Odhisha Power Generation Corporation LTD Page 1 of 3 BGR Energy Systems LTD - Power Project Division
Odhisha Power Generation Corporation LTD Page 1 of 3 BGR Energy Systems LTD - Power Project Division
Odhisha Power Generation Corporation LTD Page 1 of 3 BGR Energy Systems LTD - Power Project Division
1. Board Details
Acceptance Criteria: Ratings, Make & Type shall be as per approved Drg.
3. IR Measurement
Coil Resistance(in )
Feeder Identification
Trip Coil Closing Coil Result (Healthy/Not Helathy)
No.& Description
1F INCOMER 1 89.4 91.2 OK
10F INCOMER 2 89.4 89.9 OK
Acceptance Criteria: There shall not be any open Circuit/ Interturn winding short (Value is for
reference)
5. CRM Measurement
IR (Closed Condition)
FeederIdentification No.
& Description R Y B Remarks
R-R Y-Y B-B
1R INCOMER 1 20 09 09 OK
10F INCOMER 2 09 10 10 OK
Note
This value is only for reference
6 .Breaker Operation
1F INCOMER1 OK OK OK OK OK OK OK
10F OK OK OK OK OK OK OK
INCOMER2
7. Indications
8.Remarks