2nd AMC Report BPCL Bengalore
2nd AMC Report BPCL Bengalore
2nd AMC Report BPCL Bengalore
Rev 0
14 Aug 2019
Reviewed By
Prepared By Anshul Jain Approved By Accepted
Rev & Date
Sanjaya Rath (NACE Certified CP K B Singh BPCL
Level 3)
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
Contents
1. Introduction
2. International standards
3. Criteria for cathodic protection
4. Overview of the system
5. Status of CP system
6. Results
7. Recommendation
Annexure – 1
CP Monitoring Parameters- Old Mound
A. Transformer Rectifier Unit
B. Potential readings at REJB
C. Monitoring of Anode Groundbed
D. Monitoring of Cathode Junction Box
E. PSP at 12 o’clock position by portable Cu/CuSO4 reference cell
F. Isolation Joint testing
G. DC Decoupler testing
H. Initial condition of CP system
Annexure-2
CP Monitoring Parameters- New Mound
A. Transformer Rectifier Unit
B. Potential readings at REJB
C. Monitoring of Anode Groundbed
D. Monitoring of Cathode Junction Box
E. PSP at 12 o’clock position by portable Cu/CuSO4 reference cell
F. Isolation Joint testing
G. DC Decoupler testing
Page 2 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
1. Introduction
BPCL has an operational LPG Bottling Plant at Solur, Bangalore. This plant has 2 mounds. Details of each mound are
mentioned below in the table:
ICCP system has been provided to protect these bullets against external corrosion. BPCL has awarded AMC
contract for CP system of both the mounds to M/s KB Singh and Associates (KBSA).
th th
Field visit has been made by Mr. Sanjaya Rath (KBSA) on 19 Sept. to 20 Sept 2019. During the visit CP system for
both old and new mounds has been inspected and improvement in health of cathodic protection of bullets has
been brought. This report provides monitoring data, status of cathodic protection, activities performed and
recommendations for improving corrosion protection of mounded bullets.
2. International standards
Page 3 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
4. Overview of CP system
5. Status of CP system
Sr. New
Parameter Old
No
All 3 Zn All 3 Zn
All 3 Zn All 3 Zn
D. Anode strings Anode strings are working OK. 6 out of 8 anode strings are
taking current.
E. Electrical isolation Bullets are electrically isolated. Bullets are electrically isolated.
6. Results
a. In old mound Polarized PSP at all permanent reference cell locations of all 3 bullets (1, 2 and 3) is meeting
NACE/OISD criterion of -0.850 VCSE Instant OFF.
In New Mound polarized PSP of Bullet 4 and 6 is meeting NACE/ OISD criterion of -0.850 VCSE Instant OFF.
However in Bullet 5, 2 number reference cell locations are not meeting the criterion.
Page 5 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
e. MIJ has been tested using Tinker & Rasor RFIT IJ tester. All MIJ has been found OK.
7. Recommendations
a. To investigate high current requirement of New Mound, it was suspected that MIJ is leaking current to
earthing. In this visit MIJ has been tested with IJ Tester and all MIJs are found OK.
We propose to check coating condition of bullet by making bell-hole on top of mound during our
next visit.
b. As anode strings A6 and A7 are not drawing any CP current anode to cable joint shall also be inspected
while doing excavation on top of the mound for coating inspection.
c. Spares required
- TR Unit cards for New Mound: 106
Page 6 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
ANNEXURE-1
Page 7 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
Observation:
• TRU is kept operating in Manual mode due to faulty cards. Card 104 and 106 shall be replaced.
Page 8 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
Criteria: Instant OFF PSP shall be more negative than -0.850 VCSE.
Page 9 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
C1 5.3 0.70 A
MSV 5
C2 0.1 0.01 A
C1 0.9 0.12 A
MSV 6
C2 5.4 0.72
Observation: Instant OFF PSP of the bullets are meeting NACE/ OISD criterion of -0.850 VCSE Instant OFF.
ON PSP (V) Instant off PSP (V) ON PSP (V) Instant off PSP (V)
MSV No 4
Page 10 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
MSV No 5
Note: All PSP are wrt portable Cu/CuSO4 half cell kept at remote location.
Voltage Across
S No Description
Polarization Cell
1 Bullet 1 1.341 V
2 Bullet 2 1.308 V
3 Bullet 3 1.616 V
Page 11 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
ANNEXURE-2
Page 12 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
Make Canana
Rating: 50 V / 75 A
Commissioned in 2004
Modes of operation Manual/AVCC/Auto
Input AC supply 240 V AC
Interrupter Yes
Parameter By Manual measurement
AC Voltage 230 V
AC Current 0.4 A
DC Voltage 2.0 V
DC Current 0.13 A
Mode of operation Manual
Potential at RE 1 On: -1.681 VCSE
Instant off: -1.261 VCSE
Potential at RE 2 On: -1.539 VCSE
Instant off: -1.186 VCSE
Potential at RE 3 On: -1.508 VCSE
Instant off: -1.138 VCSE
Page 13 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
Cu/CuSO4 7
-1.518 -1.170 -1.548 -1.192 -1.537 -1.126
Cu/CuSO4 8
-1.452 -1.095 -1.435 -1.092 -1.630 -1.233
Cu/CuSO4 9
-1.586 -1.192 -1.396 -1.024 -1.438 -1.054
Zn RE 1
-0.510 -0.102 -0.446 -0.101 -0.541 -0.181
Zn RE 2
-0.645 -0.242 -0.538 -0.168 -0.607 -0.272
2Zn RE 3 -0.585 -0.208 -0.572 -0.163 -0.669 -0.252
Observations: Instant OFF PSP with all permanent Cu/CuSO4 reference cells is meeting NACE /OISD
criterion -0.850 VCSE Instant OFF.
Page 14 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
C2
C1 0.04 A
C2 0.2
C1 0.1 0. 02 A
C2
Observation: Instant OFF PSP of the bullets are meeting NACE/ OISD criterion of -0.850 VCSE Instant OFF.
ON PSP (V) Instant off PSP ON PSP (V) Instant off PSP
(V) (V)
MSV No 4
Page 15 of 16
Second AMC visit report on cathodic protection
system of mounded bullets at BPCL LPG Bottling
plant, Bangalore
KB Singh and LPG Bottling plant,
Associates, Noida Bangalore
Note: All PSP are wrt portable Cu/CuSO4 half cell kept at remote location.
Dairyland USA make Solid State DC Decouplers has been installed for earthing of each bullet at
one point.