En 809
En 809
En 809
(EN-809)
1. Introduction:
2. Procedures:
The cable shall be selected based on the demand load (current) as per
ADDC design criteria (refer Table 6 & 7). However, the connection to the
feeder pillar (whether to Type A or Type B) shall be based on the
recommended fuse rating (refer Table 8).
3. Recommendation:
1. For all new connections / reinforcement/relocation all ADDC
sections should follow same standards for selection of
equipments, fuses and cables as indicated in tables 1 to 8.
2. Review all the existing cases (or at least where there is a repeated
fuse blowing) to re-evaluate the feeding arrangement. All such
request shall be supported by a couple of actual current
readings/load details. Any fuse replacement in the existing
system should follow the standard ratings corresponding to
service cables provided (table-8) in this guideline.
3. ADDC shall not replace the fuse more than 2 times for a
consumer. At any reason, the fuse should not be replaced by
higher rating. If the customer load is the same as that of the final
cable termination application (CTA), ADDC may have to study the
loading of feeder pillar and initiate necessary
reinforcement/upgrading schemes to meet the requirement
complying with the design guideline. If the customer load is more
than that of the originally approved, Customer shall submit
application for the additional load as per LDN policy. ADDC
6. For all the existing cases, deviating from the above design
philosophy and where there is repeated fuse blowing/fuse base
overheating, shall be listed by the field staff and reported to Asset
Management Directorate to plan for developing new network and
to replace the feeder pillar with higher rating to rectify these
cases.
6+1(Spare)+
1000 1800 1800 1800/1 (2 x 3ph + 1 N) 630A 400A
1(Space)
1cx630mm2
8+1(Spare)+
1500 2700 2700 2700/1 (3 x 3ph + 2 N) 630A 400A
1(Space)
1cx630mm2
Table-3
250A-2Nos 4cx120
Type A 630A 2x4Cx240
800A 2 4+1Space 400A
(6Way) 300/350A-
4cx185
2Nos
160A-3Nos 4cx70
Type B 630A 2x4Cx240
800A 2 6+1Space 250A
(8Way) 4cx120
200A-3Nos
Note: -
For Type A FP, O/G fuse base rating is 400A (size2-NH2) and for Type B
FP, O/G fuse base is 250A (size1-NH1) hence the outgoing fuse rating of
both types should not exceed the maximum ratings provided in table -2.
Also for both types of FPs, the bus bar is rated for 800A, hence the
recommended maximum loading is 80 to 85%
Table-5
125A- 4cx25/50/
250A
4Nos 70 sqmm
4Cx70/120/
ST
400A 1 4 630A 185/240
(4Way)
sqmm 300A-
4cx185
400A 1No(Loop
sqmm
out)
Note: -
For service turret the bus bar is rated for 400A, hence the
recommended maximum loading is 80 to 85% (max 120kW).
Table-6
DERATING FACTOR- PARAMETERS
SN Factors Considered Rating factors
Soil Thermal Resistivity (1.2°C/m/W)
1 0.99
Depth of Laying (80cm) Multiple cables
2 0.96
2 4Cx25 sq mm 150 89
Table-8
L V FUSE RATING &CABLE SIZE CORRESPONDING TO LOAD
Sl Demand Load Max Load Current Recommended Recommended Nearest
2
No. Range (kW) range (A) @0.9pf Cable Size mm Fuse Rating
80A
1 0-40 62 16
2 40-55 85 25 100A
95 200A
5 90-115 177.6
120 224A
6 115-125 193
7 125-140 216 150 250A
300A
8 140-170 262.6 185
9 170-200 309 240 355A
400A-Direct from LV
Panel/separate fuse O/G
with lower capacity
10 200-250 386 2x120/2x185
1500 kVA TRANSFORMER-1 (TR-1) 1000/500/1A 1000/500/1A 1500 kVA TRANSFORMER-2 (TR-2)
OIL TYPE 10VA,5P20 10VA,5P20 OIL TYPE
DYN11 DYN11
P1 P2 E E P1 P2
11KV/0.415kV 50HZ 11KV/0.415kV 50HZ
51N
LV-PANEL
51N
11runs (3x3Phase+2xNeutral) of 11runs (3x3Phase+2xNeutral) of
1Cx630mm² XLPE/SWA/PVC Cu. CABLES 1Cx630mm² XLPE/SWA/PVC Cu. CABLES
INCOMER-2 63A TP FUSE TO TRIP HV FEEDER INCOMER-1
48V DC BATTERY CHARGER 63A TP FUSE
F16 TO TRIP HV FEEDER
48V DC BATTERY CHARGER
F16
32A SP FUSE
63A SP FUSE
11 KV SWGR & DMS RTU PANEL
CONSUMER UNIT DB
1H1,1H1
F2,F3,F4 F17,F18,F19
F5 SPACE HEATER (PTC) 2H1,2H1
F20 SPACE HEATER (PTC)
10A SP FUSE
0-500V 10A DP FUSE THERMOSTAT
F6 - F8 10A DP FUSE THERMOSTAT
V VSS 0-500V
10A SP FUSE
F15 V
VSS
TO 240V AC SUPPLY 10A SP FUSE 10A SP FUSE
F30
0-3000A 0-3000A
CT1 - CT3 CT1 - CT3
AR AY AB KWH 2500/5A KWH AB AY AR
10VA 2500/5A
MDI MDI MDI MDI MDI MDI
Provision Provision
10VA
2700A 4P ISOLATOR
2700A 4P ISOLATOR
TO 3? POWER SUPPLY
TO 3? POWER SUPPLY
RYBN F1 F2 F3 F4 F5 F6 F7 F8 F9 F1 F2 F3 F4 F5 F6 F7 F8 F9
RYB RYB RYB RYB RYB RYB RYB RYB RYB BUS COULER RYB RYB RYB RYB RYB RYB RYB RYB RYB
RYBN RYBN
ISOLATOR-2700A 4P
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
400A TP
LINE VOLTAGE
LINE VOLTAGE
P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
TERMINAL BOX FOR CT &
4Cx240mm² CABLE