Scadapack Es Hardware Manual
Scadapack Es Hardware Manual
Manual
2 SCADAPack ES Hardware Manual
Table of Contents
3
4 SCADAPack ES Hardware Manual
I SCADAPack ES Hardware
1 Technical Support
Support related to any part of this documentation can be directed to one of the following
support centers.
SCADAPack ES Hardware 5
2 Safety Information
Read these instructions carefully, and look at the equipment to become familiar with the
device before trying to install, operate, or maintain it. The following special messages may
appear throughout this documentation or on the equipment to warn of potential hazards or to
call attention to information that clarifies or simplifies a procedure.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can
result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can
result in minor or moderate injury.
CAUTION
CAUTION used without the safety alert symbol, indicates a potentially hazardous
situation which, if not avoided, can result in equipment damage..
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising
out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and
operation of electrical equipment and the installation, and has received safety training to
recognize and avoid the hazards involved.
CAUTION
EQUIPMENT OPERATION HAZARD
Verify that all installation and set up procedures have been completed.
Before operational tests are performed, remove all blocks or other temporary
holding means used for shipment from all component devices.
SCADAPack ES Hardware 7
Follow all start-up tests recommended in the equipment documentation. Store all equipment
documentation for future references.
Software testing must be done in both simulated and real environments.
Verify that the completed system is free from all short circuits and grounds, except those
grounds installed according to local regulations (according to the National Electrical Code in
the U.S.A, for instance). If high-potential voltage testing is necessary, follow
recommendations in equipment documentation to prevent accidental equipment damage.
Before energizing equipment:
Remove tools, meters, and debris from equipment.
Close the equipment enclosure door.
Remove ground from incoming power lines.
Perform all start-up tests recommended by the manufacturer.
3 Introduction
locally and remotely, without removing the RTU from its enclosure, or removing the lid. RTU
configurations are maintained in the on-board battery backed RAM and may be modified locally or
remotely.
10 SCADAPack ES Hardware Manual
4 Hardware Overview
This section presents a brief introduction to the major components of the SCADAPack ES
The SCADAPack ES is an advanced Remote Telemetry Unit (RTU) combining a high speed processor,
large memory capacity, analog and digital I/O, serial and Ethernet communications, IEC 61131-3 logic
and a number of industry standard protocols in a single unit. The complete specifications of the
SCADAPack ES RTU are in the Specifications 97 section of this manual.
Generally Power Supply ports and I/O ports are protected against surge voltages and other conditions.
However, if you need to remove the lid of the RTU for any reason, first observe the following warning.
CAUTION
The electronics inside the RTU can be destroyed by static electricity. If you need to
remove the lid you need to wear a wrist strap. This wrist strap needs to be
connected to the earth stud on the side of the unit. Not observing this simple step
can cause total or intermittent loss of operation and will void the warranty.
b Processor/Memory:
A. AMD Elan SC520 CPU - 32MB Operating System FLASH, 128MB volatile SDRAM, 2MB
Battery Backed SRAM
c Protocol options:
0. Modbus, DNP 3, Modbus TCP, TCP/IP (included in all controllers)
1. IEC 60870-5-103 Master, Protection Relay Protocol (for data transmission with IEDs)
2. IEC 60870-5-101 Slave, Standard Telecontrol Tasks (allows a 101 Master to get data &
send commands to the SCADAPack ES)
3. both IEC 60870-5-103 Master and IEC 60870-5-101 Slave protocol options
e License Option:
A. None
B. Data Concentrator License
SCADAPack ES Hardware 11
f I/O configuration:
DI DO AI AO
A. 32 16 12 4 - Fully populated I/O
B. 0 0 0 0 - Telemetry Processor
E. 16 8 6 2 - Partially populated I/O
g Power Supply:
0. 10-30 Vdc Wide Range Power input, no auxiliary power supply.
1. 10-30 Vdc Wide Range Power input, auxiliary power supply with 5 Vdc output.
2. 10-30 Vdc Wide Range Power input, auxiliary power supply with 10 Vdc output.
3. 10-30 Vdc Wide Range Power input, auxiliary power supply with 24 Vdc output.
j Custom Options:
None. (default range is 4-20mA)
V. Analog Input range set for 1-5v
C. Custom Analog Input Range (specify range)
12 SCADAPack ES Hardware Manual
DC-In Removable 3 YES Power supply input (10 to 30Vdc) and chassis
position terminal.
DC-Out Removable 3 YES Power supply output (5, 10 or 24Vdc nom.) and
position chassis terminal.
Analog Inputs Optical (channel to channel AND Fuse, zener diode and gas surge
channel to RTU) arrestor
External I/O is isolated from the RTU logic and are protected against surge voltages and other
conditions.
14 SCADAPack ES Hardware Manual
Utility Port Compact Flash Socket, OS Flash, & Boot Monitor Flash 16
Microprocessor (CPU)
The CPU is an AMD Elan SC520 Embedded device operating at 100MHz. The CPU executes a pre-
emptive multi-tasking operating system allowing the simultaneous, real-time, provision of:
Communications protocols (DNP3, TCP/IP, IEC60870-5 suite, Modbus, etc)
Time stamped event processing
Configuration management
User application execution (ISaGRAF)
RAM
The battery backed RAM is used to store
User Configuration (point definitions, port configurations etc)
User defined sequence and control applications (ISaGRAF)
Time stamped event data
16 SCADAPack ES Hardware Manual
4.4.2 Utility Port Compact Flash, OS Flash, & Boot Monitor Flash
CAUTION
The UTILITY port supports the insertion and removal of Compact Flash or utility
cards on-line (hot-swap). However, the operation of the SCADAPack ES may be
adversely affected by doing so, particularly removing cards that are in use by the
SCADAPack ES.
The UTILITY and optional internal Compact Flash interfaces support the following card types:
3.3V card types only supported
up to 2GB memory capacity cards supported
Ports 2 and 3 support the software selection of RS-232, RS-422, or RS-485. Other ports only support
RS-232.
Ethernet Ports
The SCADAPack ES has two 10/100Base-T Ethernet Ports that can be used for TCP/IP communication
and Remote I/O.
The SCADAPack ES provides a range of TCP/IP services including FTP, TELNET, BOOTP, as well as
providing other TCP/IP enabled protocols such as DNP3 and Modbus.
The Ethernet Ports are disabled by default.
18 SCADAPack ES Hardware Manual
PORT 0 RS-232
PORT 1 RS-232
PORT 4 RS-232
5 Installation
The following sections of the user manual describe specific aspects of installing the SCADAPack ES.
SCADAPack ES units are factory configured and under normal conditions do not require removal or
insertion of any peripherals or components. The configurations are stored in a combination of battery
backed RAM and FLASH memory. The battery has a shelf life of ~8 years. Life of the battery may be
increased past 8 years when the RTU is permanently connected to a power source.
CAUTION
The configuration information can be lost if the on-board battery goes flat, is
disconnected, if the RTU is damaged, or if there has been a firmware upgrage.
20 SCADAPack ES Hardware Manual
5.1 Mounting
Refer to Figure 6.1 20 for the locations of the 4 mounting holes for the SCADAPack ES.
WARNING
The Class 1, Division 2 for Hazardous Locations version of the SCADAPack ES
has a cover with integrated connector retention. Check that when replacing the
cover that all connectors have been secured and that connector removal is not
possible.
0.315" 11.260"
8mm 286mm
1.083"
27.5mm
4.055"
103mm
DI DI DI DI DO DO DO DO DO DO DO DO AI AI AI AI AI AI AOUT AOUT
17- 20 21 - 24 25 - 28 29 - 32 9 10 11 12 13 14 15 16 7 8 9 10 11 12 3 4
Ethernet Port 2 J14 J16 J18 J20 J22 J24 HEX SW1
HEX SW2
Port 2
RX TX
J2 J4 J6 J8 J10 J12 Port 3
Utility
Run
DI DI DI DI DO DO DO DO DO DO DO DO AI AI AI AI AI AI AOUT AOUT
1-4 5-8 9 - 12 13 - 16 1 2 3 4 5 6 7 8 1 2 3 4 5 6 1 2
5.3 Grounding
CAUTION
The SCADAPack ES case includes an Earth connection stud located adjacent to
the power connector terminal block. This Protective Conductor stud needs to be
connected to Earth.
The earth connection stud on the RTU’s case and the earth connection on the RTU’s power supply
terminal block should be connected to a clean earth point in the cabinet in which the RTU is installed.
Each piece of equipment (or multiple units) should be connected to the same earth point in a star
configuration.
The DC resistance between each item and the earth point should be < 0.1 ohms.
SCADAPack ES Hardware 23
WARNING
SELV (Safety or Separated Extra Low Voltage) power supplies are required on the
power input and I/O points. Power supplies with 100-240Vac inputs that comply
with safety standard IEC/EN 60950 generally have SELV outputs. Check with the
manufacturer or the agency certification listing to confirm that they have SELV
outputs.
The following 100-240Vac input, 24VDC output power supplies have SELV outputs:
Idec PS5R series (7.5 to 240W)
Weidmuller 9928890024 CP SNT 24W 24V 1A
Phoenix 2866983 MINI-SYS-PS-100-240AC/24DC/1.5
24 SCADAPack ES Hardware Manual
FS1
DC Input Power
FS2
Fuse +
FS3 +
Power supply or Battery
– –
FS4
Chassis connection suitable for cable shield
+
+
Auxiliary load
CPU Board – –
DC Auxiliary
Output
The SCADAPack ES has an Auxiliary Output available on a 3 terminal connector, labeled O/P on the
module cover.
The RTU is manufactured with several optional versions of the Auxiliary Output as shown in the table
below.
Refer to the SCADAPack ES Model Numbers 10 and Specifications 97 sections in this manual for
the voltage output and the ratings of the auxiliary DC output.
Description Comments
5VDC 5VDC (1A) is available at connector O/P. The same 5VDC is also
connected to the expansion I/O connector.
The output capacity needs to be de-rated at high temperatures. Refer to the Specifications 97 section
of this manual.
CAUTION
A SCADAPack ES with 5000 Series I/O modules or Vision display installed needs
to be configured to supply sufficient power for these devices. Refer to the modules
specification for specific power requirements. It is recommended that systems with
5000 Series I/O modules be configured with a 5V Auxiliary Output.
26 SCADAPack ES Hardware Manual
Internal fuses are provided for last resort protection of the SCADAPack ES.
It is highly recommended that external fuses and circuit breakers be used for protection and isolation of
the unit and associated power supplies.
External fuses to protect analog input circuits should be provided.
The DC Supply I/P and Auxiliary DC O/P fuses require removal of the upper I/O board before
replacement. The locations of FS1 through FS4 are shown in Figure 6.3 23 .
WARNING
RISK OF EXPLOSION
Before replacing the fuse verify that the area is non-hazardous and disconnect
power.
Failure to follow these instructions can result in death, serious
injury or equipment damage.
Before replacing the fuse assess the impact that disconnecting power may have on other devices.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment monitored and controlled by the
SCADAPack E RTU.
Replace a blown fuse with a fuse of the same rating. Under no circumstances should a fuse be
bypassed or replaced with a fuse of a higher rating.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Replace the fuse with a fuse of the same rating.
Littelfuse 396-1315
CMI part number 200091
Lower value fuses can be used in 24V
applications.
Digital Inputs are organized into groups of eight inputs each with a single (shared) common.
The common for a group of inputs is isolated from the common for other input groups on the same
SCADAPack ES I/O card.
Optical isolation is provided on digital inputs.
Wetting voltage for the volt-free contacts is usually provided by the SCADAPack ES DC power used with
the SCADAPack ES.
The example shown in Figure 6.4 29 below has one switch contact monitored by Digital Input 8.
17 18 19 20 21 22 23 24 COM 25 26 27 28 29 30 31 32 COM
I/O Board
1 2 3 4 5 6 7 8 COM 9 10 11 12 13 14 15 16 COM
+
Power Supply
–
The SCADAPack ES I/O board time-stamps digital input changes for Sequence Of Event (SOE)
applications.
The following table shows the SOE capabilities on the SCADAPack ES I/O board models.
‘A’ 10 ms 2500 ms 10 ms
‘E’ 10 ms 2500 ms 10 ms
30 SCADAPack ES Hardware Manual
The SCADAPack ES I/O board also provides digital input state de-bouncing. The minimum resolution for
de-bouncing and the maximum de-bounce period is shown in the table above.
If the SCADAPack ES configuration enables de-bouncing on a digital input channel, then SOE time-
stamping on the digital point has the same resolution as the de-bounce resolution.
Each digital input channel on the SCADAPack ES can also be used as a counter input. Specific digital
input channels have hardware counter support providing high-speed counter facilities. The other digital
input channels have support for configuration as software counters.
For more information see Section Counter Inputs 31 , and configuration information in the SCADAPack
E Configuration Technical Reference manual.
SCADAPack ES Hardware 31
SCADAPack ES digital input channel can also be used as counter input channel.
SCADAPack ES counter inputs are represented as 32-bit counters. As defined in the following table,
some inputs can be used as software counters only, whilst others have high-speed hardware counter
capability.
When Software-Only Counter Input channels are used, the corresponding digital input de-bounce and
invert settings are applied prior to counting transitions of the input. If set as non-inverting (default
configuration), counter input points count OFF to ON transitions. If configured as an inverted digital input
point, ON to OFF transitions are counted on the corresponding counter channel. De-bounce is applied
to input state changes in both directions, regardless of the point’s invert settings. A contact bounce of
duration less than the de-bounce period will not increment the software counter.
Hardware counting on hardware-capable counter channels does NOT include the capability for input de-
bounce or input state inversion. The hardware counts ON to OFF transitions only. It is recommended
that only clean-edge signals be counted using hardware counters.
If a de-bounce period is set on a digital input point corresponding to a Hardware-capable Counter input,
hardware counting is de-activated. The input will become a Software Counter with both de-bounce and
invert capability. In this case the software counter specifications apply.
32 SCADAPack ES Hardware Manual
NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C
DO 9 DO 10 DO 11 DO 12 DO 13 DO 14 DO 15 DO 16
I/O Board
DO 1 DO 2 DO 3 DO 4 DO 5 DO 6 DO 7 DO 8
C NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC NO
+
Load 3
–
+ Load 7 –
+
Power Supply
–
SCADAPack ES Model A RTU has 12 analog inputs for external connection to analog field devices.
Each analog input can be individually configured to accept one of the following input signals:
Standard calibration is 4–20mA
Optional calibration is 1–5V
Custom calibrations possible. Contact the factory.
The input signal for each input is selected through a combination of hardware jumpers and software
calibration.
Each analog input is optically isolated from both the SCADAPack ES logic electronics, and the other
analog inputs.
For each analog input channel there is one jumper. This jumper selects between current and voltage
input modes.
If a voltage exceeding 16VDC is connected to the Analog Input channel terminals, the AI
channel protection fuses will blow.
The analog inputs are polarity sensitive. The polarity is marked on the cover of the
SCADAPack ES and in Figure 6.6 35 .
The default analog input calibration is 4-20mA. Removal of the jumper associated with the analog input
will result in an un-calibrated 1-5V analog input. Refer to Table 6.5 34 for jumper settings for analog
inputs.
AI 1 AI 1 J2
AI 2 AI 2 J4
AI 3 AI 3 J6
AI 4 AI 4 J8
AI 5 AI 5 J10
AI 6 AI 6 J12
AI 7 J14
AI 8 J16
AI 9 J18
AI 10 J20
SCADAPack ES Hardware 35
AI 11 J22
AI 12 J24
If an Analog Input channel is changed from Current to Voltage mode or from Voltage to Current mode,
the AI channel calibration should be checked.
The example shown in Figure 6.6 35 below has Transmitter 1 "grounded" and connected to AI1.
Transmitter 6 is connected to the +ve supply and AI6. These two different connections are possible
because the SCADAPack ES has isolated analog inputs.
The SCADAPack ES has extensive spike and over-voltage protection on each analog channel,
consisting of: gas arrestors, fuses, zener diodes and spike filters. If a transducer/transmitter connected
to an analog channel is placed outside of the building or structure where the SCADAPack ES is
installed, there is an increased possibility of extremely severe surges caused by lightning. In such cases
additional surge protection needs to be supplied by the user.
Presentation of analog channel quantities to the SCADAPack ES software is described in the
SCADAPack E Configuration Technical Reference manual.
36 SCADAPack ES Hardware Manual
+ – + – + – + – + – + –
AI 7 AI 8 AI 9 AI 10 AI 11 AI 12
I/O Board
J2 J4 J6 J8 J10 J12
AI 1 AI 2 AI 3 AI 4 AI 5 AI 6
– + – + – + – + – + – +
+ Transmitter 1 –
+ + Transmitter 6 –
Power Supply
–
The analog output (AO) channels need to be powered with an external 9 to 30VDC (nominally 12 or
24VDC) power supply. The SCADAPack ES analog output channels can be configured to be 4-20mA or
0-20mA. If a voltage output is required (say 1V-5V), run the 4-20mA signal to the device requiring the
voltage input and place a 250 Ohm resistor across the device input terminals. The analog output is
electrically isolated from the rest of the RTU, but not isolated from the power supply.
There is a set of two jumpers controlling the operation of each analog output channel. These are 3 pin
jumpers that have been permanently configured for external power required in the SCADAPack
ES.
The example wiring shown in Figure 6.7 37 shows a load connected to AOUT2.
24V 0V + – 24V 0V + –
AOUT 3 AOUT 4
AOUT 1 AOUT 2
– + 0V 24V – + 0V 24V
+
L
O
A
D
–
+
Power Supply
–
The AO circuitry is configured internally to accept power from an external power supply on pins 3 and 4
of the removable terminal block. Pin 1 (AO –) and pin 3 (power input –) are connected internally. Analog
38 SCADAPack ES Hardware Manual
outputs are isolated from each other and the RTU logic.
Figure 6.8 38 below displays the allowable output resistance range for any given AO input supply
voltage. The load resistance for any given power supply voltage is limited on the high resistance end by
the requirement for proper operation of the analog output circuit and on the low resistance end to limited
the power dissipation in the analog output. For instance, if the AO channel is powered using a 12VDC
supply, the load resistance needs to be in the 0 to 250 ohm range. If the AO channel is powered using
a 24VDC supply, the load resistance needs to be in the 0 to 850 ohm range. If the AO channel is
powered using a 30VDC supply, the load resistance needs to be in the 150 to 1150 ohm range.
1200
1000
800
Load 600
resistance
(ohms) 400
Resistance
limits
200
0
10 20 30
Power supply (V)
Figure 6.8: Analog Output Load Resistance Range
SCADAPack ES Hardware 39
The SCADAPack ES I/O can be expanded using 5000 Series I/O expansion modules. The maximum
number of modules that can be added is 16. The 5000 Series I/O modules mount on DIN rails. Modules
addresses are configured using onboard DIP switches. Additional configuration is also possible on
some modules using onboard DIP switches.
For additional information on this feature, including supported I/O modules, refer to the SCADAPack E
5000 Series I/O Expansion Reference manual. Refer to the user manual for each expansion module for
configuration information.
The following 5000 series I/O modules are supported by SCADAPack ES controllers
Power Requirements
5000 Series Input/Output modules require 5V. The SCADAPack ES controller provides this 5V.
SCADAPack ES models have a limited amount of current available at 5V. It is recommended that
applications that use 5000 Series I/O expansion be configured with a 5V Auxiliary supply. Refer to the
Power Supply 100 section for the power limitations of these 5V outputs.
Some of the 5000 Series I/O modules require a nominal 24Vdc to power the field side circuitry. Refer to
the individual module specifications for the voltage limits and the current requirements for these modules.
SCADAPack ES Hardware 41
5000 Series I/O modules are supplied with a short inter module cable suitable for connecting two
adjacent modules. In larger systems it may become necessary to use longer inter module cables (IMC)
to complete the system. These longer cables are available in a variety of different lengths ranging from
12 inches (0.3m) to 450 inches (1.14m) long.
The inter module cable connects to the connector in the lower right corner of the SCADAPack ES as
shown in Figure 6.9 41 .
Ports 0, 1, & 2 44
Ports 3 & 4 45
See the RJ-12 Modular Connector 46 and the Serial Communication Cables 47 sections for
connection details on serial ports.
Port 0
PORT 0 is a general-purpose serial data communications port. This port is fixed as an RS-232C
communication port. Port 0 uses an industry standard RJ-12 terminal socket conforming to RS-232
standards. The RJ-12 connection on the SCADAPack ES is a Data Terminal Equipment (DTE)
connection.
Default setting: RS232C, 9600 bps, 8 data bits, 1 start bit, 1 stop bit and no parity.
Port 1
PORT 1 is a general-purpose serial data communications port. This port is fixed as an RS-232C
communication port. Port 1 uses an industry standard RJ-12 terminal socket conforming to RS-232
standards. The RJ-12 connection on the SCADAPack ES is a Data Terminal Equipment (DTE)
connection.
Default setting: RS232C, 9600 bps, 8 data bits, 1 start bit, 1 stop bit and no parity.
Port 2
PORT 2 is a general-purpose serial communication data port. This port is normally configured as an RS-
232C communication port. Optionally, it can be configured as an RS-422 port or RS-485 port by
selecting RS-422 or RS-485 for PORT 2 using the SCADAPack E Configurator.
PORT 2 uses an industry standard RJ-12 terminal socket conforming to RS-232C signaling standards
when used as an RS-232C port. The RJ-12 terminal socket also allows for a RS-422 or RS-485 port
connection. The RJ-12 connection on the SCADAPack ES is a Data Terminal Equipment (DTE)
connection.
This port could be used as the network connector to implement an RS-485 network on twisted pair. A
maximum of 32 SCADAPack ES and other devices can be connected to any one RS-485 network.
Default setting: RS232C, 9600 bps, 8 data bits, 1 start bit, 1 stop bit and no parity.
SCADAPack ES Hardware 45
Port 3
PORT 3 is a general-purpose serial communication data port. This port is normally configured as an RS-
232C communication port. Optionally, it can be configured as an RS-422 port or RS-485 port by
selecting RS-422 or RS-485 for PORT 2 using SCADAPack E Configurator.
PORT 3 uses an industry standard RJ-12 terminal socket conforming to RS-232C signaling standards
when used as an RS-232C port. The RJ-12 terminal socket also allows for a RS-422 or RS-485 port
connection. The RJ-12 connection on the SCADAPack ES is a Data Terminal Equipment (DTE)
connection.
This port could be used as the network connector to implement an RS-485 network on twisted pair. A
maximum of 32 SCADAPack ES and other devices can be connected to any one RS-485 network.
Default setting: RS232C, 9600 bps, 8 data bits, 1 start bit, 1 stop bit and no parity.
Port 4
Port 4 is generally used for diagnostic or programming purposes, but is functionally similar to Port 0 and
can be used as a general-purpose communications port. Port 4 uses an industry standard RJ-12
terminal socket conforming to RS-232C signalling standards when used as an RS-232C port. The RJ-12
connection on the SCADAPack ES is a Data Terminal Equipment (DTE) connection.
Default setting: RS232C, 9600 bps, 8 data bits, 1 start bit, 1 stop bit and no parity.
46 SCADAPack ES Hardware Manual
The following table describes the pin assignments for the SCADAPack E RTU RJ-12 connectors. The
same connector is used for the various serial interfaces. Pin numbering is shown for cables connecting
to RTU’s RJ-12 connectors:
1 6
RJ-12
PLUG
PIN SIDE
4 GND
Each SCADAPack ES serial port can be configured for a variety of communications protocols, functions,
speeds and data formats. See the SCADAPack E Configurator User Manual for configuration details.
SCADAPack ES Hardware 47
1
2 TxD
2
3 GND
TO RTU 5 TO RS232
(DTE) 4 GND
DEVICE
5 RxD (DTE)
3
6
RJ-12
9 PIN ‘D’ TYPE
PLUG
1 6 FEMALE
RJ-12
PLUG
PIN SIDE
1 TxD-
2 TxD+
3
GND
4
TO RTU TO RS485 4-wire device(s)
( DTE ) 5 RxD-
6 RxD+
RJ-12
PLUG
1 6
RJ-12
PLUG
PIN SIDE
1 TxD-
2 TxD+ TO RS485 2-wire
device(s)
3
GND
TO RTU 4
( DTE ) 5 RxD-
6 RxD+
RJ-12
PLUG
1 6
RJ-12
PLUG
PIN
SIDE
SCADAPack ES Hardware 49
1 DTR 2
‘ 0
2 TxD
2
3 1 GND
TO RTU 7 MODEM RS232
( DTE ) 4 GND 5
4 ( DCE )
5 RxD 3
6 DCD
8
RJ-12
25 PIN ‘D’
PLUG
TYPE
MALE
1 6
RJ-12
PLUG
PIN
SIDE
Certain Hayes Registers may have to be set within the modem for correct operation.
Refer to the SCADAPack E Communication Interface Reference manual.
50 SCADAPack ES Hardware Manual
Each SCADAPack ES Ethernet port can be configured for a variety of communications protocols,
functions, speeds and data formats. See the SCADAPack E TCP/IP Technical Reference manual and
the SCADAPack E Configurator User Manual for configuration details.
10/100BASE-T Networks
These networks are also known as UTP (unshielded twisted pair), copper wire, Category 3, 4 and 5
Ethernet wire, or twisted pair.
The IEEE 802.3 10BASE-T specification requires that 10BASE-T and 100BASE-T devices support UTP
100-120 Ohm unshielded twisted pair cables of not less than 100m in length. This requirement does not
factor in losses due to connectors, patch panels, punch-down blocks, or other cable management
hardware, which introduce additional loss. For each connector or other intrusive cable management
device in the total link, subtract 12m from the total allowable link length.
As long as specifications are met for the entire length of the cable, UTP cable segments can be run up
to a maximum allowable length of 200m.
SCADAPack ES Hardware 51
Single SCADAPack ES
Where the SCADAPack ES is utilized as a single RTU, it is recommended that the HEX Switches be
set to “00”. In this mode, the SCADAPack ES is a Main RTU with all facilities enabled.
CAUTION
SCADAPack ES memory contents will be lost if the on-board battery goes flat or is
replaced with the power disconnected. If this occurs, user configurations will need
to be re-loaded for correct RTU operation.
SCADAPack ES Hardware 53
6 Startup Modes
The user can change the startup mode of SCADAPack E RTUs for maintenance purposes.
00 on the HEX Switches is the normal RTU startup mode. See Run Mode 55 .
F0 on the HEX Switches is Service mode. See Service Mode 56 .
FC on the HEX Switches is Cold Boot mode. See Cold Boot Mode 57 .
01-EF settings are used for SCADAPack ES Remote I/O addresses. See SCADAPack ES Remote I/O
Switch Settings 60
Other HEX Switch settings are used for selecting special startup modes. See Other Startup Modes 58
.
SCADAPack ES Hardware 55
Cold Boot mode does not format the Flash file system. See Format Boot in Other Startup Modes 58 .
As there are startup modes that force the SCADAPack E DNP3 device address to 0, it is recommended
that DNP3 device Address ‘0’ not be configured for use in SCADAPack E RTU DNP3 systems. For
more information see the SCADAPack E DNP3 Technical Reference manual.
Changing the HEX switch settings to a value in the range 00-F0 will cause an RTU system restart with
entry into the appropriate start mode.
Switching the RTU to addresses F1 - FF will require the RTU to be separately reset (e.g. powered off &
on) in order for the special operation to take affect.
RTU Switch
Description Notes
Setting (Hex)
RTU Switch
Description Notes
Setting (Hex)
For normal RTU operation as a Single RTU, it is recommended that the SCADAPack ES or
SCADAPack ER RTU HEX Switches be set to “00”.
For more information see the SCADAPack E Remote I/O Technical Reference manual.
7 SCADAPack ES Diagnostics
A range of diagnostic information is provided by the SCADAPack ES RTUs in order to facilitate trouble-
shooting and understanding of RTU operation.
Error Codes 68
Communication Statistics 72
SCADAPack ES Hardware 61
RUN indicates the operational status of the SCADAPack ES micro-controller and software operation.
When the SCADAPack ES Boot Monitor is starting up, this LED will blink at approximately a 0.5-
second rate. Following Boot Monitor startup, it will blink rapidly in succession to indicate initialization of
the SCADAPack ES operating system firmware. After initialization is complete it blinks at approximately
a 1.5-second rate. If it ceases to blink (i.e. remains continuously on or off) for more than approx. five
seconds, the SCADAPack ES is not functioning correctly.
RX indicates receipt of date by the SCADAPack ES from a telemetry interface port (may be serial and/
or Ethernet depending upon the SCADAPack ES configuration).
RUN / RX LEDs may flash alternately when the SCADAPack ES is in Boot Monitor programming mode.
For more information see the SCADAPack E Operational Reference manual and the SCADAPack E
Firmware Update User Manual.
TX is turned on while the SCADAPack ES is transmitting data to a telemetry interface port (may be
serial and/or Ethernet depending upon the SCADAPack ES configuration).
LED1 or LANIP usually indicates TCP/IP communication activity on either of the SCADAPack ES
Ethernet Ports or via a serial port configured with a valid PPP configuration.
62 SCADAPack ES Hardware Manual
LED2 or COMM usually indicates communication activity with peripheral devices, such as PLC’s,
external to the SCADAPack ES.
UTIL may flash to indicate completion of an operation on the Compact FLASH Utility port (e.g. Security
key configuration successfully loaded from Compact FLASH card - for more information see
SCADAPack E Security Technical Reference Manual).
Ethernet LEDs adjacent to each Ethernet ports on the SCADAPack ES processor board indicates an
active UTP Ethernet connection and RX/TX data activity.
SCADAPack ES Hardware 63
By default, the indication LEDs on the SCADAPack ES I/O boards are enabled.
The default configuration for the “LED Enable Jumper” on the I/O Board appears below (jumper across
pins 2 &3, located on the top I/O board).
To disable indication LEDs on the I/O board, move the J1 jumper from the lower pins (2&3) to the upper
pins (1&2).
J1
Figure 6.15: Standard Setting for I/O Board LED Enable Jumper
64 SCADAPack ES Hardware Manual
Internal temperature
Internal Temperature o C
System Analog Point 50062
This analog system point measures the ambient temperature at the controller circuit board in degrees
Celsius. It is useful for measuring the operating environment of the controller and returns an integer value
in the range –40 to 75.
The temperature reading represents temperatures in the range –40°C to 75°C. Temperatures outside this
range cannot be measured.
Use the system point directly by assigning an analog point of this point number (50062) in the RTU
database
Read the system point into a user ISaGRAF application as an Integer or Real variable from an Input
Board connection
Internal Temperature o F
System Analog Point 50063
This analog system point measures the ambient temperature at the controller circuit board in degrees
Fahrenheit. It is useful for measuring the operating environment of the controller and returns an integer
value in the range –40 to 167.
The temperature reading represents temperatures in the range –40°C to 167°F. Temperatures outside
this range cannot be measured.
Use the system point directly by assigning an analog point at this point number (50063) in the RTU
database
Read the system point into a user ISaGRAF application as an Integer or Real variable from an input
board
SCADAPack ES Hardware 65
Use the system point directly by assigning a binary point to this point number (50206) in the RTU
database
For ISaGRAF applications, read the status point through an Input Board connection.
Use the system point directly by assigning a binary point to this point number (50207) in the RTU
database
For ISaGRAF applications, read the status point through an Input Board connection.
66 SCADAPack ES Hardware Manual
CAUTION
The "BYE" command should be issued prior to disconnecting the ASCII terminal for
correct ISaGRAF operation.
The Command line operations and diagnostic display are also supported via TCP/IP interfaces using
Telnet. In addition, command line operations are also supported via DNP3 Virtual Terminal. The RTU
need not be configured with a Cmd Line or ISaGRAF port in these cases. Multiple Telnet sessions
may be established with the RTU on the same TCP/IP interface, or multiple sessions may be
established on multiple TCP/IP interfaces, simultaneously.
68 SCADAPack ES Hardware Manual
Refer to the SCADAPack E Operational Reference manual for details of these system error codes.
SCADAPack ES Hardware 69
SCADAPack E RTU provides a system status code through an RTU Analog System Point.
00000
The most recent status is retained as the value of the system status. DNP3 event reporting may be
configured for the system status point to provide a time-stamped history of status codes.
System status is reported through the RTU System Error Point.
User defined status codes may be generated via ISaGRAF using RTUPARAM function block with the
“SYS_ERR_CODE” parameter.
ISaGRAF user application statuses are reported using the following RTU facilities:
To the ISaGRAF Workbench Debugger if connected (locally or remotely)
Through the SCADAPack E System Error Point
Via the SCADAPack E Diagnostic Display session.
1001-1009 ISaGRAF Application Load Did not load ISaGRAF application files or
Status memory application for ISaGRAF targets
1040-1049 Data Processing Status Run time data processing status codes
1060-1099 Magna I/O Status (SCADAPack I/O status reported by main OS firmware
ER only)
1100-1139 Magna I/O Status (SCADAPack I/O status reported by 386 IO Interface
ER only) firmware
For SCADAPack E System Error Point details see the SCADAPack E Operational Reference manual.
SCADAPack ES Hardware 71
7.6.2 DNP3 and PLC Device Communication Errors & TCP/IP Errors
TCP/IP Errors
TCP/IP communication and configuration errors are reported by the RTU through the Diagnostic Display
session as TCP/IP diagnostic information. These error codes are also reported through the ISaGRAF
TCP/IP function blocks in the output STATUS variable.
The TCP/IP errors are reported via the RTU System Error Point for TCP/IP configuration problems.
See the SCADAPack E TCP/IP Technical Reference manual for a complete list of TCP/IP
Communication Error Codes.
72 SCADAPack ES Hardware Manual
8 Calibration
This section describes how to calibrate the I/O interfaces provided on the SCADAPack ES.
CAUTION
The SCADAPack ES has been factory calibrated using high precision equipment.
Re-calibration of I/O should only be attempted by skilled personnel using high
quality, high precision equipment.
To check whether the calibration of the SCADAPack ES I/O meets the requirements of an attached
device, check the hardware jumper settings on the I/O board, and use SCADAPack E Configurator
software application to read from and control the RTU points associated with the device. For more
information refer to the SCADAPack E Technical Reference Manuals.
1: The analog inputs provided on the RTU have an accuracy of 0.1% over the operating
temperature range. Therefore when calibrating these a source with an accuracy of
0.05% or better should be used.
Similarly the analog outputs provided on the RTU have an accuracy of 0.1% over the
operating temperature range. Therefore when calibrating these, a meter with better
than 0.05% accuracy should be used.
2: To confirm that maximum accuracy is obtained when calibrating the analog output
channels two requirements need to be met. Firstly the RTU should be powered with
each analog output driving maximum current into a load resistance of 270 to 560
for a duration of 30 minutes prior to calibration.
This confirms that components have achieved operational temperature. In addition to
this the calibration instrument used should have an accuracy of 0.05% or better,
displaying the measurement to 3 decimal places or better.
3: Before calibrating the RTU, the RTU clock should be set with the correct date and
time. See the SCADAPack E Configurator Users Manual (Transfer Menu) for
instructions on setting the RTU time.
74 SCADAPack ES Hardware Manual
8.1 Overview
The calibration interface is implemented as a simple menu system. To access the calibration menu,
connect a null modem serial cable to Port 4 of the SCADAPack ES RTU, set the configuration Hex
switches to FE, and cycle power to the controller.
The calibration menu enables calibration of the physical I/O as well as the voltage monitor. Additional
information can also be entered via the calibration interface that enables the generation of a ‘Test and
Calibration’ certificate. If any attempts are made to calibrate physical I/O, the user will be prompted to
enter the following information:
operator name
calibration equipment (source and measurement).
The following items are consistent throughout the calibration screens:
The menu title is shown at the top, in the middle of the screen.
The menu options are drawn in the centre of the screen.
The currently selected menu item is shown in reverse video.
To activate the currently selected menu item press the enter k ey.
To change the currently selected menu item, use the arrow k eys.
Alternatively the short-cut k ey, shown to the left of the menu item, may be used to immediately activate
any menu item.
The screen may be refreshed at any time by pressing the space bar.
The R short-cut key can be used from any menu to return to the previous menu (explanation of this
menu option is omitted from the remainder of this section).
At the bottom of the screen is the feedback area. This area displays the state of various calibration
settings and physical I/O. The information displayed in this area changes depending on the menu being
displayed.
For each of the following sections where selection of a menu item leads to a further menu, detailed
description of this item will be omitted from the section describing the higher-level menu, to avoid
duplication. Calibration screen examples are given for a SCADAPack ES A model RTU with the
32/16/12/4 I/O board. Calibration screen contents may vary for different I/O board models.
SCADAPack ES Hardware 75
After the RTU starts up in calibration mode, the Main Menu is displayed. The Main Menu, as shown in
Figure 8.1 75 , provides the highest-level overview of the operations that can be performed through the
calibration interface. These operations include:
Calibration of analog inputs
Calibration of analog outputs
Calibration of the voltage monitor
Actuation of the output relays (toggles state)
Viewing and Editing the Calibration Certificate
Figure 8.1 75 shows the feedback area associated with the Main Menu. It gives an overview of the state
of various calibration settings and physical I/O including:
On-board battery status
The state of the digital inputs
The raw value of the analog inputs
Menu Items
1 is used to access the menus that permit the calibration of analog inputs 1 to 6.
2 is used to access the menus that permit the calibration of analog inputs 7 to 12.
3 is used to access the menus that permit the calibration of analog outputs 1 to 4.
4 is used to actuate the output relays for visual inspection and testing.
s is used to access the menus that permit the calibration of the power supply.
c is used to access the menus that view and edit the calibration certificate.
x is used to restart the RTU.
8.1.2 AI Menus
Selection of menu items 1 or 2 from the Main Menu will display an AI Menu as shown in Figure 8.2 76 .
This menu consists of a selection items for each analog input in the selected group. This menu is
basically a springboard to the individual channel calibration screens. The feedback area on this screen is
changed to show the state of calibration settings and current values for the selected analog input group.
AI Menu
S/N 10577
I/O 2.07 1. Calibrate AI 01
CPU 7.5-1 2. Calibrate AI 02
B/M 2.15 3. Calibrate AI 03
4. Calibrate AI 04
5. Calibrate AI 05
6. Calibrate AI 06
r. Return to previous menu
Analog Input : 1 2 3 4 5 6
Cal Minimum : 00780 00819 00819 00819 00819 00189
Cal Maximum : 03899 04095 04095 04095 04095 04095
Current Value : 00100 00010 00004 00004 00000 00000
A/D Reference = 02029 (raw count)
The Calibrate AI Menu is used to change the calibration settings for the analog inputs on a per channel
basis and is shown in Figure 8.3 77 . The menu contains items for changing the following calibration
settings and information for the selected AI channel:
Minimum input (current/voltage)
Maximum input (current/voltage)
Calibration Range (for calibration certificate)
Menu Options
1 will set the input minimum for the selected channel. This means that the input current/voltage
applied to the terminals of the selected analog input, at the time of selecting this option, will be
represented in the RTU by the value set as the user minimum (set by option 3).
2 will set the input maximum for the selected channel. This means that the input current/voltage
applied to the terminals of the selected analog input, at the time of selecting this option, will be
represented in the RTU by the value set as the user maximum (set by option 4).
c will record the calibration range for the selected channel (e.g. 1 – 5V). This entry has no effect
on the calibrations themselves and is provided for information purposes only. There is also an entry in
the Calibration Certificate menu that will set the calibration range for analog inputs (see section Analog
Input Calibration Range 91 )
Calibration Procedure
Plug current/voltage source into selected channel.
Apply desired minimum current to input and select menu option 1.
Apply desired maximum current to input and select menu option 2.
Select Calibration Range for this channel (if required). The range can be selected for ALL analog inputs
from Calibration Certificate menu entry (see section Analog Input Calibration Range 91 ).
78 SCADAPack ES Hardware Manual
8.1.4 AO Menus
Selection of menu option 3 from the Main Menu will display an AO Menu as shown in Figure 8.4 79 .
This menu consists of a menu item for each analog output. This menu is basically a springboard to the
individual channel calibration screens. The feedback area on this screen is changed to show the state of
calibration settings and current values for the analog output channels.
The Calibrate AO Menu is used to change the calibration settings for the analog outputs on a per
channel basis and is shown in Figure 8.5 80 . The menu contains options for changing the following
calibration settings and information for the selected AO channel:
minimum and maximum current output
25%, 50% and 75% current output
calibration range for this channel (for calibration certificate)
Menu Options
1 used to access menu for calibration of the minimum current output
2 used to access menu for calibration of the 25% current output
3 used to access menu for calibration of the 50% current output
4 used to access menu for calibration of the 75% current output
5 used to access menu for calibration of the maximum current output
c will record the calibration range for the selected channel (e.g. 4 – 20mA). This entry has no
effect on the calibrations themselves and is provided for information purposes only. There is also an entry
in the Calibration Certificate menu that will set the calibration range for analog outputs (see section
Analog Output Calibration Range 92 ).
Each of the menu entries shown in Figure 8.5 80 allow calibration of the selected analog output channel
at the minimum, 25%, 50%, 75%, and maximum levels. The minimum calibration menu is shown in
SCADAPack ES Hardware 81
Figure 8.6 81 .
These lower level AO menus contains options for changing the calibration settings of the selected level
(min, 25%, 50%, 75%, or max) as well as recording the measured value at that level (min, 50%, and
max levels only).
Menu Options
1 will set the channel’s output current to the selected level (min, 25%, 50%, 75%, or max).
‘ will increase the output current associated with the selected level in large steps.
/ will increase the output current associated with the selected level in small steps.
; will decrease the output current associated with the selected level in large steps.
. will decrease the output current associated with the selected level in small steps.
2 will prompt the user to enter the channel’s measured output current for the selected level (valid
for minimum, 50% and maximum levels only).
Calibration Procedure
Attach a current meter to the selected channel.
Select the menu entries corresponding to the selected channel as shown in Figure 8.4 79 .
Select the desired level for calibration (menu shown in Figure 8.5 80 ).
Select menu option 1 to set the output current to the nominal output.
Use menu options ‘, /, ; and . to set the output current to the desired value.
82 SCADAPack ES Hardware Manual
Use menu option 2 to enter the measured output current for this calibration point (valid only for minimum,
50% and maximum levels).
SCADAPack ES Hardware 83
This menu is used to change the calibration settings for the supply voltage monitoring circuit. There is
also a low supply voltage alarm. The low voltage alarm level is not set in the calibration screens as it is
configurable at runtime and can be included in RTU configuration files (see the or the SCADAPack E
Configuration Technical Reference Manual for low volts alarm point number and type). The menu,
shown in Figure 8.7 83 , contains items for performing the following operations:
Setting minimum voltage point.
Setting maximum voltage point.
Menu Items
1 will set the minimum voltage. This means that the voltage applied to the supply terminals at the
time of selecting this option will be represented in the RTU by the value set as the user minimum.
2 will set the maximum voltage. This means that the voltage applied to the supply terminals at the
time of selecting this option will be represented in the RTU by the value set as the user maximum.
Calibration Procedure
Set the RTU power supply voltage to the recommended minimum value (displayed in menu entry) and
select menu option 1.
Set the RTU power supply voltage to recommended maximum value (displayed in menu entry) select
menu option 2. (The unit should now indicate that it is calibrated, as can be seen in Figure 8.7 83 )
This menu is used to view and edit the calibration certificate and is shown in Figure 8.8 84 . The
calibration certificate displays I/O board calibrations along with other calibrations information entered by
the user to provide a single page certificate suitable for archiving. The menu contains options for the
following:
displaying the calibration certificate
entry of operator name and equipment used.
entry of PCB serial numbers.
entry of supplementary test data (e.g. dates of particular tests)
entry of a single calibration range for analog inputs / outputs.
Menu Options
1 will display the calibration certificate with the current calibration information
6 will prompt the user to enter I/O Board PCB serial number.
t is used to access the menus to enter the supplementary test dates menu
i will prompt the user to enter a single calibration range for analog inputs
o will prompt the user to enter a single calibration range for analog outputs
SCADAPack ES Hardware 85
The menu selection to display the calibration certificate will produce a display similar to that shown in
Figure 8.9 86 . The user needs to manually enter much of this information.
Selection of menu item 1 from the Calibration Certificate Menu will display a dialog box, prompting the
user to enter their name, as shown in Figure 8.10 87 . The certificate allows for a name of 32 characters
(maximum).
Selection of menu item 3 from the Calibration Certificate Menu will display two successive dialog boxes,
prompting the user to enter both the generating equipment and the measuring equipment. The prompt for
the generating equipment is shown in Figure 8.11 88 . The certificate allows for equipment names up to
32 characters each (maximum). If the same equipment was used for both source and measurement,
press <enter> when prompted for the measuring equipment to enter the generating equipment into both
fields.
Selection of menu item 4 from the Calibration Certificate Menu will display two successive dialog boxes,
prompting the user to enter both the I/O board and CPU board serial numbers. The prompt for the I/O
board serial number is shown in Figure 8.12 89 . The certificate allows for board serial numbers of 5
characters each (maximum). These serial numbers may differ from the case serial number entered from
the Main Menu.
Selection of menu item t from the Calibration Certificate Menu will display the Supplementary Test Data
menu as shown in Figure 8.13 90 . The menu entries prompt the user to enter in the appropriate dates in
the format dd/mm/yy. The feedback screen displays the test data entered in this menu along with the
last calibration date and the power supply calibration date, both of which are automatically entered by
the RTU.
The menu contains options for the entering the following data
date that RTU clock was originally set
date of serial port tests
date of Ethernet port tests
date of auxiliary power O/P test
date of digital I/O tests.
Menu Options
1 will prompt the user to enter the date that the RTU clock was initially set.
2 will prompt the user to enter the date of the serial port tests.
3 will prompt the user to enter the date of the Ethernet port tests.
4 will prompt the user to enter the date of auxiliary power output tests.
5 will prompt the user to enter the date of digital I/O tests.
Selection of menu item i from the Calibration Certificate Menu will display the Analog Input Range menu
as shown in Figure 8.14 91 . The entries through this menu have no effect on the calibrations
themselves and are provided for information purposes only. There is also an entry in the individual analog
input calibration menus that allows the calibration range to be set for an individual analog (see section
Calibrate AI Menu 77 ). This menu contains options for the entering a single calibration range for all
analog inputs.
Menu Options
1 will set the calibration range for analog inputs to be 0 – 5V
2 will set the calibration range for analog inputs to be 1 – 5V
3 will set the calibration range for analog inputs to be 0 – 10V
4 will set the calibration range for analog inputs to be 1 – 10V
5 will set the calibration range for analog inputs to be 4 – 20mA
6 will set the calibration range for analog inputs to be 3.5 – 20.5mA
7 will identify the calibration range for analog inputs as non-standard
Selection of menu item o from the Calibration Certificate Menu will display the Analog Output Range
menu as shown in Figure 8.15 92 . The entries through this menu have no effect on the calibrations
themselves and are provided for information purposes only. There is also an entry in the individual analog
output calibration menus that allows the calibration range to be set for an individual analog (see section
Calibrate AO Menu 80 ). This menu contains options for the entering a single calibration range for all
analog outputs.
Menu Options
1 will set the calibration range for analog outputs to be 0 – 5V
2 will set the calibration range for analog outputs to be 1 – 5V
3 will set the calibration range for analog outputs to be 0 – 10V
4 will set the calibration range for analog outputs to be 1 – 10V
5 will set the calibration range for analog outputs to be 4 – 20mA
6 will set the calibration range for analog outputs to be 3.5 – 20.5mA
7 will identify the calibration range for analog outputs as non-standard
Routine Recommendations 95
Handling Procedures
Treat batteries with care
Follow the manufacturers’ instructions concerning battery storage, use and disposal
Keep batteries clean, and free from contaminants or other materials that could short the terminals
Connect new batteries using the correct polarity
Replace batteries with new units of the same chemistry, capacity and make
Observe the manufacturers’ instructions regarding disposal of batteries. Considerable energy remains
in the battery.
ESD Procedures
CAUTION
Static can damage electronic devices. Follow these precautions:
Cleaning
There are no special cleaning instructions for this product.
96 SCADAPack ES Hardware Manual
The frequency of routine maintenance depends on the specific piece of equipment and the environment
in which it is installed. Routine maintenance is recommended at two time-intervals:
Every three years
Every five years
Calibrate RTU C
Modems B
Batteries (primary) B A
Batteries (secondary) A
Routine Maintenance
In some cases, the period stated is the maximum interval between maintenance activities. Experience,
or the high usage of a particular piece of equipment, may determine that maintenance procedures need
performing more frequently than indicated in the table
Check that any replaced fuses are of the correct rating
Items requiring re-calibration may not be suitable for user servicing. Contact Schneider Electric for
advice.
SCADAPack ES Hardware 97
10 Specifications
Disclaimer: Schneider Electric reserves the right to change product specifications without notice.
For more information visit Schneider Electric.
General 98
Data Capaciity 99
10.1 General
Environment 10 % RH to 95 % RH (non-condensing)
–40oC to 65oC (operating)
–40oF to 150oF (operating)
–40oC to 70oC (storage)
–40oF to 158oF (storage)
Pollution Degree 2, Installation Category I, Indoor use
Elevation 3000m.
9842 ft.
Non-volatile CMOS RAM with lithium battery retains contents for 2 years with
RAM no power
Packaging corrosion resistant zinc plated steel with black enamel paint
SCADAPack ES Hardware 99
Maximum Data
Concentrator
Approx. 15,000
points
Maximum Data
Concentrator
Approx. 100
Devices
File System
Typical Storage
10 MB
Integers 100,000
Floats 50,000
Integers 2,500,000
Floats 1,250,000
Compact FLASH 2 GB (with ISaGRAF Restart History and file copy user
Trend Storage programming. See SCADAPack E Trend Sampler technical
manual)
Integers 500,000,000
Floats 250,000,000
100 SCADAPack ES Hardware Manual
Isolation Power Input and Auxiliary Output are functionally isolated from
each other and all I/O points.
SCADAPack ES Hardware 101
Port 0 RS-232
Port 1 RS-232
Port 4 RS-232
Baud Rates Port 0, Port 1, Port 2, Port 3, Port 4 serial ports support rates up to
115200 bps.
Connector RJ12
Protection RS232 ports are static protected to ±15kV (IEC 801-2, Air-gap
discharge).
Utility Port
Compact Flash supports 3.3V cards up to 4GB capacity, Type I, Flash memory only
Buffered, hot-swap support
Turn on voltage 9V
Channels per 8
common
Status & individual relay pole feedback to software, output state poll
Reporting
Resolution 12-bit
Isolation Isolated from channel to channel and from and RTU logic.
Analog inputs need to be within the 50Vac or 70Vdc of chassis
or earth.
Resolution 12-bit
Isolation Optical
500Vac minimum to RTU logic
Range 4-20mA
Voltage output may be accomplished with external precision
resistor.
Logic End-Of-
Scan to Signal
<10ms (typically 5-8ms)
Update Latency
Status & Open Loop status, output value poll
Reporting
Controls Direct Operate and Select Before Operate
10.10 Certifications