Wind Load Clauses, Formulas and Equations - Part-1
Wind Load Clauses, Formulas and Equations - Part-1
Wind Load Clauses, Formulas and Equations - Part-1
Wind Pressures Acting on opposite faces of each building surface. In the calculation
of design wind loads for the MWFRS and for components and cladding for buildings,
the algebraic sum of the pressures acting on opposite faces of each building surface
shall be taken into account.
Minimum Design Wind Loading
The design wind load, determined by any one of the procedures specified in Sec
2.4.1, shall be not less than specified in this Section.
Main Wind-Force Resisting System: The wind load to be used in the design of the
MWFRS for an enclosed or partially enclosed building or other structure shall not be
less than 0.5 kN/m2 multiplied by the area of the building or structure projected onto
a vertical plane normal to the assumed wind direction. The design wind force for
open buildings and other structures shall be not less than 0.5 kN/m2 multiplied by the
area .
Components and Cladding: The design wind pressure for components and cladding
of buildings shall not be less than a net pressure of 0.5 kN/m2 acting in either
direction normal to the surface.
2.4.2 Method 1: Simplified Procedure
2.4.2.1 Scope
A building whose design wind loads are determined in accordance with this Section
shall meet all the conditions of Sec 2.4.2.2 or Sec 2.4.2.3. If a building qualifies only
under Sec 2.4.2.3 for design of its components and cladding, then its MWFRS shall
be designed by Method 2 or Method 3.
Limitations on Wind Speeds: Variation of basic wind speeds with direction shall not
be permitted unless substantiated by any established analytical method or wind
tunnel testing.
2.4.2.2 Main wind-force resisting systems
For the design of MWFRSs the building must meet all of the following conditions:
(1) The building is a simple diaphragm building as defined in Sec 2.1.3.
(2) The building is a low-rise building as defined in Sec 2.1.3.
(3) The building is enclosed as defined in Sec 2.1.3 and conforms to the wind-
borne debris provisions of Sec 2.4.9.3.
(4) The building is a regular-shaped building or structure as defined in Sec 2.1.3.
(5) The building is not classified as a flexible building as defined in Sec 2.1.3.
(6) The building does not have response characteristics making it subject to a
cross wind loading, vortex shedding, instability due to galloping or flutter;
and does not have a site location for which channeling effects or buffeting
in the wake of upwind obstructions warrant special consideration.
(7) The building has an approximately symmetrical cross-section in each
direction with either a flat roof or a gable or hip roof with g ≤ 45 .
(8) The building is exempted from torsional load cases as indicated in Note 5
of Figure 6.2.10, or the torsional load cases defined in Note 5 do not
control the design of any of the MWFRSs of the building.
2.4.2.3 Components and cladding
For the design of components and cladding the building must meet all the
following conditions:
(1) The mean roof height ℎ must be less than or equal to 18.3 m (ℎ ≤ 18.3 m).
(2) The building is enclosed as defined in Sec 2.1.3 and conforms to wind-
borne debris provisions of Sec 2.4.9.3.
(3) The building is a regular-shaped building or structure as defined in Sec
2.1.3.
(4) The building does not have response characteristics making it subject to
across-wind loading, vortex shedding, instability due to galloping or
flutter; and does not have a site location for which channeling effects or
buffeting in the wake of upwind obstructions warrant special
consideration.
(5) The building has either a flat roof, a gable roof with g ≤ 45 , or a hip roof
with g ≤ 27 .
2.4.2.4 Design procedure
(1) The basic wind speed shall be determined in accordance with Sec 2.4.4.
The wind shall be assumed to come from any horizontal direction.
(2) An importance factor . shall be determined in accordance with Sec 2.4.5.
(3) An exposure category shall be determined in accordance with Sec 2.4.6.3.
(4) A height and exposure adjustment coefficient, h shall be determined from
Figure 6.2.2.
Minimum Pressures: The positive design wind pressures, W*P± , from this Section
shall not be less than +0.5 kN/m2, and the negative design wind pressures, W)<" ,
from this Section shall not be less than −0.5 kN/m2.
2.4.2.4.3 Air permeable cladding
Design wind loads determined from Figure 6.2.3 shall be used for all air
permeable cladding unless approved test data or the recognized literature
demonstrate lower loads for the type of air permeable cladding being
considered.
2.4.3 Method 2: Analytical Procedure
2.4.3.1 Scopes and limitations
A building or other structure whose design wind loads are determined in
accordance with this Section shall meet all of the following conditions:
(1) The building or other structure is a regular-shaped building or structure
as defined in Sec 2.1.3.
(2) The building or other structure does not have response characteristics
making it subject to across-wind loading, vortex shedding, instability due
to galloping or flutter; or does not have a site location for which
channeling effects or buffeting in the wake of upwind obstructions
warrant special consideration.
The provisions of this Section take into consideration of the load magnification
effect caused by gusts in resonance with along-wind vibrations of flexible
buildings or other structures. Buildings or other structures not meeting the
requirements of Sec 2.4.2, or having unusual shapes or response characteristics
shall be designed using recognized literature documenting such wind load
effects or shall use the wind tunnel procedure specified in Sec 2.4.16.
2.4.3.2 Shielding
There shall be no reductions in velocity pressure due to apparent shielding
afforded by buildings and other structures or terrain features.
2.4.3.3 Air permeable cladding
Design wind loads determined from Sec 2.4.3 shall be used for air permeable
cladding unless approved test data or recognized literature demonstrate lower
loads for the type of air permeable cladding being considered.