Instrument transformers

Type SCV
Indoor current transformer

Product features
−− 6 00 volt, indoor, 10 kV BIL
−− 2 5 - 400 Hertz
−− Primary amperes: 75 - 4000
−− Mechanical rating: 180 x rated current
−− T hermal rating: 80 x rated current, one second
−− C ontinuous current rating factor:
2.0 @ 30°C ambient
1.5 @ 55°C ambient
−− Approximate weight: 29 lbs (13 kg)

Application
The SCV current transformer is used as the source of current for
relaying and metering.

Construction features
The ring-type core is insulated and toroidally wound with a fully
distributed secondary winding. The protective case, made of an
impact-resistant polycarbonate, is assembled using self-tapping
screws.

Secondary terminals
Secondary terminals are 10-32 brass terminal screws with
hardware. Space is available for a maximum of five terminals to
accommodate multi-ratio designs.

Curves
Saturation, overcurrent, ratio correction factor, and phase-angle
curves are available upon request.

Test reports
IEEE test reports are stored electronically and can be e-mailed
in various formats at the time of shipment.

Standards
This unit meets all applicable IEEE and NEMA standards and is
a UL Recognized Component.
Selection guide
IEEE metering accuracy Rating Factor
Primary IEEE
ampere rating B-0.1 B-0.2 B-0.5 B-0.9 B-1.8 30° C 55° C relaying accuracy Style number

Type SCV (6.5" window)


75 2.4 2.4 - - - 2.0 1.5 C10 7527A70G20
100 1.2 2.4 - - - 2.0 1.5 C10 7527A70G01
150 0.6 1.2 2.4 - - 2.0 1.5 C20 7527A70G02
200 0.6 0.6 1.2 - - 2.0 1.5 C20 7527A70G03

1VAP428601-DB March 2015 Rev. C


250 0.6 0.6 1.2 2.4 - 2.0 1.5 C20 7527A70G04
300 0.3 0.6 1.2 1.2 2.4 2.0 1.5 C20 7527A70G05
400 0.3 0.3 0.6 1.2 1.2 2.0 1.5 C50 7527A70G06
500 0.3 0.3 0.3 0.6 1.2 2.0 1.5 C50 7527A70G07
600 0.3 0.3 0.3 0.6 0.6 2.0 1.5 C100 7527A70G08
800 0.3 0.3 0.3 0.3 0.6 2.0 1.5 C100 7527A70G09
1000 0.3 0.3 0.3 0.3 0.3 2.0 1.5 C100 7527A70G10
1200 0.3 0.3 0.3 0.3 0.3 2.0 1.5 C200 7527A70G11
1500 0.3 0.3 0.3 0.3 0.3 2.0 1.5 C200 7527A70G12
2000 0.3 0.3 0.3 0.3 0.3 2.0 1.5 C200 7527A70G13
2500 0.3 0.3 0.3 0.3 0.3 2.0 1.5 C200 7527A70G14
3000 0.3 0.3 0.3 0.3 0.3 2.0 1.5 C200 7527A70G15
4000 0.3 0.3 0.3 0.3 0.3 2.0 1.5 C200 7527A70G16
Multi-ratio, IEEE, 5 terminals
600 0.3 0.3 0.3 0.6 0.6 2.0 1.5 C100 7525A38G01
1200 0.3 0.3 0.3 0.3 0.3 2.0 1.5 C200 7525A38G02
2000 0.3 0.3 0.3 0.3 0.3 2.0 1.5 C200 7525A38G03
3000 0.3 0.3 0.3 0.3 0.3 2.0 1.5 C200 7525A38G04
4000 0.3 0.3 0.3 0.3 0.3 2.0 1.5 C200 7525A38G05
Additional styles available upon request. Contact your ABB sales representative or call +1-252-827-3212 for more information.

Dimensions For more information please contact:


NAMEPLATE ABB Inc.
X5 X4 Medium Voltage Distribution Components
X3
X2 3022 NC 43 North
X1
Pinetops, NC 27864
9.88
[251] Ø6.50
USA
[165]
8.44 H1 9.88 Phone: +1 252 827 3212
[214] [251]
Fax: +1 252 827 4286
4.94
[125]
www.abb.com/mediumvoltage

.72
[18] Note:
1.00 The information contained in this document is for general information purposes
.72 8.44 [214] Ø.56 [14] [25]
1.38
[18] 3-HOLES
[35] only. While ABB strives to keep the information up to date and correct, it makes
9.88 [251]
3.38 [86] no representations or warranties of any kind, express or implied, about the
completeness, accuracy, reliability, suitability or availability with respect to the
Type SCV information, products, services, or related graphics contained in the document for
(Metric dimensions displayed in [mm]) any purpose. Any reliance placed on such information is therefore strictly at your
own risk. ABB reserves the right to discontinue any product or service at any time.

Copyright 2004 ABB.


All rights reserved.

UL Recognized Component; File No. E96461

You might also like