall have a drop off to pick up ratio greater than 99%.

17.15 AUXILIARY RELAY FOR INTERNAL TROUBLE:


DC voltage operated auxiliary relays provided with mechanically operated hand reset indicator and
sufficient number of hand-reset contacts (Minimum 3 NO contact per coil) shall be provided for
protection and supervision against internal troubles/faults of GIS bay, Transformer, Reactor, Circuit
Breaker and CT. Number of element and number of relays shall be as per requirement of individual
equipment.

17.16 MASTER TRIP RELAY:

Master trip relay shall be provided to cause tripping of all the associated breakers. This relay shall also
be provided in other bays for closing lock out of breaker. Master trip relay coil supervision shall be
provided. The relay shall comply with the following requirements: -
a) Shall have fast operating attracted armature multi-contact relay coil assembly, operating time should
be less than 15ms.
b) Shall be provided with electrical reset as well as hand reset arrangement.
c) Shall have cut-off contact with relay operating coil.
d) Shall have high burden and high degree of mechanical stability.

17.17 DC SUPPLY SUPERVISION RELAY:


The relay shall monitor D.C. Supply continuously, as specified in resp. Clause. The de-energization of
this relay will indicate the DC Supply failure. Auxiliary supply for the relay is 220V DC. The relay shall
have a time delay on drop off of not less than 100 milli second. The relay shall be provided with
operation indicators (Reverse flag) self reset. Sufficient number of contacts potential free may be
provided. Separate relays for dual source are to be provided.

17.18 LOCAL BREAKER BACK UP PROTECTION:


The above protection shall be stand alone type or built in function of bus bar protection scheme and
shall be provided for 400KV, 220KV & 132kV bays. The protection scheme shall be so designed that if
any circuit breaker fails to trip in the event of a fault, then after a short time delay all the adjacent
circuit breakers connected in the same bus will be tripped. The circuit breaker failure shall also block
auto-reclosing scheme. The scheme shall be complete with timer and auxiliary relays as necessary
including remote end tripping facility. The relay shall comply with the following requirements: -
a) be triple pole type.
b) havea operating time less than 15millisecond.
c) have an resetting time less than 15millisecond.
d) have three over current element with facility for phase wise initiation.
e) have a current setting range 20 to 320% of rated current for over current.
f) have a continuous thermal withstand of two times rated current irrespective of the setting.
g) have timer suitable for sub-station D.C. with a continuously adjustable setting range of 0.1 to 1sec.
h) be of solid state/ numerical type.
i) trip and lock out all the local breakers. Simultaneously direct trip signal shall be sent to remote end
circuit breakers (through both channels in case of 400KV system) and lock out its auto-reclosing
feature.
j) have necessary auxiliary relays to make a comprehensive scheme.

WBSETCL : Feb 2021 Page 34 of 53 Control & Relay Panel


k) Trip all the breakers on the particular bus in a One & Half breaker system, when any bus breaker fails
to trip in faulty condition. However, when a Tie Breaker fails to open, the LBB relay shall trip the
adjacent bus breakers as well as both the breakers at the remote end of the bays.
l) LBB for Tie breaker shall be standalone type.

17.19 TRIP CIRCUIT SUPERVISION RELAYS:


a) DC supply to each trip coil of the circuit breakers shall be supervised with an independent trip circuit
supervision relay. These relays shall be mounted in the relay panel associated with the circuit breaker.
No chattering of the relay is acceptable.
b) The relays shall supervise the healthiness of trip circuit continuously (Both pre-closing and post-
closing conditions of the circuit breakers). Healthiness of each phase trip coil and associated circuits
of the circuit breaker during “ON and OFF” conditions shall be monitored by the relays and give an
alarm for the (i) loss of D.C. supply or (ii) for faults in the trip coil or for faults in the trip circuit leads
or for faults in the breaker auxiliary contacts or faults in the supervisory relay itself.
c) The relay shall have adequate contacts for providing connection to alarm and event logger, self reset.
The relay shall have a delay in drop off at least 200ms to avoid a false alarm during a normal tripping
operation. The short circuiting of any series resistance provided in this relay or short circuiting the coil
of the relay should not energize the trip coil of the breaker.

17.20 NUMERICAL BUS BAR PROTECTION


[The relay should be latest IEC61850, Ed - 2 compliant having rear port compatible to
latest IEC 61850, Ed - 2 protocol.]

a) The bus bar protection relay should support various bus architectures selectable by means of the
relay configuration (Single bus bar, Double bus bar, Breaker and a half bus bar, two section bus bar
with a bus tie, Double bus bar with transfer bus and tie breaker) for its bus bar protection. Bus Bar
protection scheme should operate selectively for each bus bar.
b) The relay must have rejection and shall not operate on second and third harmonics. Second harmonic
rejection ratio 2:1 minimum, third harmonic rejection ratio 40 : 1 minimum.
c) The relay shall incorporate dynamic bus replica and provide necessary end zone/ blind zone fault
protection depending on the bus bar protection CT’s location.
d) The relay should have provision to configure split zone protection using section isolator status, if the
system requires. Implementation shall be WBSETCL discretion.
e) Facility to monitor the bus differential currents and bus restraint current for each zones shall be
supported in the relay display as well as through configuration tools.
f) Built-in Local Breaker Backup protection feature as a part of bus bar protection scheme shall also be
acceptable.

Bus bar protection scheme: -


a) shall be phase segregated and triple pole type with separate relay for each phase and provide
independent zone of protection. If bus section is provided, then each side of the bus section shall
have separate set of bus bar protection scheme.
b) The bus section breaker and bus coupler breakers shall be covered by overlapping bus bar protection
scheme of respective buses.
c) incorporate check zone feature for each phase and clear zone indication. The check zone shall be
without any switching. Also check zone shall not over stabilize during internal fault due to unequal
source & load distribution.
d) shall include one overall check zone protection in addition to single/multiple zones specified.
e) be transient free in operation

WBSETCL : Feb 2021 Page 35 of 53 Control & Relay Panel


f) Shall have maximum operating time up to trip impulse to trip relay for all types of faults of 20milli
seconds at 5 times setting value.
g) The bus bar protection of respective bus sections shall trip respective set of bus bar lockout relays
and shall initiate BF of respective CB. The bus bar protection scheme shall include individual high
speed hand reset tripping relays alongwith stand-alone supervision relay for each bay.
h) No inter-trip initiation is permitted between 86 circuit and 96 circuit. Sufficient contacts are to be
considered for 96 relays of Transformer bays so that individual contact of 96 relay can be assigned for
trip initiation to the Trip coil – 1, Trip coil – 2 of the other side Main Circuit Breaker as well as
Transfer bay Circuit Breaker (if available).
i) not give false operation during normal load flow in bus bars. not cause tripping for the differential
current below the load current of heaviest loaded feeder. Bidder shall submit application check for the
same.
j) Shall incorporate continuous supervision for CT secondary against any possible open circuit and if it
occurs, shall render the relevant zone of protection inoperative and initiate an alarm
k) include continuous D.C. supplies supervision.
l) include protection 'IN/OUT' switch for each zone
m) The scheme should be equipped completely for supporting four numbers spare circuits (having
maximum no. BI and BO, which is used for a particular bay in present scope) in addition to the
circuits for feeders/ bays in the single line diagram. Central unit shall be compatible for minimum 24
bays.
However for extension of bus bar protection scheme (if specified in BPS) in existing substations,
scope shall be limited to the bay or breakers covered under this specification. Suitable panels to
mount these are also included in the scope of the work.
n) At existing substations, Bus-bar protection scheme with independent zones for each bus, will be
available. All necessary co-ordination for 'AC' and 'DC' interconnections between existing schemes
(Panels) and the bays proposed under the scope of this contract shall be fully covered by the bidder.
Any auxiliary relay, trip relay, flag relay and multi tap auxiliary CTs (in case of biased differential
protection) required to facilitate the operation of the bays covered under this contract shall be fully
covered in the scope of the bidder.

17.20. For 400KV substation:


01
a) For 400KV bus bar protection two redundant full scheme of Bus Bar protection incorporating
individual buses and transfer bus is to be provided. The tripping logic should be ‘AND Logic’ in case
when both the bus bar protection relay is available. In case of non availability of one bus bar relay,
the tripping logic will be based on available relay.
b) The Central Processing Unit of bus bar protection & Bay Unit of numerical bus bar protection scheme
shall be housed in a separate set of simplex type panel along with equipment/relays.
c) One Bus bar protection scheme shall be provided for each main and transfer bus for 220KV and 132
KV voltage levels.
d) Bus Bar protection scheme shall give hundred percent security up to 50KA for fault level for 400KV

17.20. For 220KV AND 132KV substation:


02
a) Bus bar protection scheme shall be provided for both 220KV and 132kV system.
b) Bus bar protection relaying scheme shall be provided in a separate simplex type panel with all bus
differential relays and trip relays etc. as required considering future bays.
c) Bus Bar protection scheme shall give hundred percent security up to 40 KA fault level for 220KV.

WBSETCL : Feb 2021 Page 36 of 53 Control & Relay Panel


17.21 TEE DIFFERENTIAL PROTECTION
Duplicated differential protection scheme namely Tee Differential protection shall be provided for One
and Half Breaker system. This scheme shall protect the circuit between the Main breaker & the tie
breaker. Two separate differential relays on different hardware platform shall be used for Main Iand
Main II protection.

17.22 STUB PROTECTION

Stub protection scheme shall be applicable for one and half breaker system. This protection shall
protect the part of one & half breaker system, not covered by distance protection.
Stub protection scheme shall be: -
i) active only when Line isolator is open & there is no voltage from CVT for distance protection
relay.
ii) the inbuilt function of the main Numerical Protection relay.
iii) Able to sense the fault through an overcurrent sensing element & trip bus breaker under fault
condition.

17.23 CONFIGURATION AND MONITORING TOOLS FOR ALL NUMERICAL RELAYS:


The manufacturer/bidder has to provide configuration and monitoring tool for all type of numerical
relays used for a particular sub-station without any price implication.

a) PC hook-up cable for direct communication in sufficient quantity for each substation.
b) Graphical configuration tool having all the functions used in the relay and sufficient nos. of different
logic gates in the in built library (software).
c) Basic application software for setting change, service value monitoring etc.
d) Programme for disturbance record collection and evaluation of those records.
e) Any additional software, if required, for remote communication and for other facilities available in the
relay.
All the above tools/software should be WINDOWS 7/ WINDOWS 10 Operating system compatible.

18.00 PROTECTION PHILOSOPHY:

The bidder has to design the protection scheme for lines, transformers, Bus coupler, Bus Transfer bay
of 400KV, 220KV, 132KV and 33KV system as applicable depending upon the substation layout
arrangement and the schemes are to be submitted along with their offers for acceptance of the same
by WBSETCL. All the protective relays etc. of each bay shall be mounted in the respective bay panel.
Similarly for 400/220/33KV, 220/132KV and 132/33KV transformer protection, relay of each system
voltage shall be located in the respective panel. However, the protection schemes shall be generally
based on the requirement listed below:

18.01 LINE PROTECTION:

a) Main – 1 distance protection by microprocessor based numerical distance relaying scheme with carrier
aided distance protection scheme.
b) Main – 2 distance protection by microprocessor based numerical distance relaying scheme but of a
different make with carrier aided distance protection scheme (For 400kV, 220kV & 132kV).
c) For 220kV & 132kV Line, where the line length is less than 3km, and for 220kV & 132kV cable line
and if specifically asked for in Tender LOA, Main – 1 and Main – 2 Line Differential protection scheme
numerical relays of different make are to be considered. Both relays should work in same wavelength.
d) Auto reclosing, fault locator and disturbance recorder scheme, event logger etc. shall be built in with
Distance relay/ Line Differential relay as specified in resp. Clause.

WBSETCL : Feb 2021 Page 37 of 53 Control & Relay Panel


e) Local breaker back up protection scheme.
f) Direct tripping command from remote end through carrier channel.
g) Line CVT operated two stage over voltage protection (For 400kV only).

18.02 PROTECTION OF AUTO TRANSFORMER:


h) Percentage biased differential protection (three winding).
i) Circulating current protection responsive to both phase faults and earth faults. (For 315MVA, 400 /
220 / 33 KV AUTO TRANSFORMER only)
j) Restricted earth fault protection. (For 220/132/33KV AUTO TRANSFORMER only)
k) Numerical Directional Back up protection having voltage polarised three element IDMT overcurrent
with directional high set instantaneous element and single element earth fault protection with
necessary P.T. fuse failure monitoring scheme for both at HV side and MV side.
l) Over load protection alarm on HV side.
m) Transformer over flux protection on HV side & MV side.
n) Flag relays for transformer mounted protection like buchholtz, winding temperature, oil temperature,
pressure relay device etc.
o) Local breaker back up protection at HV side & MV side.
p) Numerical stand-alone type neutral displacement relay with stage operation for tertiary winding
protection either by external open delta connection or by internally derived open delta voltage in
relay. PT connection will be via 2A MCB.
q) Numerical Non-directional, IDMT, three over current protection with high set instantaneous unit (for
loaded tertiary of 220/132/33KV AUTO TRANSFORMER only).

18.03 400KV BUS REACTOR PROTECTION:

a) Differential protection.
b) Restricted earth fault protection.
c) Back up single step distance protection.
d) Reactor internal trouble i.e., buchholz, winding temperature etc. protection.
e) Local breaker back up protection.

18.04 132/33 KV STAR-DELTA TRANSFORMER PROTECTION:

a) Percentage biased differential protection (Two winding).


b) Restricted earth fault protection both at HV and LV side.
c) Numerical Directional Back up protection having voltage polarised three element IDMT overcurrent
with directional high set instantaneous element and single element earth fault protection with
necessary P.T. fuse failure monitoring scheme for both at HV side and LV side.
i) One no. separate Numerical relay shall be considered for HV side.
ii) For LV side, if BCPU is considered in the respective Tender LOA, then Over current protection
feature of BCPU shall be used for LV side. Else One no. separate Numerical relay shall be
considered for LV side.
iii) The Earth Fault coil of the LV side Numerical relay shall be utilized as Overall REF protection
using Earthing Transformer Neutral CT and Bay CT of 33kV side of the Power Transformer.
For this Overall REF protection, separate suitable nonlinear resistor to limit the pick voltage
and stabilizing resistor to prevent mal-operation during external faults shall be considered.
d) Stand-alone Numerical type relay with stage operation (setting range of 10-40%) to be considered for
Earthing transformer neutral C.T. operated definite time earth fault protection. System Earth Fault
Relay shall have three nos. voltage coils to identify the faulty phase.
The earthing transformer location shall be as per the project SLD.
e) System Earth Fault protection scheme shall be achieved by five-position selector switch.

WBSETCL : Feb 2021 Page 38 of 53 Control & Relay Panel


The Five-position Selector Switch is to be wired assuming a 33kV system having three Bus Section
and two Bus Section Circuit Breakers. Each Bus Section shall have one Power Transformer and one
Earthing Transformer, i.e. total three nos Power Transformers and three nos Earthing Transformers
shall be present in the complete 33kV system.
f) Flag relays for both Power Transformer and Earthing Transformer mounted protection like buchholtz,
winding temperature, oil temperature, pressure relay device etc.
g) This earth fault relay will trip HV breaker/breakers after a preset time delay. The switches shall be
having sufficient number of contacts. The trip relays shall have sufficient number of contacts for
extending the trip pulse to other 33KV feeders connected with generating stations.
h) Trip transfer scheme for both HV & LV side shall be provided with two separate trip transfer switch.

18.08 BUS COUPLER BAY PROTECTION:

The protection scheme of 400kV, 220kV and 132kV bus coupler bay shall be as follows: -
a) Over Current & Earth Fault Protection with Check-Sync facility.
b) Local breaker back up protection.

The protection scheme of 33kV bus coupler bay (in case of Indoor Switchgear) shall be as follows: -
a) Non-directional, IDMT, three over current protection with high set instantaneous unit.
b) Non-directional, definite time earth fault protection.
c) One common under frequency relay of setting range 45 to 55 HZ in adjustable steps and with timer
relay of 0 to 20 second adjustable setting range with sufficient number of contacts shall be provided
from tripping of all 33 KV outgoing breakers.

18.09 TRANSFER BUS BAY PROTECTION:

The breaker shall be used for transfer of any circuit (except the 33KV Shunt Capacitor bay) through
transfer bus in case of necessity. During the period of transfer the line side CT operated protection of
transferred circuit will trip the transfer bus breaker in place of respective bay circuit breaker through
trip transfer switch. Normally, the protection scheme provided in transfer bus bay, except the LBB
protection, shall be kept inoperative with the help of protection IN/ OUT selector switch (for 400 &
220kV) or 3-position make before break type protection selector switch having selection for Feeder,
transformer and off position (for 132kV & 33kV). However, its own protection shall be used when
there is trouble in the protection system of transferred circuit.

The protection scheme of 400kV, 220kV and 132kV transfer bus bay shall be as follows: -
a) Single distance protection scheme for transferred feeder protection. The transfer bay numerical
distance relay should be identical to the Distance relays used in the feeder protection for easy
replacement of the same in future, if required.
b) Numerical Directional Back up protection having voltage polarised three element IDMT overcurrent
with directional high set instantaneous element and single element earth fault protection with
necessary P.T. fuse failure monitoring scheme (For 132kV Feeder bay only).
c) Numerical Non-directional, IDMT, three over current and one earth fault protection for 132/33 KV
transformer protection. The relay plug setting should be judged properly for protecting rated to 100%
loading (For 132kV side bay of 132/33kV Transformer only).
d) Local breaker back up protection.
The protection scheme for the 33kV transfer bus bay shall be -
d) Non-directional, IDMT, three over current protection with high set instantaneous unit with protection
selector switch.
e) Non-directional, definite time earth fault protection with protection selector switch.

WBSETCL : Feb 2021 Page 39 of 53 Control & Relay Panel


f) One common under frequency relay of setting range 45 to 55 HZ in adjustable steps and with timer
relay of 0 to 20 second adjustable setting range with sufficient number of contacts shall be provided
from tripping of all 33 KV outgoing breakers.

18.10 33KV FEEDER PROTECTION:


a) If BCPU is considered in the respective Tender LOA, then Over current protection feature of BCPU
shall be used. Else One no. Numerical relay shall be considered for Directional, IDMT, three over
current protection with high set instantaneous unit.
b) Directional, definite time sensitive earth fault protection.
c) Under frequency relay operated CB tripping scheme.
d) One no. 96 relay alongwith 95/96 relay for Phase Overcurrent LBB protection.

18.11 33/11KV TRANSFORMER PROTECTION (DELTA-STAR):

a) Percentage bias differential protection (Two winding) for 10MVA and above 33/11KV transformers.
b) For Transformer rating less than 10MVA, space to be kept for installation of Numerical Differential
relay in future.
c) Non-directional, IDMT, three over current protection with high set instantaneous unit at HV side.
d) Restricted Earth fault protection for HV & LV.
e) Flag relays for transformer mounted protection like buchholtz, winding temperature, oil temperature,
pressure relay device etc.
f) Under frequency relay operated CB tripping scheme.
g) One no. 96 relay alongwith 95/96 relay for Phase Overcurrent LBB protection.

18.12 33kV SHUNT CAPACITOR BANK PROTECTION:

a) Non directional IDMTL Overcurrent & Earth Fault protection relay.


b) Unbalance Protection scheme relays for double star connected capacitor bank with floating neutral.
The relay used shall detect two current levels, one for alarm & another for tripping. It shall be able to
provide alarm in the event of failure of one or two units before tripping.
c) Over voltage & Undervoltage protective relay with both Definite time and Inverse time characteristics
as well as provision for Line and Phase voltage setting.
d) CB closing shall have interlock with a timer as per Capacitor discharge time so that the CB cannot be
closed within the capacitor discharging time.
e) One no. 96 relay alongwith 95/96 relay for Phase Overcurrent LBB protection.

18.13 BUS CONFIGURATION FOR 400KV, 220KV, 132KV AND 33KV SYSTEM OF
DIFFERENT S/S.:
Bus configuration for various voltage class shall be as per respective Tender document.

18.14 Approximate route length of different circuits of 400KV, 220KV and 132KV system controlled by
different feeder bays are as stated in GCC under “Scope of work”.

19.01 SYNCHRONISATION:

For sub-station equipped with sub-station Automation system, the requirement of synchronisation is
specified in the respective section under Sub-station Automation System and the same shall prevail.
For other sub-station which is not equipped with Sub-sub-station automation system following shall
be applicable as per requirement.
In such cases, where Trolley cannot be used for Synchronisation, Synchro check function should be
part of the main relay (if available) else stand-alone Synchro-check relay is to be considered. The

WBSETCL : Feb 2021 Page 40 of 53 Control & Relay Panel


relays equipped with synchronism and energizing check shall comply with the requirements as
mentioned below:
i) Settable voltage, phase angle, and frequency difference.
ii) Energizing for dead line - live bus, live line - dead bus or dead line– dead bus with no
synchro-check function
iii) Synchronising between live line and live bus with synchro-check function
One synchronising panel mounted on a movable trolley shall be provided for use in 400KV system
and another one for both in 220KV & 132KV system, wherever mentioned in the schedule. For
400KV synchronization shall be achieved by comparing between phase to phase voltage and for
220KV & 132KV, synchronization shall be achieved by comparing between phase to neutral voltage.
At existing sub-stations, the synchronising scheme shall be engineered to be compatible with the
existing synchronising scheme and synchronising socket/switch on the panel.

The trolley shall be equipped with –


a) Two Analog voltmeters for running & incoming, each having scale suitable for 400KV, 220KV & 132KV
system and also suitable for operation with CVT/ EMVT secondary voltage of 110v phase to phase.
b) Two Analog frequency meters each having scale range 45 to 55Hz, indicating type.
c) One suitable synchroscope with cut – off switch.
d) One suitable auxiliary voltage transformer for synchronising condition.
e) One synchronising bypass switch with necessary under voltage relaying scheme of running system
and incoming system to check inadvertent circuit breaker closing under synchronising bypass
condition.
f) One check synchronising relay with necessary auxiliary equipment which shall permit the circuit
breaker to close after checking the requirement of synchronising of incoming and running supply.
g) One guard relay to prevent the closing attempt by means of synchronising check relay when control
switch is kept in close position long before the two systems are in synchronism.
h) Two synchronizing lamps of white colour.
i) One green LED indicating lamp to indicate check synchronism in limit.
j) One red LED indicating lamp to indicate check synchronism by pass.
k) Any other equipment required to render satisfactory operation of synchronism.

19.02 MANDATORY SPARES:


Shall be supplied as per schedule.

20.00 SCHEDULE OF EQUIPMENT OF DIFFERENT PANELS:


Though the Bidder has to design the Control Panel and Protection Schemes for all the bays, which are
within the scope of the tender, as per the protection philosophy specified in the specification under Cl.
No. 18.00., the lists of equipment is given below for general guidance of the bidder. The actual
requirement for different substations is to be assessed by the bidder and to be quoted accordingly for
successful operation of the control and protection scheme. Same shall be finalized during
detailed engineering and if any additional equipment be found necessary for proper
operation, match and coordination with the existing panel, the same shall also be
arranged by the bidder without any extra price.

WBSETCL : Feb 2021 Page 41 of 53 Control & Relay Panel


20.01 CONTROL PANEL EQUIPMENTS FOR DIFFERENT VOLTAGE CLASS:

Name of Equipment Quantity Name of Panel Remarks


Digital Ammeter 3nos Each bay
Digital Wattmeter with 1set Each Line bay, Trafo bay, Tie
Transducer bay (in case of One & Half
Breaker system), Bus Transfer
bay, Bus Coupler bay
Digital Varmeter with 1set Each Line bay, Trafo bay, Tie
Transducer bay (in case of One & Half
Breaker system), Bus Reactor
bay, Capacitor bank bay, Bus
Transfer bay, Bus Coupler bay
Digital Voltmeter 2no Each Bus Coupler bay (in case If Two nos PTs are
of 2M1T system or 2M system) used in 1M system
and in any one bay (in case of with Bus Section
One & Half Breaker system) CB, two separate
voltmeters are to
be considered.
Digital Voltmeter Selector 2no Each Bus Coupler bay (in case If Two nos PTs are
switch (8 – position) of 2M1T system or 2M system) used in 1M system
and in any one bay (in case of with Bus Section
One & Half Breaker system) CB, two separate
voltmeter selector
switches are to be
considered.
Digital Voltmeter 1no Each Line bay (400kV only) and
Bus Transfer bay (in case of
1M1T system) and Capacitor
Bank bay
Digital Voltmeter Selector 1no Each Line bay (400kV only) and
switch (8 – position) Bus Transfer bay (in case of
1M1T system) and Capacitor
Bank bay
Power Factor Meter 1no Capacitor Bank bay
Digital Frequency Meter 2no Each Bus Coupler bay (in case
of 2M1T system or 2M system)
and in any one bay (in case of
One & Half Breaker system)
Digital Frequency Meter 1no Each Bus Transfer bay (in case
of 1M1T system)
Recording Voltmeter 2no Each Bus Coupler bay (in case
(Digital) of 2M1T system or 2M system)
and in any one bay (in case of
One & Half Breaker system)
(400kV only)
Recording Frequency meter 2no Each Bus Coupler bay (in case
(Digital) of 2M1T system or 2M system)
and in any one bay (in case of
One & Half Breaker system)

WBSETCL : Feb 2021 Page 42 of 53 Control & Relay Panel


(400kV only)
Multi-function Meter 1no Each bay To be considered
only in SAS
substations having
only Relay panel,
no Control panel.
CB Control Switch 1no For each Circuit Breaker (132kV
(Discrepancy type) & above)
CB Control Switch (Pistol 1no For each Circuit Breaker (33kV
grip type) & below)
Control Switch (Pistol grip 1no For each Isolator & Earth Switch
type)
Trip Transfer Switch 1no Each Line bay, Trafo bay, Bus
Reactor bay (in case of 2M1T
system or 1M1T system)
DC supply selector switch 1no Each bay (132kV & above)
(Supply 1-Independent-
Supply 2)
Bus VT selector switch (Bus Bus Coupler Each bay (in case Each bay of 132kV
VT 1 / Bus VT 2) of 2M1T/ 2M/ 1M1T system or class and above, if
2M system) of 132kV class and Two nos PTs are
above used in 1M system
AND with Bus Section
Each 33kV bay CB.
Discrepancy Switch Steady 1no Each Bus Coupler bay (in case
Lamp cut-off Switch of 2M1T system or 2M system),
Each Bus Transfer bay (in case
of 1M1T system) and in any one
bay (in case of One & Half
Breaker system)
Under Frequency protection 1no. For each 33kV panel (Feeder
ON-OFF Selector Switch bay and 33/11kV Trafo bay)
Back-up Earth Fault 1no. For each 33kV panel (Feeder
protection ON-OFF Selector bay and 33/11kV Trafo bay)
switch
Earthing Transformer 1no. For each 33kV panel (33kV side
Selection Switch (5- bay of 132/33kV Trafo &
position) 220/33kV Trafo)
LED Semaphore 1no For each Isolator & Earth Switch
LED Semaphore 1no For each Circuit Breaker (33kV
& below)
Amber LED Indicating Lamp As Reqd. For DC Fail indication
White LED Indicating Lamp As Reqd. For CB Trip coil healthiness
(One no for indication
each pole
for Single
pole
operated
CBs)
Blue LED Indicating Lamp As Reqd. For CB Spring Charged
indication
Phase Healthy Indicating 6nos Each Bus Coupler bay (in case

WBSETCL : Feb 2021 Page 43 of 53 Control & Relay Panel


Lamp of 2M1T system or 2M system)
Phase Healthy Indicating 3nos Each Bus Transfer bay (in case
Lamp of 1M1T system)
Yellow LED Indicating Lamp As Reqd For CB Auto Trip indication
(33kV & below)
Red LED Indicating Lamp As Reqd For CB ON indication
Green LED Indicating Lamp As Reqd For CB OFF indication
Annunciation windows wih As per For each Control panel
associated lamps etc. scheme
requirement
(Minimum
20nos.)
Push button for 3nos For each Control panel
Annunciator Alarm accept/
reset/ test
AC buzzer for DC fail alarm 1set Each Bus Coupler bay (in case
and associated relays for of 2M1T system or 2M system)
Annunciation scheme and Each Bus Transfer bay (in
case of 1M1T system)
DC bell for trip alarm, DC 1set For each Control panel
hooter for non-trip alarm,
associated relays for
Annunciation scheme
Push Button for Protection As Reqd For each Control panel
DC Fail check, CB Spring
Charge check, CB Trip Coil
Healthy check, DC Fail
Alarm accept, AC Fail check
etc.
One no. push button each 1set Each Bus Coupler bay (in case
for Main DC Fail Test, of 2M1T system or 2M system)
Annun DC Fail Test, Main and Each Bus Transfer bay (in
DC/ Annun DC Fail Accept, case of 1M1T system)
AC Fail Test and one no.
LED indicating lamp
(amber) each for Main DC
Fail, Annun DC Fail visual
indication.
Synchronising Socket and 1no each Each Line bay, Trafo bay, Bus Not required for
Synchronising selector Coupler bay, Bus Transfer bay, 132kV side of
Switch Tie bay (in case of One & Half 132/33kV Trafo
Breaker system),
RWTI with Selector switch 1no each Each Bus Reactor bay
ROTI 1no Each Bus Reactor bay
TTB with wiring for 1no Each Line bay, Trafo bay, Tie
intelligent electronic bay (in case of One & Half
computer compatible Breaker system)
energy meter (0.2 class)
Common items e.g. Mimic; As Reqd For each panel

WBSETCL : Feb 2021 Page 44 of 53 Control & Relay Panel


Circuit Label; Label
indicating Manufacturer’s
Name, P.O. details, Drg.
Ref. nos etc.; internally
mounted equipments like
Heater with Switch
&Thermostat, AC Cubicle
lamp with On/Off switch,
DC Emergency Cubicle
lamp with On/Off switch,
Corridor Illumination lamps
with door switches at both
ends ofthe corridor, 5/15A
Power Socket with On/Off
switch, Switches, Fuses,
Links etc. in line with Tech
Spec.

20.01 COMMON RELAY/ PROTECTION PANEL EQUIPMENTS FOR DIFFERENT VOLTAGE CLASS:

Name of Equipment Quantity Name of Panel Remarks


Common items e.g. Circuit As Reqd For each panel
Label; Label indicating
Manufacturer’s Name, P.O.
details, Drg. Ref. nos etc.;
internally mounted
equipments like Heater with
Switch &Thermostat, AC
Cubicle lamp with On/Off
switch, DC Emergency
Cubicle lamp with On/Off
switch, Corridor
Illumination lamps with
door switches at both ends
ofthe corridor, 5/15A Power
Socket with On/Off switch,
Switches, Fuses, Links etc.
in line with Tech Spec.
Bus PT selection scheme 1set For each panel (2M1T system & Except Bus Coupler
with bi-stable relays for 2M system) bay
Double Bus arrangement
Stand-alone Supervision As Reqd For each Circuit Breaker
Relays for CB Trip coils, 86
relay, 96 relay
LBB protection scheme with 1set For each Circuit Breaker (132kV
stand-alone 96 relay, aux & above)
relay etc.
Phase Overcurrent LBB 1set For each 33kV Feeder bay,
protection with stand-alone Capacitor bay and 33kV side bay
96 relay, aux relay etc. of 33/11kV Trafo

WBSETCL : Feb 2021 Page 45 of 53 Control & Relay Panel


Auxiliary relays for C.B. 1set For each Circuit Breaker
Closing/Tripping, if
necessary
CB Monitoring scheme with 1set For each Circuit Breaker Each coil should
Flag Relays/Aux. Relays (Minimum have minimum 3NO
6nos.) contacts. Multiplier
for CB SPRING
CHARGE status
should also have an
NC contact for
SPRING CHARGE
FAIL annunciation.
GIS Monitoring scheme As Reqd For each GIS bay
with Flag Relays/ Aux.
Relays
Stand-alone Protection DC 1 No each For each bay
Supply Supervision Relay for DC-1 &
DC-2
Main DC (for both DC-1 & 1 No. each Each Bus Coupler bay (in case of
DC-2), Annun DC, AC 2M1T system or 2M system) and
Supervision Relays Each Bus Transfer bay (in case
of 1M1T system)
Stand-alone Bus Bar 1 No Busbar protection panel
Protection DC supply
Supervision Relay
Main DC, Annun DC Fail 1 No. Each Bus Coupler bay (in case of
Alarm Accept Relay 2M1T system or 2M system) and
Each Bus Transfer bay (in case
of 1M1T system)
CB Discrepancy scheme 1set Each Bus Coupler bay (in case of
with Flasher relay & Timer 2M1T system or 2M system) and
Each Bus Transfer bay (in case
of 1M1T system)
Test Terminal Block As Reqd For each bay
Bus Transfer Bay Protn. 1 No. Each Bus Transfer bay
IN/OUT Selector Switch
Distance Relay Setting 1 No. Each Feeder bay & Bus Transfer
Group Selector Switch, 4 – bay (132kV & above)
position
O/C & E/F Relay Setting 1 No. Each Bus Transfer bay
Group Selector Switch, 3 –
position, TRAFO – OFF -
LINE
‘Bay transfer sequence 1set For each bay (in case of 2M1T
Incomplete’ alarm scheme system or 1M1T system)
with Timer
One no. push button each 1set For each bay
for LED reset of Numerical
relay, reset of 86 relay and
reset of 96 relay

WBSETCL : Feb 2021 Page 46 of 53 Control & Relay Panel


Notes:

i) In case of incomplete diameter (D and I type layouts), control panel shall be equipped fully as if the
diameter is complete, unless otherwise specified. Annunciation shall also be considered for the same
and if required, necessary panel shall be supplied to accommodate the same.
ii) The above list of equipments mentioned for control panel is generally applicable unless it is defined
elsewhere and in case of bay extension in existing substations, necessary equipments for matching
the existing control panel shall be supplied.

WBSETCL : Feb 2021 Page 47 of 53 Control & Relay Panel


20.02 RELAY/ PROTECTION PANEL EQUIPMENTS FOR DIFFERENT VOLTAGE CLASS:
FEEDER BAY
400kV 220kV 132kV 33kV 11kV
One no. Numerical relay for Main – I Distance Protection scheme/ Line Differential
--- ---
Protection scheme, as applicable as per resp. Clause
One no. Numerical relay for Main – II Distance Protection scheme/ Line Differential
--- --- ---
Protection scheme, as applicable as per resp. Clause
One no. Numerical relay for Directional O/C & E/F Protection scheme/ Distance
--- --- --- ---
Protection scheme, as applicable as per resp. Clause
Single and Three Phase Auto-reclosing scheme including aux. relays & tripping relays --- ---
Auto Reclose Selector switch --- ---
One no. Numerical relay for Directional O/C & E/F Protection scheme
--- ---
(Non Dir)
One no. Numerical relay for Over Voltage Protection scheme --- --- --- ---
One no. Line CVT operated Under Voltage relay
Flag relays, Carrier Receive relays, Carrier Healthy relays, DT Receive relays, Aux. As Reqd. As Reqd. As Reqd. As Reqd. As Reqd.
relays, Timers etc. as per scheme requirements (each coil having minimum 6nos. NO
contact)
Master Trip relays (86A and 86B)
Master Trip relay (only 86)
Carrier Selector Switch (One no. for each Distance protection relay)

Auto Reclose Selector Switch (ON-OFF)

Auto Reclose Selector Switch (Main I-Main II)

Selected Bus VT/ Line CVT Selector scheme and associated Relay, as finalized during
detail engineering (If Line
CVT is
available)
Carrier Received LED Indicating Lamp

DT Received LED Indicating Lamp

WBSETCL : Feb 2021 Page 48 of 53 Control & Relay Panel


HV SIDE OF TRAFO BAY
400kV side of 220kV side of 132kV side of 33kV side of
400/220kV 220/132/33kV 132/33kV Trafo 33/11kV
Trafo Trafo Trafo
Numerical Differential Protection scheme
(10MVA &
above)
Numerical Directional O/C & E/F Protection scheme
(with Check- (with Check- (with Check- (Non Dir)
Sync facility) Sync facility) Sync facility)
Numerical Over Flux Protection scheme

Overload Protection scheme

REF Protection scheme

Numerical Neutral Displacement Protection scheme

Power Transformer Auxiliary Protection scheme with Flag Relays/Aux. Relays (Minimum
8 nos. Flag relays, each having minimum 6nos. NO contact for Power Transformer
trouble trip status and Minimum 6nos Flag relays, each having minimum 3nos. NO
contact for Power Transformer trouble alarm status)
Master Trip relays 86A and 86B

Master Trip relay (only 86)

LV SIDE OF TRAFO BAY


220kV side of 132kV side of 33kV side of 33kV side of 33kV side 11kV side
400/220kV 220/132kV 220/132/33kv 132/33kV of 220/33kV of 33/11kV
Trafo Trafo Trafo Trafo Trafo Trafo
Numerical Directional O/C & E/F Protection scheme
(with Check- (with Check- (Non Dir) (Non Dir)
Sync facility) Sync facility)
Numerical Over Flux Protection scheme

REF Protection scheme

Definite time Numerical E/F relay for ET protection scheme (For


Yd Transformer)

WBSETCL : Feb 2021 Page 49 of 53 Control & Relay Panel


Earthing Transformer Auxiliary Protection scheme with Flag
Relays/Aux. Relays (Minimum 3 nos. Flag relays, each having
minimum 3nos. NO contact)
Master Trip relays 86A and 86B

Master Trip relay (only 86)


P.T. selection scheme with bi-stable relays for Double Bus
arrangement
BUS COUPLER BAY
400kV 220kV 132kV 33kV 11kV
Numerical Non-Directional O/C & E/F Protection scheme with Check-Sync facility
Under Frequency protection scheme

Master Trip relays 86A and 86B

Master Trip relay (only 86)

BUS TRANSFER BAY


400kV 220kV 132kV 33kV 11kV
Numerical Distance Protection scheme
Numerical Directional O/C & E/F Protection scheme

Selected Bus VT/ Line CVT Selector Switch ( Line VT- Inter1-Inter2-Selected Bus VT)

Master Trip relays 86A and 86B

Master Trip relay (only 86)

TIE BREAKER BAY


Main – I Numerical Teed Protection scheme with aux relays, trip relays etc.

Main – II Numerical Teed Protection scheme with aux relays, trip relays etc.

WBSETCL : Feb 2021 Page 50 of 53 Control & Relay Panel


Master Trip relays 86A and 86B

400kV Reactor bay


Numerical Differential Protection scheme

REF Protection scheme

Back-up Impedance Protection scheme


Reactor Auxiliary Protection scheme with Flag Relays/Aux. Relays

Master Trip relays 86A and 86B

33kV Capacitor Bank bay


Numerical Non-Directional O/C & E/F Protection scheme
Numerical Under voltage/ Over-voltage Protection scheme

Numerical Unbalance Protection scheme

Time delay relay

Master Trip relay (only 86)

Notes:

i) In a substation where 400kV and 220 KV lines are under the scope of the contract, bidder is required to give identical Main-1 and Main-2 distance
protection schemes for all voltage levels.
ii) These are the main protections. However, other ancillary relays required for the respective C&R panel viz. Trip Circuit supervision relay, Direct Trip
Command relay, Transformer trouble relay, High speed trip relays, contact multiplication relay etc shall be as per tender technical specifications.

WBSETCL : Feb 2021 Page 51 of 53 Control & Relay Panel


20.03 BUS ZONE PROTECTION FOR 400KV, 220KV & 132KV SYSTEM:
All Equipment/ relays, trip relays with trip coil supervision relay, Local Breaker Back-up
protection relay, CT Switching relay etc for all connected bays and bus extension bays with
the provision of future bays along with CPU & Bay unit for the bus bar protection scheme as
required for busbar protection as per resp. Clause shall be provided in one set of separate
simplex type panel.

21.00 DEVIATION:

Normally the offer should be as per technical specification without any deviation. For any
deviation in the tender quoted by the tenderer, the same shall be clearly indicated in the
deviation sheet, clause by clause, indicating reason and advantage for such deviation. Such
deviations may or may not be accepted. Deviation not indicated in the deviation sheet will not
be considered.

22.00 RECOMMANDED SPARES:

A list of spares recommended by the bidder for ten years satisfactory performance along with
item wise unit price shall be furnished with the tender. The purchaser will decide the actual
quantity of spares to be ordered on the basis of the list and item wise prices quoted. This
shall not be taken into consideration for the purpose of evaluation of bid.

23.00 TENDER DRAWING, LITERATURE AND TEST CERTIFICATES BOTH FOR ROUTINE
TESTAND TYPE TEST:
Following drawings, literatures, filled up GTP and test certificates shall be submitted with the
tender for evaluation:
a) Principal dimensioned details of each unit cubicle and complete assembly of panel board.
b) Front and rear views of the panel board with instrument and device positions marked.
c) Details of protection scheme of lines, transformers and other bays including annunciation,
monitoring, supervision etc. offered.
d) Literature describing the instruments, switches, relays and their characteristics, technical
details, relay setting calculation, operating manual etc.
e) Routine and type test certificates of all the protective relays carried out as per relevant IEC/
IS from a recognised laboratory shall be furnished. Performance certificate of all protective
relays from Power Utilities in India shall also be furnished.

24.00 CONTRACT DRAWING AND LITERATURE:


24.01 The following drawings in six (6) copies of each are to be submitted by the successful bidder
for approval of the purchaser before starting manufacturing of the same.

a) Detailed dimensional drawings of control and relay panel including foundation drg. with cable
slots showing all equipment mounted on them along with complete panel wise list of
equipmentand list of Name Plates. Weight of these panels with all the equipment mounted on
these shall also be furnished in the Drg.
b) Contact development drawings of all switches, relays etc.
c) All internal configuration logic built-up in Numerical IEDs/ BCUs.
d) Outlined drawings of internal wiring diagram of the instrument, relays, meters, annunciator
and other equipment showing external terminal connections with the equipment terminal
number.
e) Complete AC and DC Schematic diagram of all panels of control and relay board to indicate
the followings:
i) Annunciator circuit
ii) Protection and control circuit
iii) Indication and Supervision circuit
iv) Synchronising circuit
v) Other circuits as necessary

WBSETCL : Feb 2021 Page 52 of 53 Control & Relay Panel


These drawings shall show AC power connection and Secondary connections for relays,
meters, terminal blocks with their number etc. interconnection diagram between control and
relay board and circuit breaker, Power and Instrument Transformer and other equipment as
necessary.

24.02 After approval of above drawings ten sets of those drawings for each set complete set of C&R
board and wiring schedule including bus wire diagram for each panel are to be supplied by
the contractor.
One set of reproducible of the above drawings for each C&R board formation shall also be
supplied.

24.03 Six copies of the following literatures shall be supplied along with the approved drawings and
one set of the same (soft copy) shall be supplied along with the drawing in the
first submission:

a) Literature describing construction, operation, adjustment and rating specification of all


theprotective and auxiliary relays, recording instruments, metering instruments, control and
other switches, annunciators, fault locator, disturbance recorder and other equipments which
are used in the C&R panel.
b) List of spare parts, identification number of renewable parts of relays, instruments, switches
and other equipments with the help of which the purchaser will be able to procure spare
parts from the contractor at any subsequent line.
c) Commissioning, operating, maintenance instruction manual for each relay and equipment of
the panel.

25.00 TEST AT FACTORY:


The following tests shall be carried out and six (6) copies of test certificates along with test
result shall be supplied for approval.

a) Visual checking of C&R panel.


b) Checking wiring of circuits and continuity.
c) One minute applied voltage test. All equipments on panel and wiring shall be tested for a
withstand voltage of 2 KV between different circuits shorted and earth.
d) Insulation resistance of the complete wiring, circuit by circuit with all equipment mounted on
the board before and after HV test.
e) Routine tests according to the relevant standards on the instruments, relays and other
devices.

26.00 INSPECTION/ TEST WITNESS:

a) Tests shall be performed in presence of the purchaser's representative, if so desired by the


purchaser. The contractor shall give at least 21 (twenty one) days advance notice of the date
when the tests are to be carried out at manufacturer’s works.

b) Relays and meters may be further tested at our testing laboratory. If any equipment is found
to be not in conformity with the specification by our testing engineers during testing, the
same shall be replaced by you at your cost immediately.

WBSETCL : Feb 2021 Page 53 of 53 Control & Relay Panel

You might also like