DFU Calculation
DFU Calculation
DFU Calculation
Step -1:
Using Table 11.4.1 (NSPC), Drainage Fixture Unit (DFU) Values, we get the following DFU values of
plumbing fixture used in our project:
Using table 11.4.1, we can calculate total DFU for horizontal and vertical pipe in each toilet.
DFU (Drainage Fixture Units) is measure of estimated discharge in given drainage system. It measure
the amount of waste water flowing into plumbing fixtures.
For example, using Table 11.4.1 (NSPC) we find that for “Water Closet 1.6 GPF Gravity or Pressure
Tank” for heavy-use assembly DFU will be 4.
Step - 2:
After calculating total DFU(Drainage Fixture Unit) for each plumbing fixture, we use Table 11.5.1B
(NSPC), which gives maximum number of Drainage Fixture Unit (DFU) that may be connected to the
horizontal or vertical pipe (Stack).
Using table 5.2 (NSPC), we get the minimum pipe size to be used for each plumbing fixtures.
WC (Water Closet): 3” minimum pipe size. (UPC, Uniform Plumbing Code Table 7-3),
(Table 5.2, NSPC does not give minimum pipe size for WC. So we will use Table 7.3 from UPC (uniform
Plumbing code) to get minimum pipe size for WC).
We will start our pipe size calculation from 2nd Floor (top floor). Because all drain is flowing down.
SECOND FLOOR – FEMALE TOILET
Therefore, total DFU for 05 WC’s in 2nd Floor Female Toilet = 5 x 4 DFU (i.e. 20 DFU)
Using the table 7.3 (UPC) individual pipe size for each WC shall me minimum 3”. Using table 11.5.1B
NSPC), 3” pipe can load only up to 20 DFU. Therefore, horizontal pipe size in 2nd Floor female toilet
shall be minimum 3”. And Vertical pipe size from 2nd Floor up to 1st Floor female toilet will be 3”.
Total DFU for all 05 Nos. WC’s in 1st Floor = 5 x 4 DFU (i.e. 20 DFU).
Now total DFU in First Floor = 1st floor DFU + 2nd Floor DFU
Using table 11.5.1B (NSPC), 3” pipe can load only up to 20 DFU. Therefore, horizontal pipe size in 1st
floor toilet shall be minimum 3”. But Vertical pipe size from 1st Floor to Ground Floor will be 4”,
because total DFU is 40 (which is more than 20 DFU).
Similarly, total DFU for all WC in Ground Floor = 5 x 4 DFU (i.e. 20 DFU).
Now total DFU in Ground Floor = 20 DFU (2nd Floor) + 20 DFU (1st Floor) +20 DFU (Ground Floor) = 60
DFU.
Individual and horizontal pipe size shall remain same i.e. minimum 3”.
But Vertical pipe size from Ground Floor will be 4”, since total DFU is more than 20.
We will start our pipe size calculation from 2nd Floor (top floor). Because all drain is flowing down.
Therefore, total DFU for 05 WC’s in 2nd Floor Male Toilet = 5 x 4 DFU (i.e. 20 DFU)
Using the table 7.3 (UPC) individual pipe size for each WC shall me minimum 3”. Using table 11.5.1B
NSPC), 3” pipe can load only up to 20 DFU. Therefore, horizontal pipe size in 2nd Floor Male toilet shall
be minimum 3”. And Vertical pipe size from 2nd Floor up to 1st Floor Male toilet will be 3”.
Total DFU for all 05 Nos. WC’s in 1st Floor = 5 x 4 DFU (i.e. 20 DFU).
Now total DFU in First Floor = 1st floor DFU + 2nd Floor DFU
Using table 11.5.1B (NSPC), 3” pipe can load only up to 20 DFU. Therefore, horizontal pipe size in 1st
floor toilet shall be minimum 3”. But Vertical pipe size from 1st Floor to Ground Floor will be 4”,
because total DFU is 40 (which is more than 20 DFU).
Similarly, total DFU for all WC in Ground Floor = 5 x 4 DFU (i.e. 20 DFU).
Now total DFU in Ground Floor = 20 DFU (2nd Floor) + 20 DFU (1st Floor) +20 DFU (Ground Floor) = 60
DFU.
Individual and horizontal pipe size shall remain same i.e. minimum 3”.
But Vertical pipe size from Ground Floor will be 4”, since total DFU is more than 20.
We will start our pipe size calculation from 2nd Floor (top floor). Because all drain is flowing down.
We have total 04 Nos. of WB in one side toilet 01 WB and 01 JS (Janitor Sink) in other side of same
toilet.
Therefore, total DFU for 04 WB’s in 2nd Floor Toilet = 4 x 1 DFU (i.e. 4 DFU).
Also, total DFU for 01 WB’s & 01 JS in 2nd Floor Toilet = 1 x 1 DFU + 2 x 1 (i.e. 3 DFU)
1-1/2” pipe size can load up to 3 DFU in horizontal line and 2” can load up to 6 DFU in horizontal.
Total DFU in vertical pipe (stack) = 4 DFU + 3 DFU = 7 DFU. Therefore, vertical pipe size will be 2”.
Since 2” can load only up to 10 DFU in vertical position (Stack).
Therefore, total DFU for 04 WB’s in 2nd Floor Toilet = 4 x 1 DFU (i.e. 4 DFU).
Also, total DFU for 01 WB’s & 01 JS in 2nd Floor Toilet = 1 x 1 DFU + 2 x 1 (i.e. 3 DFU)
1-1/2” pipe size can load up to 3 DFU in horizontal line and 2” can load up to 6 DFU in horizontal.
Total DFU in vertical pipe (stack) = 4 DFU + 3 DFU + 7 DFU (1 st Floor DFU) = 14 DFU.
Therefore, vertical pipe size will be 3”. Since 2” can load only up to 10 DFU in vertical position
(Stack). But 3” can load up to 48 DFU in vertical position (Stack).
We have total 04 Nos. of WB in one side toilet 01 WB and 01 JS (Janitor Sink) in other side of same
toilet.
Therefore, total DFU for 04 WB’s in 2nd Floor Toilet = 4 x 1 DFU (i.e. 4 DFU).
Also, total DFU for 01 WB’s & 01 JS in 2nd Floor Toilet = 1 x 1 DFU + 2 x 1 (i.e. 3 DFU)
1-1/2” pipe size can load up to 3 DFU in horizontal line and 2” can load up to 6 DFU in horizontal.
Total DFU in vertical pipe (stack) = 4 DFU + 3 DFU + 7 DFU (1st Floor DFU) + 7 DFU (Ground Floor) = 21
DFU.
Therefore, vertical pipe size will be 3”. Since 2” can load only up to 10 DFU in vertical position
(Stack). But 3” can load up to 48 DFU in vertical position (Stack).
Horizontal pipe size in Ground Floor shall be 4”, since 3” can load only up to 20 DFU in horizontal
position.
We will start our pipe size calculation from 2nd Floor (top floor). Because all drain is flowing down.
We have total 04 Nos. of WB in one side toilet 01 WB and 01 JS (Janitor Sink) in other side of same
toilet.
Therefore, total DFU for 04 WB’s in 2nd Floor Toilet = 4 x 1 DFU (i.e. 4 DFU).
Also, total DFU for 01 WB’s & 01 JS in 2nd Floor Toilet = 1 x 1 DFU + 2 x 1 (i.e. 3 DFU)
1-1/2” pipe size can load up to 3 DFU in horizontal line and 2” can load up to 6 DFU in horizontal.
Total DFU in vertical pipe (stack) = 4 DFU + 3 DFU = 7 DFU. Therefore, vertical pipe size will be 2”.
Since 2” can load only up to 10 DFU in vertical position (Stack).
We have total 04 Nos. of WB in one side toilet 01 WB and 01 JS (Janitor Sink) in other side of same
toilet.
Therefore, total DFU for 04 WB’s in 2nd Floor Toilet = 4 x 1 DFU (i.e. 4 DFU).
Also, total DFU for 01 WB’s & 01 JS in 2nd Floor Toilet = 1 x 1 DFU + 2 x 1 (i.e. 3 DFU)
1-1/2” pipe size can load up to 3 DFU in horizontal line and 2” can load up to 6 DFU in horizontal.
Total DFU in vertical pipe (stack) = 4 DFU + 3 DFU + 7 DFU (1 st Floor DFU) = 14 DFU.
Therefore, vertical pipe size will be 3”. Since 2” can load only up to 10 DFU in vertical position
(Stack). But 3” can load up to 48 DFU in vertical position (Stack).
We have total 04 Nos. of WB in one side toilet 01 WB and 01 JS (Janitor Sink) in other side of same
toilet.
Therefore, total DFU for 04 WB’s in 2nd Floor Toilet = 4 x 1 DFU (i.e. 4 DFU).
Also, total DFU for 01 WB’s & 01 JS in 2nd Floor Toilet = 1 x 1 DFU + 2 x 1 (i.e. 3 DFU)
1-1/2” pipe size can load up to 3 DFU in horizontal line and 2” can load up to 6 DFU in horizontal.
Total DFU in vertical pipe (stack) = 4 DFU + 3 DFU + 7 DFU (1 st Floor DFU) + 7 DFU (Ground Floor) = 21
DFU.
Therefore, vertical pipe size will be 3”. Since 2” can load only up to 10 DFU in vertical position
(Stack). But 3” can load up to 48 DFU in vertical position (Stack).
Horizontal pipe size in Ground Floor shall be 4”, since 3” can load only up to 20 DFU in horizontal
position.